Reactor
Reactance value, L 12.876 mH 2.724 mH
XL-XC I Irms
XL 4.046743 81.50 99.9545 100.92814465 XL 0.856114
XC 85.54 XC 96.06
XL-XC I Irms
95.21 89.79072 89.8 109.8865
Imp
I
Column Q
Column R
Conclusion: Total Harmonic current up to 11th is 87.59 A, both the banks are suitable for worst case of sucking all the ha
Conclusion: Both the bank ratings are more than worst case of 50.99 A, hence adequate
Notes:
30 % of 5th and 7th Harmonic current is considered for the 12 pulse operation while computing effective current
Harmonic filter bank is expected to suck all harmonics numbers below it as worst case
Refer page no 82 of IEEE519 for pu values of harmonic currents
Basis for worst case