The Smartpack S Controller Panel Mounted

SP S Ctrl PM – Connection Drawing


Use this drawing as a customer connection reference for all cabling to the Smart-
pack S panel mounted controller. You find the exact location of connection termi-
nals, ports, etc. by referring to section "SP S Ctrl PM – Location of Terminals, Ports,
LEDs" on page 20

Connections
Smartpack S Controller, panel mounted
Internal & Customer Connections

Smartpack S Controller FUNCTION SIGNAL PIN-OUT


(panel mounted)

Customer Connections
X:a X:c
Input Circuit 1 + NO
Config. Input 1 Alarm Circuit 1
— Relay 1 C
Input Circuit 2
(From external equipment)

+
Config. Input 2 NC

Programmable Inputs
— NO
Input Circuit 3 Alarm Circuit 2
+
Config. Input 3 Relay 2 C
— NC

Alarm Relay Outputs


X:b X:d
Input Circuit 4 +

(To external equipment)


Config. Input 4 NO
— Alarm Circuit 3
Input Circuit 5 Relay 3 C
+ NC
Config. Input 5
— NO
Input Circuit 6 + Alarm Circuit 4
Config. Input 6 Relay 4 C
— NC
X:f
external fan)
(To and from

Fan Speed Ctrl. X:e


1 Speed Control Output
Tachometer Input NO
2 Alarm Circuit 5
Fan Speed Monitor Relay 5 C
Max. 0.5mm (20AWG) wire section NC
CAN bus node
From previous

(spring loaded terminals) NO


Alarm Circuit 6
Relay 6 C
1 NC
CAN port 1&2

Max. 0.5mm (20AWG) wire section


(spring loaded terminals)
DIP Switches
RJ45, 8 pins

To next The figure shows the position of


1
CAN bus node the relay contacts when the PS system is in
2
Or alarm mode of operation; the relay coils are
3
RJ45 CAN bus termination plug, if the then de-energized (fail-safe mode)
16 4
SP S controller is the last node in the CAN bus

Internal System Connections


X:g
To Load Fuse —
Load Fuse Sense Input
+
To Battery Fuse —
Battery Fuse Sense Input
+
To Current Shunt — RS232 or RS485 port
Current Sense Input RJ11, 6 pins
+
To System Voltage —
Voltage Sense Input
+

X:h
From Battery +
Power Input Ethernet port
— RJ45, 8 pins
To LVD Contactor 1 +
LVD Output 1

To LVD Contactor 2 +
LVD Output 2

Max. 1.5mm
(14AWG) wire section

Figure 9. Connection Drawing Smartpack S Controller, panel mounted

The Smartpack S panel mounted controllers are usually shipped from factory with
the default CAN bus address "1", as the DIP switches for CAN bus addressing are
350030.013, 2v3-2017-01

not accessible from outside. Notice that the DIP switches are accessible on the
standard Smartpack S controllers, part # 242100.410. Refer to Figure 2 on page
9 and section "CAN Bus Addressing" on page 13.