Beruflich Dokumente
Kultur Dokumente
DSEGenset
ELECTRO-MAGNETIC COMPATIBILITY
The DSE7560 is an Automatic The module will monitor multiple includes RS232 and RS485 ports TEMPERATURE
Transfer Switch and Mains (Utility) mains (utility) supplies, and upon as well as dedicated terminals for BS EN 60068-2-1
Ab/Ae Cold Test -30 oC
Control Module, designed to removal or failure detection of the system expansion. BS EN 60068-2-2
automatically synchronise multiple mains (utility) supply will Bb/Be Dry Heat +70 oC
DSE7510s with single or multiple automatically start or stop the The module’s load share functions VIBRATION
mains (utility) supplies. gen-sets being controlled by include automatic synchronising BS EN 60068-2-6
DSE7510s. The modules with built-in synchroscope and Ten sweeps in each of three
major axes
The module instructs the operational status is indicated on closing onto dead bus. 5 Hz to 8 Hz @ +/-7.5 mm,
DSE7510s to make precise the LCD display and the front 8 Hz to 500 Hz @ 2 gn
changes to the gen-set outputs, panel LEDs. MODULE CAPABILITIES HUMIDITY
and provides sophisticated • Fixed export with mains (utility) BS EN 60068-2-30
monitoring and protection A sophisticated module supply Db Damp Heat Cyclic 20/55 oC
@ 95% RH 48 Hours
functionality making the system monitoring an extensive number of • Will synchronise any BS EN 60068-2-78
ideal for a wide range of load parameters, the DSE7560 will combination of up to 16 gen- Cab Damp Heat Static 40 oC
@ 93% RH 48 Hours
sharing applications including annunciate engine shutdowns, sets with up to 16 mains
peak lopping, peak shaving and warnings, and engine status (utilities) up to a maximum of 20 SHOCK
no-break return. information on the back-lit LCD in one system e.g. 16 gen-sets BS EN 60068-2-27
Three shocks in each of three major axes
screen, by illuminated LED, on a + 4 mains, 4 gensets + 16 15 gn in 11 mS
remote PC, by audible alarm and mains etc.
DEGREES OF PROTECTION
via SMS text alerts. The module PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the supplied sealing gasket.
485
DSE7560 MSC
OTHER
VOLTS CURRENT
ISSUE 5
®
DSEGenset
DSE7560 SPECIFICATION
DC SUPPLY
MAINS (UTILITY)
VOLTAGE RANGE
15 V - 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
OUTPUTS
OUTPUT A (FUEL)
15 A DC at supply voltage
OUTPUT B (START)
15 A DC at supply voltage
OUTPUTS C & D
8 A 250 V (Volt free)
DIMENSIONS
KEY LOAD SHARE FEATURES • Multiple display languages KEY BENEFITS OVERALL
• Fixed export with mains (utility) • LED and LCD alarm indication • 132 x 64 Pixel ratio display for 240 mm x 181 mm x 42 mm
9.4” x 7.1” x 1.6”
• Volts and frequency matching • Customisable status screens clarity
• kW and kV Ar sharing • 9 configurable inputs • Real-time clock provides PANEL CUT-OUT
• Dead bus sensing • 5 configurable outputs accurate event logging 220 mm x 160 mm
8.7” x 6.3”
• Peak lopping • Configurable timers and alarms • Remote monitoring of module
• Peak shaving • Multiple date and time scheduler using comprehensive DSE7500 MAXIMUM PANEL THICKNESS
• No break return • Event log (25) PC software 8 mm
0.3”
• Load demand scheme • Mains (utility) fail monitoring • Ethernet communications (via
• R.O.C.O.F & Vector Shift • Automatic load transfer between DSE860/865 modules), provides
• Mains (utility) de-coupling test mains (utility) and generator advanced remote monitoring at
facility • Manual load transfer between low cost
• Multiple mains (utility) monitoring mains (utility) and generator • Modules can be integrated into
• Synchronising up to 16 generators • Audible alarm building management systems
• Sequential start • Backed-up real-time clock (BMS)
• Auto ID negotiation • Fully configurable via by DSE • Surplus energy/power can be
7500 PC software sold back to the grid (subject to
KEY FEATURES • Multiple display languages local mains/utility supplier)
• 4-Line back-lit LCD text display • Remote SCADA monitoring and • Licence-free PC software
• Five key menu navigation control via DSE7500 PC software • IP65 rating (with supplied
• Front panel editing with PIN • RS485 communications gasket) offers advanced
protection protection from water ingress
RELATED MATERIALS
TITLE PART NO’S OTHER RELATED MATERIALS
DSE7560 Installation Instructions 053-054 TITLE PART NO’S
DSE7500 Quick Start Guide 057-100 DSE7510 Data Sheet 055-065
DSE7560 Operator Manual 057-090 DSE7520 Data Sheet 055-066
DSE7500 PC Software Manual 057-078 DSE850 Comms Software Data Sheet 055-072
Load Share Design and Commissioning 057-047
Guide to Synchronising and Load Sharing 057-045/6
Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 055-067/08/10 (5)
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457