Beruflich Dokumente
Kultur Dokumente
Electrical Apparatus
600 A 15 and 25 kV Class
Deadbreak Apparatus Bushing 800-45
GENERAL
Cooper Power Systems 600 A 15 and
25 kV Class deadbreak apparatus
bushing meets the full requirements
of IEEE Std 386™ standard separable
insulated connector systems. All 600 A
separable connectors manufactured
according to IEEE Std 386™ standard
will operate with this bushing.
The epoxy bushings are designed for
sidewall mounting in transformers,
switches and other apparatus filled
with transformer oil or Envirotemp™
FR3™ Fluid or an approved equivalent.
Separable connector systems, such
as Cooper Power Systems Bol-T™
and T-OP II™ Deadbreak Connectors
as well as other similar systems on
the market, can be used with these
bushings.
INSTALLATION
No special tools are required. The
bushing is mounted through the
apparatus sidewall and clamped
externally. Refer to Installation
Instruction Sheet S800-35-1
(5000050608) for details. Figure 1.
600 A 15 and 25 kV Class Deadbreak Apparatus Bushing.
PRODUCTION TESTS
Tests are conducted in accordance
with IEEE Std 386™ standard.
TABLE 1 TABLE 2
n AC 60 Hz 1 Minute Withstand— Voltage Ratings and Characteristics Current Ratings and Characteristics
40 kV
Description kV Description Amperes
n Minimum Corona Voltage Level—
Standard Voltage Class 25 Continuous 600 A rms (Aluminum)
19 kV 900 A (Copper)
Maximum Rating Phase-to-Ground 15.2 Short Time 25,000 A rms symmetrical
Tests are conducted in accordance with for 0.17 s
Cooper Power Systems requirements: ac 60 Hz 1 Minute Withstand 40
10,000 A rms symmetrical
n Physical Inspection dc 15 Minute Withstand 78 for 3.0 s
BIL and Full Wave Crest 125
n Periodic Dissection
Current ratings and characteristics are in
Minimum Corona Voltage Level 19 accordance with IEEE Std 386™ standard.
n Periodic Fluoroscopic Analysis
(X-ray) Voltage ratings and characteristics are in
accordance with IEEE Std 386™ standard.
4.93 4.69
(125.2 mm) (119.1 mm)
.75
(19.1 mm)
1.36 MAX
(34.5 mm) 5/8-11 UNC
2A THREAD
1.25
(31.8 mm)
Figure 2.
600 A 15 and 25 kV Class Deadbreak Apparatus Bushing.
2
800-45
5/8-11 UNC
THREAD
2.56" BOTH ENDS
5.0 mm)
NK WALL
PENING
Ø .500" Ø 3.25"
(4 REQD) (82.6 mm)
Figure 3.
Clamp front and side view.
5.17"
(131.3 mm)
3.75"
5.3 mm)
1.25"
(31.8 mm)
5/8-11 UNC
THREAD 3
BOTH ENDS