WARNING
This service information is designed for experienced repair technicians only and is not designed for use by the general public.
It does not contain warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product.
Products powered by electricity should be serviced or repaired only by experienced professional technicians. Any attempt to
service or repair the products dealt with in this service information by anyone else could result in serious injury or death.
WARNING This indication shows the possibility of causing death or serious injury.
CAUTION This indication shows the possibility of causing injury or damage to properties.
• Carry out test run to confirm that no abnormality occurs after the servicing. Then, explain to user the operation, care and
maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference.
WARNING
2. If wiring unit is supplied as repairing part, do not repair or connect the wire even only partial wire break. Exchange the whole wiring unit.
Engage authorized dealer or specialist for installation and servicing. If installation of servicing done by the user is defective, it will cause
4.
water leakage, electrical shock or fire.
5. Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electric shock or fire.
Use the attached accessories parts and specified parts for installation and servicing. Otherwise, it will cause the set to fall, water leakage,
6.
fire or electrical shock.
Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly
7.
done, the set will drop and cause injury.
For electrical work, follow the local national wiring standard, regulation and the installation instruction. An independent circuit and single
8.
outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire.
This equipment is strongly recommended to be installed with Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD).
9.
Otherwise, it may cause electrical shock and fire in case equipment breakdown or insulation breakdown.
Do not use joint cable for indoor/outdoor connection cable. Use the specified indoor/outdoor connection cable, refer to installation
10. instruction CONNECT THE CABLE TO THE INDOOR UNIT and connect tightly for indoor/outdoor connection. Clamp the cable so that no
external force will be acted on the terminal. If connecting or fixing is not perfect, it will cause heat up or fire at the connection.
Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will
11.
cause heat-up or fire at the connection point of terminal, fire or electrical shock.
When install or relocate air conditioner, do not let any substance other than the specified refrigerant, eg. air etc. mix into refrigeration cycle
12.
(piping). (Mixing of air etc. will cause abnormal high pressure in refrigeration cycle and result in explosion, injury etc.).
Do not install outdoor unit near handrail of veranda. When installing air-conditioner unit at veranda of high rise building, child may climb up
13.
to outdoor unit and cross over the handrail and causing accident.
This equipment must be properly earthed. Earth line must not be connected to gas pipe, water pipe, earth of lightning rod and
14.
telephone. Otherwise, it may cause electrical shock in case equipment breakdown or insulation breakdown.
15. Keep away from small children, the thin film may cling to nose and mouth and prevent breathing.
Do not use unspecified cord, modified cord, joint cord or extension cord for power supply cord. Do not share the single outlet with
16.
other electrical appliances. Poor contact, poor insulation or over current will cause electrical shock or fire.
Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the flare may
17.
break and cause refrigerant gas leakage.
For R410A model, use piping, fl are nut and tools which is specified for R410A refrigerant. Using of existing (R22) piping, fl are
nut and tools may cause abnormally high pressure in the refrigerant cycle (piping), and possibly result in explosion and injury.
18.
Thickness of copper pipes used with R410A must be more than 0.6mm. Never use copper pipes thinner than 0.6mm.
It is desirable that the amount of residual oil is less than 40 mg/10m.
3
WARNING
During installation, install the refrigerant piping properly before run the compressor. (Operation of compressor without fixing refrigeration
19. piping and valves at opened condition will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury
etc.).
During pump down operation, stop the compressor before remove the refrigeration piping. (Removal of refrigeration piping while
20. compressor is operating and valves are opened condition will cause suck-in of air, abnormal high pressure in refrigeration cycle and result
in explosion, injury etc.) .
After completion of installation or service, confirm there is no leakage of refrigerant gas. It may generate toxic gas when the refrigerant
21.
contacts with fire.
22. Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when the refrigerant contacts with fire.
23. Do not insert your fingers or other objects into the unit, high speed rotating fan may cause injury
24. Must not use other parts except original parts describe in catalog and manual.
25. Using of refrigerant other than the specified type may cause product damage, burst and injury etc.
CAUTION
Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at surrounding of
1.
the unit, it may cause fire.
Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the
2.
furniture.
Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the flare may
3.
break and cause refrigerant gas leakage.
4. Do not touch outdoor unit air inlet and aluminium fin. It may cause injury.
Pb free solder has a higher melting point than standard solder; typically the melting point is 50°F – 70°F (30°C – 40°C) higher. Please use
6. a high temperature solder iron. In case of the soldering iron with temperature control, please set it to 700 ± 20°F (370 ± 10°C).
Pb free solder will tend to splash when heated too high (about 1100°F / 600°C).
CS/CU-S10/13/15/18/24PK
Power supply connection to the room air conditioner.
Use power supply cord 3 × 1.5 mm² (1.0 ~ 1.75HP) or 3 × 2.5 mm² (2.0 ~ 2.5HP) type designation 60245 IEC 57 or heavier cord. Connect
the power supply cord of the air conditioner to the mains using one of the following method. Power supply point should be in easily
accessible place for power disconnection in case of emergency. In some countries, permanent connection of this air conditioner to the
7. power supply is prohibited.
i. Power supply connection to the receptacle using power plug.
Use an approved 15/16A (1.0 ~ 1.75HP) or 16A (2.0HP) or 20A (2.5HP) power plug with earth pin for the connection to the socket.
ii. Power supply connection to a circuit breaker for the permanent connection.
Use an approved 16A (1.0 ~ 2.0HP) or 20A (2.5HP) circuit breaker for the permanent connection. It must be a double pole switch with
a minimum 3.0 mm contact gap.
Myanmar only
Power supply connection to the room air conditioner.
Use power supply cord 3 × 1.5 mm² (1.0 ~ 1.5HP) or 3 × 2.5 mm² (2.0 ~ 2.5HP) type designation 60245 IEC 57 or heavier cord. Connect
the power supply cord of the air conditioner to the mains using one of the following method. Power supply point should be in easily
accessible place for power disconnection in case of emergency. In some countries, permanent connection of this air conditioner to the
8. power supply is prohibited.
i. Power supply connection to the receptacle using power plug.
Use an approved 15/16A (1.0 ~ 1.5HP) or 16A (2.0HP) or 20A (2.5HP) power plug with earth pin for the connection to the socket.
ii. Power supply connection to a circuit breaker for the permanent connection.
Use an approved 16A (1.0 ~ 2.0HP) or 20A (2.5HP) circuit breaker for the permanent connection. It must be a double pole switch with
a minimum 3.0 mm contact gap.
Do not release refrigerant during piping work for installation, servicing, reinstallation and during repairing a refrigerant parts. Take
9.
care of the liquid refrigerant, it may cause frostbite.
10. Installation or servicing work: It may need two people to carry out the installation or servicing work.
11. Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.
12. Do not sit or step on the unit, you may fall down accidentally.
4
2. Specification
Indoor CS-S10PKH (MALAYSIA) CS-S13PKH (MALAYSIA)
Model
Outdoor CU-S10PKH (MALAYSIA) CU-S13PKH (MALAYSIA)
Performance Test Condition JIS JIS
Phase, Hz Single, 50 Single, 50
Power Supply
V 230 230
Min. Mid. Max. Min. Mid. Max.
kW 0.84 2.80 3.28 0.92 3.66 4.20
Capacity BTU/h 2860 9550 11200 3140 12500 14300
kJ/h 3020 10080 11810 3310 13180 15120
Running Current A – 3.6 – – 4.8 –
Input Power W 225 760 920 260 1.04k 1.20k
Cooling
Output Power W 40 24
QLo rpm 610 650
Lo rpm 680 720
Speed Me rpm 840 910
Hi rpm 1000 1100
SHi rpm 1130 1130
Type Propeller Fan Propeller Fan
Material PP Resin PP Resin
Outdoor Fan
5
Indoor CS-S10PKH (MALAYSIA) CS-S13PKH (MALAYSIA)
Model
Outdoor CU-S10PKH (MALAYSIA) CU-S13PKH (MALAYSIA)
Control Device Capillary Tube Capillary Tube
Refrigeration 3
Refrigerant Oil cm FV50S (250) FV50S (320)
Cycle
Refrigerant Type g (oz) R410A, 740 (26.1) R410A, 690 (24.4)
Height (I/D / O/D) mm (inch) 290 (11-7/16) 511 (20-1/8) 290 (11-7/16) 542 (21-11/32)
Dimension Width (I/D / O/D) mm (inch) 870 (34-9/32) 650 (25-19/32) 870 (34-9/32) 780 (30-23/32)
Depth (I/D / O/D) mm (inch) 214 (8-7/16) 230 (9-1/16) 214 (8-7/16) 289 (11-13/32)
Weight Net (I/D / O/D) kg (lb) 9 (20) 20 (44) 9 (20) 30 (66)
Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 9.52 (3/8) 6.35 (1/4) / 12.70 (1/2)
Standard length m (ft) 7.5 (24.6) 7.5 (24.6)
Length range (min – max) m (ft) 3 (9.8) ~ 15 (49.2) 3 (9.8) ~ 15 (49.2)
Piping
1. Cooling capacities are based on indoor temperature of 27°C DRY BULB (80.6°F DRY BULB), 19.0°C WET BULB (66°F WET BULB) and
outdoor air temperature of 35°C DRY BULB (95°F DRY BULB), 24°C WET BULB (75.2°F WET BULB)
6
Indoor CS-S15PKH (MALAYSIA)
Model
Outdoor CU-S15PKH (MALAYSIA)
Performance Test Condition JIS
Phase, Hz Single, 50
Power Supply
V 230
Min. Mid. Max.
kW 1.07 4.40 5.00
Capacity BTU/h 3650 15000 17100
kJ/h 3850 15840 18000
Running Current A – 5.4 –
Input Power W 285 1.18k 1.36k
Cooling
Output Power W 40
QLo rpm 710
Lo rpm 780
Speed Me rpm 1010
Hi rpm 1240
SHi rpm 1340
Type Propeller Fan
Material PP Resin
Outdoor Fan
7
Indoor CS-S15PKH (MALAYSIA)
Model
Outdoor CU-S15PKH (MALAYSIA)
Control Device Capillary tube
Refrigeration 3
Refrigerant Oil cm FV50S (320)
Cycle
Refrigerant Type g (oz) R410A, 950 (33.5)
Height (I/D / O/D) mm (inch) 290 (11-7/16) 542 (21-11/32)
Dimension Width (I/D / O/D) mm (inch) 870 (34-9/32) 780 (30-23/32)
Depth (I/D / O/D) mm (inch) 214 (8-7/16) 289 (11-13/32)
Weight Net (I/D / O/D) kg (lb) 9 (20) 31 (68)
Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 12.70 (1/2)
Standard length m (ft) 7.5 (24.6)
Length range (min – max) m (ft) 3 (9.8) ~ 15 (49.2)
Piping
1. Cooling capacities are based on indoor temperature of 27°C DRY BULB (80.6°F DRY BULB), 19.0°C WET BULB (66°F WET BULB) and
outdoor air temperature of 35°C DRY BULB (95°F DRY BULB), 24°C WET BULB (75.2°F WET BULB)
8
Indoor CS-S18PKH (MALAYSIA) CS-S24PKH (MALAYSIA)
Model
Outdoor CU-S18PKH (MALAYSIA) CU-S24PKH (MALAYSIA)
Performance Test Condition JIS JIS
Phase, Hz Single, 50 Single, 50
Power Supply
V 230 230
Min. Mid. Max. Min. Mid. Max.
kW 1.10 5.27 6.00 1.12 6.25 7.10
Capacity BTU/h 3750 18000 20500 3820 21300 24200
kJ/h 3960 18970 21600 4030 22500 25560
Running Current A – 6.8 – – 8.6 –
Input Power W 290 1.47k 1.70k 320 1.88k 2.20k
Cooling
Output Power W 40 40
QLo rpm 750 850
Lo rpm 820 920
Speed Me rpm 1040 1150
Hi rpm 1260 1370
SHi rpm 1400 1450
Type Propeller Fan Propeller Fan
Material PP Resin PP Resin
Outdoor Fan
9
Indoor CS-S18PKH (MALAYSIA) CS-S24PKH (MALAYSIA)
Model
Outdoor CU-S18PKH (MALAYSIA) CU-S24PKH (MALAYSIA)
Height (I/D / O/D) mm (inch) 290 (11-7/16) 619 (24-3/8) 290 (11-7/16) 695 (27-3/8)
Dimension Width (I/D / O/D) mm (inch) 1070 (42-5/32) 824 (32-15/32) 1070 (42-5/32) 875 (34-15/32)
Depth (I/D / O/D) mm (inch) 240 (9-15/32) 299 (11-25/32) 240 (9-15/32) 320 (12-5/8)
Weight Net (I/D / O/D) kg (lb) 12 (26) 32 (71) 12 (26) 44 (97)
Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 12.70 (1/2 ) 6.35 (1/4) / 15.88 (5/8)
Standard length m (ft) 5.0 (16.4) 5.0 (16.4)
Length range (min – max) m (ft) 3 (9.8) ~ 20 (65.6) 3 (9.8) ~ 20 (65.6)
Piping
1. Cooling capacities are based on indoor temperature of 27°C DRY BULB (80.6°F DRY BULB), 19.0°C WET BULB (66°F WET BULB) and
outdoor air temperature of 35°C DRY BULB (95°F DRY BULB), 24°C WET BULB (75.2°F WET BULB
10
Indoor CS-S10PKH (MYANMAR) CS-S13PKH (MYANMAR)
Model
Outdoor CU-S10PKH (MYANMAR) CU-S13PKH (MYANMAR)
Performance Test Condition JIS JIS
Phase, Hz Single, 50 Single, 50
Power Supply
V 220 240 220 240
Min. Mid. Max. Min. Mid. Max. Min. Mid. Max. Min. Mid. Max.
kW 0.84 2.85 3.28 0.84 2.85 3.28 0.92 3.67 4.20 0.92 3.67 4.20
Capacity BTU/h 2860 9720 11200 2860 9720 11200 3140 12500 14300 3140 12500 14300
kJ/h 3020 10260 11810 3020 10260 11810 3310 13210 15120 3310 13210 15120
Running Current A – 3.6 – – 3.3 – – 5.1 – – 4.6 –
Input Power W 225 730 920 225 730 920 260 1.01k 1.20k 260 1.01k 1.20k
Cooling
W/W 3.73 3.90 3.57 3.73 3.90 3.57 3.54 3.63 3.50 3.54 3.63 3.50
EER BTU/hW 12.71 13.32 12.17 12.71 13.32 12.17 12.08 12.38 11.92 12.08 12.38 11.92
kJ/hW 13.42 14.05 12.84 13.42 14.05 12.84 12.73 13.08 12.60 12.73 13.08 12.60
Power Factor % – 92 – – 92 – – 90 – – 91 –
Indoor Noise (H / L / QLo) dB-A 36 / 26 / 23 36 / 26 / 23 38 / 28 / 25 38 / 28 / 25
Outdoor Noise (H / L / QLo) dB-A 46 / – / – 47 / – / – 47 / – / – 48 / – / –
Max Current (A) / Max Input Power (W) 5.6 / 1.12k 7.4 / 1.40k
Starting Current (A) 3.6 5.1
Type Hermetic Motor / Rotary Hermetic Motor / Rotary
Compressor Motor Type Brushless (6 poles) Brushless (6 poles)
Output Power W 500 650
Type Cross-Flow Fan Cross-Flow Fan
Material ASG20K1 ASG20K1
Motor Type AC / Induction (4 poles) AC / Induction (4 poles)
Input Power W 51.0 - 58.0 51.0 - 58.0
Indoor Fan
Output Power W 24 24
QLo rpm 610 - 610 650 - 650
Lo rpm 680 - 680 720 - 720
Speed Me rpm 840 - 840 910 - 910
Hi rpm 1000 - 1000 1100 - 1100
SHi rpm 1130 - 1130 1130 - 1130
Type Propeller Fan Propeller Fan
Material PP Resin PP Resin
Outdoor Fan
11
Indoor CS-S10PKH (MYANMAR) CS-S13PKH (MYANMAR)
Model
Outdoor CU-S10PKH (MYANMAR) CU-S13PKH (MYANMAR)
Control Device Capillary Tube Capillary Tube
Refrigeration 3
Refrigerant Oil cm FV50S (250) FV50S (320)
Cycle
Refrigerant Type g (oz) R410A, 740 (26.1) R410A, 690 (24.4)
Height (I/D / O/D) mm (inch) 290 (11-7/16) 511 (20-1/8) 290 (11-7/16) 542 (21-11/32)
Dimension Width (I/D / O/D) mm (inch) 870 (34-9/32) 650 (25-19/32) 870 (34-9/32) 780 (30-23/32)
Depth (I/D / O/D) mm (inch) 214 (8-7/16) 230 (9-1/16) 214 (8-7/16) 289 (11-13/32)
Weight Net (I/D / O/D) kg (lb) 9 (20) 20 (44) 9 (20) 30 (66)
Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 9.52 (3/8) 6.35 (1/4) / 12.70 (1/2)
Standard length m (ft) 7.5 (24.6) 7.5 (24.6)
Length range (min – max) m (ft) 3 (9.8) ~ 15 (49.2) 3 (9.8) ~ 15 (49.2)
Piping
1. Cooling capacities are based on indoor temperature of 27°C DRY BULB (80.6°F DRY BULB), 19.0°C WET BULB (66°F WET BULB) and
outdoor air temperature of 35°C DRY BULB (95°F DRY BULB), 24°C WET BULB (75.2°F WET BULB)
12
Indoor CS-S18PKH (MYANMAR) CS-S24PKH (MYANMAR)
Model
Outdoor CU-S18PKH (MYANMAR) CU-S24PKH (MYANMAR)
Performance Test Condition JIS JIS
Phase, Hz Single, 50 Single, 50
Power Supply
V 220 240 220 240
Min. Mid. Max. Min. Mid. Max. Min. Mid. Max. Min. Mid. Max.
kW 1.10 5.30 6.00 1.10 5.30 6.00 1.12 6.25 7.10 1.12 6.25 7.10
Capacity BTU/h 3750 18100 20500 3750 18100 20500 3820 21300 24200 3820 21300 24200
kJ/h 3960 19080 21600 3960 19080 21600 4030 22500 25560 4030 22500 25560
Running Current A – 7.0 – – 6.4 – – 8.8 – – 8.2 –
Input Power W 290 1.44k 1.70k 290 1.44k 1.70k 320 1.88k 2.20k 320 1.88k 2.20k
Cooling
W/W 3.79 3.68 3.53 3.79 3.68 3.53 3.50 3.32 3.23 3.50 3.32 3.23
EER BTU/hW 12.93 12.57 12.06 12.93 12.57 12.06 11.94 11.33 11.00 11.94 11.33 11.00
kJ/hW 13.66 13.25 12.71 13.66 13.25 12.71 12.59 11.97 11.62 12.59 11.97 11.62
Power Factor % – 94 – – 94 – – 97 – – 96 –
Indoor Noise (H / L / QLo) dB-A 44 / 32 / 29 44 / 32 / 29 45 / 34 / 31 45 / 34 / 31
Outdoor Noise (H / L / QLo) dB-A 49 / – / – 50 / – / – 51 / – / – 52 / – / –
Max Current (A) / Max Input Power (W) 10.5 / 2.19k 11.7 / 2.35k
Starting Current (A) 7.0 8.8
Type Hermetic Motor / Rotary Hermetic Motor / Rotary
Compressor Motor Type Brushless (6 poles) Brushless (6 poles)
Output Power W 900 900
Type Cross-Flow Fan Cross-Flow Fan
Material ASG30K1 ASG30K1
Motor Type DC / Transistor (8-poles) DC / Transistor (8-poles)
Input Power W 94.8 - 94.8 94.8 - 94.8
Indoor Fan
Output Power W 40 40
QLo rpm 750 - 750 850 - 850
Lo rpm 820 - 820 920 - 920
Speed Me rpm 1040 - 1040 1150 - 1150
Hi rpm 1260 - 1260 1370 - 1370
SHi rpm 1400 - 1400 1450 - 1450
Type Propeller Fan Propeller Fan
Material PP Resin PP Resin
Outdoor Fan
13
Indoor CS-S18PKH (MYANMAR) CS-S24PKH (MYANMAR)
Model
Outdoor CU-S18PKH (MYANMAR) CU-S24PKH (MYANMAR)
Control Device Capillary Tube Capillary Tube
Refrigeration 3
Refrigerant Oil cm FV50S (450) FV50S (450)
Cycle
Refrigerant Type g (oz) R410A, 1.09k (38.5) R410A, 1.29k (45.5)
Height (I/D / O/D) mm (inch) 290 (11-7/16) 619 (24-3/8) 290 (11-7/16) 695 (27-3/8)
Dimension Width (I/D / O/D) mm (inch) 1070 (42-5/32) 824 (32-15/32) 1070 (42-5/32) 875 (34-15/32)
Depth (I/D / O/D) mm (inch) 240 (9-15/32) 299 (11-25/32) 240 (9-15/32) 320 (12-5/8)
Weight Net (I/D / O/D) kg (lb) 12 (26) 32 (71) 12 (26) 44 (97)
Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 12.70 (1/2) 6.35 (1/4) / 15.88 (5/8)
Standard length m (ft) 5.0 (16.4) 5.0 (16.4)
Length range (min – max) m (ft) 3 (9.8) ~ 20 (65.6) 3 (9.8) ~ 20 (65.6)
Piping
1. Cooling capacities are based on indoor temperature of 27°C DRY BULB (80.6°F DRY BULB), 19.0°C WET BULB (66°F WET BULB) and
outdoor air temperature of 35°C DRY BULB (95°F DRY BULB), 24°C WET BULB (75.2°F WET BULB)
14
Indoor CS-S10PKH (S.E.ASIA) CS-S13PKH (S.E.ASIA)
Model
Outdoor CU-S10PKH (S.E.ASIA) CU-S13PKH (S.E.ASIA)
Performance Test Condition JIS JIS
Phase, Hz Single, 50 Single, 50
Power Supply
V 220 240 220 240
Min. Mid. Max. Min. Mid. Max. Min. Mid. Max. Min. Mid. Max.
kW 0.84 2.85 3.28 0.84 2.85 3.28 0.92 3.67 4.20 0.92 3.67 4.20
Capacity BTU/h 2860 9720 11200 2860 9720 11200 3140 12500 14300 3140 12500 14300
kJ/h 3020 10260 11810 3020 10260 11810 3310 13210 15120 3310 13210 15120
Running Current A – 3.6 – – 3.3 – – 5.1 – – 4.6 –
Input Power W 225 730 920 225 730 920 260 1.01k 1.20k 260 1.01k 1.20k
Cooling
W/W 3.73 3.90 3.57 3.73 3.90 3.57 3.54 3.63 3.50 3.54 3.63 3.50
EER BTU/hW 12.71 13.32 12.17 12.71 13.32 12.17 12.08 12.38 11.92 12.08 12.38 11.92
kJ/hW 13.42 14.05 12.84 13.42 14.05 12.84 12.73 13.08 12.60 12.73 13.08 12.60
Power Factor % – 92 – – 92 – – 90 – – 91 –
Indoor Noise (H / L / QLo) dB-A 36 / 26 / 23 36 / 26 / 23 38 / 28 / 25 38 / 28 / 25
Outdoor Noise (H / L / QLo) dB-A 46 / – / – 47 / – / – 47 / – / – 48 / – / –
Max Current (A) / Max Input Power (W) 5.6 / 1.12k 7.4 / 1.40k
Starting Current (A) 3.6 5.1
Type Hermetic Motor / Rotary Hermetic Motor / Rotary
Compressor Motor Type Brushless (6 poles) Brushless (6 poles)
Output Power W 500 650
Type Cross-Flow Fan Cross-Flow Fan
Material ASG20K1 ASG20K1
Motor Type AC / Induction (4 poles) AC / Induction (4 poles)
Input Power W 51.0 - 58.0 51.0 - 58.0
Indoor Fan
Output Power W 24 24
QLo rpm 610 - 610 650 - 650
Lo rpm 680 - 680 720 - 720
Speed Me rpm 840 - 840 910 - 910
Hi rpm 1000 - 1000 1100 - 1100
SHi rpm 1130 - 1130 1130 - 1130
Type Propeller Fan Propeller Fan
Material PP Resin PP Resin
Outdoor Fan
15
Indoor CS-S10PKH (S.E.ASIA) CS-S13PKH (S.E.ASIA)
Model
Outdoor CU-S10PKH (S.E.ASIA) CU-S13PKH (S.E.ASIA)
Control Device Capillary Tube Capillary Tube
Refrigeration 3
Refrigerant Oil cm FV50S (250) FV50S (320)
Cycle
Refrigerant Type g (oz) R410A, 740 (26.1) R410A, 690 (24.4)
Height (I/D / O/D) mm (inch) 290 (11-7/16) 511 (20-1/8) 290 (11-7/16) 542 (21-11/32)
Dimension Width (I/D / O/D) mm (inch) 870 (34-9/32) 650 (25-19/32) 870 (34-9/32) 780 (30-23/32)
Depth (I/D / O/D) mm (inch) 214 (8-7/16) 230 (9-1/16) 214 (8-7/16) 289 (11-13/32)
Weight Net (I/D / O/D) kg (lb) 9 (20) 20 (44) 9 (20) 30 (66)
Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 9.52 (3/8) 6.35 (1/4) / 12.70 (1/2)
Standard length m (ft) 7.5 (24.6) 7.5 (24.6)
Length range (min – max) m (ft) 3 (9.8) ~ 15 (49.2) 3 (9.8) ~ 15 (49.2)
Piping
1. Cooling capacities are based on indoor temperature of 27°C DRY BULB (80.6°F DRY BULB), 19.0°C WET BULB (66°F WET BULB) and
outdoor air temperature of 35°C DRY BULB (95°F DRY BULB), 24°C WET BULB (75.2°F WET BULB)
16
Indoor CS-S15PKH (S.E.ASIA)
Model
Outdoor CU-S15PKH (S.E.ASIA)
Performance Test Condition JIS
Phase, Hz Single, 50
Power Supply
V 220 240
Min. Mid. Max. Min. Mid. Max.
kW 1.07 4.40 5.00 1.07 4.40 5.00
Capacity BTU/h 3650 15000 17100 3650 15000 17100
kJ/h 3850 15840 18000 3850 15840 18000
Running Current A – 6.0 – – 5.3 –
Input Power W 285 1.16k 1.36k 285 1.16k 1.36k
Cooling
Output Power W 40
QLo rpm 710 - 710
Lo rpm 780 - 780
Speed Me rpm 1010 - 1010
Hi rpm 1240 - 1240
SHi rpm 1340 - 1340
Type Propeller Fan
Material PP Resin
Outdoor Fan
17
Indoor CS-S15PKH (S.E.ASIA)
Model
Outdoor CU-S15PKH (S.E.ASIA)
Control Device Capillary tube
Refrigeration 3
Refrigerant Oil cm FV50S (320)
Cycle
Refrigerant Type g (oz) R410A, 950 (33.5)
Height (I/D / O/D) mm (inch) 290 (11-7/16) 542 (21-11/32)
Dimension Width (I/D / O/D) mm (inch) 870 (34-9/32) 780 (30-23/32)
Depth (I/D / O/D) mm (inch) 214 (8-7/16) 289 (11-13/32)
Weight Net (I/D / O/D) kg (lb) 9 (20) 31 (68)
Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 12.70 (1/2)
Standard length m (ft) 7.5 (24.6)
Length range (min – max) m (ft) 3 (9.8) ~ 15 (49.2)
Piping
1. Cooling capacities are based on indoor temperature of 27°C DRY BULB (80.6°F DRY BULB), 19.0°C WET BULB (66°F WET BULB) and
outdoor air temperature of 35°C DRY BULB (95°F DRY BULB), 24°C WET BULB (75.2°F WET BULB)
18
Indoor CS-S18PKH (S.E.ASIA) CS-S24PKH (S.E.ASIA)
Model
Outdoor CU-S18PKH (S.E.ASIA) CU-S24PKH (S.E.ASIA)
Performance Test Condition JIS JIS
Phase, Hz Single, 50 Single, 50
Power Supply
V 220 240 220 240
Min. Mid. Max. Min. Mid. Max. Min. Mid. Max. Min. Mid. Max.
kW 1.10 5.30 6.00 1.10 5.30 6.00 1.12 6.25 7.10 1.12 6.25 7.10
Capacity BTU/h 3750 18100 20500 3750 18100 20500 3820 21300 24200 3820 21300 24200
kJ/h 3960 19080 21600 3960 19080 21600 4030 22500 25560 4030 22500 25560
Running Current A – 7.0 – – 6.4 – – 8.8 – – 8.2 –
Input Power W 290 1.44k 1.70k 290 1.44k 1.70k 320 1.88k 2.20k 320 1.88k 2.20k
Cooling
W/W 3.79 3.68 3.53 3.79 3.68 3.53 3.50 3.32 3.23 3.50 3.32 3.23
EER BTU/hW 12.93 12.57 12.06 12.93 12.57 12.06 11.94 11.33 11.00 11.94 11.33 11.00
kJ/hW 13.66 13.25 12.71 13.66 13.25 12.71 12.59 11.97 11.62 12.59 11.97 11.62
Power Factor % – 94 – – 94 – – 97 – – 96 –
Indoor Noise (H / L / QLo) dB-A 44 / 32 / 29 44 / 32 / 29 45 / 34 / 31 45 / 34 / 31
Outdoor Noise (H / L / QLo) dB-A 49 / – / – 50 / – / – 51 / – / – 52 / – / –
Max Current (A) / Max Input Power (W) 10.5 / 2.19k 11.7 / 2.35k
Starting Current (A) 7.0 8.8
Type Hermetic Motor / Rotary Hermetic Motor / Rotary
Compressor Motor Type Brushless (6 poles) Brushless (6 poles)
Output Power W 900 900
Type Cross-Flow Fan Cross-Flow Fan
Material ASG30K1 ASG30K1
Motor Type DC / Transistor (8-poles) DC / Transistor (8-poles)
Input Power W 94.8 - 94.8 94.8 - 94.8
Indoor Fan
Output Power W 40 40
QLo rpm 750 - 750 850 - 850
Lo rpm 820 - 820 920 - 920
Speed Me rpm 1040 - 1040 1150 - 1150
Hi rpm 1260 - 1260 1370 - 1370
SHi rpm 1400 - 1400 1450 - 1450
Type Propeller Fan Propeller Fan
Material PP Resin PP Resin
Outdoor Fan
19
Indoor CS-S18PKH (S.E.ASIA) CS-S24PKH (S.E.ASIA)
Model
Outdoor CU-S18PKH (S.E.ASIA) CU-S24PKH (S.E.ASIA)
Control Device Capillary Tube Capillary Tube
Refrigeration 3
Refrigerant Oil cm FV50S (450) FV50S (450)
Cycle
Refrigerant Type g (oz) R410A, 1.09k (38.5) R410A, 1.29k (45.5)
Height (I/D / O/D) mm (inch) 290 (11-7/16) 619 (24-3/8) 290 (11-7/16) 695 (27-3/8)
Dimension Width (I/D / O/D) mm (inch) 1070 (42-5/32) 824 (32-15/32) 1070 (42-5/32) 875 (34-15/32)
Depth (I/D / O/D) mm (inch) 240 (9-15/32) 299 (11-25/32) 240 (9-15/32) 320 (12-5/8)
Weight Net (I/D / O/D) kg (lb) 12 (26) 32 (71) 12 (26) 44 (97)
Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 12.70 (1/2) 6.35 (1/4) / 15.88 (5/8)
Standard length m (ft) 5.0 (16.4) 5.0 (16.4)
Length range (min – max) m (ft) 3 (9.8) ~ 20 (65.6) 3 (9.8) ~ 20 (65.6)
Piping
1. Cooling capacities are based on indoor temperature of 27°C DRY BULB (80.6°F DRY BULB), 19.0°C WET BULB (66°F WET BULB) and
outdoor air temperature of 35°C DRY BULB (95°F DRY BULB), 24°C WET BULB (75.2°F WET BULB)
20
3. Location of Controls and Components
3.1 Indoor Unit
Aluminium Fin Auto OFF/ON button
Air Filters • Use when remote control is misplaced or a malfunction occurs
Indicator
Front panel (Green)
POWER (Green)
TIMER (Orange)
R
PO WE
TIMER
AUTO
COMFORT
NANO E
-G
AUTO COMFORT (Green)
RFUL
PO WE
QUIET
21
4. Dimensions
4.1 Indoor Unit
4.1.1 CS-S10PK CS-S13PK CS-S15PK
22
4.1.2 CS-S18PK CS-S24PK
23
4.2 Outdoor Unit
4.2.1 CU-S10PK
24
4.2.3 CU-S18PK
25
4.2.4 CU-S24PK
26
5. Refrigeration Cycle Diagram
5.1 CS-S10PK CU-S10PK CS-S13PK CU-S13PK CS-S15PK CU-S15PK
INDOOR OUTDOOR
LIQUID
SIDE CAPILLARY TUBE STRAINER
PIPE
TEMP.
2-WAY SENSOR
VALVE
PIPE
TEMP.
SENSOR
INTAKE INTAKE
TEMP.
TEMP.
SENSOR SENSOR
GAS
SIDE
3-WAY
VALVE
COMPRESSOR
TEMP. SENSOR
COMPRESSOR
COOLING
27
5.2 CS-S18PK CU-S18PK CS-S24PK CU-S24PK
INDOOR OUTDOOR
LIQUID
SIDE CAPILLARY TUBE STRAINER
PIPE
TEMP.
2-WAY SENSOR
VALVE
PIPE
TEMP.
SENSOR
INTAKE
INTAKE
TEMP. TEMP.
SENSOR
SENSOR
GAS
SIDE
3-WAY
VALVE
COMPRESSOR
TEMP.
SENSOR
COMPRESSOR
COOLING
28
6. Block Diagram
6.1 CS-S10PKH CU-S10PKH (Malaysia only)
29
6.2 CS-S10PK CU-S10PK (except Malaysia)
30
6.3 CS-S13PK CU-S13PK
31
6.4 CS-S15PK CU-S15PK
32
6.5 CS-S18PK CU-S18PK
33
6.6 CS-S24PK CU-S24PK
34
7. Wiring Connection Diagram
7.1 Indoor Unit
7.1.1 CS-S10PKH (Malaysia only) CS-S15PK CS-S18PK CS-S24PK
35
7.1.2 CS-S10PK (except Malaysia) CS-S13PK
Resistance of Indoor Fan Motor Windings Resistance of Indoor Fan Motor Windings
CS-S10PKH / CS-S13PKH
MODEL CS-S13PKH (Malaysia only) MODEL
(except Malaysia)
CONNECTION CWA921441 CONNECTION CWA921442
BLUE-YELLOW 366Ω BLUE-YELLOW 407.7Ω
BLUE-RED 338Ω BLUE-RED 370.6Ω
Note: Resistance at 20°C of ambient temperature. Note: Resistance at 20°C of ambient temperature.
36
7.2 Outdoor Unit
7.2.1 CU-S10PK
YELLOW (YLW)
37
7.2.2 CU-S13PK
TO INDOOR UNIT YELLOW (YLW)
1 2 3 TERMINAL
(BLACK) (WHITE) (RED) BOARD
REACTOR
BLUE (BLU) RED (RED)
TRADE MARK
RED COMP. TERMINAL
GRY GRY
RAT2 RAT1
FUSE104 (GRY) (GRY)
DATA (15A 250V)
(RED) OUTDOOR AIR TEMP.
WHT
BLK
SENSOR (THERMISTOR)
1 t
0
4
(BLK) CIRCUIT PIPING TEMP.
SENSOR (THERMISTOR)
FUSE101
(20A 250V) FUSE102
T3.15A L250V SWITCHING POWER
AC-WHT SUPPLY CIRCUIT
(WHT) COMP. TEMPERATURE
SENSOR (THERMISTOR)
FG1 CN-TANK 1 t
0
FG2
GRN (GRN) PFC RECTIFICATION
CIRCUIT CIRCUIT
38
7.2.3 CU-S15PK
TO INDOOR UNIT YELLOW (YLW)
1 2 3 TERMINAL
(BLACK) (WHITE) (RED) BOARD
REACTOR
BLUE (BLU) RED (RED)
TRADE MARK
RED COMP. TERMINAL
GRY GRY
RAT2 RAT1
FUSE104 (GRY) (GRY)
DATA (15A 250V)
(RED) OUTDOOR AIR TEMP.
WHT
BLK
SENSOR (THERMISTOR)
1 t
0
4
(BLK) CIRCUIT PIPING TEMP.
SENSOR (THERMISTOR)
FUSE101
(20A 250V) FUSE102
T3.15A L250V SWITCHING POWER
AC-WHT SUPPLY CIRCUIT
(WHT) COMP. TEMPERATURE
SENSOR (THERMISTOR)
FG1 CN-TANK 1 t
0
FG2
GRN (GRN) PFC RECTIFICATION
CIRCUIT CIRCUIT
39
7.2.4 CU-S18PK
YELLOW
TO INDOOR UNIT (YEL) OR (C)
1 2 3 TERMINAL
(BLACK) (WHITE) (RED) BOARD
REACTOR BLUE RED
(BLU) OR (R) (RED) OR (S)
TRADE MARK
SENSOR (THERMISTOR)
1 t
0
CIRCUIT 4
(BLK)
PIPING TEMP.
SENSOR (THERMISTOR)
FUSE 103
(20A 250V) FUSE 104
T3.15A L250V
AC-WHT
(WHT)
FG1 CN-TANK 1 t
0
40
7.2.5 CU-S24PK
TO INDOOR UNIT YELLOW (YLW)
1 2 3 TERMINAL
(BLACK) (WHITE) (RED) BOARD
REACTOR
BLUE (BLU) RED (RED)
TRADE MARK
SENSOR (THERMISTOR)
1 t
0
1
FUSE1
T2.50A L250V
BLU FAN MOTOR
M RED 5 CIRCUIT
1~ YLW P
(RED) RED
CN-ACFM U
(WHT) (BLU) BLU MS
V
FAN MOTOR (YLW) YLW 3~
BLU W
CAPACITOR N
COMPRESSOR
ELECTRONIC CONTROLLER
41
8. Electronic Circuit Diagram
8.1 Indoor Unit
8.1.1 CS-S10PKH (Malaysia only) CS-S15PK CS-S18PK CS-S24PK
42
8.1.2 CS-S10PK (except Malaysia) CS-S13PK
43
8.2 Outdoor Unit
8.2.1 CU-S10PK
50 50
Resistance (kΩ)
Resistance (kΩ)
40 40
1
30 30
2
20 20
10 10
0 0
-10 0 10 20 30 40 50 20 40 60 80 100 120 140
o
Temperature ( C) Temperature ( oC)
44
8.2.2 CU-S13PK CU-S15PK
TO INDOOR UNIT
REACTOR
1 2 3 TERMINAL
(BLACK) (WHITE) (RED) BOARD
GRY GRY
RAT2 RAT1 5V
RED FUSE104
(15A 250V) R11 R12
15.8k 15.0k
DATA 1% 1%
(RED) 541
C6 C7
1µ 1µ OUTDOOR TEMP.
WHT
BLK
277
NOISE FILTER 3
CIRCUIT 4
AC-BLK
(BLK) COMMUNICATION G8 CN-TH PIPE TEMP.
CIRCUIT WHITE SENSOR1 (4.96kΩ 3800
FUSE101
(20A 250V) FUSE102
T3.15A L250V
AC-WHT SWITCHING POWER
(WHT) SUPPLY CIRCUIT
FG1
GRN (GRN)
5V CN-TANK
WHITE
FG2 1
GRN (GRN) PFC RECTIFICATION
3
CIRCUIT CIRCUIT
C3 R1
4.99k
TANK TEMP.
1µ
10V 1% SENSOR (50kΩ 3950)
G8 G8
BLU FM1 (BLU) FUSE103
T3.15A L250V
M RED FM2 (RED) FAN MOTOR
1~ YLW FM3 (YLW) CIRCUIT
P
(RED) RED
U
FAN MOTOR (BLU) BLU MS
V
(YLW) YLW 3~
W
N
COMPRESSOR
50 50
Resistance (kΩ)
Resistance (kΩ)
40 40
1
30 30
2
20 20
10 10
0 0
-10 0 10 20 30 40 50 20 40 60 80 100 120 140
o
Temperature ( C) Temperature ( oC)
45
8.2.3 CU-S18PK
TO INDOOR UNIT
REACTOR
1 2 3 TERMINAL
(BLACK) (WHITE) (RED) BOARD
GRY GRY
RAT2 RAT1
(GRY) (GRY) 5V
RED
R11 R12
15.8k 15.0k
1% 1%
+ C88
220µ
10V
DATA C9 C10
1µ 1µ
(RED) 10V 10V OUTDOOR TEMP.
G2 SENSOR (15kΩ 3950)
WHT
BLK
G2 419 1
2
420 3
NOISE FILTER 4
AC-BLK CIRCUIT
G2 CN-TH1 PIPE TEMP.
(BLK) COMMUNICATION SENSOR1 (4.96kΩ 3800
CIRCUIT
FUSE 103
(20A 250V) FUSE 104
T3.15A L250V
5V CN-TANK
AC-WHT WHITE
(WHT) 1
3
FG1 C5 R1 COMP. TEMP.
GRN (GRN) 1µ 4.99k
10V 1% SENSOR (50kΩ 3950)
G2 G2
FG2
GRN (GRN)
FAN MOTOR
P
(RED) RED
U
(BLU) BLU MS
V
(YLW) YLW 3~
W
N
COMPRESSOR
50 50
Resistance (kΩ)
Resistance (kΩ)
40 40
1
30 30
2
20 20
10 10
0 0
-10 0 10 20 30 40 50 20 40 60 80 100 120 140
o
Temperature ( C) Temperature ( oC)
46
8.2.4 CU-S24PK
TO INDOOR UNIT
REACTOR
1 2 3 TERMINAL
(BLACK) (WHITE) (RED) BOARD
GRY GRY
L2-1 L2-0 5V
RED 90
R101 R100
COM3 15.8k 15.0k
(RED) OUTDOOR AIR TEMP.
C46 C45 SENSOR (THERMISTOR)
WHT
BLK
1µ 1µ
6.3V 6.3V (15kΩ 3950)
97 1
98 2
NOISE FILTER
99 3
AC-BLK CIRCUIT 4
(BLK)
CN-TH1 PIPE TEMP. SENSOR
(THERMISTOR)
FUSE3 (4.96kΩ 3800)
(20A 250V) FUSE2 COMMUNICATION
T3.15A L250V CIRCUIT
AC-WHT
(WHT)
SWITCHING
POWER 5V
FG01 SUPPLY CN-TANK
GRN (GRN) 1
CIRCUIT 102 3
1
FUSE1
T3.15A L250V
BLU FAN MOTOR
M RED 5 CIRCUIT
1~ YLW P
(RED) RED
CN-ACFM U
(WHT) (BLU) BLU MS
V
FAN MOTOR (YLW) YLW 3~
BLU W
CAPACITOR N
COMPRESSOR
50 50
Resistance (kΩ)
Resistance (kΩ)
40 40
1
30 30
2
20 20
10 10
0 0
-10 0 10 20 30 40 50 20 40 60 80 100 120 140
o o
Temperature ( C) Temperature ( C)
47
9. Printed Circuit Board
9.1 Indoor Unit
9.1.1 Main Printed Circuit Board
AC304 AC303
G301
RY-PWR
SW01
CN-FM
CN-RMT
CN-STM2
CN-STM1
CN-DISP
CN-MSENS
CN-TH
CN-CLN
48
9.1.1.2 CS-S10PK (except Malaysia) CS-S13PK
RY-PWR
CN-PCFM
SW01
CN-FB
CN-RMT
CN-STM2
CN-STM1
CN-DISP
CN-MSENS
CN-TH
CN-CLN
49
9.1.2 Indicator Printed Circuit Board
CN-DISP
GND
CN-SENS1 CN-SENS2
CN-MSENS
50
9.1.5 Human Activity Sensor Printed Circuit Board
51
9.2 Outdoor Unit
9.2.1 Main Printed Circuit Board
9.2.1.1 CU-S10PK
52
9.2.1.2 CU-S13PK CU-S15PK
53
9.2.1.3 CU-S18PK
54
9.2.1.4 CU-S24PK
55
9.2.2 Noise Filter Printed Circuit Board
9.2.2.1 CU-S10PK
56
10.1.3 Indoor/Outdoor Unit Installation
10. Installation Instruction Diagram
(Except Myanmar)
57
10.2 Indoor Unit
10.2.1 How to Fix Installation Plate
The mounting wall shall be strong and solid enough to prevent if from the vibration.
Dimension
Model
○
1 ○
2 ○
3 ○4 ○
5 ○
6
S10***, S13***,
490 mm 82 mm 439 mm 432 mm 93 mm 145 mm
S15***
S18***, S24*** 590 mm 82 mm 539 mm 532 mm 219 mm 269 mm
○
B : For left side piping, piping connection for liquid should be about ○
5 from this line.
: For left side piping, piping connection for gas should be about ○
6 from this line.
1 Mount the installation plate on the wall with 5 screws or more (at least 5 screws).
(If mounting the unit on the concrete wall, consider using anchor bolts.)
o Always mount the installation plate horizontally by aligning the marking-off line with the thread and using
a level gauge.
2 Drill the piping plate hole with ø70 mm hole-core drill.
o Putting measuring tape at position as shown in the diagram above.
The hole center is obtained by measuring the distance namely 128 mm for left and right hole
respectively. Another method is intersection point of arrow mark extension.
The meeting point of the extension arrow mark is the hole center position.
o Drill the piping hole at either the right or the left and the hole should be slightly slanting to the outdoor
side. (refer to 10.2.2)
CAUTION Approx. 5 - 7 mm
58
10.2.3 Indoor Unit Installation
59
10.2.4 Connect the Cable to the Indoor Unit
The power supply cord, indoor and outdoor unit connection cable can be connected without removing the front grille.
1 Install the indoor unit on the installing holder that mounted on the wall.
2 Open the front panel and grille door by loosening the screw.
3 Cable connection to the power supply through Isolating Devices (Disconnecting means).
o Connect the approved polychloroprene sheathed power supply cord 3 × 1.5 mm2 (1.0 ~ 1.75HP) or
3 × 2.5 mm2 (2.0 ~ 2.5HP), type designation 60245 IEC 57 or heavier cord to the terminal board, and
connect the other end of the cable to Isolating Devices (Disconnecting means).
o Do not use joint power supply cord. Replace the wire if the existing wire (from concealed wiring, or
otherwise) is too short.
o In unavoidable case, joining of power supply cord between isolating devices and terminal board of air
conditioner shall be done by using approved socket and plug with earth pin rated 15/16A (1.0 ~ 1.75HP
or 16A (2.0HP) or 20A (2.5HP). Wiring work to both socket and plug must follow to national wiring
standard.
4 Bind all the power supply cord lead wire with tape and route the power supply cord via the left escapement.
5 Connection cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 × 1.5
mm2 (1.0 ~ 1.75HP) or 4 × 2.5 mm2 (2.0 ~ 2.5HP) flexible cord, type designation 60245 IEC 57 or heavier
cord. Do not use joint connection cable. Replace the wire if the existing wire (from concealed wiring, or
otherwise) is too short.
6 Bind all the indoor and outdoor connection cable with tape and route the connection cable via the right
escapement.
60
7 Remove the tapes and connect the power supply cord and connection cable between indoor unit and outdoor
unit according to the diagram below.
8 Secure the power supply cord and connection cable onto the control board with the holder.
9 Close grille door by tighten with screw and close the front panel.
Note:
• Isolating Devices (Disconnecting means) should have minimum 3.0 mm contact gap.
• Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor’s respectively.
• Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires as shown in the figure for the
electrical safety in case of the slipping out of the cord from the anchorage.
61
62
10.3 Outdoor Unit
10.3.1 Install the Outdoor Unit
• After selecting the best location, start installation to Indoor/Outdoor Unit Installation Diagram.
1 Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10 mm).
2 When installing at roof, please consider strong wind and earthquake.
3 Please fasten the installation stand firmly with bolt or nails.
A B
C
Model A B C D
S10*** 474 mm 87 mm 18.5 mm 261 mm
S13***, S15*** 570 mm 105 mm 18.5 mm 261 mm
S18*** 540 mm 160 mm 18.5 mm 330 mm
D
S24*** 613 mm 131 mm 16 mm 360.5 mm
63
AIR PURGING METHOD IS PROHIBITED FOR R410A SYSTEM
1 Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way
valve.
o Be sure to connect the end of the charging hose with the push pin to the service port.
2 Connect the center hose of the charging set to a vacuum pump.
3 Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from
0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
4 Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the
gauge does not move after approximately five minutes.
Note: BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERENT GAS LEAKAGE.
5 Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6 Tighten the service port caps of the 3-way valve at a torque of 18 N•m with a torque wrench.
7 Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN”
using a hexagonal wrench (4 mm).
8 Mount valve caps onto the 2-way valve and the 3-way valve.
o Be sure to check for gas leakage.
64
10.3.4 Connect the cable to the Outdoor Unit
1 Remove the control board cover from the unit
by loosening the screw.
2 Connection cable between indoor unit and
outdoor unit shall be approved
polychloroprene sheathed 4 × 1.5 mm2 (1.0 ~
1.75HP) or 4 × 2.5 mm2 (2.0 ~ 2.5HP) flexible
cord, type designation 60245 IEC 57 or
heavier cord. Do not use joint connection
cable. Replace the wire if the existing wire
(from concealed wiring, or otherwise) is too
short.
65
11. Installation Instruction 11.1.3 Indoor/Outdoor Unit Installation
Diagram
(For Myanmar only)
66
11.2 Indoor Unit
11.2.1 How to Fix Installation Plate
The mounting wall shall be strong and solid enough to prevent if from the vibration.
Dimension
Model
○1 ○2 ○3 ○4 ○5 ○6
○
B : For left side piping, piping connection for liquid should be about ○
5 from this line.
: For left side piping, piping connection for gas should be about ○
6 from this line.
3 Mount the installation plate on the wall with 5 screws or more (at least 5 screws).
(If mounting the unit on the concrete wall, consider using anchor bolts.)
o Always mount the installation plate horizontally by aligning the marking-off line with the thread and using
a level gauge.
4 Drill the piping plate hole with ø70 mm hole-core drill.
o Putting measuring tape at position as shown in the diagram above.
The hole center is obtained by measuring the distance namely 128 mm for left and right hole
respectively. Another method is intersection point of arrow mark extension.
The meeting point of the extension arrow mark is the hole center position.
o Drill the piping hole at either the right or the left and the hole should be slightly slanting to the outdoor
side. (refer to 11.2.2)
CAUTION Approx. 5 - 7 mm
67
11.2.3 Indoor Unit Installation
68
11.2.4 Connect the Cable to the Indoor Unit
The power supply cord, indoor and outdoor unit connection cable can be connected without removing the front grille.
4 Install the indoor unit on the installing holder that mounted on the wall.
5 Open the front panel and grille door by loosening the screw.
6 Cable connection to the power supply through Isolating Devices (Disconnecting means).
o Connect the approved polychloroprene sheathed power supply cord 3 × 1.5 mm2 (1.0 ~ 1.5HP) or
3 × 2.5 mm2 (2.0 ~ 2.5HP), type designation 60245 IEC 57 or heavier cord to the terminal board, and
connect the other end of the cable to Isolating Devices (Disconnecting means).
o Do not use joint power supply cord. Replace the wire if the existing wire (from concealed wiring, or
otherwise) is too short.
o In unavoidable case, joining of power supply cord between isolating devices and terminal board of air
conditioner shall be done by using approved socket and plug with earth pin rated 15/16A (1.0 ~ 1.5HP or
16A (2.0HP) or 20A (2.5HP). Wiring work to both socket and plug must follow to national wiring standard.
7 Bind all the power supply cord lead wire with tape and route the power supply cord via the left escapement.
8 Connection cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 × 1.5
mm2 (1.0 ~ 1.5HP) or 4 × 2.5 mm2 (2.0 ~ 2.5HP) flexible cord, type designation 60245 IEC 57 or heavier cord.
Do not use joint connection cable. Replace the wire if the existing wire (from concealed wiring, or otherwise)
is too short.
9 Bind all the indoor and outdoor connection cable with tape and route the connection cable via the right
escapement.
69
10 Remove the tapes and connect the power supply cord and connection cable between indoor unit and outdoor
unit according to the diagram below.
11 Secure the power supply cord and connection cable onto the control board with the holder.
12 Close grille door by tighten with screw and close the front panel.
Note:
• Isolating Devices (Disconnecting means) should have minimum 3.0 mm contact gap.
• Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor’s respectively.
• Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires as shown in the figure for the
electrical safety in case of the slipping out of the cord from the anchorage.
70
71
11.3 Outdoor Unit
11.3.1 Install the Outdoor Unit
• After selecting the best location, start installation to Indoor/Outdoor Unit Installation Diagram.
1 Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10 mm).
2 When installing at roof, please consider strong wind and earthquake.
3 Please fasten the installation stand firmly with bolt or nails.
A B
C
Model A B C D
S10*** 474 mm 87 mm 18.5 mm 261 mm
S13*** 570 mm 105 mm 18.5 mm 261 mm
S18*** 540 mm 160 mm 18.5 mm 330 mm
D
S24*** 613 mm 131 mm 16 mm 360.5 mm
72
AIR PURGING METHOD IS PROHIBITED FOR R410A SYSTEM
9 Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way
valve.
o Be sure to connect the end of the charging hose with the push pin to the service port.
10 Connect the center hose of the charging set to a vacuum pump.
11 Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from
0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
12 Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the
gauge does not move after approximately five minutes.
Note: BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERENT GAS LEAKAGE.
13 Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
14 Tighten the service port caps of the 3-way valve at a torque of 18 N•m with a torque wrench.
15 Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN”
using a hexagonal wrench (4 mm).
16 Mount valve caps onto the 2-way valve and the 3-way valve.
o Be sure to check for gas leakage.
73
11.3.4 Connect the cable to the Outdoor Unit
6 Remove the control board cover from the unit
by loosening the screw.
7 Connection cable between indoor unit and
outdoor unit shall be approved
polychloroprene sheathed 4 × 1.5 mm2 (1.0 ~
1.5HP) or 4 × 2.5 mm2 (2.0 ~ 2.5HP) flexible
cord, type designation 60245 IEC 57 or
heavier cord. Do not use joint connection
cable. Replace the wire if the existing wire
(from concealed wiring, or otherwise) is too
short.
74
12. Operation Control
12.1 Basic Function
Inverter control, which equipped with a microcomputer in determining the most suitable operation mode as time
passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operation
mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and
performing temperature shifting. The compressor at outdoor unit is operating following the frequency instructed by
the microcomputer at indoor unit that judging the condition according to internal setting temperature and intake air
temperature.
Cooling
operation
23°C
Soft Dry
operation
Indoor intake
Air Temp
• After the operation mode is decided, the unit operation will follow the respective operation mode control.
75
12.2 Indoor Fan Motor Operation
12.2.1 Basic Rotation Speed
• Manual Fan Speed
o Fan motor’s number of rotation is determined according to remote control setting.
Remote control ○ ○ ○ ○ ○
Tab Hi Me+ Me Me- Lo
Fan Speed a b c d e f g h a b
Higher
Medium
Lower
[1 pattern : 10s]
• Feedback control
o Immediately after the fan motor is started, feedback control is performed once every second.
o During fan motor on, if fan motor feedback ≥ 2550 rpm or <50 rpm continuously for 10 seconds, the fan
motor error counter increased; fan motor is then stopped and restarted. If the fan motor error counter
increased to 7, then H19 – fan motor error is detected. Operation stopped and could not be restarted.
ON ON
Compressor OFF
ON Fan Speed ON
Outdoor Fan 30 sec OFF
ON ON
Compressor OFF
ON Fan Speed ON
Outdoor Fan 30 sec OFF
76
12.5 Airflow Direction
• There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by
vertical vanes).
• Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat
exchanger temperature and intake air temperature) and manual (angles of direction can be adjusted using
remote control).
CS-S18, 24PK
Vane Angle (°)
Operation Mode Airflow Direction
1 2 3 4 5
Auto 5 ~ 35
Cooling
Manual 5 12.5 20 27.5 35
Auto 5 ~ 35
Soft Dry
Manual 5 12.5 20 27.5 35
• Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the
angles as stated above. It does not swing during fan motor stop. When the air conditioner is stopped using
remote control, the vane will shift to close position.
• Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and
the positions of the vane are as figure below. When the air conditioner is stopped using remote control, the vane
will shift to close position.
2 135° 2 140°
3 3
4 Close position 4 Close position
5 5
CS-S10, 13, 15PK CS-S18, 24PK
• Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated below and
the positions of the vane are as figure below:
Top View
2 5
3 4
1
77
CS-S10, 13, 15PK
Pattern 1 2 3 4 5
Airflow Direction
Patterns at Remote
Control
Vane Angle (°) 90 65 77.5 102.5 115
CS-S18, 24PK
Pattern 1 2 3 4 5
Airflow Direction
Patterns at Remote
Control
Vane Angle (°) 90 70 80 100 110
• Control condition
o Quiet operation start condition
When Quiet button at remote control is pressed Quiet INDICATOR illuminates.
o Quiet operation stop condition
When one of the following conditions is satisfied, quiet operation stops:
• ECONAVI button is pressed.
• Powerful button is pressed.
• Mild Dry Cooling button is pressed.
• Stop by OFF/ON button.
• OFF Timer activates.
• Quiet button is pressed again.
When quiet operation is stopped, operation is shifted to normal operation with previous setting.
When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
When operation mode is changed, quiet operation is shifted to quiet operation of the new mode.
During quiet operation, if ON timer activates, quiet operation maintains.
After off, when on back, quiet operation is not memorized.
• Control content
o Fan speed is changed from normal setting to quiet setting of respective fan speed. This is to reduce sound of
Hi, Me, Lo for 3dB (more than 3dB for some models).
o Fan speed for quiet operation is -1 step from setting fan speed.
78
12.8 Timer Control
• There are 2 sets of ON and OFF timer is available to turn the unit ON or OFF at different preset time.
• If more than one timer had been set, the upcoming timer will be display and will activated in sequence.
60 minutes before the set ON time, indoor (at fan speed of Lo-) and outdoor fan motor start operation for 30 seconds
to determine the indoor intake air temperature and outdoor air temperature in order to judge the operation starting
time.
From the above judgment, the decided operation will start operation earlier than the set time as shown below.
Indoor intake air
temperature (°C)
15 min
30
10 min
25
5 min
Outdoor air
30 35 temperature (°C)
Note:
• If POWER LED blinks, the possible operation of the unit is operation mode judgment, or ON timer sampling.
• If TIMER LED blinks, there is an abnormal operation occurs.
79
12.11 nanoe-G Operation
• This operation provides clean air by producing great amount of negative ions and distribute through the
discharge airflow to capture or deactivate molds, bacteria or viruses.
• Timer control
o When ON Timer activates when unit stops, previous operation resumes and restored last saved nanoe-G
operation status.
o When ON Timer activates during any operation, no change on current operation.
o When OFF Timer activates during any operation, all operation stops and the latest nanoe-G operation status
is saved.
• Indicator
o When nanoe-G starts, nanoe-G indicator ON.
• Power failure
o During nanoe-G individual operation, if power failure occurs, after power resumes, nanoe-G individual
operation resumes immediately.
o During combination operation, if power failure occurs, after power resumes, combination operation resume
immediately.
80
• nanoe-G check mode
o To enable nanoe-G check mode, during nanoe-G operation ON:
SET
Troubleshooting method
• Connect the connector or stop operation to cancel the blinking.
• Switch off the power supply and unplug before cleaning.
• Clean the dirty nanoe-G generator with cotton bud.
Troubleshooting method
• Press nanoe-G button or OFF/ON button to stop the operation and check the nanoe-G connector at
PCB.
• After that, press nanoe-G button again to confirm the nanoe-G indicator do not blinks.
• The 24 timer counter will be clear after 10 minutes of normal operation or when operation stops.
81
o nanoe-G breakdown error
Judgment method
• Hi-feedback voltage (at microcontroller) supplied to the nanoe-G system when nanoe-G operation is
OFF; nanoe-G breakdown error show immediately.
• It is due to indoor PCB or nanoe-G high voltage power supply damage.
• Operations except nanoe-G continue. Both Timer indicator and nanoe-G indicator blink.
Troubleshooting method
• Press nanoe-G button or OFF/ON button to stop the operation.
• Change nanoe-G high voltage power supply or main PCB.
• When Lo-feedback voltage supplied to nanoe-G system during nanoe-G operation ON, nanoe-G
indicator and Timer indicator stop blinking.
• Control contents:
o When the unit operate in Cool or Dry mode before turned off.
1. The unit will operate fan operation, fan motor will operate at 500rpm for 30 minutes then stop.
2. During fan operation, horizontal vane will fixed at 115° for 30 minutes then close.
3. After 30 minutes the unit will continue with common control.
o Common control.
- nanoe-G generator will operate for 120 minutes.
• Timer control
o When ON Timer activates during in filter deactivation operation, in-filter deactivation operation stops.
o When OFF Timer activates during in filter deactivation operation, in-filter operation will continue.
• Indicator
o nanoe-G indicator ON.
o Power indicator OFF.
• Power failure
o During in-filter operation, if power failure occurs, after power resumes in-filter deactivation operation will not
resume.
82
12.13 Mild Dry Cooling Operation
• This operation helps to prevent decreases in room humidity while maintaining the setting temperature.
• During unit running at Cooling operation mode, if “Mild Dry Cooling” button is pressed, Mild Dry Cooling operation
starts and Mild Dry Cooling indicators turns ON at remote control display.
• Mild dry cooling operation is unavailable when the unit is operating Auto mode, Soft Dry mode, Patrol individual
operation or e-ion individual operation.
• Mild dry cooling operation is cancelled when the unit turned OFF, pressed again Mild Dry Cooling button or when
the operation mode changed from Cooling to other mode.
• ECONAVI, Powerful, Quiet and Mild Dry Cooling mode cannot function at the same time, the unit will follows the
operation according to the last signal received.
• During this operation, the compressor frequency changes according to operating condition to prevent room
humidity decreases and when AUTO AIR SWING is set, the vertical airflow direction fixed at lower limit position.
83
12.14.1 Human Activity Sensor
• Area of human availability, activity level and absent is judged based on pulses by using 2 infrared sensors. The
internal setting temperature shift, fan speed and horizontal airflow direction are adjusted in order to provide
comfort environment while maintain the energy saving level.
Signal Detection
Information Log
84
12.14.1.1 Signal Detection
7m
A C
2m
B
7m
120º
• Human Activity sensor will turns on according to infrared sensors signal detection.
• However, once the Human Activity Indicator is ON, it will maintain ON status for 5 seconds. If there is no signal
detection from either infrared sensor, the final display condition will be kept until absence status.
85
12.14.1.7 Setting Position Judgment
• According to installation position when there is only one activity area detected, the horizontal airflow direction
louver position is fixed according to chart below:
• When 3 activity areas have been detected, according to Human Activity Level the timing of horizontal airflow
louver steps at the targeted activity areas is judged.
• When 3 activity areas have same activity level, the horizontal airflow direction louver will swing left and right.
* During low activity, fan speed 1 tap up for first 15 minutes or until set temperature is reached.
** During human absence, maximum fan speed for COOL/DRY mode is medium fan.
86
12.14.1.9 Rhythmic Temperature Wave Operation
• To further maximize the energy saving during ECONAVI or AUTO COMFORT operates at low activity level.
• Start condition
o The unit is operates in Cool or Dry mode under ECONAVI or AUTO COMFORT operation, and
o Human activity sensor detects low activity level continuously for 60 minutes, and
o ON Timer is not activated.
• Stop condition
o Unit is off, or
o ECONAVI or AUTO COMFORT is off, or
o Human activity sensor detects high activity level or absent, or
o ON Timer is activated.
• Control contents
o When all start conditions complied, set temperature will shift accordingly as following:
87
12.14.1.10 ECONAVI and AUTO COMFORT Demo Mode
• To enable ECO DEMO mode:
SET
• Operation details
• The target area will maintain for 5 seconds before changeover to next detection.
• If no activity detection, the last action will maintain for 30 seconds before changeover to human absence status.
88
12.14.1.11 Human Activity Sensor Abnormality
• Abnormality detection:
Connector disconnection / Wire cut abnormality
o Sensor judge Hi level continuously for 25 seconds
Circuit abnormality
o 70 seconds after power ON, if human activity sensor judge Lo level continuously for 25 seconds
• When error code happened, the unit is able to operate without AUTO COMFORT / ECONAVI.
SET
• During ECONAVI is ON, when CHECK signal received, if either sensors has abnormality, the 4 times abnormality
counter is ignored, ECONAVI Indicator will blink immediately and error code is memorized.
• The unit could operate without ECONAVI or AUTO COMFORT.
• The ECONAVI indicator blinking could be cancelled by pressing ECONAVI button again.
• If the human activity sensor has no abnormality, the CHECK process will end and continue with normal operation.
89
12.14.2 Sunlight Sensor
• During ECONAVI operation, the sunlight sensor detects sunlight intensity coming through windows and
differentiates between sunny and cloudy or night to further optimize energy saving by adjusting the temperature.
• Sunlight judgment is as following
Temperature shift
90
12.14.2.2 Judge Sunlight Intensity
• Based on sunlight sensor output voltage, the sunlight intensity value will be computed and logged to sunlight
intensity database.
• The sunlight sensor sensitivity could be adjusted:
Set to Level. 4
Press
Timer Transmit
SET solar radiation
level
Set to Level. 5 &
after *2 secs
go back to
normal mode
Set to Level. 1
Set to Level. 2
• In a room without window or with thick curtain, the sunlight sensor will judge as cloudy/night.
91
12.14.2.5 Sunlight Sensor Check Mode
• To enable sunlight sensor check mode, during unit is OFF (power standby):
SET
• Operation details
o The sunlight sensor check mode will be operated for 5 minutes.
o During check mode, the ON and OFF timer will be memorized but it operation be ignored.
o During check mode, if the sunlight sensor check code is retransmitted, the 5 minutes counter will be reset.
o During check mode, if sunlight sensor detected the sunlight intensity value above minimum level, the
ECONAVI indicator turns ON. Else if sunlight sensor detected sunlight intensity value below minimum level,
the ECONAVI indicator is OFF.
• To disable sunlight sensor check mode
o After check mode is ended (5 minutes counter elapsed), press AUTO OFF/ON button at indoor unit.
o If the sunlight sensor detected sunlight intensity is at abnormal range, the check mode will be ended.
Please check for error code.
92
13. Protection Control
13.1 Restart Control (Time Delay Safety Control)
• The compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on
again by pressing OFF/ON button at remote control within this period.
• This control is not applicable if the power supply is cut off and on again.
• This phenomenon is to balance the pressure inside the refrigerant cycle.
(B)
38.5°C
(A) 37.5°C
93
13.5 Compressor Overheating Prevention Control (For S18, S24PK only)
• Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The
changes of frequency are as below.
• If compressor discharge temperature exceeds 112°C, compressor will be stopped, occurs 4 times per 20 minutes,
timer LED will be blinking. “F97” is indicated.
Compressor=OFF Compressor=OFF
103°C 112°C
88°C 97°C
Compressor Frequency Compressor Frequency
99°C Reduced 110°C Reduced
87°C 96°C
Compressor Frequency Compressor Frequency
96°C Maintain 100°C Maintain
86°C 90°C
Free Free
Comp Discharge temperature Comp Discharge temperature
(S18PK only)
94
13.10 Outdoor Air Temperature Control
• The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the
diagram below.
• This control will begin 1 minute after the compressor starts.
• Compressor frequency will adjust based on outdoor air temperature.
Free
38°C
37°C
Limited Frequency
95
13.15 Odor Cut Control
• To reduce the odor released from the unit.
o Start Condition
AUTO FAN Speed is selected during COOL or DRY operation.
During freeze prevention control and timer preliminary operation, this control is not applicable.
o Control content
Depends on compressor conditions:
1. Compressor OFF → Compressor ON.
The indoor unit fan stops temporarily and then starts to blow at minimum airflow for 30 seconds.
2. Compressor ON → Compressor OFF.
The indoor unit fan stops for 90 seconds and then blows at minimum airflow for 20 seconds.
96
14. Servicing Mode
14.1 Auto Off/On Button
Auto OFF/ON Auto OFF/ON
Button Pressed Button Pressed
5 sec
Auto Operation Test Run Operation Stop
(Forced Cooling Operation)
Beep
1 AUTO OPERATION MODE
The Auto Operation will be activated immediately once the Auto OFF/ON button is pressed. This operation
can be used to operate air conditioner with limited function if remote control is misplaced or malfunction.
The Auto OFF/ON button may be used together with remote control to set / change the advance setting of air
conditioner operation.
There are 4 types of remote control transmission code could be selected. The indoor unit will only operate
when received signal with same transmission code from remote control. This could prevent signal
interference when there are 2 or more units installed nearby together.
To change remote control transmission code, short or open jumpers at the remote control printed circuit
board.
After Auto OFF/ON button is pressed, the 20 seconds counter for Remote Control Receiving Sound OFF/ON
Mode is restarted.
97
14.2 Remote Control Button
14.2.1 SET Button
• To check remote control transmission code and store the transmission code to EEPROM
o Press “Set” button continuously for 10 seconds by using pointer
o Press “Timer Set” button unit a “beep” sound is heard as confirmation of transmission code change.
o Confirm setting by pressing “Timer Set” button, a “beep” sound will be heard. LCD returns to original display
after 2 seconds.
o LCD returns to original display if remote control does not operate for 30 seconds.
14.2.4 TIMER ▲
• To change indoor unit indicators’ intensity:
o Press continuously for 5 seconds.
14.2.5 TIMER ▼
• To change remote control display from Degree Celsius (°C) to Degree Fahrenheit (°F)
o Press continuously for 10 seconds.
98
15. Troubleshooting Guide
15.1 Refrigeration Cycle System
In order to diagnose malfunctions, ensure the air conditioner is free Normal Pressure and Outlet Air Temperature (Standard)
from electrical problems before inspecting the refrigeration cycle. Gas Pressure Outlet air
Mpa Temperature
Such problems include insufficient insulation, problem with the 2
(kg/cm G) (°C)
power source, malfunction of a compressor and a fan. The normal
outlet air temperature and pressure of the refrigeration cycle Cooling Mode 0.9 ~ 1.2 (9 ~ 12) 12 ~ 16
depends on various conditions, the standard values for them are Condition: Indoor fan speed = High
shown in the table to the right. Outdoor temperature = 35°C at cooling mode.
Compressor operate at rated frequency
Excessive amount
of refrigerant
Cooling
Gas side Mode High
Inefficient compressor • Measuring gas side
pressure pressure
Low
Insufficient refrigerant
99
15.1.1 Relationship between the condition of the air conditioner and pressure and
electric current
Inefficient compression Ò Ô Ô
• Carry out the measurement of pressure, electric current, and temperature fifteen minutes after an operation is started.
100
15.2 Breakdown Self Diagnosis Function
15.2.1 Self Diagnosis Function (Three Digits Alphanumeric Code)
• Once error occurred during operation, the unit will stop its operation, and Timer LED blinks.
• Although Timer LED goes off when power supply is turned off, if the unit is operated under a breakdown
condition, the LED will ON again.
• In operation after breakdown repair, the Timer LED will not blink. The last error code (abnormality) will be stored
in IC memory.
101
15.3 Error Code Table
Diagnosis Emergency
Abnormality / Protection control Abnormality Judgment Primary location to verify
display Operation
H00 No abnormality detected - Normal operation
Indoor / Outdoor abnormal > 1 min after starting Indoor fan operation • Internal / external cable connection
H11
communication operation only • Indoor / outdoor PCB
Continuously for 90 sec
H12 Connection capability rank abnormality - -
after power supplied
Indoor intake air temperature sensor • Intake air temperature sensor
H14 Continue for 5 sec. -
abnormality (defective or disconnected)
Outdoor compressor temperature sensor • Compressor temperature sensor
H15 Continue for 5 sec. -
abnormality (defective or disconnected)
• Outdoor PCB
H16 Outdoor current transformer open circuit - -
• IPM (Power transistor) module
7 occurrences • Indoor PCB
H19 Indoor fan motor mechanism locked -
continuously • Fan motor
Indoor heat exchanger temperature ○ • Heat exchanger temperature sensor
H23 Continue for 5 sec.
sensor abnormality (defective or disconnected)
○ • Indoor PCB
H25 nanoe-G abnormality -
• nanoe-G PCB
Outdoor air temperature sensor ○ • Outdoor temperature sensor
H27 Continue for 5 sec.
abnormality (defective or disconnected)
• Outdoor heat exchanger
Outdoor heat exchanger temperature ○
H28 Continue for 5 sec. temperature sensor (defective or
sensor abnormality
disconnected)
Discharge temperature sensor • Outdoor discharge temperature
H30 Continue for 5 sec.
abnormality sensor (defective or disconnected)
H33 Indoor / outdoor wrong connection - - • Indoor / outdoor supply voltage
H38 Indoor / outdoor mismatch (brand code) - - -
• ECONAVI sensor (defective or
○
H59 ECONAVI sensor abnormality Continue for 25 sec. disconnected)
• ECONAVI PCB
Low output continue for • Light sensor (defective or
H70 Light sensor abnormal -
24hours, 15days disconnected)
2 occurrences within 30
H97 Outdoor fan lock abnormality • Outdoor fan motor locked
minutes
• Air filter dirty
H98 Indoor temperature rise abnormality - -
• Air circulation short circuit
Indoor heat exchanger freeze prevention • Insufficient refrigerant
H99 - -
protection • Air filter dirty
4 occurrences within 30 • 4-way valve
F11 4 way valve switching failure * -
minutes • v-coil
System and compressor microcomputer 2 occurrences within 5 • Compressor
F90 -
communication error(for S10*** only) seconds • Outdoor PCB
4 occurrences within 20
F90 Power factor correction abnormality - • Outdoor PCB
minutes
2 occurrences within 20 • No refrigerant ( 3-way valve is
F91 Refrigerant cycle abnormal -
minutes closed)
4 occurrences within 20
F93 Outdoor compressor abnormal revolution - • Outdoor compressor
minutes
4 occurrences within 20
F95 Cooling high pressure protection - • Outdoor refrigerant circuit
minutes
• Excess refrigerant
Intelligent power transistor overheating
F96 - - • Improper heat radiation
protection
• IPM (Power transistor)
Compressor temperature rise protection 4 times occurrence within • Insufficient refrigerant
F97 -
control 20 minutes • Compressor
3 times occurrence within • Excess refrigerant
F98 Total running current protection -
20 minutes • Improper heat radiation
• Outdoor PCB
Outdoor direct current (DC) peak 7 times occurrence
F99 - • IPM (Power transistor)
detection continuously
• Compressor
Note:
“○” – Frequency measured and fan speed fixed
“ * ”– For cooling only model, it is the indication when indoor heat exchanger sensor or indoor air intake sensor has
abnormality.
The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until “beep”
sound heard following by pressing the CHECK button at remote control.
Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors
(refer to Error Code Table) by using remote control or Auto OFF/ON button at indoor unit. However, the remote
control signal receiving sound is changed from one “beep” to four “beep” sounds.
102
15.4 Troubleshooting Flowchart
15.4.1 H11 (Indoor/Outdoor Abnormal Communication)
Malfunction Decision Conditions
• During startup and operation of cooling, the data received from outdoor unit in indoor unit signal transmission is
checked whether it is normal.
Malfunction Caused
• Faulty indoor unit PCB.
• Faulty outdoor unit PCB.
• Indoor unit-outdoor unit signal transmission error due to wrong wiring.
• Indoor unit-outdoor unit signal transmission error due to breaking of wire in the connection wires between the
indoor and outdoor units.
• Indoor unit-outdoor unit signal transmission error due to disturbed power supply waveform.
Troubleshooting
103
15.4.2 H12 (Indoor/Outdoor Capacity Rank Mismatched)
Malfunction Decision Conditions
• During startup, error code appears when different types of indoor and outdoor units are interconnected.
Malfunction Caused
• Wrong models interconnected.
• Wrong indoor unit or outdoor unit PCBs mounted.
• Indoor unit or outdoor unit PCBs defective.
• Indoor-outdoor unit signal transmission error due to wrong wiring.
• Indoor-outdoor unit signal transmission error due to breaking of wire 3 in the connection wires between the indoor
and outdoor units.
Troubleshooting
104
15.4.3 H14 (Indoor Intake Air Temperature Sensor Abnormality)
Malfunction Decision Conditions
• During startup and operation of cooling, the temperatures detected by the indoor intake air temperature sensor
are used to determine sensor errors.
Malfunction Caused
• Faulty connector connection.
• Faulty sensor.
• Faulty PCB.
Troubleshooting
105
15.4.4 H15 (Compressor Temperature Sensor Abnormality)
Malfunction Decision Conditions
• During startup and operation of cooling, the temperatures detected by the outdoor compressor temperature
sensor are used to determine sensor errors.
Malfunction Caused
• Faulty connector connection.
• Faulty sensor.
• Faulty PCB.
Troubleshooting
106
15.4.5 H16 (Outdoor Current Transformer Open Circuit)
Malfunction Decision Conditions
• A current transformer (CT) is detected by checking the compressor running frequency (≥ rated frequency) and
CT detected input current (less than 1.14A) for continuously 20 seconds.
Malfunction Caused
• CT defective
• Outdoor PCB defective
• Compressor defective (low compression)
Troubleshooting
107
15.4.6 H19 (Indoor Fan Motor – DC Motor Mechanism Locked)
Malfunction Decision Conditions
• The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor
(feedback of rotation > 2550rpm or < 50rpm)
Malfunction Caused
• Operation stops due to short circuit inside the fan motor winding.
• Operation stops due to breaking of wire inside the fan motor.
• Operation stops due to breaking of fan motor lead wires.
• Operation stops due to Hall IC malfunction.
• Operation error due to faulty indoor unit PCB.
Troubleshooting
108
15.4.7 H23 (Indoor Pipe Temperature Sensor Abnormality)
Malfunction Decision Conditions
• During startup and operation of cooling, the temperatures detected by the indoor heat exchanger temperature
sensor are used to determine sensor errors.
Malfunction Caused
• Faulty connector connection.
• Faulty sensor.
• Faulty PCB.
Troubleshooting
109
15.4.8 H25 (nanoe-G Air Purifying System Abnormal)
Malfunction Decision Conditions
• During standby of cooling operation, nanoe-G breakdown occurs and air conditioner stops operation.
Malfunction Caused
• Faulty indoor main PCB.
• Faulty indoor nanoe-G power module.
Troubleshooting
110
15.4.9 H27 (Outdoor Air Temperature Sensor Abnormality)
Malfunction Decision Conditions
• During startup and operation of cooling, the temperatures detected by the outdoor air temperature sensor are
used to determine sensor errors.
Malfunction Caused
• Faulty connector connection.
• Faulty sensor.
• Faulty PCB.
Troubleshooting
111
15.4.10 H28 (Outdoor Pipe Temperature Sensor Abnormality)
Malfunction Decision Conditions
• During startup and operation of cooling, the temperatures detected by the outdoor pipe temperature sensor are
used to determine sensor errors.
Malfunction Caused
• Faulty connector connection.
• Faulty sensor.
• Faulty PCB.
Troubleshooting
112
15.4.11 H30 (Compressor Discharge Temperature Sensor Abnormality)
Malfunction Decision Conditions
• During startup and operation of cooling, the temperatures detected by the outdoor discharge pipe temperature
sensor are used to determine sensor errors.
Malfunction Caused
• Faulty connector connection.
• Faulty sensor.
• Faulty PCB.
Troubleshooting
113
15.4.12 H33 (Unspecified Voltage between Indoor and Outdoor)
Malfunction Decision Conditions
• The supply power is detected for its requirement by the indoor/outdoor transmission.
Malfunction Caused
• Wrong models interconnected.
• Wrong indoor unit and outdoor unit PCBs used.
• Indoor unit or outdoor unit PCB defective.
Troubleshooting
114
15.4.13 H59 (Human Activity Sensor Abnormality)
Malfunction Decision Conditions
• Feedback signal of human activity sensor.
Malfunction Caused
• Feedback signal is fixed at 0VDc or 5VDc continuously for 25 seconds during ECONAVI or AUTO COMFORT
operation.
• Feedback signal is detected during ECONAVI or AUTO COMFORT off.
Troubleshooting
115
15.4.14 H70 (Light Sensor Abnormality)
Malfunction Decision Conditions
• Feedback signal of light sensor.
Malfunction Caused
• Feedback value is 0VDC continuously.
Troubleshooting
116
15.4.15 H97 (Outdoor Fan Motor – DC Motor Mechanism Locked)
Malfunction Decision Conditions
• The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor.
Malfunction Caused
• Operation stops due to short circuit inside the fan motor winding.
• Operation stops due to breaking of wire inside the fan motor.
• Operation stops due to breaking of fan motor lead wires.
• Operation stops due to Hall IC malfunction.
• Operation error due to faulty outdoor unit PCB.
Troubleshooting
117
15.4.16 H98 (Indoor High Pressure Protection)
Error Code will not display (no Timer LED blinking) but store in EEPROM
Malfunction Caused
• Clogged air filter of the indoor unit
• Dust accumulation on the indoor unit heat exchanger
• Air short circuit
• Detection error due to faulty indoor pipe temperature sensor
• Detection error due to faulty indoor unit PCB
Troubleshooting
118
15.4.17 H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry)
Malfunction Decision Conditions
• Freeze prevention control takes place (when indoor pipe temperature is lower than 2°C)
Malfunction Caused
• Clogged air filter of the indoor unit
• Dust accumulation on the indoor unit heat exchanger
• Air short circuit
• Detection error due to faulty indoor pipe temperature sensor
• Detection error due to faulty indoor unit PCB
Troubleshooting
119
15.4.18 F11 (Indoor Pipe Temperature Sensor Abnormality)
Malfunction Decision Conditions
• When cooling operation, when indoor pipe temperature or indoor heat exchanger temperature sensor is above
45°C.
Malfunction Caused
• Faulty connector connection.
• Faulty indoor pipe temperature sensor.
• Faulty indoor main PCB.
Troubleshooting
120
15.4.19 F90 (Power Factor Correction Protection)
Malfunction Decision Conditions
• During startup and operation of cooling, when Power Factor Correction (PFC) protection circuitry at the outdoor
unit main PCB senses abnormal high DC voltage level.
Malfunction Caused
• DC voltage peak due to power supply surge.
• DC voltage peak due to compressor windings not uniform.
• Faulty outdoor PCB.
Troubleshooting
121
15.4.20 F91 (Refrigeration Cycle Abnormality)
Malfunction Decision Conditions
• During cooling, compressor frequency = Fcmax.
• During cooling and heating operation, running current: 0.65A < I < 1.65A.
• During cooling, indoor intake - indoor pipe < 4°C.
Malfunction Caused
• Refrigerant shortage (refrigerant leakage)
• Poor compression performance of compressor.
• 2/3 way valve closed.
• Detection error due to faulty indoor intake air or indoor pipe temperature sensors.
Troubleshooting
122
15.4.21 F93 (Compressor Rotation Failure)
Malfunction Decision Conditions
A compressor rotation failure is detected by checking the compressor running condition through the position
detection circuit.
Malfunction Caused
• Compressor terminal disconnect
• Outdoor PCB malfunction
Troubleshooting
123
15.4.22 F95 (Cooling High Pressure Abnormality)
Malfunction Decision Conditions
During operation of cooling, when outdoor unit heat exchanger high temperature data (61°C) is detected by the
outdoor pipe temperature sensor.
Malfunction Caused
• Outdoor pipe temperature rise due to short circuit of hot discharge air flow.
• Outdoor pipe temperature rise due to defective of outdoor fan motor.
• Outdoor pipe temperature rise due to defective outdoor pipe temperature sensor.
• Outdoor pipe temperature rise due to defective outdoor unit PCB.
Troubleshooting
124
15.4.23 F96 (IPM Overheating)
Malfunction Decision Conditions
During operating of cooling, when IPM temperature data (100°C) is detected by the IPM temperature sensor.
Malfunction Caused
• IPM overheats due to short circuit of hot discharge air flow.
• IPM overheats due to defective of outdoor fan motor.
• IPM overheats due to defective of internal circuitry of IPM.
• IPM overheats due to defective IPM temperature sensor.
Troubleshooting
125
15.4.24 F97 (Compressor Overheating)
Malfunction Decision Conditions
During operation of cooling, when compressor tank temperature data (112°C) is detected by the compressor tank
temperature sensor.
Malfunction Caused
• Refrigerant shortage (refrigerant leakage).
• 2/3 way valve closed.
• Detection error due to faulty compressor tank temperature sensor.
Troubleshooting
126
15.4.25 F98 (Input Over Current Detection)
Malfunction Decision Conditions
During cooling operation, when an input over-current is detected by checking the input current value being detected
by current transformer (CT) with the compressor running.
Malfunction Caused
• Over-current due to compressor failure.
• Over-current due to defective outdoor unit PCB.
• Over-current due to defective inverter main circuit electrolytic capacitor.
• Over-current due to excessive refrigerant.
Troubleshooting
127
15.4.26 F99 (DC Peak Detection)
Malfunction Decision Conditions
During startup and operation of cooling, when inverter DC peak data is received by the outdoor internal DC peak
sensing circuitry.
Malfunction Caused
• DC current peak due to compressor failure.
• DC current peak due to defective power transistor (IPM).
• DC current peak due to defective outdoor unit PCB.
• DC current peak due to short circuit.
Troubleshooting
128
16. Disassembly and Assembly Instructions
WARNING
High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with
repair work. Failure to heed this caution may result in electric shocks.
Figure 1
Figure 2
129
9. Pull out the main 10. Detach 6 connectors as labeled from
electronic controller the electronic controller. Then pull out
controller halfway. main controller gently
AC303 (WHT)
RY-PWR
8. Remove screw to
remove terminal board
complete.
CN-FM
Figure 3 Figure 4
130
16.1.1.4 To remove control board
Figure 6
Figure 8
131
19. Push the holdfast to the left and lift up the evaporator.
Evaporator
132
WARNING
High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with
repair work. Failure to heed this caution may result in electric shocks.
Figure 11
4. Bend the horizontal vane slightly 5. Release the hooks from 2 6. Release the hook that holds the
to remove vane’s shaft from body. fulcrums. vertical vanes.
Figure 12
133
16.2.1.3 To remove power electronic controller
Figure 13
AC303 (WHT)
RY-PWR
8. Remove screw to
remove terminal board
complete.
CN-FM
Figure 14 Figure 15
134
16.2.1.4 To remove discharge grille
Figure 17
135
18. Remove the bearing by pulling it
out gently
Figure 19
19. Push the holdfast to the left and lift up the evaporator.
Evaporator 20. Remove the cross flow fan from 21. Fan motor can be removed after the
the unit by pulling it to the left and removal of cross flow fan.
downward.
Reminder: To reinstall the fan motor, adjust
the fan motor connector to 45° towards you
before fixing control board.
Figure 20
136
17. Technical Data
17.1 Operation Characteristics
17.1.1 CS-S10PKH CU-S10PKH (Malaysia Only)
• Cooling Characteristic
o Room temperature: 27°C (DBT), 19°C (WBT)
o Operation condition: High fan speed
o Piping length: 7.5m
o Compressor Frequency = Fc
137
• Piping Length Characteristic
o Room temperature: 27°C (DBT), 19°C (WBT)
o Operation condition: High fan speed
o Outdoor temperature: 35°C (DBT), 24°C (WBT)
o Compressor Frequency = Fc
138
17.1.2 CS-S13PKH CU-S13PKH (Malaysia Only)
• Cooling Characteristic
o Room temperature: 27°C (DBT), 19°C (WBT)
o Operation condition: High fan speed
o Piping length: 7.5m
o Compressor Frequency = Fc
139
• Piping Length Characteristic
o Room temperature: 27°C (DBT), 19°C (WBT)
o Operation condition: High fan speed
o Outdoor temperature: 35°C (DBT), 24°C (WBT)
o Compressor Frequency = Fc
140
17.1.3 CS-S15PKH CU-S15PKH (Malaysia Only)
• Cooling Characteristic
o Room temperature: 27°C (DBT), 19°C (WBT)
o Operation condition: High fan speed
o Piping length: 7.5m
o Compressor Frequency = Fc
141
• Piping Length Characteristic
o Room temperature: 27°C (DBT), 19°C (WBT)
o Operation condition: High fan speed
o Outdoor temperature: 35°C (DBT), 24°C (WBT)
o Compressor Frequency = Fc
142
17.1.4 CS-S18PKH CU-S18PKH (Malaysia Only)
• Cooling Characteristic
o Room temperature: 27°C (DBT), 19°C (WBT)
o Operation condition: High fan speed
o Piping length: 5m
o Compressor Frequency = Fc
143
• Piping Length Characteristic
o Room temperature: 27°C (DBT), 19°C (WBT)
o Operation condition: High fan speed
o Outdoor temperature: 35°C (DBT), 24°C (WBT)
o Compressor Frequency = Fc
144
17.1.5 CS-S24PKH CU-S24PKH (Malaysia Only)
• Cooling Characteristic
o Room temperature: 27°C (DBT), 19°C (WBT)
o Operation condition: High fan speed
o Piping length: 5m
o Compressor Frequency = Fc
145
• Piping Length Characteristic
o Room temperature: 27°C (DBT), 19°C (WBT)
o Operation condition: High fan speed
o Outdoor temperature: 35°C (DBT), 24°C (WBT)
Compressor Frequency = Fc
146
17.1.6 CS-S10PK CU-S10PK
• Cooling Characteristic
o Room temperature: 27°C (DBT), 19°C (WBT)
o Operation condition: High fan speed
o Piping length: 7.5m
o Compressor Frequency = Fc
147
• Piping Length Characteristic
o Room temperature: 27°C (DBT), 19°C (WBT)
o Operation condition: High fan speed
o Outdoor temperature: 35°C (DBT), 24°C (WBT)
o Compressor Frequency = Fc
148
17.1.7 CS-S13PK CU-S13PK
• Cooling Characteristic
o Room temperature: 27°C (DBT), 19°C (WBT)
o Operation condition: High fan speed
o Piping length: 7.5m
o Compressor Frequency = Fc
149
• Piping Length Characteristic
o Room temperature: 27°C (DBT), 19°C (WBT)
o Operation condition: High fan speed
o Outdoor temperature: 35°C (DBT), 24°C (WBT)
o Compressor Frequency = Fc
150
17.1.8 CS-S15PK CU-S15PK
• Cooling Characteristic
o Room temperature: 27°C (DBT), 19°C (WBT)
o Operation condition: High fan speed
o Piping length: 7.5m
o Compressor Frequency = Fc
151
• Piping Length Characteristic
o Room temperature: 27°C (DBT), 19°C (WBT)
o Operation condition: High fan speed
o Outdoor temperature: 35°C (DBT), 24°C (WBT)
o Compressor Frequency = Fc
152
17.1.9 CS-S18PK CU-S18PK
• Cooling Characteristic
o Room temperature: 27°C (DBT), 19°C (WBT)
o Operation condition: High fan speed
o Piping length: 5m
o Compressor Frequency = Fc
153
• Piping Length Characteristic
o Room temperature: 27°C (DBT), 19°C (WBT)
o Operation condition: High fan speed
o Outdoor temperature: 35°C (DBT), 24°C (WBT)
o Compressor Frequency = Fc
154
17.1.10 CS-S24PK CU-S24PK
• Cooling Characteristic
o Room temperature: 27°C (DBT), 19°C (WBT)
o Operation condition: High fan speed
o Piping length: 5m
o Compressor Frequency = Fc
155
• Piping Length Characteristic
o Room temperature: 27°C (DBT), 19°C (WBT)
o Operation condition: High fan speed
o Outdoor temperature: 35°C (DBT), 24°C (WBT)
Compressor Frequency = Fc
156
18. Exploded View and Replacement Parts List
18.1 Indoor Unit
18.1.1 CS-S10PKH CS-S13PKH CS-S15PKH
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
157
CS-S10PKH CS-S13PKH CS-S15PKH
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. REMARK
Malaysia only
1 CHASSIS COMPLETE 1 CWD50C1653 ← ←
2 FAN MOTOR 1 ARW7628AC CWA921441 ARW7628AC O
3 CROSS-FLOW FAN COMPLETE 1 CWH02C1149 ← ←
4 BEARING ASSY 1 CWH64K007 ← ←
5 SCREW - CROSS-FLOW FAN 1 CWH551146 ← ←
6 GENERATOR COMPLETE 1 CWH94C0043 ← ←
7 EVAPORATOR 1 CWB30C4401 CWB30C4267 CWB30C4374
8 FLARE NUT (LIQUID) 1 CWT251030 ← ←
9 FLARE NUT (GAS) 1 CWT251031 CWT251032 ←
10 CLIP FOR SENSOR 1 CWH711019 ← ←
11 CONTROL BOARD CASING 1 CWH102449 ← ←
12 TERMINAL BOARD COMPLETE 1 CWA28C2405 CWA28C2381 ← O
13 ELECTRONIC CONTROLLER - MAIN 1 CWA73C7275 CWA73C7277 CWA73C7279 O
14 ELECTRONIC CONTROLLER - HVU 1 N0GE1F000002 ← ← O
15 ELECTRONIC CONTROLLER - INDICATOR 1 CWA746634 ← ← O
16 SENSOR COMPLETE 1 CWA50C2401 ← ← O
17 SENSOR COMPLETE (ECO) 1 CWA50C2809 ← ← O
ELECTRONIC CONTROLLER (ECO
18 1 CWA745791 ← ← O
SENSOR)
ELECTRONIC CONTROLLER (ECO
19 1 CWA746206 ← ← O
SENSOR)
ELECTRONIC
20 1 CWA746653 ← ← O
CONTROLLER(COMPARATOR)
21 LEAD WIRE - PCB ECO 1 CWA67C9785 ← ←
22 CONTROL BOARD CASING FOR PCB ECO 1 CWD933407 ← ←
23 CONTROL BOARD TOP COVER 1 CWH131467 ← ←
24 INDICATOR HOLDER 1 CWD933406 ← ←
25 CONTROL BOARD FRONT COVER CO. 1 CWH13C1247 ← ←
26 DISCHARGE GRILLE COMPLETE 1 CWE20C3235 ← ←
27 BACK COVER CHASSIS 1 CWD933233 ← ←
28 FULCRUM 1 CWH621131 ← ←
29 VERTICAL VANE 8 CWE241374 ← ←
30 CONNECTING BAR (RIGHT) 1 CWE261250 ← ←
31 CONNECTING BAR (LEFT) 1 CWE261256 ← ←
32 AIR SWING MOTOR 1 CWA98K1016 ← ← O
33 AIR SWING MOTOR 1 CWA981264 ← ← O
34 CAP - DRAIN TRAY 1 CWH521259 ← ←
35 HORIZONTAL VANE COMPLETE 1 CWE24C1385 ← ←
36 REMOTE CONTROL COMPLETE 1 CWA75C4185 ← ← O
37 FRONT GRILLE COMPLETE 1 CWE11C5053 ← ← O
38 INTAKE GRILLE COMPLETE 1 CWE22C1723 ← ← O
39 GRILLE DOOR COMPLETE 1 CWE14C1090 ← ←
40 AIR FILTER 2 CWD001279 ← ←
41 SCREW - FRONT GRILLE 2 XTT4+16CFJ ← ←
42 CAP - FRONT GRILLE 2 CWH521227 ← ←
43 DRAIN HOSE 1 CWH851174 ← ←
44 INSTALLATION PLATE 1 CWH361134 ← ←
45 BAG COMPLETE - INSTALLATION SCREW 1 CWH82C1705 ← ←
46 OPERATING INSTRUCTION 1 CWF568827 ← ←
47 INSTALLATION INSTRUCTION 1 CWF615577 ← ←
48 INSTALLATION INSTRUCTION 1 CWF615578 ← ←
158
CS-S10PKH CS-S13PKH CS-S15PKH
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. REMARK
Malaysia only
49 INSTALLATION INSTRUCTION 1 CWF615579 ← ←
50 BAG 1 CWG861497 ← ←
51 SHOCK ABSORBER (L) 1 CWG713386 ← ←
52 SHOCK ABSORBER (R) 1 CWG713387 ← ←
53 C.C.CASE 1 CWG568782 CWG568783 CWG568784
(Note)
• All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
• “O” marked parts are recommended to be kept in stock.
159
CS-S10PKH CS-S13PKH
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. REMARK
Myanmar only
1 CHASSIS COMPLETE 1 CWD50C1653 ←
2 FAN MOTOR 1 CWA921442 ← O
3 CROSS-FLOW FAN COMPLETE 1 CWH02C1149 ←
4 BEARING ASSY 1 CWH64K007 ←
5 SCREW - CROSS-FLOW FAN 1 CWH551146 ←
6 GENERATOR COMPLETE 1 CWH94C0043 ←
7 EVAPORATOR 1 CWB30C4265 CWB30C4267
8 FLARE NUT (LIQUID) 1 CWT251030 ←
9 FLARE NUT (GAS) 1 CWT251031 CWT251032
10 CLIP FOR SENSOR 1 CWH711019 ←
11 CONTROL BOARD CASING 1 CWH102449 ←
12 TERMINAL BOARD COMPLETE 1 CWA28C2405 CWA28C2381 O
13 ELECTRONIC CONTROLLER - MAIN 1 CWA73C7288 CWA73C7289 O
14 ELECTRONIC CONTROLLER - HVU 1 N0GE1F000002 ← O
15 ELECTRONIC CONTROLLER - INDICATOR 1 CWA746634 ← O
16 SENSOR COMPLETE 1 CWA50C2122 CWA50C2401 O
17 SENSOR COMPLETE (ECO) 1 CWA50C2809 ← O
18 ELECTRONIC CONTROLLER (ECO SENSOR) 1 CWA745791 ← O
19 ELECTRONIC CONTROLLER (ECO SENSOR) 1 CWA746206 ← O
20 ELECTRONIC CONTROLLER (COMPARATOR) 1 CWA746653 ← O
21 LEAD WIRE - PCB ECO 1 CWA67C9785 ←
22 CONTROL BOARD CASING FOR PCB ECO 1 CWD933407 ←
23 CONTROL BOARD TOP COVER 1 CWH131467 ←
24 INDICATOR HOLDER 1 CWD933406 ←
25 CONTROL BOARD FRONT COVER CO. 1 CWH13C1247 ←
26 DISCHARGE GRILLE COMPLETE 1 CWE20C3235 ←
27 BACK COVER CHASSIS 1 CWD933233 ←
28 FULCRUM 1 CWH621131 ←
29 VERTICAL VANE 8 CWE241374 ←
30 CONNECTING BAR (RIGHT) 1 CWE261250 ←
31 CONNECTING BAR (LEFT) 1 CWE261256 ←
32 AIR SWING MOTOR 1 CWA98K1016 ← O
33 AIR SWING MOTOR 1 CWA981264 ← O
34 CAP - DRAIN TRAY 1 CWH521259 ←
35 HORIZONTAL VANE COMPLETE 1 CWE24C1385 ←
36 REMOTE CONTROL COMPLETE 1 CWA75C4185 ← O
37 FRONT GRILLE COMPLETE 1 CWE11C5053 ← O
38 INTAKE GRILLE COMPLETE 1 CWE22C1723 ← O
39 GRILLE DOOR COMPLETE 1 CWE14C1090 ←
40 AIR FILTER 2 CWD001279 ←
41 SCREW - FRONT GRILLE 2 XTT4+16CFJ ←
42 CAP - FRONT GRILLE 2 CWH521227 ←
43 DRAIN HOSE 1 CWH851174 ←
44 INSTALLATION PLATE 1 CWH361134 ←
45 BAG COMPLETE - INSTALLATION SCREW 1 CWH82C1705 ←
46 OPERATING INSTRUCTION 1 CWF568828 ←
47 INSTALLATION INSTRUCTION 1 CWF615626 ←
50 BAG 1 CWG861497 ←
51 SHOCK ABSORBER (L) 1 CWG713386 ←
160
CS-S10PKH CS-S13PKH
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. REMARK
Myanmar only
52 SHOCK ABSORBER (R) 1 CWG713387 ←
53 C.C.CASE 1 CWG568782 CWG568783
(Note)
• All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
• “O” marked parts are recommended to be kept in stock.
161
CS-S10PKH CS-S13PKH CS-S15PKH
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. REMARK
S.E.Asia
1 CHASSIS COMPLETE 1 CWD50C1653 ← ←
2 FAN MOTOR 1 CWA921442 ← ARW7628AC O
3 CROSS-FLOW FAN COMPLETE 1 CWH02C1149 ← ←
4 BEARING ASSY 1 CWH64K007 ← ←
5 SCREW - CROSS-FLOW FAN 1 CWH551146 ← ←
6 GENERATOR COMPLETE 1 CWH94C0043 ← ←
7 EVAPORATOR 1 CWB30C4265 CWB30C4267 CWB30C4374
8 FLARE NUT (LIQUID) 1 CWT251030 ← ←
9 FLARE NUT (GAS) 1 CWT251031 CWT251032 ←
10 CLIP FOR SENSOR 1 CWH711019 ← ←
11 CONTROL BOARD CASING 1 CWH102449 ← ←
12 TERMINAL BOARD COMPLETE 1 CWA28C2405 CWA28C2381 ← O
13 ELECTRONIC CONTROLLER - MAIN 1 CWA73C7274 CWA73C7276 CWA73C7278 O
14 ELECTRONIC CONTROLLER - HVU 1 N0GE1F000002 ← ← O
15 ELECTRONIC CONTROLLER - INDICATOR 1 CWA746634 ← ← O
16 SENSOR COMPLETE 1 CWA50C2122 CWA50C2401 ← O
17 SENSOR COMPLETE (ECO) 1 CWA50C2809 ← ← O
ELECTRONIC CONTROLLER (ECO
18 1 CWA745791 ← ← O
SENSOR)
ELECTRONIC CONTROLLER (ECO
19 1 CWA746206 ← ← O
SENSOR)
ELECTRONIC CONTROLLER
20 1 CWA746653 ← ← O
(COMPARATOR)
21 LEAD WIRE - PCB ECO 1 CWA67C9785 ← ←
22 CONTROL BOARD CASING FOR PCB ECO 1 CWD933407 ← ←
23 CONTROL BOARD TOP COVER 1 CWH131467 ← ←
24 INDICATOR HOLDER 1 CWD933406 ← ←
25 CONTROL BOARD FRONT COVER CO. 1 CWH13C1247 ← ←
26 DISCHARGE GRILLE COMPLETE 1 CWE20C3235 ← ←
27 BACK COVER CHASSIS 1 CWD933233 ← ←
28 FULCRUM 1 CWH621131 ← ←
29 VERTICAL VANE 8 CWE241374 ← ←
30 CONNECTING BAR (RIGHT) 1 CWE261250 ← ←
31 CONNECTING BAR (LEFT) 1 CWE261256 ← ←
32 AIR SWING MOTOR 1 CWA98K1016 ← ← O
33 AIR SWING MOTOR 1 CWA981264 ← ← O
34 CAP - DRAIN TRAY 1 CWH521259 ← ←
35 HORIZONTAL VANE COMPLETE 1 CWE24C1385 ← ←
36 REMOTE CONTROL COMPLETE 1 CWA75C4185 ← ← O
37 FRONT GRILLE COMPLETE 1 CWE11C5053 ← ← O
38 INTAKE GRILLE COMPLETE 1 CWE22C1723 ← ← O
39 GRILLE DOOR COMPLETE 1 CWE14C1090 ← ←
40 AIR FILTER 2 CWD001279 ← ←
41 SCREW - FRONT GRILLE 2 XTT4+16CFJ ← ←
42 CAP - FRONT GRILLE 2 CWH521227 ← ←
43 DRAIN HOSE 1 CWH851174 ← ←
44 INSTALLATION PLATE 1 CWH361134 ← ←
45 BAG COMPLETE - INSTALLATION SCREW 1 CWH82C1705 ← ←
46 OPERATING INSTRUCTION 1 CWF568828 ← ←
47 INSTALLATION INSTRUCTION 1 CWF615577 ← ←
50 BAG 1 CWG861497 ← ←
162
CS-S10PKH CS-S13PKH CS-S15PKH
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. REMARK
S.E.Asia
51 SHOCK ABSORBER (L) 1 CWG713386 ← ←
52 SHOCK ABSORBER (R) 1 CWG713387 ← ←
53 C.C.CASE 1 CWG568782 CWG568783 CWG568784
(Note)
• All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
• “O” marked parts are recommended to be kept in stock.
163
18.1.2 CS-S18PKH CS-S24PKH
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
164
CS-S18PKH CS-S24PKH
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. REMARK
Malaysia only
1 CHASSIS COMPLETE 1 CWD50C1654 ←
2 FAN MOTOR 1 ARW7628AC ← O
3 CROSS-FLOW FAN COMPLETE 1 CWH02C1150 ←
4 BEARING ASSY 1 CWH64K007 ←
5 SCREW - CROSS-FLOW FAN 1 CWH551146 ←
6 GENERATOR COMPLETE 1 CWH94C0043 ←
7 EVAPORATOR 1 CWB30C4320 CWB30C4312
8 FLARE NUT (LIQUID) 1 CWT251030 ←
9 FLARE NUT (GAS) 1 CWT251032 CWT251033
10 CLIP FOR SENSOR 1 CWH711019 ←
11 CONTROL BOARD CASING 1 CWH102449 ←
12 TERMINAL BOARD COMPLETE 1 CWA28C2364 CWA28C2365 O
13 ELECTRONIC CONTROLLER - MAIN 1 CWA73C7281 CWA73C7283 O
14 ELECTRONIC CONTROLLER - HVU 1 N0GE1F000002 ← O
15 ELECTRONIC CONTROLLER - INDICATOR 1 CWA746634 ← O
16 SENSOR COMPLETE 1 CWA50C2401 ← O
17 SENSOR COMPLETE(ECO) 1 CWA50C2826 ← O
18 ELECTRONIC CONTROLLER (ECO SENSOR) 1 CWA745791 ← O
19 ELECTRONIC CONTROLLER (ECO SENSOR) 1 CWA746206 ← O
20 ELECTRONIC CONTROLLER (COMPARATOR) 1 CWA746653 ← O
21 LEAD WIRE - PCB ECO 1 CWA67C9934 ←
22 CONTROL BOARD CASING FOR PCB ECO 1 CWD933407A ←
23 CONTROL BOARD TOP COVER 1 CWH131467 ←
24 INDICATOR HOLDER 1 CWD933406 ←
25 CONTROL BOARD FRONT COVER CO. 1 CWH13C1247 ←
26 DISCHARGE GRILLE COMPLETE 1 CWE20C3242 ←
27 BACK COVER CHASSIS 1 CWD933031 ←
28 FULCRUM 2 CWH621138 ←
29 VERTICAL VANE 11 CWE241374 ←
30 CONNECTING BAR (RIGHT) 1 CWE261257 ←
31 CONNECTING BAR (LEFT) 1 CWE261258 ←
32 AIR SWING MOTOR 1 CWA98K1018 ← O
33 AIR SWING MOTOR 1 CWA981241 ← O
34 CAP - DRAIN TRAY 1 CWH521259 CWH521096
35 HORIZONTAL VANE COMPLETE 1 CWE24C1392 ←
36 REMOTE CONTROL COMPLETE 1 CWA75C4185 ← O
37 FRONT GRILLE COMPLETE 1 CWE11C5091 ← O
38 INTAKE GRILLE COMPLETE 1 CWE22C1728 ← O
39 GRILLE DOOR COMPLETE 1 CWE14C1090 ←
40 AIR FILTER 2 CWD001283 ←
41 SCREW - FRONT GRILLE 3 XTT4+16CFJ ←
42 CAP - FRONT GRILLE 3 CWH521227 ←
43 DRAIN HOSE 1 CWH851174 ←
44 INSTALLATION PLATE 1 CWH361098 ←
45 BAG COMPLETE - INSTALLATION SCREW 1 CWH82C1705 ←
46 OPERATING INSTRUCTION 1 CWF568827 ←
47 INSTALLATION INSTRUCTION 1 CWF615577 ←
48 INSTALLATION INSTRUCTION 1 CWF615578 ←
49 INSTALLATION INSTRUCTION 1 CWF615579 ←
165
CS-S18PKH CS-S24PKH
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. REMARK
Malaysia only
50 BAG 1 CWG861498 ←
51 SHOCK ABSORBER (L) 1 CWG713402 ←
52 SHOCK ABSORBER (R) 1 CWG713403 ←
53 C.C.CASE 1 CWG568785 CWG568786
(Note)
• All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
• “O” marked parts are recommended to be kept in stock.
166
CS-S18PKH CS-S24PKH
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. REMARK
Myanmar only
1 CHASSIS COMPLETE 1 CWD50C1654 ←
2 FAN MOTOR 1 ARW7628AC ← O
3 CROSS-FLOW FAN COMPLETE 1 CWH02C1150 ←
4 BEARING ASSY 1 CWH64K007 ←
5 SCREW - CROSS-FLOW FAN 1 CWH551146 ←
6 GENERATOR COMPLETE 1 CWH94C0043 ←
7 EVAPORATOR 1 CWB30C4320 CWB30C4312
8 FLARE NUT (LIQUID) 1 CWT251030 ←
9 FLARE NUT (GAS) 1 CWT251032 CWT251033
10 CLIP FOR SENSOR 1 CWH711019 ←
11 CONTROL BOARD CASING 1 CWH102449 ←
12 TERMINAL BOARD COMPLETE 1 CWA28C2364 CWA28C2365 O
13 ELECTRONIC CONTROLLER - MAIN 1 CWA73C7290 CWA73C7291 O
14 ELECTRONIC CONTROLLER - HVU 1 N0GE1F000002 ← O
15 ELECTRONIC CONTROLLER - INDICATOR 1 CWA746634 ← O
16 SENSOR COMPLETE 1 CWA50C2401 ← O
17 SENSOR COMPLETE (ECO) 1 CWA50C2826 ← O
18 ELECTRONIC CONTROLLER (ECO SENSOR) 1 CWA745791 ← O
19 ELECTRONIC CONTROLLER (ECO SENSOR) 1 CWA746206 ← O
20 ELECTRONIC CONTROLLER (COMPARATOR) 1 CWA746653 ← O
21 LEAD WIRE - PCB ECO 1 CWA67C9934 ←
22 CONTROL BOARD CASING FOR PCB ECO 1 CWD933407A ←
23 CONTROL BOARD TOP COVER 1 CWH131467 ←
24 INDICATOR HOLDER 1 CWD933406 ←
25 CONTROL BOARD FRONT COVER CO. 1 CWH13C1247 ←
26 DISCHARGE GRILLE COMPLETE 1 CWE20C3242 ←
27 BACK COVER CHASSIS 1 CWD933031 ←
28 FULCRUM 2 CWH621138 ←
29 VERTICAL VANE 11 CWE241374 ←
30 CONNECTING BAR (RIGHT) 1 CWE261257 ←
31 CONNECTING BAR (LEFT) 1 CWE261258 ←
32 AIR SWING MOTOR 1 CWA98K1018 ← O
33 AIR SWING MOTOR 1 CWA981241 ← O
34 CAP - DRAIN TRAY 1 CWH521259 CWH521096
35 HORIZONTAL VANE COMPLETE 1 CWE24C1392 ←
36 REMOTE CONTROL COMPLETE 1 CWA75C4185 ← O
37 FRONT GRILLE COMPLETE 1 CWE11C5091 ← O
38 INTAKE GRILLE COMPLETE 1 CWE22C1728 ← O
39 GRILLE DOOR COMPLETE 1 CWE14C1090 ←
40 AIR FILTER 2 CWD001283 ←
41 SCREW - FRONT GRILLE 3 XTT4+16CFJ ←
42 CAP - FRONT GRILLE 3 CWH521227 ←
43 DRAIN HOSE 1 CWH851174 ←
44 INSTALLATION PLATE 1 CWH361098 ←
45 BAG COMPLETE - INSTALLATION SCREW 1 CWH82C1705 ←
46 OPERATING INSTRUCTION 1 CWF568828 ←
47 INSTALLATION INSTRUCTION 1 CWF615626 ←
50 BAG 1 CWG861498 ←
51 SHOCK ABSORBER (L) 1 CWG713402 ←
167
CS-S18PKH CS-S24PKH
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. REMARK
Myanmar only
52 SHOCK ABSORBER (R) 1 CWG713403 ←
53 C.C.CASE 1 CWG568785 CWG568786
(Note)
• All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
• “O” marked parts are recommended to be kept in stock.
168
CS-S18PKH CS-S24PKH
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. REMARK
S.E.Asia
1 CHASSIS COMPLETE 1 CWD50C1654 ←
2 FAN MOTOR 1 ARW7628AC ← O
3 CROSS-FLOW FAN COMPLETE 1 CWH02C1150 ←
4 BEARING ASSY 1 CWH64K007 ←
5 SCREW - CROSS-FLOW FAN 1 CWH551146 ←
6 GENERATOR COMPLETE 1 CWH94C0043 ←
7 EVAPORATOR 1 CWB30C4320 CWB30C4312
8 FLARE NUT (LIQUID) 1 CWT251030 ←
9 FLARE NUT (GAS) 1 CWT251032 CWT251033
10 CLIP FOR SENSOR 1 CWH711019 ←
11 CONTROL BOARD CASING 1 CWH102449 ←
12 TERMINAL BOARD COMPLETE 1 CWA28C2364 CWA28C2365 O
13 ELECTRONIC CONTROLLER - MAIN 1 CWA73C7280 CWA73C7282 O
14 ELECTRONIC CONTROLLER - HVU 1 N0GE1F000002 ← O
15 ELECTRONIC CONTROLLER - INDICATOR 1 CWA746634 ← O
16 SENSOR COMPLETE 1 CWA50C2401 ← O
17 SENSOR COMPLETE (ECO) 1 CWA50C2826 ← O
18 ELECTRONIC CONTROLLER (ECO SENSOR) 1 CWA745791 ← O
19 ELECTRONIC CONTROLLER (ECO SENSOR) 1 CWA746206 ← O
20 ELECTRONIC CONTROLLER (COMPARATOR) 1 CWA746653 ← O
21 LEAD WIRE - PCB ECO 1 CWA67C9934 ←
22 CONTROL BOARD CASING FOR PCB ECO 1 CWD933407A ←
23 CONTROL BOARD TOP COVER 1 CWH131467 ←
24 INDICATOR HOLDER 1 CWD933406 ←
25 CONTROL BOARD FRONT COVER CO. 1 CWH13C1247 ←
26 DISCHARGE GRILLE COMPLETE 1 CWE20C3242 ←
27 BACK COVER CHASSIS 1 CWD933031 ←
28 FULCRUM 2 CWH621138 ←
29 VERTICAL VANE 11 CWE241374 ←
30 CONNECTING BAR (RIGHT) 1 CWE261257 ←
31 CONNECTING BAR (LEFT) 1 CWE261258 ←
32 AIR SWING MOTOR 1 CWA98K1018 ← O
33 AIR SWING MOTOR 1 CWA981241 ← O
34 CAP - DRAIN TRAY 1 CWH521259 CWH521096
35 HORIZONTAL VANE COMPLETE 1 CWE24C1392 ←
36 REMOTE CONTROL COMPLETE 1 CWA75C4185 ← O
37 FRONT GRILLE COMPLETE 1 CWE11C5091 ← O
38 INTAKE GRILLE COMPLETE 1 CWE22C1728 ← O
39 GRILLE DOOR COMPLETE 1 CWE14C1090 ←
40 AIR FILTER 2 CWD001283 ←
41 SCREW - FRONT GRILLE 3 XTT4+16CFJ ←
42 CAP - FRONT GRILLE 3 CWH521227 ←
43 DRAIN HOSE 1 CWH851174 ←
44 INSTALLATION PLATE 1 CWH361098 ←
45 BAG COMPLETE - INSTALLATION SCREW 1 CWH82C1705 ←
46 OPERATING INSTRUCTION 1 CWF568828 ←
47 INSTALLATION INSTRUCTION 1 CWF615577 ←
50 BAG 1 CWG861498 ←
51 SHOCK ABSORBER (L) 1 CWG713402 ←
169
CS-S18PKH CS-S24PKH
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. REMARK
S.E.Asia
52 SHOCK ABSORBER (R) 1 CWG713403 ←
53 C.C.CASE 1 CWG568785 CWG568786
(Note)
• All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
• “O” marked parts are recommended to be kept in stock.
170
18.2 Outdoor Unit
18.2.1 CU-S10PKH
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
171
CU-S10PKH
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. REMARK
Malaysia only
1 CHASSIS ASSY 1 CWD50K2235
2 FAN MOTOR BRACKET 1 CWD541069
3 SCREW - FAN MOTOR BRACKET 2 CWH551217
4 FAN MOTOR 1 CWA951702 O
5 SCREW - FAN MOTOR MOUNT 4 CWH55252J
6 PROPELLER FAN ASSY 1 CWH03K1020
7 NUT - PROPELLER FAN 1 CWH56053J
8 COMPRESSOR 1 5SS072XGA21 O
9 ANTI - VIBRATION BUSHING 3 CWH501038
10 NUT - COMPRESSOR MOUNT 3 CWH56000J
11 CONDENSER 1 CWB32C3782
12 CAPILLARY TUBE ASSY 1 CWB15K1228
13 DISCHARGE MUFFLER 1 CWB121010
14 HOLDER COUPLING 1 CWH351222
15 2-WAYS VALVE (LIQUID) 1 CWB021463 O
16 3-WAY VALVE (GAS) 1 CWB011580 O
17 TERMINAL COVER 1 CWH171041
19 SOUND PROOF BOARD 1 CWH151185
21 SOUND PROOF MATERIAL 1 CWG302700
22 SENSOR CO - COMP TEMP 1 CWA50C3062 O
23 CONTROL BOARD COVER - TOP 1 CWH131324
24 ELECTRONIC CONTROLLER - MAIN 1 CWA73C7395R O
25 ELECTRONIC CONTROLLER - NF 1 CWH14C7640 O
26 TERMINAL BOARD ASSY 1 CWA28K1036J O
27 CABINET SIDE PLATE CO. 1 CWE04C1396
28 SENSOR CO - AIR TEMP AND PIPE TEMP 1 CWA50C2502 O
29 CABINET SIDE PLATE (LEFT) 1 CWE041205A
30 CABINET FRONT PLATE CO. 1 CWE06K1090
31 CABINET TOP PLATE 1 CWE031041A
32 PLATE - C. B. COVER TERMINAL 1 CWH131325
33 CONTROL BOARD COVER CO. 1 CWH13C1186
35 STRAINER 1 CWB11025
36 BAG 1 CWG861216
37 BASE BOARD - COMPLETE 1 CWG62C1046
38 SHOCK ABSORBER (LEFT) 1 CWG712435
39 SHOCK ABSORBER (RIGHT) 1 CWG712437
40 C.C.CASE 1 CWG568777
41 PLATE SPRING 1 CWH71044
(Note)
• All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
• “O” marked parts are recommended to be kept in stock.
172
CU-S10PKH
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. REMARK
Myanmar only
1 CHASSIS ASSY 1 CWD50K2235
2 FAN MOTOR BRACKET 1 CWD541069
3 SCREW - FAN MOTOR BRACKET 2 CWH551217
4 FAN MOTOR 1 CWA951702 O
5 SCREW - FAN MOTOR MOUNT 4 CWH55252J
6 PROPELLER FAN ASSY 1 CWH03K1020
7 NUT - PROPELLER FAN 1 CWH56053J
8 COMPRESSOR 1 5SS072XGA21 O
9 ANTI - VIBRATION BUSHING 3 CWH501038
10 NUT - COMPRESSOR MOUNT 3 CWH56000J
11 CONDENSER 1 CWB32C3782
12 CAPILLARY TUBE ASSY 1 CWB15K1228
13 DISCHARGE MUFFLER 1 CWB121010
14 HOLDER COUPLING 1 CWH351222
15 2-WAYS VALVE (LIQUID) 1 CWB021463 O
16 3-WAY VALVE (GAS) 1 CWB011580 O
17 TERMINAL COVER 1 CWH171041
19 SOUND PROOF BOARD 1 CWH151185
21 SOUND PROOF MATERIAL 1 CWG302700
22 SENSOR CO - COMP TEMP 1 CWA50C3062 O
23 CONTROL BOARD COVER - TOP 1 CWH131324
24 ELECTRONIC CONTROLLER - MAIN 1 CWA73C7398R O
25 ELECTRONIC CONTROLLER - NF 1 CWH14C7640 O
26 TERMINAL BOARD ASSY 1 CWA28K1036J O
27 CABINET SIDE PLATE CO. 1 CWE04C1396
28 SENSOR CO - AIR TEMP AND PIPE TEMP 1 CWA50C2502 O
29 CABINET SIDE PLATE 1 CWE041205A
30 CABINET FRONT PLATE CO. 1 CWE06K1090
31 CABINET TOP PLATE 1 CWE031041A
32 PLATE - C. B. COVER TERMINAL 1 CWH131325
33 CONTROL BOARD COVER CO. 1 CWH13C1186
35 STRAINER 1 CWB11025
36 BAG 1 CWG861216
37 BASE BOARD - COMPLETE 1 CWG62C1046
38 SHOCK ABSORBER (LEFT) 1 CWG712435
39 SHOCK ABSORBER (RIGHT) 1 CWG712437
40 C.C.CASE 1 CWG568777
41 PLATE SPRING 1 CWH71044
(Note)
• All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
• “O” marked parts are recommended to be kept in stock.
173
CU-S10PKH
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. REMARK
S.E.Asia
1 CHASSIS ASSY 1 CWD50K2235
2 FAN MOTOR BRACKET 1 CWD541069
3 SCREW - FAN MOTOR BRACKET 2 CWH551217
4 FAN MOTOR 1 CWA951702 O
5 SCREW - FAN MOTOR MOUNT 4 CWH55252J
6 PROPELLER FAN ASSY 1 CWH03K1020
7 NUT - PROPELLER FAN 1 CWH56053J
8 COMPRESSOR 1 5SS072XGA21 O
9 ANTI - VIBRATION BUSHING 3 CWH501038
10 NUT - COMPRESSOR MOUNT 3 CWH56000J
11 CONDENSER 1 CWB32C3782
12 CAPILLARY TUBE ASSY 1 CWB15K1228
13 DISCHARGE MUFFLER 1 CWB121010
14 HOLDER COUPLING 1 CWH351222
15 2-WAYS VALVE (LIQUID) 1 CWB021463 O
16 3-WAY VALVE (GAS) 1 CWB011580 O
17 TERMINAL COVER 1 CWH171041
19 SOUND PROOF BOARD 1 CWH151185
21 SOUND PROOF MATERIAL 1 CWG302700
22 SENSOR CO - COMP TEMP 1 CWA50C3062 O
23 CONTROL BOARD COVER - TOP 1 CWH131324
24 ELECTRONIC CONTROLLER - MAIN 1 CWA73C7395R O
25 ELECTRONIC CONTROLLER - NF 1 CWH14C7640 O
26 TERMINAL BOARD ASSY 1 CWA28K1036J O
27 CABINET SIDE PLATE CO. 1 CWE04C1396
28 SENSOR CO - AIR TEMP AND PIPE TEMP 1 CWA50C2502 O
29 CABINET SIDE PLATE (LEFT) 1 CWE041205A
30 CABINET FRONT PLATE CO. 1 CWE06K1090
31 CABINET TOP PLATE 1 CWE031041A
32 PLATE - C. B. COVER TERMINAL 1 CWH131325
33 CONTROL BOARD COVER CO. 1 CWH13C1186
35 STRAINER 1 CWB11025
36 BAG 1 CWG861216
37 BASE BOARD - COMPLETE 1 CWG62C1046
38 SHOCK ABSORBER (LEFT) 1 CWG712435
39 SHOCK ABSORBER (RIGHT) 1 CWG712437
40 C.C.CASE 1 CWG568777
41 PLATE SPRING 1 CWH71044
(Note)
• All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
• “O” marked parts are recommended to be kept in stock.
174
18.2.2 CU-S13PKH
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
175
18.2.3 CU-S15PKH
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
176
CU-S13PKH CU-S15PKH
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. REMARK
Malaysia only
1 CHASSIS ASSY 1 CWD52K1256 CWD50K2071
2 FAN MOTOR BRACKET 1 CWD541157 CWD541089
3 SCREW - FAN MOTOR BRACKET 2 CWH551217 ←
4 FAN MOTOR 1 CWA951703 CWA951699 O
5 SCREW - FAN MOTOR MOUNT 4 CWH55252J ←
6 PROPELLER FAN ASSY 1 CWH03K1010 ←
7 NUT - PROPELLER FAN 1 CWH56053J ←
8 COMPRESSOR 1 5RS092XCE21 5RS102XBC21 O
9 ANTI - VIBRATION BUSHING 3 CWH50077 ←
10 NUT - COMPRESSOR MOUNT 3 CWH56000J ←
11 CONDENSER 1 CWB32C2976 CWB32C2788
12 CAPILLARY TUBE ASSY 1 CWB15K1264 CWB15K1265
13 DISCHARGE MUFFLER 1 CWB121010 ←
14 HOLDER COUPLING 1 CWH351233 ←
15 2-WAYS VALVE (LIQUID) 1 CWB021564 ← O
16 3-WAY VALVE (GAS) 1 CWB011663 ← O
17 TERMINAL COVER 1 CWH171039A ←
18 NUT - TERMINAL COVER 1 CWH7080300J ←
19 SOUND PROOF BOARD 1 CWH151172 ←
21 SOUND PROOF MATERIAL 1 CWG302431 ←
22 SENSOR CO- COMP TEMP 1 CWA50C2205 ← O
23 CONTROL BOARD COVER - TOP 1 CWH131264 ←
24 ELECTRONIC CONTROLLER - MAIN 1 CWA73C7341R CWA73C7342R O
26 TERMINAL BOARD ASSY 1 CWA28K1036J ← O
27 CABINET SIDE PLATE CO. 1 CWE04C1452 CWE04C1102
28 SENSOR CO - AIR TEMP AND PIPE TEMP 1 CWA50C2764 ← O
29 CABINET SIDE PLATE (LEFT) 1 CWE041031A ←
30 CABINET FRONT PLATE CO. 1 CWE06C1039 ←
31 CABINET TOP PLATE 1 CWE031014A ←
32 CONTROL BOARD COVER 1 CWH131301 ←
33 CONTROL BOARD COVER - COMPLETE 1 CWH13C1211 ←
34 HANDLE 1 CWE161010 ←
35 STRAINER 1 CWB11025 ←
36 REACTOR 1 G0C103J00029 G0C103J00012 O
37 BAG 1 CWG861078 ←
38 BASE BOARD - COMPLETE 1 CWG62C1095 ←
39 SHOCK ABSORBER (LEFT) 1 CWG712969 ←
40 SHOCK ABSORBER (RIGHT) 1 CWG712970 ←
41 C.C.CASE 1 CWG568778 CWG568779
(Note)
• All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
• “O” marked parts are recommended to be kept in stock.
177
CU-S13PKH
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. REMARK
Myanmar only
1 CHASSIS ASSY 1 CWD52K1256
2 FAN MOTOR BRACKET 1 CWD541157
3 SCREW - FAN MOTOR BRACKET 2 CWH551217
4 FAN MOTOR 1 CWA951703 O
5 SCREW - FAN MOTOR MOUNT 4 CWH55252J
6 PROPELLER FAN ASSY 1 CWH03K1010
7 NUT - PROPELLER FAN 1 CWH56053J
8 COMPRESSOR 1 5RS092XCE21 O
9 ANTI - VIBRATION BUSHING 3 CWH50077
10 NUT - COMPRESSOR MOUNT 3 CWH56000J
11 CONDENSER 1 CWB32C2976
12 CAPILLARY TUBE ASSY 1 CWB15K1264
13 DISCHARGE MUFFLER 1 CWB121010
14 HOLDER COUPLING 1 CWH351233
15 2-WAYS VALVE (LIQUID) 1 CWB021564 O
16 3-WAY VALVE (GAS) 1 CWB011663 O
17 TERMINAL COVER 1 CWH171039A
18 NUT - TERMINAL COVER 1 CWH7080300J
19 SOUND PROOF BOARD 1 CWH151172
21 SOUND PROOF MATERIAL 1 CWG302431
22 SENSOR CO - COMP TEMP 1 CWA50C2205 O
23 CONTROL BOARD COVER - TOP 1 CWH131264
24 ELECTRONIC CONTROLLER - MAIN 1 CWA73C7348R O
26 TERMINAL BOARD ASSY 1 CWA28K1036J O
27 CABINET SIDE PLATE CO. 1 CWE04C1452
28 SENSOR CO - AIR TEMP AND PIPE TEMP 1 CWA50C2764 O
29 CABINET SIDE PLATE (LEFT) 1 CWE041031A
30 CABINET FRONT PLATE CO. 1 CWE06C1039
31 CABINET TOP PLATE 1 CWE031014A
32 CONTROL BOARD COVER 1 CWH131301
33 CONTROL BOARD COVER - COMPLETE 1 CWH13C1211
34 HANDLE 1 CWE161010
35 STRAINER 1 CWB11025
36 REACTOR 1 G0C103J00029 O
37 BAG 1 CWG861078
38 BASE BOARD - COMPLETE 1 CWG62C1095
39 SHOCK ABSORBER (LEFT) 1 CWG712969
40 SHOCK ABSORBER (ROGHT) 1 CWG712970
41 C.C.CASE 1 CWG568778
(Note)
• All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
• “O” marked parts are recommended to be kept in stock.
178
CU-S13PKH CU-S15PKH
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. REMARK
S.E.Asia
1 CHASSIS ASSY 1 CWD52K1256 CWD50K2071
2 FAN MOTOR BRACKET 1 CWD541157 CWD541089
3 SCREW - FAN MOTOR BRACKET 2 CWH551217 ←
4 FAN MOTOR 1 CWA951703 CWA951699 O
5 SCREW - FAN MOTOR MOUNT 4 CWH55252J ←
6 PROPELLER FAN ASSY 1 CWH03K1010 ←
7 NUT - PROPELLER FAN 1 CWH56053J ←
8 COMPRESSOR 1 5RS092XCE21 5RS102XBC21 O
9 ANTI - VIBRATION BUSHING 3 CWH50077 ←
10 NUT - COMPRESSOR MOUNT 3 CWH56000J ←
11 CONDENSER 1 CWB32C2976 CWB32C2788
12 CAPILLARY TUBE ASSY 1 CWB15K1264 CWB15K1265
13 DISCHARGE MUFFLER 1 CWB121010 ←
14 HOLDER COUPLING 1 CWH351233 ←
15 2-WAYS VALVE (LIQUID) 1 CWB021564 ← O
16 3-WAY VALVE (GAS) 1 CWB011663 ← O
17 TERMINAL COVER 1 CWH171039A ←
18 NUT - TERMINAL COVER 1 CWH7080300J ←
19 SOUND PROOF BOARD 1 CWH151172 ←
21 SOUND PROOF MATERIAL 1 CWG302431 ←
22 SENSOR CO - COMP TEMP 1 CWA50C2205 ← O
23 CONTROL BOARD COVER - TOP 1 CWH131264 ←
24 ELECTRONIC CONTROLLER - MAIN 1 CWA73C7341R CWA73C7342R O
26 TERMINAL BOARD ASSY 1 CWA28K1036J ← O
27 CABINET SIDE PLATE CO. 1 CWE04C1452 CWE04C1102
28 SENSOR CO - AIR TEMP AND PIPE TEMP 1 CWA50C2764 ← O
29 CABINET SIDE PLATE (LEFT) 1 CWE041031A ←
30 CABINET FRONT PLATE CO. 1 CWE06C1039 ←
31 CABINET TOP PLATE 1 CWE031014A ←
32 CONTROL BOARD COVER 1 CWH131301 ←
33 CONTROL BOARD COVER - COMPLETE 1 CWH13C1211 ←
34 HANDLE 1 CWE161010 ←
35 STRAINER 1 CWB11025 ←
36 REACTOR 1 G0C103J00029 G0C103J00012 O
37 BAG 1 CWG861078 ←
38 BASE BOARD - COMPLETE 1 CWG62C1095 ←
39 SHOCK ABSORBER (LEFT) 1 CWG712969 ←
40 SHOCK ABSORBER (RIGHT) 1 CWG712970 ←
41 C.C.CASE 1 CWG568778 CWG568779
(Note)
• All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
• “O” marked parts are recommended to be kept in stock.
179
18.2.4 CU-S18PKH
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
180
CU-S18PKH
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. REMARK
Malaysia only
1 CHASSIS ASSY 1 CWD52K1283
2 FAN MOTOR BRACKET 1 CWD541167
3 SCREW - FAN MOTOR BRACKET 2 CWH551217
4 FAN MOTOR 1 CWA951830 O
5 SCREW - FAN MOTOR MOUNT 4 CWH55252J
6 PROPELLER FAN ASSY 1 CWH03K1066
7 NUT - PROPELLER FAN 1 CWH56053J
8 COMPRESSOR 1 5RD132XGA21 O
9 ANTI - VIBRATION BUSHING 3 CWH50077
10 NUT - COMPRESSOR MOUNT 3 CWH56000J
11 CONDENSER 1 CWB32C3783
12 CAPILLARY TUBE ASSY 1 CWB15K1483
14 HOLDER COUPLING 1 CWH351233
15 2-WAYS VALVE (LIQUID) 1 CWB021564 O
16 3-WAY VALVE (GAS) 1 CWB011663 O
17 TERMINAL COVER 1 CWH171039A
18 NUT - TERMINAL COVER 1 CWH7080300J
19 SOUND PROOF BOARD 1 CWH151274
20 SOUND PROOF MATERIAL 1 CWG302792
21 SOUND PROOF MATERIAL 1 CWG302600
22 SENSOR CO - COMP TEMP 1 CWA50C2830 O
24 ELECTRONIC CONTROLLER - MAIN 1 CWA73C7343R O
26 TERMINAL BOARD ASSY 1 CWA28K1036J O
27 CABINET SIDE PLATE CO. 1 CWE04C1443
28 SENSOR CO - AIR TEMP AND PIPE TEMP 1 CWA50C2825 O
29 CABINET SIDE PLATE 1 CWE041616A
30 CABINET FRONT PLATE CO. 1 CWE06C1360
31 CABINET TOP PLATE 1 CWE031148A
33 CONTROL BOARD COVER - COMPLETE 1 CWH13C1253
34 CONTROL BOARD COVER 1 CWH131470A
36 REACTOR 1 G0C153J00006 O
37 SOUND PROOF MATERIAL 1 CWG302793
43 CONTROL BOARD COVER - TOP 1 CWH131473
46 BAG 1 CWG861078
47 BASE BOARD - COMPLETE 1 CWG62C1144
48 SHOCK ABSORBER (RIGHT) 1 CWG713415
49 SHOCK ABSORBER (LEFT) 1 CWG713416
50 C.C.CASE 1 CWG568780
(Note)
• All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
• “O” marked parts are recommended to be kept in stock.
181
CU-S18PKH
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. REMARK
Myanmar only
1 CHASSIS ASSY 1 CWD52K1283
2 FAN MOTOR BRACKET 1 CWD541167
3 SCREW - FAN MOTOR BRACKET 2 CWH551217
4 FAN MOTOR 1 CWA951830 O
5 SCREW - FAN MOTOR MOUNT 4 CWH55252J
6 PROPELLER FAN ASSY 1 CWH03K1066
7 NUT - PROPELLER FAN 1 CWH56053J
8 COMPRESSOR 1 5RD132XGA21 O
9 ANTI - VIBRATION BUSHING 3 CWH50077
10 NUT - COMPRESSOR MOUNT 3 CWH56000J
11 CONDENSER 1 CWB32C3783
12 CAPILLARY TUBE ASSY 1 CWB15K1483
14 HOLDER COUPLING 1 CWH351233
15 2-WAYS VALVE (LIQUID) 1 CWB021564 O
16 3-WAY VALVE (GAS) 1 CWB011663 O
17 TERMINAL COVER 1 CWH171039A
18 NUT - TERMINAL COVER 1 CWH7080300J
19 SOUND PROOF BOARD 1 CWH151274
20 SOUND PROOF MATERIAL 1 CWG302792
21 SOUND PROOF MATERIAL 1 CWG302600
22 SENSOR CO - COMP TEMP 1 CWA50C2830 O
24 ELECTRONIC CONTROLLER - MAIN 1 CWA73C7349R O
26 TERMINAL BOARD ASSY 1 CWA28K1036J O
27 CABINET SIDE PLATE CO. 1 CWE04C1443
28 SENSOR CO - AIR TEMP AND PIPE TEMP 1 CWA50C2825 O
29 CABINET SIDE PLATE 1 CWE041616A
30 CABINET FRONT PLATE CO. 1 CWE06C1360
31 CABINET TOP PLATE 1 CWE031148A
33 CONTROL BOARD COVER - COMPLETE 1 CWH13C1253
34 CONTROL BOARD COVER 1 CWH131470A
35 STRAINER 1 CWB11025
36 REACTOR 1 G0C153J00006 O
37 SOUND PROOF MATERIAL 1 CWG302793
43 CONTROL BOARD COVER - TOP 1 CWH131473
46 BAG 1 CWG861078
47 BASE BOARD - COMPLETE 1 CWG62C1144
48 SHOCK ABSORBER (RIGHT) 1 CWG713415
49 SHOCK ABSORBER (LEFT) 1 CWG713416
50 C.C.CASE 1 CWG568780
(Note)
• All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
• “O” marked parts are recommended to be kept in stock.
182
CU-S18PKH
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. REMARK
S.E.Asia
1 CHASSIS ASSY 1 CWD52K1283
2 FAN MOTOR BRACKET 1 CWD541167
3 SCREW - FAN MOTOR BRACKET 2 CWH551217
4 FAN MOTOR 1 CWA951830 O
5 SCREW - FAN MOTOR MOUNT 4 CWH55252J
6 PROPELLER FAN ASSY 1 CWH03K1066
7 NUT - PROPELLER FAN 1 CWH56053J
8 COMPRESSOR 1 5RD132XGA21 O
9 ANTI - VIBRATION BUSHING 3 CWH50077
10 NUT - COMPRESSOR MOUNT 3 CWH56000J
11 CONDENSER 1 CWB32C3783
12 CAPILLARY TUBE ASSY 1 CWB15K1483
14 HOLDER COUPLING 1 CWH351233
15 2-WAYS VALVE (LIQUID) 1 CWB021564 O
16 3-WAY VALVE (GAS) 1 CWB011663 O
17 TERMINAL COVER 1 CWH171039A
18 NUT - TERMINAL COVER 1 CWH7080300J
19 SOUND PROOF BOARD 1 CWH151274
20 SOUND PROOF MATERIAL 1 CWG302792
21 SOUND PROOF MATERIAL 1 CWG302600
22 SENSOR CO - COMP TEMP 1 CWA50C2830 O
24 ELECTRONIC CONTROLLER - MAIN 1 CWA73C7343R O
26 TERMINAL BOARD ASSY 1 CWA28K1036J O
27 CABINET SIDE PLATE CO. 1 CWE04C1443
28 SENSOR CO - AIR TEMP AND PIPE TEMP 1 CWA50C2825 O
29 CABINET SIDE PLATE (LEFT) 1 CWE041616A
30 CABINET FRONT PLATE CO. 1 CWE06C1360
31 CABINET TOP PLATE 1 CWE031148A
33 CONTROL BOARD COVER - COMPLETE 1 CWH13C1253
34 CONTROL BOARD COVER 1 CWH131470A
35 STRAINER 1 CWB11025
36 REACTOR 1 G0C153J00006 O
37 SOUND PROOF MATERIAL 1 CWG302793
43 CONTROL BOARD COVER - TOP 1 CWH131473
46 BAG 1 CWG861078
47 BASE BOARD - COMPLETE 1 CWG62C1144
48 SHOCK ABSORBER (RIGHT) 1 CWG713415
49 SHOCK ABSORBER (LEFT) 1 CWG713416
50 C.C.CASE 1 CWG568780
(Note)
• All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
• “O” marked parts are recommended to be kept in stock.
183
18.2.5 CU-S24PKH
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
184
CU-S24PKH
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. REMARK
Malaysia only
1 CHASSIS ASSY 1 CWD52K1249
2 ANTI - VIBRATION BUSHING 3 CWH50077
3 COMPRESSOR 1 5RD132XHA21 O
4 NUT - COMPRESSOR MOUNT 3 CWH56000J
5 SOUND PROOF MATERIAL 1 CWG302600
6 FAN MOTOR BRACKET 1 CWD541154
7 FAN MOTOR 1 CWA951879 O
8 SCREW - FAN MOTOR BRACKET 3 CWH551217
9 SCREW - FAN MOTOR MOUNT 4 CWH55252J
10 PROPELLER FAN ASSY 1 CWH03K1017
11 NUT - PROPELLER FAN 1 CWH561092
12 CONDENSER 1 CWB32C3697
14 CAPILLARY TUBE ASSY 1 CWB15K1515
15 STRAINER 1 CWB11025
16 HOLDER COUPLING 1 CWH351225
17 3-WAY VALVE (GAS) 1 CWB011656
18 2-WAYS VALVE (LIQUID) 1 CWB021462
19 SOUND PROOF BOARD 1 CWH151257
20 TERMINAL COVER 1 CWH171039A
21 NUT - TERMINAL COVER 1 CWH7080300J
22 SENSOR CO - COMP TEMP 1 CWA50C2185 O
26 SENSOR CO - AIR TEMP AND PIPE TEMP 1 CWA50C2769 O
28 REACTOR 1 G0C153J00005 O
29 TERMINAL BOARD ASSY 1 CWA28K1036J O
30 ELECTRONIC CONTROLLER - MAIN 1 CWA73C7344R O
31 CONTROL BOARD COVER - TOP 1 CWH131333
32 CABINET SIDE PLATE CO. 1 CWE041554A
33 HANDLE 1 CWE161010
34 CABINET SIDE PLATE (LEFT) 1 CWE041592A
35 CABINET FRONT PLATE CO. 1 CWE06K1077
36 CABINET TOP PLATE 1 CWE031083A
37 CONTROL BOARD COVER 1 CWH131409A
38 CONTROL BOARD COVER - COMPLETE 1 CWH13C1238
39 RECEIVER 1 CWB14011
40 CAPACITOR 1 DS461355QP-A O
41 SOUND PROOF MATERIAL 1 CWG302624
42 SOUND PROOF MATERIAL 1 CWG302800
43 BAG 1 CWG861461
44 BASE BOARD - COMPLETE 1 CWG62C1131
45 SHOCK ABSORBER (LEFT) 1 CWG713217
46 SHOCK ABSORBER (RIGHT) 1 CWG713218
47 C.C.CASE 1 CWG568781
(Note)
• All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
• “O” marked parts are recommended to be kept in stock.
185
CU-S24PKH
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. REMARK
Myanmar only
1 CHASSIS ASSY 1 CWD52K1249
2 ANTI - VIBRATION BUSHING 3 CWH50077
3 COMPRESSOR 1 5RD132XHA21 O
4 NUT - COMPRESSOR MOUNT 3 CWH56000J
5 SOUND PROOF MATERIAL 1 CWG302600
6 FAN MOTOR BRACKET 1 CWD541154
7 FAN MOTOR 1 CWA951879 O
8 SCREW - FAN MOTOR BRACKET 3 CWH551217
9 SCREW - FAN MOTOR MOUNT 4 CWH55252J
10 PROPELLER FAN ASSY 1 CWH03K1017
11 NUT - PROPELLER FAN 1 CWH561092
12 CONDENSER 1 CWB32C3697
14 CAPILLARY TUBE ASSY 1 CWB15K1515
15 STRAINER 1 CWB11025
16 HOLDER COUPLING 1 CWH351225
17 3-WAY VALVE (GAS) 1 CWB011656 O
18 2-WAYS VALVE (LIQUID) 1 CWB021564 O
19 SOUND PROOF BOARD 1 CWH151257
20 TERMINAL COVER 1 CWH171039A
21 NUT - TERMINAL COVER 1 CWH7080300J
22 SENSOR CO - COMP TEMP 1 CWA50C2185 O
26 SENSOR CO - AIR TEMP AND PIPE TEMP 1 CWA50C2769 O
28 REACTOR 1 G0C153J00005 O
29 TERMINAL BOARD ASSY 1 CWA28K1036J O
30 ELECTRONIC CONTROLLER - MAIN 1 CWA73C7344R O
31 CONTROL BOARD COVER - TOP 1 CWH131333
32 CABINET SIDE PLATE CO. 1 CWE041554A
33 HANDLE 1 CWE161010
34 CABINET SIDE PLATE (LEFT) 1 CWE041592A
35 CABINET FRONT PLATE CO. 1 CWE06K1077
36 CABINET TOP PLATE 1 CWE031083A
37 CONTROL BOARD COVER 1 CWH131409A
38 CONTROL BOARD COVER-COMPLETE 1 CWH13C1238
39 RECEIVER 1 CWB14011
40 CAPACITOR 1 DS461355QP-A O
41 SOUND PROOF MATERIAL 1 CWG302624
42 SOUND PROOF MATERIAL 1 CWG302800
43 BAG 1 CWG861461
44 BASE BOARD - COMPLETE 1 CWG62C1131
45 SHOCK ABSORBER (LEFT) 1 CWG713217
46 SHOCK ABSORBER (RIGHT) 1 CWG713218
47 C.C.CASE 1 CWG568781
(Note)
• All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
• “O” marked parts are recommended to be kept in stock.
186
CU-S24PKH
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. REMARK
S.E.Asia
1 CHASSIS ASSY 1 CWD52K1249
2 ANTI - VIBRATION BUSHING 3 CWH50077
3 COMPRESSOR 1 5RD132XHA21 O
4 NUT - COMPRESSOR MOUNT 3 CWH56000J
5 SOUND PROOF MATERIAL 1 CWG302600
6 FAN MOTOR BRACKET 1 CWD541154
7 FAN MOTOR 1 CWA951879 O
8 SCREW - FAN MOTOR BRACKET 3 CWH551217
9 SCREW - FAN MOTOR MOUNT 4 CWH55252J
10 PROPELLER FAN ASSY 1 CWH03K1017
11 NUT - PROPELLER FAN 1 CWH561092
12 CONDENSER 1 CWB32C3697
14 CAPILLARY TUBE ASSY 1 CWB15K1515
15 STRAINER 1 CWB11025
16 HOLDER COUPLING 1 CWH351225
17 3-WAY VALVE (GAS) 1 CWB011656 O
18 2-WAYS VALVE (LIQUID) 1 CWB021564 O
19 SOUND PROOF BOARD 1 CWH151257
20 TERMINAL COVER 1 CWH171039A
21 NUT - TERMINAL COVER 1 CWH7080300J
22 SENSOR CO - COMP TEMP 1 CWA50C2185 O
26 SENSOR CO - AIR TEMP AND PIPE TEMP 1 CWA50C2769 O
28 REACTOR 1 G0C153J00005 O
29 TERMINAL BOARD ASSY 1 CWA28K1036J O
30 ELECTRONIC CONTROLLER - MAIN 1 CWA73C7344R O
31 CONTROL BOARD COVER - TOP 1 CWH131333
32 CABINET SIDE PLATE CO. 1 CWE041554A
33 HANDLE 1 CWE161010
34 CABINET SIDE PLATE (LEFT) 1 CWE041592A
35 CABINET FRONT PLATE CO. 1 CWE06K1077
36 CABINET TOP PLATE 1 CWE031083A
37 CONTROL BOARD COVER 1 CWH131409A
38 CONTROL BOARD COVER - COMPLETE 1 CWH13C1238
39 RECEIVER 1 CWB14011
40 CAPACITOR 1 DS461355QP-A O
41 SOUND PROOF MATERIAL 1 CWG302624
42 SOUND PROOF MATERIAL 1 CWG302800
43 BAG 1 CWG861461
44 BASE BOARD - COMPLETE 1 CWG62C1131
45 SHOCK ABSORBER (LEFT) 1 CWG713217
46 SHOCK ABSORBER (RIGHT) 1 CWG713218
47 C.C.CASE 1 CWG568781
(Note)
• All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
• “O” marked parts are recommended to be kept in stock.
Printed in Malaysia
SB1112-0
187