8 7 6 5 4 3 2 1

201 202 203 204 205 206 207 301 7,700 7,700 NOTE
PN N 1. ALL DIMENSIONS ARE IN MILLIMETTERS UNLESS NOTED.
900(TYP.)
2. ALL LEVELS AND COORDINATES ARE IN METERS UNLESS
BLOCK 1 4,000 54,500 (BLOCK 2) 1,000 OTHERWISE NOTED
10.
29° 3. ELEVATION

900(TYP.)
(EXISTING BLDG.)

100 100
7,500 10,000 10,000 9,000 10,000 8,000 3.1. MEAN SEAWATER LEEVEL(MML) = EL±0.000

200
H 3.2. GROUND LEVEL(GL) = EL+2.800 H
C1 WG1 3.3. MAIN BUILDING GROUND FLOOR LEVEL = EL+3.100
3,300 6,700 5,300 3,700 C1 4. CONCRETE GRADE / MAX.AGGREGATE SIZE / WATER CEMENT RATIO
200 200 CONCRETE MAX. MINI. CEMENT MAX. WATER
GRADE APPLICATION AGGREGATE CONTENT CEMENT RATIO
( f'c) SIZE(mm) (KG/M3) BY WEIGHT
100 100 100 100
PLANT
TRUE

4,300

4,300
MATCH LINE 15 MPa LEVELING CONC. 40 200 0.52
475 1,325 (E.J LINE)
25 MPa STRUCTURAL CONC 20 275 0.50
SILENECER#2 DETAIL

WG1

WG1
30 MPa ST FDN, CCB, INTAKE
MRT-CA02-P0UMA-180045 5of5 STG BLDG, CW SUMP
EL.+3.100(T.O.G) HANDRAIL PIT , DISCHARGE 20 300 0.50
DIA 40mm - 3.5mmTHK 7,000 TUNNEL & OUTFALL
EL.+3.060(T.O.S) 500 C1 C1 WG1

100 100
DETAIL-2 STEEL PIPE W/ PAINT (H=1.05m)

200
WHERE, f'c=CYLINDER COMPRESSICE STRENGTH AT 28-DAY
-

2,800 1,800 1,200


AA AA
3,700 1,600 5. REINFORCING BAR STRENGTH

D
EL.+6.277(T.O.C)
5.1. DEFORMED BARS

SLPOE
3 : fy=413MPa (ATSM A615 Grade 60 / JIS-G 3112)

3,600
C
F
G 5.2. MESH REINFORCEMENT : fy=413MPa(ASTM A185)

1,600
4,300

1,530
COLUMN LOCATION PLAN BEAM GIRDER FRAMING PLAN

E
7 8
525

6. CEMENT G
∅400
3,135 3,132 6.1. ASTM C150 TYPE-I : FOR CONCRETE WORK ABOVE GRADE
4,300 700 700

- SCALE : 1/80 - SCALE : 1/80


LEVEL OTHERWISE INDICATED.

690
F

60

60
PG207 PG208 PG214 6.2. ASTM C150 TYPE-II : ONLY FOR FOUNDATIONS AT OR BELOW

E
∅500 ∅500 GRADE.

C
F

3 6.3. ASTM C150 TYPE-V : FOR STRUCTURES IN DIRECT CONTACT


5,000

3 7,700
GS1 DETAIL-2 WITH SEA WATER OR GROUND WATER WITH SIMILAR BEHAVIOR.
1,390 1,465 1,465
400 200
∅200 3 ∅200
1,150
∅150
-
7. CONCRETE COVER (CAST-IN-PLACE CONCTERE)
LG203
700400 1,360 900 1,375 985 1,540 1,540

370
4,500
∅200 PG205 PG206 MIN. CONC.

410

410
E DN ITEM
1,250

800375
2,320 COVER(mm)

770
350

370
F212 3 EG21
LG204
3 3
PG201 FOUNDATION 75
EL.+3.100(T.O.G)

595550
EG22
3,900 515 115
∅200 D10@200 TOP : 4-D16 TIE BEAMS/GIRDER BEAMS BELOW GRADE 75
PIPE TRENTCH ∅550 ∅550 520 300
EL.+3.060(T.O.S)

390
PG215 MARINE STRUCTURES (INCONTACT WITH SEA WATER) 75

175
∅200

400
1,400 3,000 ∅150
7,500

HOOP : D10@200

500
H301 CONCRETE IN CONTACT WITH GROUND SURFACE 75

1,208 1,056
PG209 PG210 PG202
LG201
8-D19
600

PG211 PG212 PG213


DG21 DG22 DETAIL-3 PEDESTALS 50
PIPE TRENTCH PLAN
3,000 1,500 EL.+3.100(T.O.G) 1,200 - COLUMNS 40
GS2
2,050

∅150 BOT. : 4-D16


2,800

DG23 DG24 3,160 EL.+3.060(T.O.S) BEAM, SLAB & PRECAST PANEL 25

1,896
MRT-CA02-P0UMA-180045 4,446 1,208
C1
750

∅200 LG205
F WG1

610
PG203 8. CHAMFERED CORNERS OF CONCRETE ALL EXTERIOR CORNERS
D 3

4,300
725
DG25 DG26
DETAIL-2 (ANGLE OF 90° OR LESS) OF REINFORCED CONCRETE SHALL BE F

1,500
2,888 F237 350
∅200
300 3,300

10 COLUMN DETAIL 11 GIDER DETAIL CHAMFERED (25mmX25mm).


850
DG27 DG28
-
4,520

H301

H301
1,190
3,550
5,750 PG204

740
9. THE FOLLOWING ITEMS, SEE STANDARD DRAWING UNLESS
350
∅300
900

700
200 400 20 SCALE : 1/10 SCALE : 1/10 OTHERWISE NOTED.
LG202 - -
7,500

∅150 900 2,375 PG216 F205 (TYP.) -MINIMUM CONCRETE COVER

1,205
1,185
35,000

350
350 -HOOK, DEVELOPMENT AND SPLICES OR REBAR
TRENTCH SECTION DETAIL 10. GROUT

4,150

3,000
417 2,980

MRT-CA02-P0UMA-180045 3 A 3,500 B 10.1 NON SHRINKAGE GROUT HAVING 60 MPa STRENGTH AT 28-DAY
F214 4,500 (ASTM C109)
H301
280

C 11. THE INFORMATION ABOUT ANCHOR BOLT IS SHOWN AS REFERENCE.


F245 EL.+6.625(T.O.S) PURLIN ANCHOR BOLT SHALL BE INSTALLED ON THE BASIS OF MECHANICAL
2,550 3,000 1,300 THK20.ISOLATION JOINT(TYP.) 3 GS1 (LC-200x75x20x3.2)
700 700 4,300

3 DRAWING.
5,000

GS1 3,300 2,000 2,825 2,675 2,500 12. BEFORE CONSTRUCTION OF EQUIPMENT FOUNDATION, ELECTRICAL
A A
EL.+3.100(T.O.C) CONDUIT OF EQUIPMENT HAVE TO BE INSTALLED AS PER EQUIPMENT
D13@200(T.&B.) GENERAL ARRANGEMENT DRAWINGS & EMBEDDED CONDUIT DRAWINGS
PT/SA 9 STEEL FRAMING PLAN
400 1,570

F238

2,650 85
B D13@200(T.&B.) 13. SMALL OPENING WORK FOR SLAB & WALL (PIPE, CABLE & ETC.) SHALL

1,020
300 2,300

SCALE : 1/80 BE CARRIED OUT AT SITE AS PER MECHANICAL & ELECTRICAL DRAWING.
2,800

4,175 1,675 - 3
EL.+3.100(T.O.C) C1
4,590

E F226
ABBREVIATION

6,000

100 200
E
A B F222
4,000

GB1
GS1 D : ARCH. F : FIRE FIGHTING
10,000

400 3,950 6,950 400 2,650 M : MECH. S :SKODA


F213 F221 C1 C1 L : PLUMBING
400

3 P : PIPING

4,300
3,300 700 2,750 2,900
E : ELEC.
D13@200

3,655
B

3,300
F220 3 F223 H : HVAC.
F

C1 C1 100 450 450 100

900
A REFERENCE DRAWING
825

900
1,600

DRAWING NO. DRAWING TITLE

TURBINE OIL SUMP


F

3 STOOP B 5,250 3,600


12 "AA" SECTION DETAIL MRT-CA00-P0UMA-180015~17,19

MRT-CA01-P0UMA-180027
GROUND, MEZZ., OPERATING & ROOF FLOOR PLAN (ENLARGED)

GROUND FLOOR FRAMING PLAN


1,450 2,400 7,700 - SCALE : 1/10
700 700
MRT-CA03-P0UMA-180028~32 MEZZ, OPERATING & LOWER ROOF FLOOR FRAMING PLAN
EXCITER ROOM COLUM,
TURBINE OIL SUMP PLAN BEAM GIRDER & DETAILS MRT-CA00-P0UMA-180047 FLOOR OPENING SCHEDULE
D
F D
MRT-CA02-P0UMA-180045 - 50 350 50 MRT-CA02-P0UMA-180045 EQUIPMENT FOUNDATION REBAR DETAIL
3
400 700
GROUND FLOOR EQUIPMENT FOUNDATION & SLAB OUTLINE PLAN -1 50 125 125 50 4-M16(A.B) H301
NOTE: SCALE : 1/200 EL.+6.625(T.O.S)
300 400 125
- FOR SLEEVE DETAIL OF CONCRETE SLAB & WALL OPENING ,

50

50 125 125 50
REFER TO STANDARD DRAWING MRT-CC05-P0ZEN-175046. H301

300
D10@200
- SOME GRATING OPENINGS AND OTHERS SHALL BE REINFORCED WITH SUPPORT ANGEL AT SITE IF REQUIRED.
FOOTPATH (W:1,000)

350
FOR DETAIL REFER TO DWG. NO MRT-CA03-P0UMA-180039_15 OF 18 H301

18
(GROUTING) 30
3 BB BB
EL.+3.100(T.O.C) EL.+6.277(T.O.C) FOR CONSTRUCTION

50
STANDARD DRAWINGS 4-M16(A.B)

H301
SEE DWG. NO. MRT-CC05-P0ZEN-175045
EL.+2.800(G.L) S9 201
700

BASE PLATE:
BLOCK 1 4,000 350x350x18t
CW PIT EL.+3.100(T.O.C) TG1 3 17.APR.2019 REVISED AS PER MECH. & ELEC. ARRANGEMENT DRAWINGS.
(EXISTING BLDG.) Y.C.JEONG N.Y.KOO K.S.ROH

885 20 VAR. 20 250 PLAN 'BB' SECTION DETAIL 2 08.OCT.2018 REVISED AS PER OWNERS ON COMMENTS Y.C.JEONG N.Y.KOO K.S.ROH
700

C C
(LENGTH HAVE TO BE CONFIRMED
2-D10 AS PER SITE CONDITION) 1 25.MAY.2018 Approved by Owner on 5th DRM Y.C.JEONG N.Y.KOO K.S.ROH

13 DETAIL-3(BASE PLATE) REV.


NO.
DATE DESCRIPTION DRAWN CHKD. APPD.

- SCALE : 1/80
CHIPPING OF CONC. Project
3 SECTION "C-C" GS1 EL.+3.100(T.O.C) GS1 MUARA TAWAR COMBINED CYCLE
- SCALE : 1/40 4-D25 (TOP & BOTT.)

200
POWER PLANT BLOCK 2, 3 & 4
ADD-ON PROJECT
F
4 DETAIL-2(TR PIT + TG1 SECTION)
D13 @200 TG1 Owner
- SCALE : 1/50
450 500 350 3,600
D13 @200
EXCITER ROOM COLUM, BEAM GIRDER & DETAILS
1 SECTION "A-A" (BLOCK#2) SCALE : 1/80
- SCALE : 1/40
D10@200 Owner's Engineer

EL.+3.100(T.O.C) 3
B 3 B
EL.+2.800(G.L)
300

A
F LEGEND EPC Contractor

825
F
A GRATING (THK.40)
TG1 3 575 250 250 20
D13 @200 EL.+3.100(F.F.L) / EL.+3.060(T.O.S)
450 500 350 1,225(F LINE)
D13 @200 4-D10 5 SECTION "D-D" D13@200
D13 @200 825(A LINE)
REMOVABLE GRATING (THK.40)
EL.+3.100(F.F.L) / EL.+3.060(T.O.S)
Sub Contractor

- SCALE : 1/40 FOOTPATH (W:1,000) FOOTPATH (W:1,000) FOOTPATH (W:1,000)


CHECKED PLATE (THK.6)
BLOCK #2 FOUNDATION LIST
EL.+3.100(T.O.C) EL.+3.100(T.O.C) GS1 EL.+3.100(T.O.C) GS1
EQUIPMENT NO. EUIPMENET NAME EA REMARK S.O.G SLAB DRAWING TITLE
200

200 200
EL.+2.800(G.L) EL.+2.800(G.L) EL.+2.800(G.L)
300

300

300

F 205 WATER BOX VACUUM PUMP 2 EL.+3.100(F.F.L)


F 213 CLOSED COOLING WATER PUMP 2 CONC DECK SLAB OR GRATING DIRECTION
TG1
A F 214 CLOSED COOLING WATER H/E 2 - UNNAMED SLAB : GS1 A
4-D10 400 200
D13 @200
F 220 CHEMICAL DOSING SYSTEM 1 TG1
D13 @200 14 SECTION "F-F" D13 @200
F 223 AIR COMPRESSOR 1 SCALE : 1/40
F 226 EXCITATION TRANSFORMER 1
6 SECTION "E-E" 2 SECTION "B-B" -
0 5 10 25 50
GRAPHIC SCALE
100 200m
SCALE DRAWING NUMBER SHEET NO. REV. NO.

- SCALE : 1/40 - SCALE : 1/40 1 : 200 MRT-CA01-P0UMA-180044 1 OF 8 3


F237 AUTO SELF CLEANING STRAINER 2

8 7 6 5 4 3 2 1 A1 (594 x 841mm)
8 7 6 5 4 3 2 1

207 301 302 303 304 305 306 401 402 403 404 405 406 407 NOTE
PN N 1. ALL DIMENSIONS ARE IN MILLIMETTERS UNLESS NOTED.
2. ALL LEVELS AND COORDINATES ARE IN METERS UNLESS
1,000 56,500 (BLOCK 3) 57,000 (BLOCK 4) CCB OTHERWISE NOTED
10.
29° 3. ELEVATION
4,000 3.1. MEAN SEAWATER LEEVEL(MML) = EL±0.000
7,500 9,000 10,000 10,000 11,000 9,000 7,500 9,000 10,000 10,000 12,000 8,500
H 3.2. GROUND LEVEL(GL) = EL+2.800 H
3.3. MAIN BUILDING GROUND FLOOR LEVEL = EL+3.100
4. CONCRETE GRADE / MAX.AGGREGATE SIZE / WATER CEMENT RATIO
STAIR DETAIL
CONCRETE MAX. MINI. CEMENT MAX. WATER
MRT-CA03-P0UMA-180039 GRADE APPLICATION AGGREGATE CONTENT CEMENT RATIO
MATCH LINE ( f'c) SIZE(mm) (KG/M3) BY WEIGHT
PLANT
TRUE

(E.J LINE) 3,725 1,800 HANDRAIL 3,725 1,800 HANDRAIL 15 MPa LEVELING CONC. 40 200 0.52
DIA 40mm - 3.5mmTHK DIA 40mm - 3.5mmTHK
SILENECER#3,4 DETAIL DETAIL-2 STEEL PIPE W/ PAINT (H=1.05m) STEEL PIPE W/ PAINT (H=1.05m) 25 MPa STRUCTURAL CONC 20 275 0.50
DETAIL-2
MRT-CA02-P0UMA-180045 5of5 MRT-CA01-P0UMA-180044 MRT-CA01-P0UMA-180044 30 MPa ST FDN, CCB, INTAKE
1 of 8 1 of 8 STG BLDG, CW SUMP
EL.+4.200(T.O.G) EL.+4.200(T.O.G) DETAIL-2 PIT , DISCHARGE 20 300 0.50
EL.+4.160(T.O.S) 8,000 500 1,600 EL.+4.160(T.O.S) MRT-CA01-P0UMA-180044 TUNNEL & OUTFALL
1,500 1,700 700 2,500 1,500 1,700 700 2,500 1 of 8
1,650 WHERE, f'c=CYLINDER COMPRESSICE STRENGTH AT 28-DAY

3,000 1,800 1,200


3,000 1,800 1,200
1,650 1,600 DETAIL-2
5. REINFORCING BAR STRENGTH
MRT-CA01-P0UMA-180044 5.1. DEFORMED BARS
1 of 8

SLPOE
C D : fy=413MPa (ATSM A615 Grade 60 / JIS-G 3112)

700 3,500
G D 5.2. MESH REINFORCEMENT : fy=413MPa(ASTM A185)
1,600
4,300

3,310
700 600

810
6. CEMENT G
6.1. ASTM C150 TYPE-I : FOR CONCRETE WORK ABOVE GRADE

700
LEVEL OTHERWISE INDICATED.

750

750
F C D PG309 D 6.2. ASTM C150 TYPE-II : ONLY FOR FOUNDATIONS AT OR BELOW
700

∅500 PG309 ∅500 GRADE.


DN DN
STOOP(TYP.) 6.3. ASTM C150 TYPE-V : FOR STRUCTURES IN DIRECT CONTACT
5,000

4,300

3 3 WITH SEA WATER OR GROUND WATER WITH SIMILAR BEHAVIOR.


1,390 1,150 1,390 1,150 7. CONCRETE COVER (CAST-IN-PLACE CONCTERE)
2,750 950
3 L305 635
2,750 950
3 L405 635
∅650 ∅650 MIN. CONC.
E ITEM

370

370
1,250

1,250
510

510
COVER(mm)

600

600
3,000 2,980 3,000 2,980

1,800

1,800
F312
∅300
PG305
∅150
PG313
F412 ∅300
PG405
∅150
PG413 FOUNDATION 75
PG306 PG406
∅150
A A TIE BEAMS/GIRDER BEAMS BELOW GRADE 75

635

635
1,390
∅550
2,120
∅550
420 1,420
PG310
1,900
DETAIL-2 ∅550 ∅550
420 1,420
PG410
1,900 3 MARINE STRUCTURES (INCONTACT WITH SEA WATER) 75
875 880 1,500 735 1,390 875 2,120 880 1,500 735
1,770 2,100
7,500

PG312 PG412
850 125

850 125
PIPE TRENTCH PLAN PG311
1,770 2,100 1,950 MRT-CA01-P0UMA-180044 1OF8 PG411
CONCRETE IN CONTACT WITH GROUND SURFACE 75
296 100

296 100
3,385 3,385

5,000

5,000
∅200 ∅200
1,265 PEDESTALS 50
600

600
MRT-CA02-P0UMA-180045 PG301 PG302 PG303 PG304 ∅200 L301 1,265 GS2 PG401 PG402 PG403 PG404 ∅200 L401
EL.+3.100(T.O.G)
EL.+3.100(T.O.G) COLUMNS 40
1,208

1,208
DG31 DG32 4,480 1,500 DG41 DG42 4,480 1,500
2,700

2,700

2,700

2,700
1,300 1,300
1,800 1,800

1,800 1,800
3 2,150
EL.+3.060(T.O.S) BEAM, SLAB & PRECAST PANEL 25

1,300 1,300
∅150
F337 EL.+3.060(T.O.S) 3 F337
880 1,396

880 1,396
DG33 DG34 L303 DG43 DG44 ∅150
750

5,215 750
1,208 2,796 ∅200

610
2,400 550

2,400 550
F

350

610
8. CHAMFERED CORNERS OF CONCRETE ALL EXTERIOR CORNERS

350
∅200 L304 ∅150 L404
D DG35 DG36 ∅150 DG45 DG46 L403
2,150 (ANGLE OF 90° OR LESS) OF REINFORCED CONCRETE SHALL BE F
2,888 PG308
6,800 2,888 PG308
5,950 GS1 CHAMFERED (25mmX25mm).
5,270

1,440

1,440
5,750 850 DG37 DG38 5,750 850 DG47 DG48 975
3 3 B B 9. THE FOLLOWING ITEMS, SEE STANDARD DRAWING UNLESS
1,945

1,945
870 PG314 870 PG414
OTHERWISE NOTED.
300

300
7,500

L302 L402
∅150

1,400

1,400
3 F362 ∅150 -MINIMUM CONCRETE COVER
1,440 1,430 1,440 1,430 F462

1,510 2,620

1,510 2,620
35,000

F363 F463 -HOOK, DEVELOPMENT AND SPLICES OR REBAR


F405 10. GROUT
F305

605 3,035
3,000

3,000
550 2,980

F314 F414 10.1 NON SHRINKAGE GROUT HAVING 60 MPa STRENGTH AT 28-DAY

2,730

2,730
2,925 830 2,925 830 3,500 3,500
1,000

1,000
F364 1,053 1,010 F464 1,053 1,010 (ASTM C109)
C A B 3,500 2,500 A B 11. THE INFORMATION ABOUT ANCHOR BOLT IS SHOWN AS REFERENCE.
F445 ANCHOR BOLT SHALL BE INSTALLED ON THE BASIS OF MECHANICAL
F345 3,800 4,300
4,300

2,550 3,000 3,696 3,800 4,300 2,550 3,000 3,696 DRAWING.


5,000

GS1 GS1 12. BEFORE CONSTRUCTION OF EQUIPMENT FOUNDATION, ELECTRICAL


2,000 2,800 2,700 2,500 2,000 2,800 2,700 2,500 CONDUIT OF EQUIPMENT HAVE TO BE INSTALLED AS PER EQUIPMENT
THK.20 ISOLATION JOINT(TYP.)
700

GENERAL ARRANGEMENT DRAWINGS & EMBEDDED CONDUIT DRAWINGS


B 3,325 5,850 C1 C1 3,325 5,850 C1 C1 13. SMALL OPENING WORK FOR SLAB & WALL (PIPE, CABLE & ETC.) SHALL
1,570

1,570
1,720

1,720
700

BE CARRIED OUT AT SITE AS PER MECHANICAL & ELECTRICAL DRAWING.


2,800

2,800
3

3,100

3,100
400

400
1,500
4,590

4,590
E

7,700

7,700
400 2,950 8,950 400 400 2,950 8,950 400 ABBREVIATION E
400 4,000

400 4,000
A B A B
F322 F422 D : ARCH. F : FIRE FIGHTING

3,200

3,200
3 GB1
10,000

F313 F320 650 F413 F420 M : MECH. S :SKODA


F321 F421 L : PLUMBING
C1 C1 C1 C1 P : PIPING

700 3,600
E : ELEC.

4,600
3,300 700 2,800 3,300 700 2,800

GB1
3,700

3,700
GS1 3 4,750 F323 3 F423 F426 H : HVAC.
4,750

1,600 825
1,075 825

1,075 825
A C REFERENCE DRAWING
DRAWING NO. DRAWING TITLE

3 TURBINE OIL SUMP PLAN 3 TURBINE OIL SUMP PLAN C MRT-CA00-P0UMA-180015~17,19 GROUND, MEZZ., OPERATING & ROOF FLOOR PLAN (ENLARGED)

MRT-CA02-P0UMA-180045 5,400 3,600 2,400 MRT-CA02-P0UMA-180045 MRT-CA01-P0UMA-180027 GROUND FLOOR FRAMING PLAN
1,400 2,400 500 1,400 2,400 1,100 7,200
MRT-CA03-P0UMA-180028~32 MEZZ, OPERATING & LOWER ROOF FLOOR FRAMING PLAN
1,400 STOOP(TYP.)
MRT-CA00-P0UMA-180047 FLOOR OPENING SCHEDULE
D GROUND FLOOR EQUIPMENT FOUNDATION & SLAB OUTLINE PLAN -2 MRT-CA02-P0UMA-180045 EQUIPMENT FOUNDATION REBAR DETAIL
D
NOTE: SCALE : 1/200
207 301 407
3 - FOR SLEEVE DETAIL OF CONCRETE SLAB & WALL OPENING ,
REFER TO STANDARD DRAWING MRT-CC05-P0ZEN-175046.
1,000 975 - SOME GRATING OPENINGS AND OTHERS SHALL BE REINFORCED WITH SUPPORT ANGEL AT SITE IF REQUIRED.
FOR DETAIL REFER TO DWG. NO MRT-CA03-P0UMA-180039_15 OF 18
20 250 250 480 250 250 20 20 250 250 725 3
20 4,300 4,300 4,300

D13 @200 DITCH(BY CIVIL)


DETAIL-3
FOR CONSTRUCTION
EL.+3.100(T.O.C) GS1 EL.+3.100(T.O.C) 900(TYP.)
GS1 GS1 GS1 MRT-CA01-P0UMA-180044
EL.+2.800(G.L) 1 of 8
300
400

900(TYP.)

100 100
200
3 17.APR.2019 REVISED AS PER MECH. & ELEC. ARRANGEMENT DRAWINGS. Y.C.JEONG N.Y.KOO K.S.ROH

WG1
C1 C1

1,360
1,185 700 2 08.OCT.2018 REVISED AS PER OWNERS ON COMMENTS Y.C.JEONG N.Y.KOO K.S.ROH
C TG1 TG1 D13 @200 TG1 C
D13 @200 D13 @200 1 25.MAY.2018 Approved by Owner on 5th DRM Y.C.JEONG N.Y.KOO K.S.ROH
D13 @200
2 SECTION "B-B" C1 COLUMN DETAIL WG1 GIDER DETAIL

900
1 SECTION "A-A" SCALE : 1/40 MRT-CA01-P0UMA-180044 MRT-CA01-P0UMA-180044
REV.
NO.
DATE DESCRIPTION DRAWN CHKD. APPD.

SCALE : 1/40 - 1 of 8 Project


- 1 of 8
200 200 PURLIN

1,375
F MUARA TAWAR COMBINED CYCLE
(LC-200x75x20x3.2)
F 100 100 100 100 POWER PLANT BLOCK 2, 3 & 4
7,700

7,700

7,700
450 500 350 1,600 3 ADD-ON PROJECT
3

985
450 500 275 175 CHAMFER 1,205 740 Owner
D13@200 3 LEGEND
WG1

WG1
FOOTPATH (W:1,000)

1,540
GRATING (THK.40)
EL.+3.100(T.O.C) EL.+3.100(T.O.C)
425 150 150

GS1 EL.+3.100(F.F.L) / EL.+3.060(T.O.S)


250 50

Owner's Engineer
EL.+2.800(G.L) EL.+2.800(G.L) GRATING (THK.40)
EL.+3.900(F.F.L) / EL.+3.860(T.O.S)
B B

1,540
D13@200 PURLIN
REMOVABLE GRATING (THK.40)
C1 C1 (LC-200x75x20x3.2)
100 100

D10@200 WG1 EL.+3.100(F.F.L) / EL.+3.060(T.O.S)


D13 @200
200

TG1 D13 @200 TG1 EPC Contractor


AA AA CHECKED PLATE (THK.6)
D13 @200
3 SECTION "C-C" 4 SECTION "D-D" EL.+6.625(T.O.S)
- SCALE : 1/40
- SCALE : 1/40 "A-A" SECTION DETAIL EL.+6.277(T.O.C) S.O.G SLAB
3 3 EL.+3.100(F.F.L)
MRT-CA01-P0UMA-180044 Sub Contractor
BLOCK #3,4 FOUNDATION LIST 1 of 8 CONC DECK SLAB OR GRATING DIRECTION
EQUIPMENT NO. EUIPMENET NAME EA REMARK
F 305 , F 405 WATER BOX VACUUM PUMP 4
5 COLUMN LOCATION PLAN 6 BEAM GIRDER FRAMING PLAN 7 STEEL FRAMING PLAN - UNNAMED SLAB : GS1

- SCALE : 1/80 - SCALE : 1/80 - SCALE : 1/80 GRATING (THK.40)


F 313 , F 413 CLOSED COOLING WATER PUMP 4 EL.+4.200(T.O.G) / EL.+4.100(T.O.S) DRAWING TITLE

F 314 , F 414 CLOSED COOLING WATER H/E 4


F 320 , F 420 CHEMICAL DOSING SYSTEM 2 EXCITER ROOM COLUM, BEAM GIRDER & DETAILS
A SCALE : 1/80 A
F 322 , F 422 AIR COMPRESSOR 4
(BLOCK#3,4)
F 323 , F 424 AIR DRYER 2
F 326 , F 426 EXCITATION TRANSFORMER 3 2
GRAPHIC SCALE SCALE DRAWING NUMBER SHEET NO. REV. NO.
2 0 5 10 25 50 100 200m
F 337 , F 437 AUTO SELF CLEANING STRAINER 4 1 : 200 MRT-CA01-P0UMA-180044 2 OF 8 3
8 7 6 5 4 3 2 1 A1 (594 x 841mm)
8 7 6 5 4 3 2 1

NOTE
1. ALL DIMENSIONS ARE IN MILLIMETTERS UNLESS NOTED.
203 2. ALL LEVELS AND COORDINATES ARE IN METERS UNLESS
10 OTHERWISE NOTED
.2
° 3. ELEVATION
201 202 203 204 205 206 207 301 7,700 10,000 3.1. MEAN SEAWATER LEEVEL(MML) = EL±0.000
H 3.2. GROUND LEVEL(GL) = EL+2.800 H
17,350 350 3.3. MAIN BUILDING GROUND FLOOR LEVEL = EL+3.100
4. CONCRETE GRADE / MAX.AGGREGATE SIZE / WATER CEMENT RATIO
BLOCK 1(EXISTING BLDG.) 4,000 54,500 7,350 700 9,300 CONCRETE MAX. MINI. CEMENT MAX. WATER
GRADE APPLICATION AGGREGATE CONTENT CEMENT RATIO
3,000 54,500 (BLOCK 2) 1,000 ( f'c) SIZE(mm) (KG/M3) BY WEIGHT
15 MPa LEVELING CONC. 40 200 0.52
7,500 10,000 10,000 9,000 10,000 8,000 EL.+9.700(T.O.C)
25 MPa STRUCTURAL CONC 20 275 0.50
DETAIL-4
30 MPa ST FDN, CCB, INTAKE
3,300 6,700 5,300 3,700 180044 4of8 STG BLDG, CW SUMP

700 700 275

100 100
20 300 0.50

100 100
PIT , DISCHARGE
2,300 17,700 TUNNEL & OUTFALL
∅150
100 100

1,925

1,925
F WHERE, f'c=CYLINDER COMPRESSICE STRENGTH AT 28-DAY
L205 1,000 5. REINFORCING BAR STRENGTH
5.1. DEFORMED BARS
DETAIL-4 : fy=413MPa (ATSM A615 Grade 60 / JIS-G 3112)

200
550 900 550
G 180044 4of8 5.2. MESH REINFORCEMENT : fy=413MPa(ASTM A185)
3 EL.+9.100(T.O.C)

5,775
SLAB END LINE
6. CEMENT G
GRATING END LINE S201 S202 S211
DETAIL-2
B UP UP 6.1. ASTM C150 TYPE-I : FOR CONCRETE WORK ABOVE GRADE

4,200

3,600

3,600
LUBE OIL DIKE DETAIL OILY SUMP 675 680 265 SUMP PIT DETAIL - LEVEL OTHERWISE INDICATED.
5,600 5,000 2,550 6.2. ASTM C150 TYPE-II : ONLY FOR FOUNDATIONS AT OR BELOW
- - 2,245 1,660 320 320
A 270 570 600 270 GRADE.

2,530
300
- 270 270 6.3. ASTM C150 TYPE-V : FOR STRUCTURES IN DIRECT CONTACT
GRATING END LINE ∅250 WITH SEA WATER OR GROUND WATER WITH SIMILAR BEHAVIOR.
4,300

100 100
300
2,082 1,225 1,190 250 700 970 2,870

250

250
7. CONCRETE COVER (CAST-IN-PLACE CONCTERE)

350
20

250
∅300 ∅250
4,300 700 700

680
275
150

∅150
1,000 500 700 MIN. CONC.
P238 ITEM

298 160

690
F
P201 P229 P230
DETAIL-3 COVER(mm)

110
2,300 1,250
L205

240 320

830 298
P231

238
P236
325 800 1,850 680 265 P237 FOUNDATION 75
3

900
P234
700

450
L207
F233

1,728
∅100 ∅200
TIE BEAMS/GIRDER BEAMS BELOW GRADE 75
5,000

∅150 ∅150
H=900 CONCRETE WALL
1,950

3 MARINE STRUCTURES (INCONTACT WITH SEA WATER) 75


REMOVABLE

2,050
P233 300 500
S201 S202 S211 ∅400 F232 CONCRETE IN CONTACT WITH GROUND SURFACE 75
CONC. COVER FOR CEP 3

2,530
2,200 450
1 LUBE OIL DIKE DETAIL

450
PEDESTALS 50
100 1,550

∅150

700
150
500

150
∅200 L206 ∅150

950
320 320
COLUMNS 40

370

300
P232
E 4,460 1,080 P228 L208
- EL.+9.100(F.F.L)
SCALE : 1/100
380 1,030 600

200782

867
1,900 1,960 L201 ∅200 P227
∅150
P219 S203 P240 P241 2,220 1,930
HANDRAIL EL.+8.900(T.O.S) BEAM, SLAB & PRECAST PANEL 25
300

L209
3 840 840
∅150 ∅200 450 DIA 40mm - 3.5mmTHK
SLAB END LINE

1,775
F P244
200
UNLESS OTHERWISE NOTED HEIGHT OF DIKE WALL IS 600mm. 8. CHAMFERED CORNERS OF CONCRETE ALL EXTERIOR CORNERS
380 380

5,050
P245 P242 P243
STEEL PIPE W/ PAINT (H=1.05m) (ANGLE OF 90° OR LESS) OF REINFORCED CONCRETE SHALL BE F
P246
REMOVABLE 3
7,500

∅150
P247 ∅200 CHAMFERED (25mmX25mm).
P268
GRATING COVER FOR CEP
5,255 300 ∅300 P203 2,540 8" CONC. BLOCK 270 270 1,170 270 270 9. THE FOLLOWING ITEMS, SEE STANDARD DRAWING UNLESS

1,050
900 2,674 3,156 260300
P202
P266 P267 ∅500 ∅150 1,560 740 OTHERWISE NOTED.
354 1,290
300 650 950150

∅650
350 L210 ∅150
MONOLITHIC STEEL TROWEL -MINIMUM CONCRETE COVER

2,175
∅150 P205
∅300 2,050 2,970 MONOLITHIC STEEL TROWEL

2,300

180 1,200
P263
-HOOK, DEVELOPMENT AND SPLICES OR REBAR

1,710
P226
FINISH W/ OIL RESISTANCE PAINT
1,600

600 600

405 250
P264 P265 S204
FINISH W/ OIL RESISTANCE PAINT
1,200
P204 S206
700

∅1000 P206
D ∅150 10. GROUT
3 3
∅150
350 995 250 2,040
275 450
3 EL.+9.700(T.O.C) EL.+9.700(T.O.C) 10.1 NON SHRINKAGE GROUT HAVING 60 MPa STRENGTH AT 28-DAY
1,535 1,230 350 350 1,760

300 1,450 496 1,390 ∅200 150

2,400

2,550
260 1,450 1,900 200
S207 S208 50 (ASTM C109)
1,046 1,810 100

200 200 200


L211
∅250 290 200 11. THE INFORMATION ABOUT ANCHOR BOLT IS SHOWN AS REFERENCE.
250

350 764
527

∅150 D10@200

600
S209
S212 ∅200 P223 ANCHOR BOLT SHALL BE INSTALLED ON THE BASIS OF MECHANICAL
7,500

P207 S216
D10@200

495
200
2,300 1,960 ∅150 ∅150 P225
100

1,096
EL.+9.100(T.O.C) EL.+9.100(T.O.C) DRAWING.
1,530

2,495 400 1,035


35,000

P208 S210 3 12. BEFORE CONSTRUCTION OF EQUIPMENT FOUNDATION, ELECTRICAL

2,100
P249

400 200 750390


P224
∅250 CONDUIT OF EQUIPMENT HAVE TO BE INSTALLED AS PER EQUIPMENT
4,052

4,000
P250
3,825

2,639
2,370

846 S205 P248 P251 ∅200 GENERAL ARRANGEMENT DRAWINGS & EMBEDDED CONDUIT DRAWINGS
D10-D200
250 250 710
610 300

545 410

∅250
EL.+8.900(T.O.S)
340
∅250 P259

1,550
350 P209 495 1,460 400 1,300
S215 P222
D10-D200 13. SMALL OPENING WORK FOR SLAB & WALL (PIPE, CABLE & ETC.) SHALL

1,350 620 790

150
250 180
445 450

P212 S213 1,015 2,940


C L203
200 80

BE CARRIED OUT AT SITE AS PER MECHANICAL & ELECTRICAL DRAWING.


345

L202

500
L212 L213
880

S214
150 3

1,780
P252 ∅150
505 600 ∅150
3 P262
∅150
∅150
3,700
167 96
1,940 200 1,065 145
P253 ∅150
3 ∅150
2 SECTION "A" 3 SECTION "B"
700 700 4,300

300 1,000 760 453 ∅200 ∅150 L221


1,500
E
5,000

∅150 200 105 3,000

5,700
870 615
1,030 L204
- SCALE : 1/20 - SCALE : 1/20 ABBREVIATION E
∅200 ∅150 350 1,850 350 1,255 670 700 700430
L214 L215 ∅400 L216 ∅150
1,500

1,500

300 750 2,100 350 1,155 700 D : ARCH. F : FIRE FIGHTING

400

175 175

150
400

550 150

100 3,400 100

900 285
550 335
700 1,200

∅150 P218
M : MECH. S :SKODA
290

1,190 1,825 350 1,450 350


500

P239
805

E205 E206
700

B L222
L217 E203 L : PLUMBING

350 1,000 825 175


P260 E215
E216

175
E214

1,335
∅250 1,450 1,600 2,600 E217 P : PIPING
2,750

3 E204
E : ELEC.

2,150
3,900
3
2,690

2,850
150
365
P235 1,625 4,240 H : HVAC.
3

350
E202 L219 ∅100
∅200
1,150 E201
E207 E208 ∅150 200

4,565
∅300 P216 P217

900
3,175 400 400
1,975
∅300
10,000

∅300 L220
REFERENCE DRAWING

245
P254 ∅200 150 E209 E210

1,900
∅100

1,205
L218

300
350
E211
DRAWING NO. DRAWING TITLE
2,600

∅200 350 350 1,850 350 1,195 645 3,820


P257
1,300

750

12
P255 MRT-CA00-P0UMA-180015~17,19 GROUND, MEZZ., OPERATING & ROOF FLOOR PLAN (ENLARGED)
∅200 ∅200 ∅200
P258 2,060 875 18,440425
500

575 3,400
P256
∅150 ∅200
CAN FOR L.O.RESERVING THK.4 PLATE(TYP.)
2,315

P213 P214 P215 E213 E212


350 3,395 ∅100 MRT-CA01-P0UMA-180027 GROUND FLOOR FRAMING PLAN
1,350

∅200 L218
(300X300X300-12T)
685 700
1,200

1,200

∅200 E218 E219 MRT-CA03-P0UMA-180028~32 MEZZ, OPERATING & LOWER ROOF FLOOR FRAMING PLAN
3
735

700
535

175

A P261

MRT-CA00-P0UMA-180047 FLOOR OPENING SCHEDULE


3 3
D 1,300 150 2,265 785 1,800 800 3,200 500 140 D
FLOOR DRAIN MRT-CA02-P0UMA-180045 EQUIPMENT FOUNDATION REBAR DETAIL

150 400 SLAB END LINE 440 SLAB END LINE


1,050 PAD DETAIL
7,500 4 SUMP PIT DETAIL
3 GRATING END LINE SCALE : 1/20
-

400
3
D16 @200 MEZZANINE EQUIPMENT FOUNDATION & SLAB OUTLINE PLAN-1 200 100
FOR CONSTRUCTION
SCALE : 1/200 200
D16 @200 NOTE:
- FOR SLEEVE DETAIL OF CONCRETE SLAB & WALL OPENING , BLIND FLANGE SLIP-ON FLANGE
REFER TO STANDARD DRAWING MRT-CC05-P0ZEN-175046. SLIP-ON FLANGE
24"/BLIND/#150/A105 24"/SORF/#150/A105
24"/SORF/#150/A105
200

- SOME GRATING OPENINGS AND OTHERS SHALL BE REINFORCED WITH SUPPORT ANGEL AT SITE IF REQUIRED.
FOR DETAIL REFER TO DWG. NO MRT-CA03-P0UMA-180039_15 OF 18 PIPE : 24"/SCH. STD/A53B 3 17.APR.2019 REVISED AS PER MECH. & ELEC. ARRANGEMENT DRAWINGS. Y.C.JEONG N.Y.KOO K.S.ROH

3 C
200

2 08.OCT.2018 REVISED AS PER OWNERS ON COMMENTS Y.C.JEONG N.Y.KOO K.S.ROH

455
C C

900
1 25.MAY.2018 Approved by Owner on 5th DRM Y.C.JEONG N.Y.KOO K.S.ROH

445

445
EL.+9.100(T.O.C) REV.

100
DATE DESCRIPTION DRAWN CHKD. APPD.
NO.
7 PAD DETAIL Project
SCALE : 1/20
- STUD BOLT WITH HEAVY HEX NUTS C EL.+8.900(T.O.S) STUD BOLT WITH HEAVY HEX NUTS MUARA TAWAR COMBINED CYCLE
1-1/4"x170L(20SETS), A193Gr.B7/A194Gr.2H THK.8 RING PLATE(TYP.) 1-1/4"x170L(20SETS), A193Gr.B7/A194Gr.2H POWER PLANT BLOCK 2, 3 & 4
ADD-ON PROJECT
GASKET : 24" SPIRAL WOUND
304SS HOOP WITH GRAPHITE FILLER
CS OUTER RING 4.5mm THK
SECTION-CC Owner

200 100
200
SLIP-ON FLANGE
5 DETAIL-2 (24" (DN600))
BLIND FLANGE SLIP-ON FLANGE SCALE : 1/20
Owner's Engineer

16"/BLIND/#150/A105 16"/SORF/#150/A105 -
B 16"/SORF/#150/A105 B
PIPE : 16"/SCH. STD/A53B
C
LEGEND EPC Contractor
555
900

GRATING (THK.40)
345

345

EL.+9.100(T.O.C) EL.+9.100(F.F.L) / EL.+9.060(T.O.S)


100

BLOCK #2 FOUNDATION LIST


REMOVABLE GRATING (THK.40) Sub Contractor
EQUIPMENT NO. EUIPMENET NAME EA REMARK
EL.+9.100(F.F.L) / EL.+9.060(T.O.S)
F232 STEAM JET AIR EJECTOR 1
STUD BOLT WITH HEAVY HEX NUTS C EL.+8.900(T.O.S) STUD BOLT WITH HEAVY HEX NUTS
1"x135L(16SETS), A193Gr.B7/A194Gr.2H 1"x135L(16SETS), A193Gr.B7/A194Gr.2H CHECKED PLATE (THK.6)
F233 WATER BOX VACCUM COMTROL TANK 1 THK.8 RING PLATE(TYP.)
GASKET : 16" SPIRAL WOUND CONC DECK SLAB (THK.200,2-SPAN CONTINUOUS) DRAWING TITLE
304SS HOOP WITH GRAPHITE FILLER
CS OUTER RING 4.5mm THK
SECTION-CC EL.+9.100(F.F.L) / EL.+8.900(T.O.S)
CONC DECK SLAB OR GRATING DIRECTION
A A
6 DETAIL-3 (16" (DN400)) - UNNAMED SLAB : DS1

- SCALE : 1/20
GRAPHIC SCALE SCALE DRAWING NUMBER SHEET NO. REV. NO.
0 5 10 25 50 100 200m
1 : 200 MRT-CA01-P0UMA-180044 3 OF 8 3
8 7 6 5 4 3 2 1 A1 (594 x 841mm)
8 7 6 5 4 3 2 1

NOTE
1. ALL DIMENSIONS ARE IN MILLIMETTERS UNLESS NOTED.
207 301 302 303 304 305 306 401 402 403 404 405 406 407 2. ALL LEVELS AND COORDINATES ARE IN METERS UNLESS
OTHERWISE NOTED
3. ELEVATION
3.1. MEAN SEAWATER LEEVEL(MML) = EL±0.000
H 169,000 CCB 3.2. GROUND LEVEL(GL) = EL+2.800 H
10. 4,000 3.3. MAIN BUILDING GROUND FLOOR LEVEL = EL+3.100
2 ° 1,000 56,500 (BLOCK 3) 57,000 (BLOCK 4) 4. CONCRETE GRADE / MAX.AGGREGATE SIZE / WATER CEMENT RATIO
CONCRETE MAX. MINI. CEMENT MAX. WATER
7,500 9,000 10,000 10,000 11,000 9,000 7,500 9,000 10,000 10,000 12,000 8,500 GRADE APPLICATION AGGREGATE CONTENT CEMENT RATIO
( f'c) SIZE(mm) (KG/M3) BY WEIGHT
3,750 3,750 4,500 4,500 5,000 5,000 5,000 5,000 5,500 5,500 3,750 3,750 4,500 4,500 5,000 5,000 5,000 5,000 4,000 4,000 4,000 4,250 4,250 15 MPa LEVELING CONC. 40 200 0.52
25 MPa STRUCTURAL CONC 20 275 0.50
30 MPa ST FDN, CCB, INTAKE
MATCH LINE STG BLDG, CW SUMP
PIT , DISCHARGE 20 300 0.50
(E.J LINE) TUNNEL & OUTFALL
LUBE OIL DIKE DETAIL LUBE OIL DIKE DETAIL
GRATING END LINE

WHERE, f'c=CYLINDER COMPRESSICE STRENGTH AT 28-DAY

SLAB END LINE

SLAB END LINE


- - 5. REINFORCING BAR STRENGTH
5.1. DEFORMED BARS
725 : fy=413MPa (ATSM A615 Grade 60 / JIS-G 3112)
G 5.2. MESH REINFORCEMENT : fy=413MPa(ASTM A185)
6. CEMENT G
6,500 2,000 2,550 2,175 6,500 2,000 2,550 2,175 6.1. ASTM C150 TYPE-I : FOR CONCRETE WORK ABOVE GRADE
1,000 1,000 SLAB END LINE LEVEL OTHERWISE INDICATED.
4,300

100 100 6.2. ASTM C150 TYPE-II : ONLY FOR FOUNDATIONS AT OR BELOW
3 700 875
∅500
810
3 700 375
∅500
3,310
4,300 700 700

GRADE.
275

SUMP PIT DETAIL ∅150 3 ∅250 6.3. ASTM C150 TYPE-V : FOR STRUCTURES IN DIRECT CONTACT

300 860

300 860
750

750
300860

300860
F
P332
1,210 1,950 SUMP PIT DETAIL P432
1,210 1,950 3

1,635

1,635
970 970

2,300 1,250

2,300 1,250
2,125

2,125
P434
MRT-CA01-P0UMA-180044 3OF8 L302 P338 P339 L402 P438 P439
WITH SEA WATER OR GROUND WATER WITH SIMILAR BEHAVIOR.

2,350 2,075
P334 MRT-CA01-P0UMA-180044 3OF8 P454

300

300
∅150 P353 ∅200 ∅150 P453 ∅200

2,350
325 325

1,010 720

100

1,010 720

100
P336 P337 P436 P437

450

450
265 135 P333 ∅150 265 135 P433 ∅150400 3,110 7. CONCRETE COVER (CAST-IN-PLACE CONCTERE)
3 535 1,265 ∅250 P354 3 535 1,265 ∅200
5,000

400 610

2,050 900

2,050 900
500 700 1,445 2,025 300 500 700 1,445 2,325 300
UP
∅450 L305 300500 ∅450 L405 300 1,500
MIN. CONC.
F332 P335 REMOVABLE P435 ITEM COVER(mm)
S301 S302 S323S324
∅450
S401 S402 S423S424
F432 ∅450 REMOVABLE

2,650

2,650
2,750 2,195 2,170

2,540

2,540
270
F333 CONC. COVER 270 2,750 2,195 2,170
F433

450

450
∅150 ∅150

150

150
CONC. COVER FOUNDATION 75

600 700

600 700
∅300 ∅300
∅150 P351 L306 ∅150 L406

725
L304 L404
TIE BEAMS/GIRDER BEAMS BELOW GRADE 75

370

370

370

370
P340 P450 P440

225

225
300 500

300 500
E P303 P403 P451
300 500

300 500
850 660

850 660
P350
∅150 ∅150 MARINE STRUCTURES (INCONTACT WITH SEA WATER) 75
L301
P304 L303
3 L307
3 L401
P404 L403 L407
3

2,335

2,335
∅150 ∅150

2,570

2,570
∅150
450 300 ∅300 P346
435 3,070 450 ∅150
∅150
450 300 ∅300 P446
435 3,070
3 450 ∅150
P441
CONCRETE IN CONTACT WITH GROUND SURFACE 75
3,435 P347 P341
3,435 P447
4,400 P348 4,400 P448

5,375
385 385
PEDESTALS 50

85 85

85 85
240

240
∅400 200 P349 2,580 ∅200 REMOVABLE ∅400 200 P449 2,580 ∅200 REMOVABLE COLUMNS 40
7,500

185 185
600 1,265 650 300 250 1,255 485 3,130 600 1,155 650 300 250 1,255 485 3,130
P308
320 1,485 400 1,200 ∅13 T301 GRATING COVER P408
320 1,485 400 1,200 ∅13
GRATING COVER FOR CEP BEAM, SLAB & PRECAST PANEL 25

410

410
5 3 5 T303
2,120

2,120

300 250
300 250
120
3 230 ∅1200
3

170

170
575 2,235 400 1,732 300 ∅200 160 4,380 2,070 530 575 2,235 400 1,732 300 ∅200 160 4,380 2,070 530
F
715 315

825 315
P309 P310 82 S305 815 P409 P410 82 S405 8. CHAMFERED CORNERS OF CONCRETE ALL EXTERIOR CORNERS
904 843 300

904 843 300


650 500600

1,050 580 650 570600


P330 P430
∅200 P306 ∅200 P406
(ANGLE OF 90° OR LESS) OF REINFORCED CONCRETE SHALL BE F

425 1,025 1,025 425

425 1,025 1,025 425


S306 S406

600 1,214 300820 800 920 750

600 1,214 300820 800 920 750


845 800 845 800

300

300
S315 E301 E306 E307 S415 E401 E406 E407
400 1,500

400 1,500
S303 ∅200 S403 ∅200

350

350
70

1,975

1,975
∅500 300 875 P331 ∅500 P431
P342 P343 P329
HANDRAIL P442 P443 P429
CHAMFERED (25mmX25mm).
1,527 480 1,345

105 1,420 480 1,345


S304 S404
□ 100 □ 100 300 875

750 750

750 750
D S307
3
P328 E302 E304
DIA 40mm - 3.5mmTHK S407
3 P428 E402 E404
9. THE FOLLOWING ITEMS, SEE STANDARD DRAWING UNLESS

2,738

2,738
75
75
300

300
1,050

∅200 P305 P345 P327 E308 E309 ∅200 P405 P445 S408 P427 E408 E409
585 S308
STEEL PIPE W/ PAINT (H=1.05m) 585 OTHERWISE NOTED.

2,500

2,500
200 300 700

200 300 700


350

350
E303 E305 E403 E405

300

300
□ 100 3,200 D151 400 □ 100 3,200 400 -MINIMUM CONCRETE COVER
360 685

360 685
P344 ∅200 S309 P444 ∅200 S409
2,200

2,200
P326 1,000 1,000 325 P426 1,000 1,000 325
S310 700 650 3 3 S410 700 650 3 -HOOK, DEVELOPMENT AND SPLICES OR REBAR
E310 E311 E312 E410 E411 E412 10. GROUT
7,500

∅200 T302 ∅200 T304


3 2,760 975
S311
505
3 177 3 2,760
S411
975 600 200 177 3 10.1 NON SHRINKAGE GROUT HAVING 60 MPa STRENGTH AT 28-DAY

2,300

2,300
400 215 1,325 575 980 550 2,620 20 1,600 400 215 1,325 575 980 550 2,620 20 1,600
35,000

300 300
600 200 505
250
S312
250
P319
∅200
3
250
S412 3 250
P419
∅200 250250 1,690
(ASTM C109)
440 550 11. THE INFORMATION ABOUT ANCHOR BOLT IS SHOWN AS REFERENCE.
1,840250

1,840 250
1,680 300

1,680 300
1,680 200

1,680 200
400

400
400

800 1,300 550

800 1,300 550


600 1,450 400
315

250 400

250 400
P321 1,200 1,500 P421 1,200 1,500
S317 P320 S417 P420

2,150

2,150
10 505 600 S313 S314 505 600 S413 S414 ANCHOR BOLT SHALL BE INSTALLED ON THE BASIS OF MECHANICAL
600 1,450

S316 S416

170
∅200 150 470 P322 ∅200 150 470 P422
600 2,155 ∅250 600 2,155 ∅250

800

650
DRAWING.

200

200
150

∅200 ∅200
290

L309
C

100
P318 L408 L409 P418
275

275
350

350
445

445
500

500
12. BEFORE CONSTRUCTION OF EQUIPMENT FOUNDATION, ELECTRICAL
400

400
∅350 L315 ∅350 L415

1,160 280 280 280 280 280 800


780 715 710 780
1,350

1,350
3,450 3,450

100
∅150 500 400

320 320 320 320 260


S318 ∅150 S418
∅150 ∅150 CONDUIT OF EQUIPMENT HAVE TO BE INSTALLED AS PER EQUIPMENT

225
L308 3,505
∅150 1,275 550 1,345 580 550 1,150 P317
3 L314 ∅150 1,275 550 1,345 580 550 1,150 P417 L414
4,300

550 3,505 550


□ 100 □ 100 GENERAL ARRANGEMENT DRAWINGS & EMBEDDED CONDUIT DRAWINGS
5,000

255 508 255 508


∅400 ∅1650 P302 □ 100 2,050 ∅1415 P402 □ 100 3,050
1,010 550 68

1,010 550 68
∅150 ∅150
1,010 550 68

1,010 550 68
∅400
2,295

3,680 3,680
495
∅500
160 515
L316
505 525 13. SMALL OPENING WORK FOR SLAB & WALL (PIPE, CABLE & ETC.) SHALL

3,400
S320 S321 425 ∅150 S420 S421 415 ∅500 L416
∅150 ∅150
1,050
3 L313 1,050 L413
3 BE CARRIED OUT AT SITE AS PER MECHANICAL & ELECTRICAL DRAWING.
1,105 645

1,105 645
3
550 1,050

550 1,050
S319 S322 L319 S419 S422 L419
P352 P452
720

720

150
L310 L410
405

405

405

405

405

405

1,455
P325 P425
175

175
700

1,700 1,700 E413 2,555 565 2,935 600


∅300 ∅300 ∅300 ∅300

210

210
∅150 ∅150 ∅150 ∅150
E B P307 ∅150
3,000
P407
3,000
2,035

E313

2,035
S325 S425
320

320
700

P323 P324 P423 P424


2,140 2,140 ABBREVIATION E
∅200 550
2,695 420 3,675 3 ∅200 550
2,695 420 3,675 3
∅250
3 ∅250 3
2,690

2,690
D : ARCH. F : FIRE FIGHTING
2,905

2,905
P311
625
P411
4,475 625
3 M : MECH. S :SKODA

5,100
L320 ∅100 3,400 100 150 L420 ∅100
3 3 L : PLUMBING T :TOSHIBA
4,565

4,565
400 535

400 535
10,700

P316 P416
3,130

3,130
L317
3 L417
P : PIPING
10,000

∅300 ∅300
9,300

∅150 L418 ∅150


∅200
∅100
L318 ∅200
∅100
E : ELEC.
P312 2,150 440 P412 2,150 440 H : HVAC.
1,290

1,290
∅200 265 265

575 700 3,500


1,350 2,050

P313 P413
REFERENCE DRAWING

3,400
1,625

1,625
∅200 ∅200 ∅200 ∅200
L311 P314 3 L411 3

1,350
1,925

100
1,255

1,255

1,255

1,255
L312 P315 L412 P415 DRAWING NO. DRAWING TITLE
735

735
210

210
A
575

575
∅150 ∅150
∅150
MRT-CA00-P0UMA-180015~17,19 GROUND, MEZZ., OPERATING & ROOF FLOOR PLAN (ENLARGED)
3 2,010
∅150
3,080 2,010 3,080
315 360 315 360 MRT-CA01-P0UMA-180027 GROUND FLOOR FRAMING PLAN
150 SLAB END LINE 150 7,350 150 SLAB END LINE 3,810 4,690
GRATING END LINE MRT-CA03-P0UMA-180028~32 MEZZ, OPERATING & LOWER ROOF FLOOR FRAMING PLAN
GRATING END LINE MRT-CA00-P0UMA-180047 FLOOR OPENING SCHEDULE
3
D D
MRT-CA02-P0UMA-180045 EQUIPMENT FOUNDATION REBAR DETAIL
303 403 MEZZANINE EQUIPMENT FOUNDATION & SLAB OUTLINE PLAN-2
NOTE: SCALE : 1/200
- FOR SLEEVE DETAIL OF CONCRETE SLAB & WALL OPENING ,
7,700 10,000 REFER TO STANDARD DRAWING MRT-CC05-P0ZEN-175046.
- SOME GRATING OPENINGS AND OTHERS SHALL BE REINFORCED WITH SUPPORT ANGEL AT SITE IF REQUIRED.
17,350 350 FOR DETAIL REFER TO DWG. NO MRT-CA03-P0UMA-180039_15 OF 18
3
7,350 700 9,300
FOR CONSTRUCTION
EL.+9.700(T.O.C)
∅(NOMINAL SIZE)
DETAIL-4
275

3 CL OF PIPE
3 17.APR.2019 REVISED AS PER MECH. & ELEC. ARRANGEMENT DRAWINGS. Y.C.JEONG N.Y.KOO K.S.ROH

F PIPE SLEEVE 2 08.OCT.2018 REVISED AS PER OWNERS ON COMMENTS Y.C.JEONG N.Y.KOO K.S.ROH
700 700

C C
1,925

1,925

40 THK.6 ANCHOR PLATE


L302 1 25.MAY.2018 Approved by Owner on 5th DRM Y.C.JEONG N.Y.KOO K.S.ROH
∅150 1,000
DETAIL-4
REV. DATE DESCRIPTION DRAWN CHKD. APPD.
20
200

50 100 100 50

NO.
1,265
550 900 550

265 535 135


5,775

∅100
∅150 ∅100 EL.+9.100(T.O.C) Project

B UP UP MUARA TAWAR COMBINED CYCLE


4,200

3,600

3,600

180044 3of8
3
S301S302 S323S324
S401S402 S423S424
A POWER PLANT BLOCK 2, 3 & 4
ADD-ON PROJECT
180044 3of8 270 570 600 270
2,440

300 2,000 2,700 350 350 FLEXIBLE JOINT MATERIAL


270 270 Owner
300

250

250

SILICON SEALANT(AROUND PIPE)


250

250

DETAIL-3
MRT-CA01-P0UMA-180044-03 4 FLOOR OPENING DETAIL FOR LUBE OIL ROOM Owner's Engineer

B H=900 CONCRETE WALL - SCALE : NONE B

1 LUBE OIL DIKE DETAIL 3


EL.+9.100(F.F.L) LEGEND
- EL.+8.900(T.O.S) SCALE : 1/100 3 EPC Contractor

UNLESS OTHERWISE NOTED HEIGHT OF DIKE WALL IS 600mm. PIPE SLEEVE


GRATING (THK.40)
3 EL.+9.100(F.F.L) / EL.+9.060(T.O.S)
BLOCK #2 FOUNDATION LIST 50(TYP.)
DUCT or PIPE CONC. SLAB REMOVABLE GRATING (THK.40) Sub Contractor
EQUIPMENT NO. EUIPMENET NAME EA REMARK
100

EL.+9.100(F.F.L) / EL.+9.060(T.O.S)
F332, F432, STEAM JET AIR EJECTOR 1 F.B-150x6
CHECKED PLATE (THK.6)
F333, F433, WATER BOX VACCUM COMTROL TANK 1
GRATING
CONC DECK SLAB (THK.200,2-SPAN CONTINUOUS) DRAWING TITLE
100

AUTOMATIC END-WELDED CONC ANCHORS EL.+9.100(F.F.L) / EL.+8.900(T.O.S)


FOR SLEEVES LESS THAN 150mm, USE 2 ANCHORS
CONC DECK SLAB OR GRATING DIRECTION
FOR SLEEVES 150mm & LESS THAN 600mm, USE 4 ANCHORS
A - UNNAMED SLAB : DS1 A
FOR SLEEVES 600mm & LESS THAN 1200mm, USE 8 ANCHORS

2 FLOOR OPENING FOR GRATING 3 FLOOR OPENING FOR DECK SLAB GRAPHIC SCALE SCALE DRAWING NUMBER SHEET NO. REV. NO.
0 5 10 25 50 100 200m
- SCALE : NONE - SCALE : NONE 1 : 200 MRT-CA01-P0UMA-180044 4 OF 8 3
8 7 6 5 4 3 2 1 A1 (594 x 841mm)
8 7 6 5 4 3 2 1

201 202 203 204 205 206 207 301


NOTE
1. ALL DIMENSIONS ARE IN MILLIMETTERS UNLESS NOTED.
10
.2 2. ALL LEVELS AND COORDINATES ARE IN METERS UNLESS
° 4,000 169,000 OTHERWISE NOTED
BLOCK 1
3. ELEVATION
(EXISTING BLDG.) 3.1. MEAN SEAWATER LEEVEL(MML) = EL±0.000
H 3,000 54,500 (BLOCK 2) 1,000 H
3.2. GROUND LEVEL(GL) = EL+2.800
1,000 7,500 10,000 10,000 9,000 10,000 8,000
3.3. MAIN BUILDING GROUND FLOOR LEVEL = EL+3.100
4. CONCRETE GRADE / MAX.AGGREGATE SIZE / WATER CEMENT RATIO
CONCRETE MAX. MINI. CEMENT MAX. WATER
GRADE APPLICATION AGGREGATE CONTENT CEMENT RATIO
( f'c) SIZE(mm) (KG/M3) BY WEIGHT
15 MPa LEVELING CONC. 40 200 0.52
MATCH LINE 25 MPa STRUCTURAL CONC 20 275 0.50
(E.J LINE) 30 MPa ST FDN, CCB, INTAKE
STG BLDG, CW SUMP
PIT , DISCHARGE 20 300 0.50
TUNNEL & OUTFALL

800 3,200 REMOVABLE CONC. COVER REMOVABLE CONC. COVER WHERE, f'c=CYLINDER COMPRESSICE STRENGTH AT 28-DAY
5. REINFORCING BAR STRENGTH
5.1. DEFORMED BARS
SLAB END LINE : fy=413MPa (ATSM A615 Grade 60 / JIS-G 3112)

B
G 5.2. MESH REINFORCEMENT : fy=413MPa(ASTM A185)
100 4,040 3,360 2,050 3,150 1,500 950 800 1,150 4,000
1,700 1,9701,500580 2,350 2,970 6. CEMENT
500 700 G
200 ∅150 6.1. ASTM C150 TYPE-I : FOR CONCRETE WORK ABOVE GRADE
4,300 700 700

275
640 480

1,9501,000
200 600
LEVEL OTHERWISE INDICATED.

1,4001,550
2,800 1,700
400
L252 P262 L253
∅400

300 160
240 300
F P269

100 3,500 1,400

225 350

2,350 2,075
P251 S251
P261
6.2. ASTM C150 TYPE-II : ONLY FOR FOUNDATIONS AT OR BELOW
3,240

P263 P264 P265 P266 P252


∅200
900 700 800 3,125 700 4,650 GRADE.
340 770 ∅400
5,000

6.3. ASTM C150 TYPE-V : FOR STRUCTURES IN DIRECT CONTACT


SLAB END LINE 300 500 WITH SEA WATER OR GROUND WATER WITH SIMILAR BEHAVIOR.

P0UMA-180029-01 B
5,500 3

SECTION "A-A"
5,100 REMOVABLE CONC. COVER 7. CONCRETE COVER (CAST-IN-PLACE CONCTERE)

600700
∅150

575
MIN. CONC.

150
260

650

370
250
L254 P270

370 280
E L251
∅150 ITEM COVER(mm)

400
FOUNDATION 75
3 TIE BEAMS/GIRDER BEAMS BELOW GRADE 75

5,525
340 8,710 725 175 450 955 1,490 500
REMOVABLE CONC. COVER MARINE STRUCTURES (INCONTACT WITH SEA WATER) 75
7,500

550 890330170

1,000
1,000
S252
□ 150x200
200 CONCRETE IN CONTACT WITH GROUND SURFACE 75
3

360
P253

224 300 465 OPEN PEDESTALS 50

390
776

∅500 COLUMNS 40

3,590
P254

2,600
4001,200 BEAM, SLAB & PRECAST PANEL 25
1,450

P255 3,450 900


F 8. CHAMFERED CORNERS OF CONCRETE ALL EXTERIOR CORNERS
200

450
200150
C C (ANGLE OF 90° OR LESS) OF REINFORCED CONCRETE SHALL BE F

700
S262
3
2,450

∅850
900550 200 CHAMFERED (25mmX25mm).
1,030 3 E321
HANDRAIL 9. THE FOLLOWING ITEMS, SEE STANDARD DRAWING UNLESS
DIA 40mm - 3.5mmTHK
1,005

P256 □ 150x200 OTHERWISE NOTED.


7,500

6,850
6,317
S253
3 STEEL PIPE W/ PAINT (H=1.05m) -MINIMUM CONCRETE COVER
35,000

535 465
3 1,490 500 -HOOK, DEVELOPMENT AND SPLICES OR REBAR
2,210
300 1,060 300 1,000 600 315 3,220 1,525 2,515 800 1,810 300 400 600800 830 10. GROUT

1,000
40 340 400 10.1 NON SHRINKAGE GROUT HAVING 60 MPa STRENGTH AT 28-DAY
630 270 470
500 150 500
420 200

230 420
260 390
(ASTM C109)

655 470
170

146 300
370

0
850
S255 480
395 340

300 370
S258

180
180

C
420

S254 S260
11. THE INFORMATION ABOUT ANCHOR BOLT IS SHOWN AS REFERENCE.

900

1,500
P257 S259 850 850

2,345
P268 S261 ANCHOR BOLT SHALL BE INSTALLED ON THE BASIS OF MECHANICAL
130
4,300

S256 3,750 580


3 966 □ 250
440 440

2,100
DRAWING.
5,000

∅400
3 330 2,010 740 500 3,080 1,100 1,230 300
P258
12. BEFORE CONSTRUCTION OF EQUIPMENT FOUNDATION, ELECTRICAL
SECTION "B-B" 540 305 750
∅950
P259 P260 120
∅400 CONDUIT OF EQUIPMENT HAVE TO BE INSTALLED AS PER EQUIPMENT

1501,100
300 1,600 670700 ∅150
350 1,155 700
P0UMA-180029-01 ∅150 2,950 630 2,020
850
GENERAL ARRANGEMENT DRAWINGS & EMBEDDED CONDUIT DRAWINGS

150
∅150
700

290

285
300

300
335
500
190 605

550

200 1,000
13. SMALL OPENING WORK FOR SLAB & WALL (PIPE, CABLE & ETC.) SHALL

550
700

900
L255 L256 L258
BE CARRIED OUT AT SITE AS PER MECHANICAL & ELECTRICAL DRAWING.
700

P267 E323
3

4,565 1,335
E322 E324
E325

900
∅150
3 750 850 2,600
700
430
E L257

3 ABBREVIATION E
10,000

D : ARCH. F : FIRE FIGHTING


9,300

M : MECH. S :SKODA
L : PLUMBING
P : PIPING
E : ELEC.

3,400
H : HVAC.
100 3,400100
A

REFERENCE DRAWING
575

A
DRAWING NO. DRAWING TITLE
A

SLAB END LINE MRT-CA00-P0UMA-180015~17,19 GROUND, MEZZ., OPERATING & ROOF FLOOR PLAN (ENLARGED)
DECK SUPPORTING ANGLE DETAIL(TYP.) MRT-CA01-P0UMA-180027 GROUND FLOOR FRAMING PLAN
MRT-CA03-P0UMA-180039-15 MRT-CA03-P0UMA-180028~32 MEZZ, OPERATING & LOWER ROOF FLOOR FRAMING PLAN
3
MRT-CA00-P0UMA-180047 FLOOR OPENING SCHEDULE
D OPERATING EQUIPMENT FOUNDATION & SLAB OUTLINE PLAN-1 MRT-CA02-P0UMA-180045 EQUIPMENT FOUNDATION REBAR DETAIL
D
SCALE : 1/200
NOTE:
FOR SLEEVE DETAIL OF CONCRETE SLAB & WALL OPENING ,
REFER TO STANDARD DRAWING MRT-CC05-P0ZEN-175046.

FOR CONSTRUCTION

3 17.APR.2019 REVISED AS PER MECH. & ELEC. ARRANGEMENT DRAWINGS. Y.C.JEONG N.Y.KOO K.S.ROH

2 08.OCT.2018 REVISED AS PER OWNERS ON COMMENTS Y.C.JEONG N.Y.KOO K.S.ROH


C C
1 25.MAY.2018 Approved by Owner on 5th DRM Y.C.JEONG N.Y.KOO K.S.ROH

REV. DATE DESCRIPTION DRAWN CHKD. APPD.


NO.

Project

MUARA TAWAR COMBINED CYCLE


POWER PLANT BLOCK 2, 3 & 4
ADD-ON PROJECT
Owner

A F 206

575 975 150 Owner's Engineer

LEGEND
B 700 275 B

EPC Contractor
HANDRAIL GRATING (THK.40)
STUD BOLT STUD BOLT STUD BOLT EL.+14.600(F.F.L) / EL.+14.560(T.O.S)
D16@1500 D16@1500 D16@1500
END PL-6t END PL-6t END PL-6t GRATING (THK.40)
(L=135) (L=135) (L=135)
100

100

100

EL.+14.600(T.O.C) EL.+14.600(T.O.C) EL.+14.600(T.O.C) EL.+14.600(F.F.L) / EL.+14.560(T.O.S)


Sub Contractor
REMOVABLE GRATING (THK.40)
EL.+14.400(T.O.S) EL.+14.400(T.O.S) EL.+14.400(T.O.S) EL.+14.600(F.F.L) / EL.+14.560(T.O.S)
CHECKED PLATE (THK.6) + THK.50 LEAN CONC.
STUD BOLT STUD BOLT STUD BOLT EL.+14.600(F.F.L) / EL.+14.544(T.O.S) DRAWING TITLE
L-100x100x7 D19@640 D19@640 D19@640 S.O.G SLAB
@1000 (L=130) (L=130) (L=130) EL.+14.600(F.F.L)

A CONC DECK SLAB OR GRATING DIRECTION A


- UNNAMED SLAB : DS2
SECTION "A-A" SECTION "B-B" SECTION "C-C" GRAPHIC SCALE
SCALE : 1/20 SCALE : 1/20 SCALE : 1/20 SCALE DRAWING NUMBER SHEET NO. REV. NO.
0 5 10 25 50 100 200m
1 : 200 MRT-CA01-P0UMA-180044 5 OF 8 3
8 7 6 5 4 3 2 1 A1 (594 x 841mm)
8 7 6 5 4 3 2 1

207 301 302 303 304 305 306 401 402 403 404 405 406 407 NOTE
1. ALL DIMENSIONS ARE IN MILLIMETTERS UNLESS NOTED.
2. ALL LEVELS AND COORDINATES ARE IN METERS UNLESS
169,000 CCB OTHERWISE NOTED
3. ELEVATION
4,000
10 1,000 56,500 (BLOCK 3) 57,000 (BLOCK 4) 3.1. MEAN SEAWATER LEEVEL(MML) = EL±0.000
H .2
° 3.2. GROUND LEVEL(GL) = EL+2.800 H
7,500 9,000 10,000 10,000 11,000 9,000 7,500 9,000 10,000 10,000 12,000 8,500 3.3. MAIN BUILDING GROUND FLOOR LEVEL = EL+3.100
4. CONCRETE GRADE / MAX.AGGREGATE SIZE / WATER CEMENT RATIO
CONCRETE MAX. MINI. CEMENT MAX. WATER
GRADE APPLICATION AGGREGATE CONTENT CEMENT RATIO
( f'c) SIZE(mm) (KG/M3) BY WEIGHT
15 MPa LEVELING CONC. 40 200 0.52
MATCH LINE 25 MPa STRUCTURAL CONC 20 275 0.50
(E.J LINE)
30 MPa ST FDN, CCB, INTAKE
STG BLDG, CW SUMP
3 3 PIT , DISCHARGE 20 300 0.50
TUNNEL & OUTFALL
REMOVABLE CONCRETE COVER REMOVABLE CONCRETE COVER REMOVABLE CONCRETE COVER 3 REMOVABLE CONCRETE COVER 725
150 WHERE, f'c=CYLINDER COMPRESSICE STRENGTH AT 28-DAY
FOR LUBE OIL SYSTEM FOR STEAM JET AIR EJECTOR REMOVABLE CONCRETE COVER FOR LUBE OIL SYSTEM FOR STEAM JET AIR EJECTOR 5. REINFORCING BAR STRENGTH
SLAB END LINE 3 FOR CEP REMOVABLE CONCRETE COVER
SLAB END LINE 5.1. DEFORMED BARS
SLAB END LINE FOR CEP : fy=413MPa (ATSM A615 Grade 60 / JIS-G 3112)
R.C COVER PLAN & SECTION - 1 2,600 1,700 1,570 1,700 1,970 1,580 2,3501,925 R.C COVER PLAN & SECTION - 1 2,600 1,800 1,570 1,700 1,970 1,580 2,350 2,925 5.2. MESH REINFORCEMENT : fy=413MPa(ASTM A185)
G 450 300 2,895 535 4,000 500700 5,150 700 450 300 2,895 535 4,000 500700 700
MRT-CA03-P0UMA-180029-01 1,000 205 MRT-CA03-P0UMA-180029-01 900 205 6. CEMENT G
∅200 ∅150 1,500 ∅150 1,500 6.1. ASTM C150 TYPE-I : FOR CONCRETE WORK ABOVE GRADE
4,300 700 700

∅300 ∅300 ∅200


275

400 55 400 55

455 400

455 400

270400
P351 P352

2,600 1,230

2,600 1,230
LEVEL OTHERWISE INDICATED.

425 400
P451 P452

1,950 300
400150

400150
300 860

300 860

300 860

300 860
2,000 780

2,000 780
300
L352 L352

30

30

155 30
300
F P468
3,500 1,400

P364 P464

100 3,240 1,660


1,400 850

1,400 850
P368
SLAB END LINE 6.2. ASTM C150 TYPE-II : ONLY FOR FOUNDATIONS AT OR BELOW

2,350 2,075

2,350 2,075
S351 ∅150 P467 S451 ∅150
P367 L351 L451
P353 P354 P355 P356 P454 P454 P455 P456
P365 P465
GRADE.

1,950
745600745 ∅300 4,715 745600745 ∅3004,715
∅300 ∅300
5,000

6.3. ASTM C150 TYPE-V : FOR STRUCTURES IN DIRECT CONTACT


300 500 3 300 1,500 800
WITH SEA WATER OR GROUND WATER WITH SIMILAR BEHAVIOR.
∅150 ∅150
∅150 7. CONCRETE COVER (CAST-IN-PLACE CONCTERE)

600700

600700
P366 L459

575

575
L353 L453
MIN. CONC.

520
100

280 280

520
620

830 220

620

830 220

570
370

370
L358 L458 P466
E ITEM

575 475
575 475
2,380 2,380

450 600
575 475

576 474
S452

450 600

450600

450 600
S352
COVER(mm)

850

850
∅150 P357 150 4,420 ∅150 P457 5,075 ∅150

530

530
∅150
4,140 3 ∅400 ∅400
3 FOUNDATION 75
3,950 3,400 800510 850 3,950 6,500
3,400 510 850 410 1,270 315 385
TIE BEAMS/GIRDER BEAMS BELOW GRADE 75

5,525

5,525
620 410 1,270 315 385
3 1,740 250 3 3
1,740 250 620
MARINE STRUCTURES (INCONTACT WITH SEA WATER) 75
7,500

CONCRETE IN CONTACT WITH GROUND SURFACE 75


750 500

500
PEDESTALS 50

750 500
3
350 200

350 200
1,490 1,490 500 COLUMNS 40
900 1,055 1,450

1,055 1,450
500
P360 P460
4,390 900 4,390 900 BEAM, SLAB & PRECAST PANEL 25
1,150

500 1,200 850 1,150


900550 1,340 650 900550 1,340 650
F 8. CHAMFERED CORNERS OF CONCRETE ALL EXTERIOR CORNERS
D

450

450
850

400900
840 400 200 840 400 200
(ANGLE OF 90° OR LESS) OF REINFORCED CONCRETE SHALL BE F

700

700
P.C COVER PLAN & SECTION - 2, 3 S453
A A
400

S353
500 1,200

1,840 150 1,840 150 CHAMFERED (25mmX25mm).


290

290
E331 E341
455

455
MRT-CA03-P0UMA-180029-01 P461
9. THE FOLLOWING ITEMS, SEE STANDARD DRAWING UNLESS
250

250
P361
3
150

150
S359 S459 ∅900
∅900
□ 100x100 1,000 □ 100x100 1,000
P.C COVER PLAN & SECTION - 2, 3 OTHERWISE NOTED.
7,500

∅200 □ 100x350 ∅200


1,315395 1,740 250 □ 100x350
S360 1,315395 1,740 250 S460 -MINIMUM CONCRETE COVER
250

250
MRT-CA03-P0UMA-180029-01
35,000

250

250
440 440 S361
3,400 1,310 800
S461 S454 -HOOK, DEVELOPMENT AND SPLICES OR REBAR
250 1,273 795 390 250 1,023 795 390
1,242

1,242
S354 □ 150x100 3,400 1,310 800
S362 S462
120 670 250 410 □ 150x100
670 250 410 10. GROUT
3,230

3,230
400

400
S355 S455 800
S357 S457 ∅150 10.1 NON SHRINKAGE GROUT HAVING 60 MPa STRENGTH AT 28-DAY

600 450
640 300

600 450

640 300
600 450

662 250
662 250

600 450
1,400

1,400

220 830
220 830

150 400 150 400


842
(ASTM C109)

842

500
550 350

550 350
S356 S363 S456 S463 L460
C 11. THE INFORMATION ABOUT ANCHOR BOLT IS SHOWN AS REFERENCE.
1,000

1,000
250 1,272

250 1,272
S364
250 595 1,883
S464 250 1,883 3 ANCHOR BOLT SHALL BE INSTALLED ON THE BASIS OF MECHANICAL
4,300

395 3,905

395 3,905
2,725 3,800 3,400 ∅1150 S358 2,725 3,800 3,400 S458
550 550 595 ∅1150 DRAWING.
5,000

2,000

2,000
305 430 3 3 850
P363
1,235 415 2,255 250 1,100 850 285 430 3 850
P463
1,235 415 2,255 250 1,100 750 12. BEFORE CONSTRUCTION OF EQUIPMENT FOUNDATION, ELECTRICAL
2,350

2,350
3 ∅150 ∅150 ∅150 3 ∅150 ∅150 CONDUIT OF EQUIPMENT HAVE TO BE INSTALLED AS PER EQUIPMENT
L355 L455
3 GENERAL ARRANGEMENT DRAWINGS & EMBEDDED CONDUIT DRAWINGS
403

403
700

300

300

300

300

300

300
∅150 ∅150
B L356 L357 L456 13. SMALL OPENING WORK FOR SLAB & WALL (PIPE, CABLE & ETC.) SHALL
230

1,335 230
L354 L454 L457
585
700

P369 P469 ∅150 BE CARRIED OUT AT SITE AS PER MECHANICAL & ELECTRICAL DRAWING.
2,180 6,860 2,180 6,860 4,000
3
E HANDRAIL(TYP.) HANDRAIL(TYP.) 3
REMOVABLE CONCRETE COVER 100 3,400 100 REMOVABLE CONCRETE COVER ABBREVIATION E

4,565

2,200
10,000

FOR GCB FOR GCB 4,105 4,395 150 D : ARCH. F : FIRE FIGHTING
9,300

M : MECH. S :SKODA

600 3,600 100


L : PLUMBING T :TOSHIBA
P : PIPING

4,300
E : ELEC.
3,400 H : HVAC.
100 100
REFERENCE DRAWING
575

A
DRAWING NO. DRAWING TITLE

120 (E.J) SLAB END LINE MRT-CA00-P0UMA-180015~17,19 GROUND, MEZZ., OPERATING & ROOF FLOOR PLAN (ENLARGED)
P.C COVER PLAN & SECTION - 1 P.C COVER PLAN & SECTION - 1
440 440 PLAN & SECTION DETAIL OF BRIDGE MRT-CA01-P0UMA-180027 GROUND FLOOR FRAMING PLAN
MRT-CA03-P0UMA-180029-02 MRT-CA03-P0UMA-180029-02
MRT-CA03-P0UMA-180039-05 MRT-CA03-P0UMA-180028~32 MEZZ, OPERATING & LOWER ROOF FLOOR FRAMING PLAN
DECK SUPPORTING ANGLE DETAIL(TYP.)
MRT-CA03-P0UMA-180039-15 MRT-CA00-P0UMA-180047 FLOOR OPENING SCHEDULE
3 D
D
OPERATING EQUIPMENT FOUNDATION & SLAB OUTLINE PLAN-2 MRT-CA02-P0UMA-180045 EQUIPMENT FOUNDATION REBAR DETAIL

SCALE : 1/200
NOTE:
FOR SLEEVE DETAIL OF CONCRETE SLAB & WALL OPENING ,
REFER TO STANDARD DRAWING MRT-CC05-P0ZEN-175046.

FOR CONSTRUCTION

3 17.APR.2019 REVISED AS PER MECH. & ELEC. ARRANGEMENT DRAWINGS. Y.C.JEONG N.Y.KOO K.S.ROH

2 08.OCT.2018 REVISED AS PER OWNERS ON COMMENTS Y.C.JEONG N.Y.KOO K.S.ROH


C C
1 25.MAY.2018 Approved by Owner on 5th DRM Y.C.JEONG N.Y.KOO K.S.ROH

REV. DATE DESCRIPTION DRAWN CHKD. APPD.


NO.

Project

MUARA TAWAR COMBINED CYCLE


POWER PLANT BLOCK 2, 3 & 4
ADD-ON PROJECT
Owner

3
407 E
Owner's Engineer

725 50 1,050 LEGEND


B B

EPC Contractor
STUD BOLT CHK'D DECK SLAB GRATING (THK.40)
PL-4.5t TAG.
D16@1500 EL.+14.600(F.F.L) / EL.+14.560(T.O.S)
END PL-6t EL.+14.400(T.O.C)
(L=135)
100

EL.+14.600(T.O.C) GRATING (THK.40)


EL.+14.600(F.F.L) / EL.+14.560(T.O.S)
EL.+14.200(T.O.S) Sub Contractor
EL.+14.400(T.O.S) REMOVABLE GRATING (THK.40)
EL.+14.600(F.F.L) / EL.+14.560(T.O.S)
CHECKED PLATE (THK.6) + THK.50 LEAN CONC.
STUD BOLT BY CIVIL L-100x100x7 EL.+14.600(F.F.L) / EL.+14.544(T.O.S)
D19@640 L-100x100x7 @1000 DRAWING TITLE

(L=130) @1000 S.O.G SLAB


CORNER L50x50x4 EL.+14.600(F.F.L)
W/ D10x150@400 CONC DECK SLAB OR GRATING DIRECTION
A A
- UNNAMED SLAB : DS2
SECTION "A-A" SECTION "B-B"
SCALE : 1/20 SCALE : 1/20 GRAPHIC SCALE SCALE DRAWING NUMBER SHEET NO. REV. NO.
0 5 10 25 50 100 200m
1 : 200 MRT-CA01-P0UMA-180044 6 OF 8 3
8 7 6 5 4 3 2 1 A1 (594 x 841mm)
8 7 6 5 4 3 2 1

LEGEND NOTE
201 202 203 204 205 206 207 301 1. ALL DIMENSIONS ARE IN MILLIMETTERS UNLESS NOTED.
10 2. ALL LEVELS AND COORDINATES ARE IN METERS UNLESS
.2
°
OTHERWISE NOTED
BLOCK 1 4,000 169,000 3. ELEVATION
GRATING (THK.40)
3.1. MEAN SEAWATER LEEVEL(MML) = EL±0.000
H (EXISTING BLDG.) EL.+17.900(F.F.L) / EL.+17.860(T.O.S) H
3,000 54,500 (BLOCK 2) 1,000 3.2. GROUND LEVEL(GL) = EL+2.800
MATCH LINE GRATING (THK.40) 3.3. MAIN BUILDING GROUND FLOOR LEVEL = EL+3.100
1,000 7,500 10,000 10,000 9,000 10,000 8,000 (E.J LINE) 4. CONCRETE GRADE / MAX.AGGREGATE SIZE / WATER CEMENT RATIO
EL.+17.900(F.F.L) / EL.+17.860(T.O.S)
CONCRETE MAX. MINI. CEMENT MAX. WATER
REMOVABLE GRATING (THK.40) GRADE APPLICATION AGGREGATE CONTENT CEMENT RATIO
EL.+17.900(F.F.L) / EL.+17.860(T.O.S) ( f'c) SIZE(mm) (KG/M3) BY WEIGHT
15 MPa LEVELING CONC. 40 200 0.52
CHECKED PLATE (THK.6)
25 MPa STRUCTURAL CONC 20 275 0.50
4,300 700 700
EL.+17.900(F.F.L)
30 MPa ST FDN, CCB, INTAKE
F S.O.G SLAB STG BLDG, CW SUMP
EL.+17.900(F.F.L) PIT , DISCHARGE 20 300 0.50
TUNNEL & OUTFALL
5,000

CONC DECK SLAB OR GRATING DIRECTION


WHERE, f'c=CYLINDER COMPRESSICE STRENGTH AT 28-DAY
- UNNAMED SLAB : DS2
5. REINFORCING BAR STRENGTH
E 5.1. DEFORMED BARS
: fy=413MPa (ATSM A615 Grade 60 / JIS-G 3112)
G 5.2. MESH REINFORCEMENT : fy=413MPa(ASTM A185)
6. CEMENT G
6.1. ASTM C150 TYPE-I : FOR CONCRETE WORK ABOVE GRADE
7,500

LEVEL OTHERWISE INDICATED.


6.2. ASTM C150 TYPE-II : ONLY FOR FOUNDATIONS AT OR BELOW
GRADE.
6.3. ASTM C150 TYPE-V : FOR STRUCTURES IN DIRECT CONTACT
WITH SEA WATER OR GROUND WATER WITH SIMILAR BEHAVIOR.
D 7. CONCRETE COVER (CAST-IN-PLACE CONCTERE)
MIN. CONC.
ITEM COVER(mm)
FOUNDATION 75
7,500

TIE BEAMS/GIRDER BEAMS BELOW GRADE 75


35,000

MARINE STRUCTURES (INCONTACT WITH SEA WATER) 75


CONCRETE IN CONTACT WITH GROUND SURFACE 75
PEDESTALS 50
COLUMNS 40
C 3 BEAM, SLAB & PRECAST PANEL 25
1,750 1,250
4,300

F SLAB END LINE SLAB END LINE 8. CHAMFERED CORNERS OF CONCRETE ALL EXTERIOR CORNERS
4,500 3,500 330
5,000

150 150 (ANGLE OF 90° OR LESS) OF REINFORCED CONCRETE SHALL BE F


1,550 800 1,160 425 200 215 CHAMFERED (25mmX25mm).
150

550 150
800 875
1,000 215 800 800 1,160

150
9. THE FOLLOWING ITEMS, SEE STANDARD DRAWING UNLESS

700
700

3 OTHERWISE NOTED.

150
1,075 655 1,145 655 1,145 655 1,170 800 200
B

145
TRANS. WDB TRANS. ELDB MLDB
150
TRANS.

250 210
FOR BLK-2 FOR BLK-2
-MINIMUM CONCRETE COVER
700

FOR BLK-2

100

1,310
450
1,730 800
720 640 640 640 825

2,540

2,540
1,150200 1,750 400 1,515
800 -HOOK, DEVELOPMENT AND SPLICES OR REBAR
640 1,585

185
3,625

3,625

3,665

3,665
3,725

3,730
3,850
335
335 335 150 150 10. GROUT
120 200 120

150 360 335 685 2,165 685 685 335 150 235
455 650 650 530 650 645 605

600 500 500

335
385

385
315 295 200 605525 245 200 455 245 200 560 560 560 560 170 255 300 300 245 10.1 NON SHRINKAGE GROUT HAVING 60 MPa STRENGTH AT 28-DAY

6,000
250 300
200

525 150 150 270 150 150 200

300 265 265 265 705 315 300 265 280 280 650 800 800 300 800 800 300 800 800 240 440 240 750 800 300 300 300 800
585 95
(ASTM C109)

585 95

250 250
1,480

250

250250
TRANS. TRANS.

4,590
145

145
10,000

600
BLK-2 400V

315
BLK-2 220V BLK-2 220V UPS ACDB

640
BLK-2 UNIT PDC SWGR 205 190 205 150 UNIT DCDB-2
BLK-2 BATTERY BLK-2 BATTERY
BLK-2
COMMON MCC UNIT DCDB-1 CHARGER-1 CHARGER-2
11. THE INFORMATION ABOUT ANCHOR BOLT IS SHOWN AS REFERENCE.
9,300

315
205 190 190190 630 780 780220780 410 410195 285

600
500 6,345 2,070
1,490

ANCHOR BOLT SHALL BE INSTALLED ON THE BASIS OF MECHANICAL


680 640 1,530

150 410 410 410 410 410 150


1,955

280 320 280 100 3,400 100


1,500 200 200 200 200 200 270 200 260320 320 320 310 145 205 200 425 1,160 800
215
2,365 150
MV SWGR FOR BLOCK-2
2,800 200 3,150 200 3,100 400 DRAWING.
800 800 800 250 250 800 800 650 650 800 280 280 280 800 800 800 150

505 155
1,480

12. BEFORE CONSTRUCTION OF EQUIPMENT FOUNDATION, ELECTRICAL


250250

250250
200 120

315
210250

6,085
925 1,075

TRAFO.-A FEEDER

170
SPARE MOTOR

TRAFO. FEEDER
BLOCK-2 HP BFP

BLOCK-2 HP BFP

BLOCK-2 HP BFP
600

PUMP-1 MOTOR

PUMP-2 MOTOR

PUMP-3 MOTOR

SPARE MOTOR
315

CONDENSATE

CONDENSATE

CONDENSATE
EXTRACTION

EXTRACTION

EXTRACTION

SPARE PDC

CW PUMP

CW PUMP
BLK-2 400V UNIT MCC

TIE TO BLK-3
FEEDER-2

UNIT PDC

BLOCK-2A

BLOCK-2B
BLK-2 400V ESS MCC

I/C FROM UAT


FEEDER-1

BLOCK-2
BUS PT
BLK-2 UNIT ACDB

PUMP-1

PUMP-2

PUMP-3
330
CONDUIT OF EQUIPMENT HAVE TO BE INSTALLED AS PER EQUIPMENT

3,300
200

600
5752,675

150 150 2,590

250
∅2

800 280 650 800 600 600 600 700 600 600 600 1,200 600 600 600 600 600 600 1,300
T S R R S T

GENERAL ARRANGEMENT DRAWINGS & EMBEDDED CONDUIT DRAWINGS


785 1,440

1,300 600

00

2,670

2,670
SLAB END LINE 270
2,515

2,515

2,520
1,090275

2,425
200 200 300 200 200 200 200 200 200 200

2,525
515 905

13. SMALL OPENING WORK FOR SLAB & WALL (PIPE, CABLE & ETC.) SHALL
1,300

∅200
A 3 BE CARRIED OUT AT SITE AS PER MECHANICAL & ELECTRICAL DRAWING.

2,400
120
E
330 550 (E.J) ABBREVIATION E
100 SLAB END LINE D : ARCH. F : FIRE FIGHTING
540 1,260 540 1,260 540 1,460 540 1,255 500 1,400 500
230 3,000 300 M : MECH. S :SKODA
L : PLUMBING
P : PIPING
E : ELEC.
207 301 302 303 304 305 306 401 402 403 404 405 406 407 H : HVAC.

169,000 REFERENCE DRAWING


CCB
4,000 DRAWING NO. DRAWING TITLE
1,000 56,500 (BLOCK 3) 57,000 (BLOCK 4)
MRT-CA00-P0UMA-180015~17,19 GROUND, MEZZ., OPERATING & ROOF FLOOR PLAN (ENLARGED)
MATCH LINE
(E.J LINE) 7,500 9,000 10,000 10,000 11,000 9,000 7,500 9,000 10,000 10,000 12,000 8,500 MRT-CA01-P0UMA-180027 GROUND FLOOR FRAMING PLAN

MRT-CA03-P0UMA-180028~32 MEZZ, OPERATING & LOWER ROOF FLOOR FRAMING PLAN

MRT-CA00-P0UMA-180047 FLOOR OPENING SCHEDULE


D 300 8,200 725 D
MRT-CA02-P0UMA-180045 EQUIPMENT FOUNDATION REBAR DETAIL
4,300 700 700

2,095 250250
F 315
250250 2,015

800 350250300 300 245 800 950


315
5,000

200 255 300 300 300 200


2,155

800 775 800


600
207 301

BLK-4 230V UNIT ACDB


600

275 200 225


∅2
00
1,000

1,195

100 100
BLK-4 UPS ACDB
E
330 120 550 FOR CONSTRUCTION

1,750
1,960
600
∅2
00
(E.J) 2,095

650 650
250250

200
315
SLAB END LINE
7,500

470 650 800 800 800 800 800 350 250 800 800
CHK'D PL.- 6t

350 200 200 200 200 200 200 200 200


765 2,050
SLAB END LINE

3,945
TAG.

430 800 780 1,020 850 780 550 580


CORNER L50x50x4

200

220 450
∅2
EL.+17.900(T.O.C) W/D10x150@400 TYP.
00 3 17.APR.2019 REVISED AS PER MECH. & ELEC. ARRANGEMENT DRAWINGS. Y.C.JEONG N.Y.KOO K.S.ROH

1,595
600

COMMON PDC
2 08.OCT.2018 REVISED AS PER OWNERS ON COMMENTS Y.C.JEONG N.Y.KOO K.S.ROH
C D C
EL.+17.700(T.O.S)

COMMON MCC
1 25.MAY.2018 Approved by Owner on 5th DRM Y.C.JEONG N.Y.KOO K.S.ROH

REV. DATE DESCRIPTION DRAWN CHKD. APPD.


NO.
7,500

765 2,050
Project
35,000

L-100x100x7@1,000
MUARA TAWAR COMBINED CYCLE
E.J SECTION "D-D"
2,155 600 4,470 385 890
END PL.-6t (TYP.)

2,810
3 POWER PLANT BLOCK 2, 3 & 4
SCALE : 1/20
C TYP. ADD-ON PROJECT
Owner
4,300

330120550(E.J) SLAB END LINE SLAB END LINE


5,000

200 200 100 3,400 100 200 200


550 150

150

550 150

305 430 1,900 200 1,400 200


700

875 175 2151,160 1,050 2151,160 850 215 1,160 1,650 800 800 1,160 1,230 800 1,160 850 800 1,160 1,245 560 560 560 560
150

B
230

800 800 800 800


125 210 405 500 715
210345

210345

GLAND PLATE

716 X 275 MM

210 345

210 345
240 440 240
500 500 975 550 650 625 625 650 550 650

CUTOUT

200 210 210 215


150

250 885

250 885
585

320 850
250885

250885
Owner's Engineer
700

200 170 205 180220 180 205 385


150 150 200 150 150 250
185

MLDB
1,310

TRANS. TRANS. ELDB TRANS. WDB

3,400
2,240
GLAND PLATE

716 X 275 MM
CUTOUT

FOR BLK-3 FOR BLK-3 FOR BLK-3 MLDB TRANS. ELDB TRANS. WDB
4,885
250

800 TRANS. BLK-4 BATTERY BLK-4 BATTERY


385 1,540

385 1,540

385 1,540

FOR BLK-4
150 1,000 3,085 800 1,070 FOR BLK-4
3,325

3,325

3,325

800
3,365

3,365

3,365
FOR BLK-4
3,425

3,425
CHARGER-1 CHARGER-2
3,550

335
3,680

150
GLAND PLATE

405 X 275 MM
CUTOUT

B 165 245 150 150 3 B

2,290
685 240 335 335 685 685 685 335 335 685 1,415 685 335 335 335 335 150 2,170 685 685 335 335 680
GLAND PLATE

385
405 X 275 MM

385
CUTOUT

200 200 950 200 255 300165 200 1,005 245 200 455 245 200 560 450400 240 345 265 200 200 200 200 200 200 200 1,155 245 200 455 245 200
210 405

2,500 715 715 555 555 405 405 350 715 300 265 210 265 705 315 300 265 280 300 265 265 265 655 585 315 295 265 285
800 800 800 800 800 300 300 270 800 800 300 800 800 300 800 800 240 150 560 560 480 650 800 800 800 800 800 235 265 800 800 300 800 800 300 800 800
GLAND PLATE

555 X 275 MM
CUTOUT

170 205 180 210 180 205150


585 95

585 95

585 95

TRANS. TRANS.
250250

250250

UPS

250250
TRANS. TRANS.
145

145

145

BLK-4 220V BLK-4 220V


3,260 5,240
600

600

600
BLK-3 220V BLK-3 220V
315

315

315

2,300
555
4,590

GLAND PLATE
275 1,890 275

555 X 275 MM
640

BLK-3 BATT.
CUTOUT

BLK-3 230V ACDB BLK-3 UPS ACDB BLK-3 BATT.


BLK-4 UNIT PDC SWGR
GLAND PLATE GLAND PLATE GLAND PLATE GLAND PLATE GLAND PLATE GLAND PLATE GLAND PLATE GLAND PLATE
10,000

CUTOUT CUTOUT CUTOUT CUTOUT CUTOUT CUTOUT CUTOUT CUTOUT

305 BLK-4 400V UNIT MCC UNIT DCDB-1 UNIT DCDB-2


00
BLK-3 UNIT PDC SWGR UNIT DCDB-1 UNIT DCDB-2
BLK-4

716 X 275 MM 716 X 275 MM 555 X 275 MM 555 X 275 MM 405 X 275 MM 405 X 275 MM 716 X 275 MM 716 X 275 MM

CHARGER-1 CHARGER-2
∅2
350165 715

385 185 170 430 430 800 800 430 430 800 1,350 00 205 190 190 190 625 635 2,075 220 200 190 210
9,300

800
GLAND PLATE

716 X 275 MM
CUTOUT

2,500
BLK-2 UPS
715 715 405 405 555 555 350 715 ∅2 3,615 800 EPC Contractor
800 295 170 615 200 180 170 190 780 410 410 410 410 150 780 780 410 410 780

100
250250 1,800

BLK-3 UPS
170 205 180 210 180 205150 430 150 155

3,600 100
GLAND PLATE

716 X 275 MM
CUTOUT

650 1,910 650 800 3,070 1,850 400 1,200 400 900 800
716 X 275 MM 716 X 275 MM 405 X 275 MM 405 X 275 MM 555 X 275 MM 555 X 275 MM 716 X 275 MM 716 X 275 MM

00 1,745 150 3,650 200 3,000 200 3,650 150 3,030 200 2,950 150 3,750 200 3,830 3,030 200 2,445 150 2,850 200 3,850
∅2
CUTOUT CUTOUT CUTOUT CUTOUT CUTOUT CUTOUT CUTOUT CUTOUT

270
GLAND PLATE GLAND PLATE GLAND PLATE GLAND PLATE GLAND PLATE GLAND PLATE GLAND PLATE GLAND PLATE

MV SWGR FOR BLOCK-4


315 275

MV SWGR FOR COMMON 150 150


150 275 1,995
D D
505 155

505 155

505 155
3,675
300
BLOCK-2 MV SWGR.

STATION SERVICE
STATION SERVICE
TRAFO. RECIFIER

TRAFO. RECIFIER

COMMON MV SWGR.
170

170

120
WTP SERVICE

FIGHTING PUMP
HP FEED WATER

HP FEED WATER

HP FEED WATER

CHLORINATION

SPARE SERVICE

SPARE SERVICE
PLANT TRAFO.-B
CHLORINATION

A/C ROOM
PLANT TRAFO.-A
SPARE SERVICE
600

600

WTP SERVICE
FOR ECP UNIT-1

FOR ECP UNIT-2


BUS COUPLER

700
COMMON SWGR.

SPARE SERVICE

CONDENSATE
CONDENSATE
PDC TRAFO.-1

HP FEED WATER

HP FEED WATER

HP FEED WATER
CONDENSATE
SPARE MOTOR

SPARE MOTOR

LCP FOR FIRE


CONDENSATE

CONDENSATE

CONDENSATE

EXTRACTION
EXTRACTION

EXTRACTION
SPARE MOTOR

SPARE MOTOR
BUS RISER
EXTRACTION

EXTRACTION

EXTRACTION

HSBT
I/C FROM UAT

BLK-3 400V UNIT MCC


TRAFO.-A
BUS PT A
TRAFO.-B

TRAFO.-A
UNIT PDC

UNIT PDC

I/C FROM UAT


TRAFO.-A

TRAFO.-B

BUS TIE TO

BLOCK-4A
BLK-4 SWGR.

CW PUMP

CW PUMP
FEEDER-1

BUS PT B

TRAFO.-1

TRAFO.-1

BLK-3 400V ESS MCC


BUS TIE YO

BLOCK-3

BLOCK-3

TRAFO.-A
BLOCK-3

BLOCK-3

BLOCK-3

UNIT PDC

UNIT PDC
BLK-3 SWGR.

TRAFO.-B

BLOCK-4B
BUS PT

BUS TIE TO
CW PUMP

PUMP-3
CW PUMP

TRAFO.-B

PUMP-1
FEEDER-1

FEEDER-2

505
PUMP-1

PUMP-2

PUMP-3

TRAFO.-B

PUMP-2
UNIT PDC

FEEDER-1

FEEDER-2

BLOCK-4

BUS PT
BLOCK-4

BLOCK-4

BLOCK-4

BLOCK-4
BLOCK-3A

BUS TIE TO

PUMP-2

PUMP-3

PUMP-1
SPARE
BLOCK-3B

BUS TIE

BLOCK-3

TRAFO.-1
PUMP-1

PUMP-2

PUMP-3

380
1,265 800 800 800 800 800 270 230 800 800 800 480 800 800 285 280 280 280 260 R S T

600 600 600 600 600 1,200 600 600 600 600 600 600 600 600 600 445
T S R R S T 100 3,400 100 ∅2 R S T

600 600 600 1,000 600 600 900 900 600 600 600 600 600 600 600 600
R S T R S T

600 600 600 600 600 600 605 600 600 1,200 600 600 600 600 600
T S R

00
2,670

2,670

2,605
200 200 200 200 200 200 200 200 260
2,515

200 255 320320 320 320150


2,475

2,475
2,425

2,425

2,425
200 395 200 200 FOR
200 BLOCK-3
200 200 200 200 200 200 200 150 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 395 200 200 200 200 200
3,400

MV SWGR
150 150 Sub Contractor
1,260

600
575

A
2,400

2,400
3
SLAB END LINE SLAB END LINE DRAWING TITLE

2,700 3,000 3,000


A 200 A

OPERATING EQUIPMENT FOUNDATION & SLAB OUTLINE PLAN-3


SCALE : 1/200 GRAPHIC SCALE SCALE DRAWING NUMBER SHEET NO. REV. NO.
NOTE:
0 5 10 25 50 100 200m
FOR SLEEVE DETAIL OF CONCRETE SLAB & WALL OPENING ,
REFER TO STANDARD DRAWING MRT-CC05-P0ZEN-175046.
1 : 200 MRT-CA01-P0UMA-180044 7 OF 8 3
8 7 6 5 4 3 2 1 A1 (594 x 841mm)
8 7 6 5 4 3 2 1

LEGEND NOTE
201 202 203 204 205 206 207 301 A
1. ALL DIMENSIONS ARE IN MILLIMETTERS UNLESS NOTED.
2. ALL LEVELS AND COORDINATES ARE IN METERS UNLESS
4,000 169,000 575 OTHERWISE NOTED
BLOCK 1 3. ELEVATION
10 GRATING (THK.40)
.2
° (EXISTING BLDG.) 150
3.1. MEAN SEAWATER LEEVEL(MML) = EL±0.000
H 3,000 54,500 (BLOCK 2) 1,000 EL.+22.900(F.F.L) / EL.+22.860(T.O.S) 3.2. GROUND LEVEL(GL) = EL+2.800 H

1,000 GRATING (THK.40) 3.3. MAIN BUILDING GROUND FLOOR LEVEL = EL+3.100
7,500 10,000 10,000 9,000 10,000 8,000 EL.+22.900(F.F.L) / EL.+22.860(T.O.S) 4. CONCRETE GRADE / MAX.AGGREGATE SIZE / WATER CEMENT RATIO
CONCRETE MAX. MINI. CEMENT MAX. WATER
MATCH LINE REMOVABLE GRATING (THK.40) GRADE APPLICATION AGGREGATE CONTENT CEMENT RATIO
(E.J LINE) EL.+22.900(F.F.L) / EL.+22.860(T.O.S) ( f'c) SIZE(mm) (KG/M3) BY WEIGHT
15 MPa LEVELING CONC. 40 200 0.52
CHECKED PLATE (THK.6)
EL.+22.900(F.F.L) 25 MPa STRUCTURAL CONC 20 275 0.50

1,500
30 MPa ST FDN, CCB, INTAKE
END PL-6t S.O.G SLAB STG BLDG, CW SUMP
EL.+22.900(F.F.L) PIT , DISCHARGE 20 300 0.50
DECK SLAB TUNNEL & OUTFALL
F CONC DECK SLAB OR GRATING DIRECTION
WHERE, f'c=CYLINDER COMPRESSICE STRENGTH AT 28-DAY
LOW ROOF - UNNAMED SLAB : DS3
5. REINFORCING BAR STRENGTH
5,000

EL.+22.900(T.O.C) 5.1. DEFORMED BARS


DADO WALL : THK.150 , HEIGHT 500mm

300
: fy=413MPa (ATSM A615 Grade 60 / JIS-G 3112)

200
G EL.+22.700(T.O.S) 5.2. MESH REINFORCEMENT : fy=413MPa(ASTM A185)
E 6. CEMENT G
6.1. ASTM C150 TYPE-I : FOR CONCRETE WORK ABOVE GRADE
3 LEVEL OTHERWISE INDICATED.
6.2. ASTM C150 TYPE-II : ONLY FOR FOUNDATIONS AT OR BELOW
L-100x100x7 GRADE.
7,500

@1000 6.3. ASTM C150 TYPE-V : FOR STRUCTURES IN DIRECT CONTACT


WITH SEA WATER OR GROUND WATER WITH SIMILAR BEHAVIOR.
7. CONCRETE COVER (CAST-IN-PLACE CONCTERE)
SECTION "A-A"(PARAPET) MIN. CONC.
SCALE : 1/20 ITEM COVER(mm)
D
3 FOUNDATION 75
TIE BEAMS/GIRDER BEAMS BELOW GRADE 75
MARINE STRUCTURES (INCONTACT WITH SEA WATER) 75
7,500

CONCRETE IN CONTACT WITH GROUND SURFACE 75


B B
PEDESTALS 50
35,000

3 COLUMNS 40
BEAM, SLAB & PRECAST PANEL 25
WALL OPENING 150 375 150 550 700 150
F 430x200(B.O.O EL +23,260) 8. CHAMFERED CORNERS OF CONCRETE ALL EXTERIOR CORNERS
WALL OPENING
C DIA.150(C.O.O EL +23,205) (ANGLE OF 90° OR LESS) OF REINFORCED CONCRETE SHALL BE F
3 CHAMFERED (25mmX25mm).
150 4,400 3,400 100 STUD BOLT 9. THE FOLLOWING ITEMS, SEE STANDARD DRAWING UNLESS
SLAB END LINE 150 150 150 150
5,000

3 D16@1500 OTHERWISE NOTED.


3 100
(L=135)

C
350 -MINIMUM CONCRETE COVER
150

150
550 850

STUD BOLT -HOOK, DEVELOPMENT AND SPLICES OR REBAR


3

500
B

150
B END PL-6t D16@1500 10. GROUT

800
150 150
375

LOW ROOF LOW ROOF 10.1 NON SHRINKAGE GROUT HAVING 60 MPa STRENGTH AT 28-DAY

375
1,050
(L=135)

400

100
3,500

2,100
EL.+22.900(T.O.C) EL.+22.900(T.O.C) (ASTM C109)
150

C
1,500 3,210 2,030 2,360 900 2,380 150 450

1,200
C1 11. THE INFORMATION ABOUT ANCHOR BOLT IS SHOWN AS REFERENCE.
FSS2

3,870
4,730
B

SLAB END LINE ANCHOR BOLT SHALL BE INSTALLED ON THE BASIS OF MECHANICAL
620 F280 EL.+22.700(T.O.S) EL.+22.700(T.O.S) DRAWING.
FSS1
10,000

900 4,000 580 12. BEFORE CONSTRUCTION OF EQUIPMENT FOUNDATION, ELECTRICAL


800 2,185 800 2,185

1,405

ACCU01 2,130 CONDUIT OF EQUIPMENT HAVE TO BE INSTALLED AS PER EQUIPMENT


1,300

AHU01 GENERAL ARRANGEMENT DRAWINGS & EMBEDDED CONDUIT DRAWINGS


281 3 STUD BOLT

4,880
L60x60x6 13. SMALL OPENING WORK FOR SLAB & WALL (PIPE, CABLE & ETC.) SHALL
1,405

D19@640(L=130) 3 BE CARRIED OUT AT SITE AS PER MECHANICAL & ELECTRICAL DRAWING.

825 1,350
ACCU01

1,500
1,400

A
AHU01
E
150 425
575

A ABBREVIATION E
SECTION "B-B"(DADO WALL) SECTION "C-C" D : ARCH. F : FIRE FIGHTING
M : MECH. S :SKODA

A
SCALE : 1/20 SCALE : 1/20
280 600 L : PLUMBING
SLAB END LINE SLAB END LINE
100 120 P : PIPING
E : ELEC.
H : HVAC.

REFERENCE DRAWING
207 301 302 303 304 305 306 401 402 403 404 405 406 407
DRAWING NO. DRAWING TITLE

MRT-CA00-P0UMA-180015~17,19 GROUND, MEZZ., OPERATING & ROOF FLOOR PLAN (ENLARGED)


169,000 CCB
MRT-CA01-P0UMA-180027 GROUND FLOOR FRAMING PLAN
4,000
1,000 56,500 (BLOCK 3) 57,000 (BLOCK 4) MRT-CA03-P0UMA-180028~32 MEZZ, OPERATING & LOWER ROOF FLOOR FRAMING PLAN

MRT-CA00-P0UMA-180047 FLOOR OPENING SCHEDULE


7,500 9,000 10,000 10,000 11,000 9,000 7,500 9,000 10,000 10,000 12,000 8,500 D
D MRT-CA02-P0UMA-180045 EQUIPMENT FOUNDATION REBAR DETAIL
MATCH LINE 725
(E.J LINE)
SLAB END LINE
SLAB END LINE
SLAB END LINE
207 301

975
F 1,000 FOR CONSTRUCTION
5,000

280 600 280 120 600 500 280


(E.J)
E CHK'D PL.- 6t 3 17.APR.2019 REVISED AS PER MECH. & ELEC. ARRANGEMENT DRAWINGS. Y.C.JEONG N.Y.KOO K.S.ROH

TAG. TYP.
CORNER L50x50x4 825 150 2 08.OCT.2018 REVISED AS PER OWNERS ON COMMENTS Y.C.JEONG N.Y.KOO K.S.ROH
C C
W/D10x150@400 EL.+23.200(T.O.C) 1 25.MAY.2018 Approved by Owner on 5th DRM
7,500

Y.C.JEONG N.Y.KOO K.S.ROH

150 150
REV.

300
DATE DESCRIPTION DRAWN CHKD. APPD.
NO.
EL.+22.900(T.O.C) Project

D LOW ROOF MUARA TAWAR COMBINED CYCLE


POWER PLANT BLOCK 2, 3 & 4
ADD-ON PROJECT
D10-D200
7,500

D10-D200 Owner

E.J SECTION "D-D"


35,000

3
SCALE : 1/20
WALL OPENING WALL OPENING WALL OPENING WALL OPENING 3
430x200(B.O.O EL +23,260) 3 DIA.150(C.O.O EL +23,155) 430x200(B.O.O EL +23,260) 3 DIA.150(C.O.O EL +23,155)
C 3 FSS1 DETAIL Owner's Engineer
150 5,400 3,600 150 8,700 150
B SEE DWG NO. B
SLAB END LINE
5,000

3 100 3,400100 MRT-CA02-P0UMA-180045_6of6


415 415
305 430
550 850

375 1,550

3 3 EPC Contractor
150375150

B
230
585

1,050

1,050
3,500

2,100

3,500

2,100
150

1,200

1,200
C1 C1
3,085 1,400 1,775 FSS2 1,520 FSS2
4,730

520 3,210 8001,900 2,080


SLAB END LINE 900
100 6,275 1,150 225 Sub Contractor
1,405

700
1,615

FSS1 FSS1
6,600
10,000

1,950

F380 F480
8,625

450 150
1,405

ACCU02 900 4,000 580 4,900 580 145.33


150400

3,600 100
AHU02
1,300
1,300

AHU03 ACCU03
2,130 2,130
800

1,300

150450 450 150


130150 3
2,400 1,405

3
1,950 1,615

1,650 1,950

1,7001,405

ACCU02 100
AHU02 DRAWING TITLE
825 1,350

D D 381
AHU03 ACCU03
481
1,500

1,500

3
825
575

600
A 3
A A
280 600 2,130 675 675 2,130 1,400 5,255 1,845 150
SLAB END LINE 120 100
LOWER ROOF SLAB OUTLINE PLAN 0 5 10 25 50
GRAPHIC SCALE
100 200m
SCALE DRAWING NUMBER SHEET NO. REV. NO.

SCALE : 1/200
1 : 200 MRT-CA01-P0UMA-180044 8 OF 8 3
8 7 6 5 4 3 2 1 A1 (594 x 841mm)