2. Electronic characteristics
・250CF(35SF)、660CF(600CF)、800CF(700CF)、400KH(350KH)、600KH(600KH)
Less than 0.5 (Regular current, AC sine wave current)
Less than 0.4 (Pulse wave-form for inverters, power regulators, etc)
・250GH、350GH、660GH、600SPF、1000SPF
Less than 0.8 (Regular current, AC sine wave current)
Less than 0.6 (Pulse wave-form for inverters, power regulators, etc)
・1000GH、1500SPF
Less than 0.6 (Regular current, AC sine wave current)
Less than 0.5 (Pulse wave-form for inverters, power regulators, etc)
2.3 Current waves
The effective value of current
2 2 2
Circuit current 回路電流実効値
effective value =
I1 ´ t1 + I 2 ´ t 2 + I 3 ´ t 3
T
I2
Current
I3
I1
t1 t2 t3 Time
T
If one cycle (T) is less than 100msec, the rated current of a fuse will be determined by using the
reduction coefficient in 2.2 Regular current.
※ If the pausing time is longer than the operating time, the above calculation will not work
even though one cycle (T) is less than 100msec. Please contact to us for the details.
2.4 Interrupting
・Breaking capacity
The short-circuit breaking capacity is shown on the fuse. Fuses should be used at a level
below the breaking capacity.
・Total I2t
A combination of pre-arc I2t and arc I2t is specified as the total I2t. The total I2t in our
catalogue is a value at the maximum rated voltage. If a fuse is used at lower circuit than
the rated voltage, please refer to the table RMS Circuit Voltage Vs. I2t Correction Factor in
our catalogue. When selecting a fuse, the total I2t of the fuse should not exceed the I2t of
semiconductor elements.
Voltage
Time
Total time
Arc time
Fusing time
Cut-off current
Current
Time
Pre-arc I2t Arc I2t
・Cut-off current
The relation between peak let-thru value and current is expressed as the Current Limiting
Characteristics. Please refer to our catalogue for the characteristics of each fuse.
・Operating over loaded voltage
When a fuse cuts off, the high arc voltage will occur between the fuse electrodes, and this arc
voltage is called the operating over loaded voltage. At maximum, this will be 2 times larger
than the rated voltage.
・DC interrupting
Interrupting operation at DC circuit is easily influenced by circuit time constant. Please
refer to our catalogue for circuit voltages expressed against the circuit time constant.
・Minimum interrupting current
Protect fuses for semiconductor devices are designed so that they do not cut off and can’t be
interrupted at a low current. The minimum interrupting current depends on each fuse.
Please refer to the minimum interrupting current in our catalogue. Please use fuses in
conjunction with other protectors if the short-circuit current of the circuit is lower than the
minimum interrupting current.
・Melting time-current characteristics
The curves show the relation between the current and time starting from the over loaded
current flow into the fuse until the fuse element cuts off. This characteristics specify its
average value, and the current will be fused at ±15% in the current axis.
A switch for sending a signal electrically at the point of contact is installable to an indicator.
3.Installation
Our fuses are divided into 3 types; cylindrical fuses used with fuse holders, circle fuses with
L-shaped terminals fixed with screws, and square body fuses bolted at both ends. Please
select the appropriate type by considering usage. Fuse holders for cylindrical fuses are also
available. When fuses are installed as described below (parallel), please leave the described
space to allow heat to be released.
0.8
低減係数
Reduction
coefficient 0.6
0.4
0.2
0
0 50 100 150
周囲温度 (単位:℃)
Ambient temperature
3.3 Vibration
The guaranteed vibration test is at 10-30Hz for 1 minute, total amplitude 1mm 3 distances for
30 minutes per distance.
4. Operating longevity
Load factor
Ta=25℃
7
10
(A) Regular load (rectified circuit, etc)
Load factor: less than 0.8 (A)
(B) Repetitive operating and pausing.
With adequate pausing time (C)
(B)
Load factor: less than 0.7 106
N number
105
N
4
10
operating pausing 3
10
0.1 0.2 0.3 0.4 0.5 0.7 0.9
0.6 0.8 1.0
Load factor
Effective value of operating
operetingccurrent
urrent
Load factor =
Rated Current
Operating Pausing
IS:Test current value
IM:Fusing current at t1 time
IS
t1:Operating time
t2:Pausing time (time for sufficient cooling down)
t1 t2
IS IM
Current (A)
・250GH Series
・350GH Series
・660GH Series
・SPF Series
1.0E+06
Operating time
① Less than 100ms
② Less than 1s
③ Less than 10s
回数N
1.0E+05
④ Less than 100s N
Number
1.0E+04
1.0E+03
0.1 1
Load負荷率
factor