Beruflich Dokumente
Kultur Dokumente
1.0 Concrete
To be read in conjunction with preliminaries, General Conditions and the Qatar Construction Specification
Section 5
1.1.1 Standards
Unless modified by this Specification the procedures to be used in producing, transporting,
sampling and testing of the concrete shall comply with BS 5328: Parts 3 and 4. References are
also made to individual clauses of BS 5328: Part 1 and the concrete mixes are specified in
accordance with the methods given in BS 5328: Part2 In cases of conflict, this Specification
takes precedence over BS 5328.
A bracketed asterisk (*) indicates that this clause of the Specification modifies the provisions of
BS 8110 or BS 5328. This indication is included for convenience only; its absence does not
mean that the provisions of BS 8110 or BS 5328 have not been modified by this Specification.
The advice given in Ciria Guide 31 “Guide to Concrete Construction in the Gulf Region” Shall
also be followed.
1.1.2 Definitions
1.2 Materials
1.2.1 Cement
1.2.1.1 General
Cement shall comply with the relevant British Standard BS12 (Table 1 of BS 5328: Part 1).
Permitted types are specified in Forms A and C.
All cement shall be delivered to the site in sealed containers “bags” 50 kg each.
Super sulfated cement shall be used for substructure works including slab on grade and ordinary
Portland cement for other works.
Any proprietary grouts or mortars used in the Works shall not contain high alumina cement.
1.2.2 Aggregates
1.2.2.1 General
All aggregates shall comply with the relevant British Standard BS 882, (Table 2 of BS
532: Part 1). Permitted types are specified in Forms A and C.
1.2.2.2 Uniformity
The Contractor shall ensure that sufficient supplies of sand(s) and coarse aggregate(s) of
the quality and type specified are available to complete the Contract. Change of approved
aggregate source is not permitted unless new trial mix design is carried out
1.2.2.3 Absorption
Aggregates having a water absorption greater than 5.0% by weight, shall not be used in
grade C35X mixes 1 and 2 concrete as specified in From A.
1.2.3 Admixtures
Where permitted by this Specification, concrete admixtures shall comply with the requirements
of 3.4 in BS 5328: part 1. Acceptance of admixtures into the Works will only be made upon
provision of satisfactory information relating to name, source, type, dosage and justification for
use.
1.2.5 Water
Water shall comply with the requirements in 3.7 of BS 5328: part1.
1.2.6 Chlorides
The total chloride content of the concrete mix shall not exceed the limits in Table 4 of BS 5328:
part 1. The total chloride content shall be calculated from the mix proportions and measured
content of each of the constituents.
1.2.7 Sulfates
The total acid soluble sulfate content of the concrete mix, expressed as SO3, shall not exceed 4%
SO3 by mass of the cement in the mix. The sulfate content shall be calculated as the total from
the various constituents of the mix.
The constituent materials in concrete mixes designated with suffix X in form A shall comply
with the following requirement.
The combination of concrete materials will not suffer deleterious alkali-aggregate reactions in
the environmental exposure to be experienced by the structural elements. This shall be certified
by an independent expert in concrete petrography and chemistry before any concrete is supplied
to the works.
1.2.9 Concrete
Trial mixes and tests shall be carried out on concrete grades C35X mix references 1
and 2.
1.2.10.1 General
Before any concrete is supplied to the Works, evidence shall be provided for each
grade of concrete showing that, at the intended workability, the proposed mix
proportions and manufacturing method will produce concrete of the required quality.
1.2.10.2 Strength
The evidence shall comprise either:
The results of trial mixes from three separate batched of concrete each made using the
proposed mix and constituent materials and under full scale production conditions.
The workability of each trial batch shall be determined and shall be within the
tolerances stated in BS 5328.
Three cubes shall be made from each batch, and shall be tested at 28 days. The
average strength of the nine 28 day cubes shall exceed the specified characteristic
strength by not less than 11.5N/mm 2. Alternatively, earlier tests on nine cubes shall
demonstrate that the specified characteristic strength will be exceeded by 11.5N/mm 2.
OR
These results shall demonstrate that the mean strength of the concrete mix exceeds the
specified characteristic strength by more than 1.64 times the standard deviation of the
results.
The mixes below shall be supplied as designed mixes in accordance with the project
specification
1. Mix reference 1 2
2. Strength grade C35X C35X
3. Nominal maximum size of aggregate, mm 10 20
4. Type of aggregate Coarse (* = permitted) BS 882* BS 882*
Other BS 1047 BS 1047
Sand
Other BS 882* BS 882*
5. Sulfate class 2 2 See Bore hole test
6. Cement type(s) or combinations complying
with (* = = permitted) BS 12 PC PC
BS 146 PBFC* PBFC*
BS 6588 PPFAC PPFAC
BS 4027 SRPC SRPC
Others
7. Minimum cement content, kg/m3 350 330 See Drawings
8. Maximum free water / cement ratio 0.55 0.50
9. Quality assurance requirements See Spec. See Spec.
10.Rate pf sampling intended by the purchaser See Spec. See Spec.
for strength testing (for information)
11. Other requirements:
11.1 Maximum chloride content See Spec. See Spec.
11.2 ASR requirements (Mix X) See Spec. See Spec.
11.3 Temperature (max./min. C) See Spec. See Spec.
11.4 Density (max./min.kg/m3)
11.5 Admixtures See Spec. See Spec.
11.6 Air content
11.7 Max. cement content 450 450
11.8 Max drying shrinkage See Spec. See Spec.
11.9 Special cement
11.10 Special aggregates See Spec. See Spec.
11.11 (AR: Additional See Notes See Notes
Requirements Schedule) 1and 2 1and 2
Section to be completed by purchaser of fresh concrete
12. Workability
(* method and give target) Slump, mm -
Compacting
factor
Vebe,s
Flow, mm
(ii) T: Type 2 deformed high yield steel bars complying with BS 4449
with a characteristic strength of 460N/mm2.
Steel fabric shall comply with BS 4483 and shall be delivered to site in flat sheets.
Horizontal and vertical water bars shall be linked to form a continuous network.
They shall be jointed with purpose-made junction pieces and in accordance with the
manufacturer’s written instructions.
1.2.14.1 Cement
Cement shall be used in the order that it is received on site.
1.2.14.2 Aggregates
Aggregates shall be stored on hard paved self-draining areas or in suitable hoppers or
containers with protection from wind blown salts and dust.
1.2.14.3 Reinforcement
Reinforcement shall be stored clear of the ground and protected from mud, oil, salts,
and other substances which may adversely affect its use in the Works.
Steel fabric shall be delivered and stored flat.
1.3 Workmanship
No Metal part of any device for maintaining formwork in the correct location shall remain
permanently within the specified concrete cover to the reinforcement.
In watertight construction, methods of fixing formwork which result in holes through the
concrete section when the formwork is removed shall not be used. In addition all wall ties
shall have water baffles and wall kickers shall be cast monolithically with the base slab.
Release agents shall be stored and used strictly in accordance with the manufacturer’s
instructions.
Where masonry units such as rubble stone walls or hollow blocks are to be used as
permanent formwork they shall be thoroughly washed to remove salt contamination before
being placed. Once in place they shall be protected from wind blown salts and other
contaminants until all reinforcement and concrete are placed.
The spacing of Construction joints shall be such that the areas of concrete to be poured can
be properly resourced, placed compacted, finished and cured properly.
(i) The position and spacing of joints which will be acceptable will vary from place to
place but Table 1 gives an indication of acceptable limits.
1.3.4 Reinforcement
Each bundle of bars shall be clearly tagged with their schedule and mark numbers
All reinforcement shall be positively held in its correct position before concreting starts.
Spacers between reinforcement and formwork shall be of either concrete or plastic.
Where concrete spacer blocks are required in exposed concrete they shall be made from
the materials that will be used in the surrounding concrete.
Any reading which indicate poor electrical connection ie, resistance readings in excess of
1 ohm, shall have attention of the Owner’s authorized representative and remedial works
implemented.
Prior to concreting the Contractor shall ensure that a satisfactory test for electrical
continuity has been carried out.
On completion of the superstructure works the Contractor shall measure the resistance to
earth of the earth termination network and record the results. These tests shall be carried
out in accordance with the method recommended in BS CP 1013, clause 401, at each down
conductor column position.
1.3.5 Concreting
The concrete shall not be placed directly against a vertical form face but shall be caused to
flow to this surface during the compaction process. Care shall be taken to avoid the form
face being splashed with mortar during the placing operation.
Compaction shall start as soon as casting starts and shall continue during the placing
operation so that at no time shall there be a large volume of uncompacted concrete in the
formwork.
Starter sections (kickers or plinths) or walls, columns, etc, shall be cast and compacted in
such a way that their strength and other characteristics are at lest equal to those specified
for the whole member.
1.3.5.5 Cleaning
All equipment used for mixing, transporting, placing and compacting concrete shall be
thoroughly cleaned before changing from one type of aggregate or cement to another and
whenever mixing ceases.
(ii) Concrete in walls, columns and beams shall have formwork left in place for a
minimum 24 hours. Metal formwork shall be insulated. On removal of formwork the
concrete shall be closely wrapped with wet hessian and enclosed with polythene
sheeting. The hessian should be kept wet and retained in position for 7 days. On
removal of the hessian and sheeting the concrete shall be sprayed with a curing
membrane.
1.3.6.2 Protection
Any formwork made of metal, concrete or other material of high thermal capacity shall be
cooled with water before concrete is placed against it.
1.3.7.1 General
Before any formwork is removed the Contractor shall ensure that the concrete has attained
sufficient strength for striking to proceed.
The structure shall not be distorted, damaged or overloaded in any way by the removal of
the formwork.
1.3.9.1 General
Unless shown otherwise on the drawings, formed concrete finished shall be type A.
Unformed concrete surfaces shall be type 2U.
(ii) Type 2U: after the concrete has stiffened sufficiently, the Type 1U finish shall be
floated by hand or machine sufficiently just to produce a uniform surface free from
screed marks.
(iii) Type 3U: when the surface moisture has disappeared and the concrete has stiffened
sufficiently to prevent laitance from being worked to the surface, a type 1U finish to
be steel-trowelled under firm pressure to produce a dense, smooth uniform surface
free from trowel marks.
1.3.10.1 General
All sampling and testing of sands and aggregates shall be carried out in accordance with
BS 812.
For the grades of concrete other than 7, 10 and 15, the grading of each size of sand and
aggregate from each pit, quarry or other source of supply shall be determined at least once
weekly. The results of such tests shall be used to check whether the gradings are similar to
those of the samples used in the establishment of the batch weights. The results of routine
control tests carried out by the aggregate producer will be accepted for this purpose.
1.3.11.1 General
The results of all tests shall be provided weekly.
The rate of sampling shall be in accordance with clause 8.2 and Table 15 of BS 5328: Part
1.
In addition, for each sample, one cube shall be made for testing at 7 days.
In addition, test of the crushed cubes for chloride content by weight of cement in the
concrete.
One test shall be made from each delivery, or each batch, whichever is the lesser volume.
1.3.13.1 Recalibration
Ensure that recalibration of the measuring equipment by the manufacturer or his agent is
undertaken at intervals of not more than 3 months.
Compliance with the following requirements adjusted as necessary by any specified pre-camber
shall be established before de-propping.
End of Section