Section 3

Blast Dampers
Overview Physics of a Blast

Wozair manufacture two types of Blast An explosion releases energy into the
Damper: atmosphere. Pressure increases almost
instantaneously from ambient to a
Wozair Type BRD – peak pressure (also referred to as
Blast Resistant Damper Peak Overpressure) forming
a pressure shock wave with highly

Dampers
Designed as a robust heavy duty compressed air known as the
device used as an HVAC louvre on a Incident Blast Wave. The
module or building blast wall. Although minuscule rise time from ambient
the device is structurally designed to to peak pressure is referred as the
withstand a blast, it provides a limited in Blast Duration. The blast wave
reduction of the over pressure. rapidly expands into the atmosphere
spherically until equilibrium is reached,
Wozair Type BPD – thereafter pressure decays with time
Blast Protection Damper and displacement. A negative pressure
phase is also formed in the process as
This is a unique (Patent Pending) shown below. The negative pressure
device that, in conjunction with a phase is longer in duration and is not
Wozair Blast Resistant Damper is considered critical in designing blast
designed to not only maintain integrity resistant and blast proof structures.
after a blast event but also to reduce
over pressurisation to a safe level,
protecting personnel and equipment.

Blast Dampers are primarily designed


to protect inhabitants in an enclosed
area against resulting over pressure
from a blast penetrating through the
openings of a structure such as the
HVAC duct system. The transient
over pressure loads generated by a
blast event can cause severe human
biological effects such as ear and lung
injuries as well as damage to sensitive
equipment and internal fittings.
Incorporating blast dampers into the
HVAC system should be considered
+ Pressure
mandatory where risks related to Positive Phase

explosion have been identified. Peak


Pressure

Atmospheric Time
Pressure
Blast
Duration
- Pressure
Negative Phase

Pressure Transient

23
Section 3

When the Incident Blast Wave Blast Damper Rating Design of Wozair Blast
impinges on a surface it is reflected Dampers
and amplified and is referred to as the In order to establish a correct selection
Reflected Blast Pressure. The of a blast damper it is important for From conceptual to final design
amplification depends on the Incident the system designers to specify the Wozair has extensively utilized
Angle of the pressure shock front. Reflected Blast Pressure (typically Computational Fluid Dynamics
between 0.35 barg/35 kPa and 1.0 (CFD) modelling (provided by BMT
Maximum pressure is experienced by a barg/100 kPa) and Blast Duration Fluid Mechanics Ltd) to analyse the
surface if the blast wave impinges on it (typically between 7ms and 22ms). behaviour of blast waves. Typical
perpendicular to the direction in which Incident pressure is not considered offshore blast scenarios were simulated
Dampers

it travels. If the surface is parallel only when rating blast dampers as other in the virtual environment to optimize
the incident pressure is experienced, structural elements may constitute the performance of the blast dampers
therefore reflected pressure is always reflection of the blast wave further both in normal operating as well as
greater than incident pressure at the increasing blast pressure. blast conditions. Results obtained from
same distance from the blast epicentre. the CFD simulations have been verified
by Det Norske Veritas (DNV).
The peak reflected pressure is a
function of the incident angle and
the incident blast pressure which is a
function of the blast source (explosive
material, weight etc) and distance.

24
Section 3

Blast Resistant
Damper
Wozair type BRD
Introduction

Designed for the offshore and onshore


oil and gas industries the Wozair Blast
Resistant Damper is a robust heavy

Dampers
duty device used as an HVAC louvre on
a module or building blast wall.

Description

Materials
Wozair Blast Resistant Dampers are
available manufactured in stainless
steel throughout.

Casing Linkage Auto Reset


This is a continuously welded channel Dampers with multiple blades are Louvre blades are held at
section 250mm deep formed from 5mm fitted with a linkage to provide a approximately 45° open position by a
thick material. Flange drillings are in parallel motion. Robust blade links torsion spring pack, selected to close
accordance with Wozair standard or are welded to the louvre blade shafts upon the specified blast pressure
to specific client requirements. Casings and connected together by flat bar and then return the blades to the
are provided with 20mm diameter lifting and stainless steel pins. The linkage open position once the blast pressure
holes as standard. arrangement is contained within the subsides.
flanges of the damper frame.
Debris Catcher Manual Reset
At the inlet face to the Blast Resistant Controls Options Louvre blades are held at
Damper is fitted a Debris Catcher that Wozair Blast Resistant Dampers can approximately 45° open position by
consists of 30mm x 3mm interlocking be supplied with the following control a spring loaded latching mechanism,
flat bars on edge arranged as a welded options, both fitted into a robust 3mm selected to close upon the specified
grid. enclosure with removable cover, blast pressure and then remain closed
mounted on the damper side frame until manually reset.
directly connected to the louvre blade
Louvre Blades drive shaft. Options
The louvre blades are single skin Materials: Stainless Steel 304L
formed from 5mm thick material and (1.4307), 316L (1.4404) and 316L
are welded to 25.4mm diameter solid (1.4432) Mo > 2.5%
shafts. Louvre blades rotate in oil
impregnated sintered bronze bearings
fitted into the damper frame and
retained with welded thrust discs. 5mm
top and bottom blade stops are welded
into the casing.

25
Section 3

Dimensional Limits

The minimum size is 200mm wide


x 200mm high. The maximum
single module size is 1200mm wide
x 1200mm high. For larger sizes
multiple dampers can be supplied
for bolting together at site or building
into site support framework. Specific
requirements should be discussed with
Dampers

Wozair engineers.

Performance

Pressure Drop vs Velocity - BRD


350

300

250
Pressure Drop (Pa)

200

150

100

50

0
0 1 2 3 4 5 6 7
Velocity (m/s)

Weights

Unit weights (kg) for indicative sizes are


detailed below, for other sizes please
contact Wozair.

( )
)
(

26
Section 3

Blast Protection
Damper
Wozair type BPD
Introduction

Designed for the offshore and onshore


oil and gas industries the Wozair Blast
Protection Damper is a unique (Patent

Dampers
Pending) design, static blast absorption
device, used on the HVAC inlet or
exhaust penetration through a module
or building blast wall. Dimensional Limits

Correctly selected and in conjunction The minimum size is 200mm wide


with Wozair Blast Resistant Damper x 200mm high. The maximum
the arrangement reduces a blast wave single module size is 1200mm wide
to an acceptable over pressure that x 1200mm high. For larger sizes
prevents injury to personnel or damage multiple dampers can be supplied
to equipment within the module or for bolting together at site or building
building. into site support framework. Specific
requirements should be discussed with
Description Wozair engineers.

Materials Performance
Wozair Blast Protection Dampers are
available manufactured in stainless
steel throughout. Pressure Drop vs Velocity - BPD
900

Casing 800

This is a continuously welded channel 700

section 600mm deep (for a pressure 600


Pressure Drop (Pa)

up to 0.5barg) and 1200mm deep (for


a pressure up to 1.0barg) formed from
500

5mm thick material. Flange drillings are 400

in accordance with Wozair standard or 300

to specific client requirements. Casings


200
are provided with suitable lifting lugs as
100
standard.
0

Deflection Tubes
0 1 2 3 4 5 6 7
Velocity (m/s)

A series of strategically positioned


tubes are welded across and down the
length of the casing section to deflect
and dissipate the blast pressure. The
tubes also perform the function of a
debris catcher.

Options
Casing Materials: Stainless Steel 304L
(1.4307), 316L (1.4404) and 316L
(1.4432) Mo > 2.5%

27
Section 3

Weights

Unit weights (kg) for indicative sizes are


detailed below, for other sizes please
contact Wozair.
Dampers

Installation Options

DUCT DUCT FLANGE SUPPORT FRAME DUCT FLANGE DUCT

BLAST DAMPER

BULK HEAD / BLAST WALL

SLIP ON FLANGE
CENTRE FLANGE FOR BULKHEAD MOUNTING

DUCT

DUCT

DUCT
DUCT FLANGE
FLANGE

BLAST DAMPER

BULKHEAD / BLAST WALL

DUCT FLANGE

DUCT DUCT FLANGE

BLAST DAMPER DUCT

28