SCHEDULE OF QUANTITIES

GENERAL NOTES

1 All items of work under this Contract shall be executed strictly to fulfill the requirements laid down in
the specifications. Type of equipment, material specification, methods of installation and testing and
type of control shall be in accordance with the specifications, approved shop drawings and the
relevant Indian Standards, however capacity of each component and their quantities shall be such
as to fulfill the above mentioned requirement.

2 The unit rate for all equipments or materials shall include cost in RUPEES for equipment and
materials including all taxes and duties and also including forwarding, freight, insurance and
transport into Contractor’s store at site, storage, installation, testing, balancing, commissioning and
other works required.

3 The rate for each item of work included in the Schedule of Quantities shall, unless expressly stated
otherwise, include cost of :

a All materials, fixing materials, accessories, appliances tools, plants, equipment, transport, labour
and incidentals required in preparation for and in the full and entire execution, testing, balancing,
commissioning and completion of work called for in the item and as per Specifications and
Drawings.

b First fill of oil and diesel over and above that requires for testing as per contract.

c Wastage on materials and labour.

d Consumables for testing

e Loading, transporting, unloading, handling/double handling, hoisting to all levels, setting, fitting and
fixing in position, protecting, disposal of debris and all other labour necessary in and for the full and
entire execution and for the job in accordance with the contract documents, good practice and
recognize principles.

f Liabilities, obligations and risks arising out of Conditions of Contract.

g All requirements of Specifications, whether such requirements are mentioned in the item or not. The
Specifications and Drawings where available, are to be read as complimentary to and part of the
Schedule of Quantities and any work called for in one shall be taken as required for all.

h In the event of conflict between Schedule of Quantities and other documents including the
Specifications, the most stringent shall apply. The interpretation of the Consultant/Project Manager
shall be final and binding.

4 All equipments, quantities and technical data indicated in this Schedule are for the Contractor’s
guidance only, these are based on the documents prepared by the Consultant. This schedule must
be read in conjunction with other documents. The Contractor shall be paid for the actual quantity of
work executed by him in accordance with the approved Shop Drawings at the contract rates.

5 This Schedule shall be fully priced and the extensions and totals duly checked. The rates for all
items shall be filled in INK including NIL / Rate Only (RO) items.

6 No alteration whatsoever is to be made to the text or quantities of this Schedule unless such
alteration is authorised in writing by Consultant. Any such alterations, notes or additions shall,
unless authorized in writing, be disregarded when tender documents are considered.

AECOM INDIA PVT. LTD., MUMBAI SQ-1


NODD12032-DG-06-0000-00_00 – Residential Project at Borivili, Mumbai : SOQ for LT D.G. Set System
7 In the event of an error occurring in the amount of the Schedule, as a result of wrong extension of
the unit rate and quantity, the unit rate quoted by the tenderer shall be regarded as firm and the
extensions shall be amended on the basis of rates.

8 Any error in totaling in the amount column and in carrying forward total shall be corrected. Any error,
in description or in quantity, omission of items from this Schedule shall not vitiate this Contract but
shall be corrected and deemed to be variation required by the Consultant/Project Manager.

9 Rates have been called for a number of items of works, as alternatives which, for the present do not
form part of the total value of tender. However the rates for these items shall be quoted, with due
care so that in the event of choice of an alternative item of work, said rate shall form part of the
contract and shall not violate the contract any way.

10 The Contractor shall procure and bring Materials/Equipment to the site only on the basis of
drawings approved for construction and shop drawings and not on the basis of Schedule of
Quantities which are provisional only. This also applies to the Contractor’s requisition for Owner
supplied materials.

11 Painting of all piping shall be as per IS.

AECOM INDIA PVT. LTD., MUMBAI SQ-2


NODD12032-DG-06-0000-00_00 – Residential Project at Borivili, Mumbai : SOQ for LT D.G. Set System
ANNEXURE : I
BILL OF QUANTITIES

NAME OF WORK : 750 KVA DG SET WORK


WO NO: #REF!

SR. DESCRIPTION TOTAL AMOUNT


NO.

A. SUPPLY AND INSTALLATION OF 2 Nos. 750 KVA DG SET WITH ACCESSORIES 8,349,000.00

B. DG AMF CUM AUTO SYNCRONIZATION & AUTO LOAD SHARING PANEL 1,660,250.00

C. EARTHING INSTALLATION (FOR DG SETS) 1,147,500.00

D. CABLES AND CABLE TRAYS 598,220.00

GRAND TOTAL 11,754,970.00

CGST 9% 1,057,947.30
SGST 9% 1,057,947.30

TOTAL AMOUNT (A) 13,870,864.60

NON COMPREHENSIVE AMC COST


1 Total Non Comp AMC Charges for 3 Years after 2 Years Warrantee 88,000.00

TOTAL AMOUNT 88,000.00


GST / TAXES EXTRA AT PREVAILING PERIOD

AECOM INDIA PVT. LTD., MUMBAI SQ-3


NODD12032-DG-06-0000-00_00 – Residential Project at Borivili, Mumbai : SOQ for LT D.G. Set System
ANNEXURE : I
BILL OF QUANTITIES

NAME OF WORK : 2 Nos - 750 KVA DG SET


WO NO :

RATE
SR.NO ITEM DESCRIPTION UNIT QUANTITY AMOUNT
SUPPLY INSTALLATION TOTAL
A SUPPLY AND INSTALLATION OF DG SET WITH ACCESSORIES

Supply, installation, testing & commissioning of 750 KVA (600 KW at


0.8 PF) Prime Rating diesel generating set radiator type with accoustic
enclosure alongwith day oil fuel tank including first fill of diesel with
fuel piping to and from DG set including vibration mounts, base
frame, hardware Batteries, Engine control panel,electronic governor,
with accessories first fill of lube oil residential exhaust silencers along
with stainless steel flexible bellows, alarms, engine control panel
1 (Terminals shall be provided for remote ON/OFF facility and RS 485 Set 2 3,685,000.00 185,000.00 3,870,000.00 7,740,000.00
facility to read all parameters from control room), expansion joints
etc.. complete and with all associated equipment / work as
per specifications. The Fuel tank capacity within enclosure shall be
990 Litre with all associated fuel piping of MS class ‘C’ pipes cut to
required lengths and installed with all welded joints. Providing and
fixing in position the necessary fittings like elbows, tees and reducers,
sockets,DG set enclosure shall be suitable for outdoor duty

2 EXHAUST PIPING

Providing, fixing & installing MS class-B exhaust pipe and all fixing
accessories and hardwares. The exhaust pipes shall be insulated with
75 mm thick mineral wool (density 125 kg/m3) insulation wrapped in
chicken mesh and clad with 26 gauge aluminium sheet including MS
with Red Oxide Primer & Two coats Synthetic Enamel black Paint
support with structural as required. Cost of flexible bellows for
exhaust piping shall be considered as per manufacturer's
recommendation. The temperature of Aluminum Cladding shall not
be more than 65° C.

2.1 200 mm dia RM 30 650.00 250.00 900.00 27,000.00

2.2 350 mm dia RM 0 4,500.00 1,500.00 6,000.00 -

2.3 400mm dia RM 100 4,150.00 1,500.00 5,650.00 565,000.00

2.4 500 mm dia RM 0 7,800.00 1,800.00 9,600.00 -

Supply, installation, testing and commissioning of 150 AH IGBT


Technology based battery charger with 150 AH Battery unit with
3 provisions of Boost charging, and Float charging. Suitable for 230 V No. 2 8,500.00 8,500.00 17,000.00
single phase ± 10% AC, 50 Hz supply as per specifications to give DC
output of 24 volts. (Cabling for Battery Charger till Batteries shall be
inclusive)

TOTAL AMOUNT 8,349,000.00


B DG AMF CUM AUTO SYNCRONIZATION & AUTO LOAD SHARING PANEL

The rates for the DG AMF Panels apart from the Breakers and instruments shall also include the following :

1 Supporting rigid steel framework.

2 Cubicle type, 14 gauge CRCA sheet steel enclosed.

3 Complete with interconnections and distribution bus bars.

4 Proper bonding to earth.

5 Painting/lettering on Breakers and distribution boards, the location they serve, providing on each panel its circuit diagram.

6 Providing cable clamps / supports within cable alley of distribution boards.

7 All MCB’s shall be of appropriate breaking capacity but minimum of 10 KA breaking capacity.

8 The breaking capacity of MCCB’s are mentioned panel wise.

9 All motor feeders MCCBs / MCBs shall be of motor duty.

10 Distribution panels shall be Powder Coated with Siemens gray paint shade no. RAL-7032 of IS-5

11 Degree of protection for following type of distribution panel enclosure shall be as per IS:13947-1993.

a IP 52 for indoor panels.

b IP 65 for outdoor panels.

12 All MCCB’s shall be provided with extended operating mechanism for door interlock.

13 Current density of aluminium bus bars shall be 1.0 amps for 1 sq.mm of rated current of bus bars and 1.4 for copper busbars.

14 GI / Aluminium earth bus shall be provided through out the length of each board.

15 All measuring instruments (Meters) shall be of digital electronic (LED Type) of approved make and comptiable with BAS.

16 All hinged door shall be earthed through 2.5 sq mm tinned braided copper wire.

17 All panels shall have provision of the following:

a Pad locking of Switch board doors.

b Pad locking of MCCB’s handles in “OFF” Position.

MCB’s used for protection of resistive and lightly inductive load shall be type “B” characteristic, inductive (motor) load shall be of type “C” characteristic and discharge lamps and UPS etc. shall be of type D
18 characteristic.

19 All incoming and outgoing air circuit breakers shall be located on middle portion of the vertical section in single tier formation.

20 All KWH meters shall be suitable for hook-up with IBMS

21 All Trivect meters shall be suitable for hook up with BMS.


22 Adequate Provision to be kept in the Panel for running the trace tube piping for Gas supression System.
All Panels with Incomer rating 200 amps and above to be provided with gas supression system by fire fighting contractor and proper sealing to be done for openings/ holes made to the sheet steel for
running the gas piping so as to ensure that the degree of protection is maintained.

RATE
SR.NO ITEM DESCRIPTION UNIT QUANTITY AMOUNT
SUPPLY INSTALLATION TOTAL
B DG AMF CUM AUTO SYNCRONIZATION & AUTO LOAD SHARING PANEL

Design, fabrication, assembling, wiring, supply, installation, testing and commissioning of


DG Synch cum auto load sharing Panel fabricated out of 14 gauge CRCA sheet steel in cubicle
compartmentised free standing floor mounted, dust and vermin proof with reinforcement of
suitable size angle iron, channel `T’ section and / or flats wherever necessary. 3 mm thick cable
gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be
1 treated with all anticorrosive process before powder coating as per specification and final
approved shade. 2 Nos. earthing terminals shall be provided for all panels. Panels shall be
suitable for 415 V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in
all panels. Approval shall be taken for each panel in the form of shop drawings before
fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels.

Approval shall be taken for each panel in the form of shop drawings before fabrication.
Galvanised hardwares with zinc passivation shall be used in fabrication of panels.

DG panel for 750 KVA DG sets

1 AMF CUM AUTO SYNCHRONIZATION AND AUTO LOAD SHARING PANEL (IP44)

A. Incoming Air Circuit Breaker `A’ & "B"


(For DG -1 & DG-2 Supply )

1250 amps FP electrically operated fully drawout type air circuit breaker with built in
microprocessor based release unit for protection and measurment as per specification and with Sets 2
following accessories :

Phase indicating light through 415V /sq.rt 3 : 110V/sq.rt.3 415 V / 110 V PT, Primary / Secondary
i. Sets 2
of PT's shall be protected by 2 amps MCB’s.

ii. Breaker ON / OFF / TRIP indicating lights with control MCB’s. Set 2

iii. Under voltage release Set 2

iv. 24 V DC Shunt trip coil Set 2

3 Nos. 96 x 96 mm sq. 0-1250/ 5 amps CTR digital ammeter with 3 nos.1250/ 5 amps 15 VA CL : 1
v. Set 2
CT’s

96 x 96 mm sq. 0-500 Volt digital voltmeter with selector switch through 415 V /√3 : 110 V/√3
vi. Set 2
PT’s, Primary and Secondary of PT’s shall be protected by 2 amp TP MCB’s

Load manager (with RS 485 and open protocol for BMS) of accuracy class-I, with 3 Nos. 1600 /5A
vii Set 2
amps 15VA class 1 CTs to measure and display the following electrical quantities :
RATE
SR.NO ITEM DESCRIPTION UNIT QUANTITY AMOUNT
SUPPLY INSTALLATION TOTAL

Real Time
Total active energy (KWH/MWH)
Maximum demand (KVA/MVA) (KW/MW)
Maximum demand reset count.
Instantaneous power factor
Logging of active energy eight time of a day
Current
Voltage
Frequency / Harmonics

viii. Breaker control switch Set 2

Protection Relays & Interlocking:Multi functional numeric relay with mode bus RS 485 ports for
ix. Set 2
following protection.

a Under voltage relay (27) 3 Set


b Over voltage relay (59) 3 Set
c Reverse power relay(32) 3 Set
d Three over current relay (50V)
e Earth fault relay (51N) 3 Set
f Phase fault relay(87G), 3 Set
g Loss of field relay(40), 3 Set
h Frequency relay(81), 3 Set

i Diferential protection relay (87 G) with PS class CT’s on alternator neutral terminals (by alternator
supplier) and on panel side (by panel manufacturer).
j Master trip lockout relay (86) 3 Set
k Trip cirrcuit supervision relay (TCS) with indication lamp
l Breaker control switch 3 Set
m Battery charger 2 Set

n 16 Window alarm annunicator panel with hooter, push buttons, aux. Contactors etc as required as
per specification
o Cranking relay, etc. 3 Set.
p Auxiliary contacts required for necessary interlocking of breakers.
q Breaker Failure Protection
r Under Power
s Voltage restrained over current protecton (50 V / 51 V).
t Thermal overload (49)
u Current unbalance (46)
v 24 V DC shunt trip.
w Mains supply voltage sensing relay.
x locable Emergency stop push button.
y Selector switch for Auto / Manual / Test
z Selector switch for engine control OFF/ON.
aa Five push buttons – start, stop, reset, test and accept.
bb Three indicating lamps “load on set’, ‘Load on Mains’ and “ Set fail to start’.
cc Numeric stater restricted earth fault (64 R)
dd Breaker Control Switch
ee Excitation Ammeter
f Excitation voltmeter
gg Temperature Scanner

hh All Metering & Protection CT's & PT's of appropriate Class with suitable VA burden to perform
during the
RATE
SR.NO ITEM DESCRIPTION UNIT QUANTITY AMOUNT
SUPPLY INSTALLATION TOTAL

NOTE: For incoming breakers if 4P ACB is not feasible, quote for TP EDO ACB with neutral isolating
ii contactor of suitable rating (400A TP Motorized contactor for 1250 A TP ACB or As per
Manufacturer standard)

x 3 nos. 1600 /5A, 5VA line CTS for controller 2

xi 3nos. 415/110V line PTs with control fuses, for feedback to controller. 2

xii Grid supply voltage sensing relay 2

xiiii Battery charger voltmeter of range 0-50V and 2

xiv ammeter of range 0-50A for trickle and boost charging 2

xv Sycnhronization Controller with Manual synchronization feature/ 2

B. Bus Coupler : Breaker `C’

1250 amps 4 pole electrically operated fully drawout type air circuit breaker with ON / OFF / TRIP Set 1
indicating lamps with control MCB’s, shunt trip, breaker control switch etc.

C. Bus Bars

2500 amps 4 pole (35 KA) Aluminium bus bars with colour coded heat shrinkable insulating Set 1
sleeves

D. Outgoing Bus-1

800 amps 4 pole manually drawout type air circuit breaker with ON/OFF/TRIP indicating lamps
i. Set 2
with MCB’s and microprocessor based release for protection & indication as per specification.

iii. 315 amps TPN MCCB No. 1

iv. 250 amps TPN MCCB No. 3

v. 200 amps TPN MCCB No. 1

vi. 160 amps TPN MCCB No. 2

E. Outgoing-2

800 amps 4 pole manually drawout type air circuit breaker with ON/OFF/TRIP indicating lamps
i. Set 2
with MCB’s and microprocessor based release for protection & indication as per specification.

iii. 400 amps TPN MCCB No. 1

iv. 250 amps TPN MCCB No. 4

v. 160 amps TPN MCCB No. 3


RATE
SR.NO ITEM DESCRIPTION UNIT QUANTITY AMOUNT
SUPPLY INSTALLATION TOTAL
Notes :

i. All outgoing feeders shall have suitable range of followings (except capacitor feeders)

a. Digital electronic KWH meter with RS 485 port.

b. Digital electronic ammeter with selector switch and 3 Nos. CT’s.

c. Three phase indicating lamps through 415 / 110 V PT, primary / secondary of PT's shall be
protected by 2 amps SP MCBs.

ii All breakers shall be electrically/ mechanically interlocked as per schematic diagram.

ii. All MCCB’s shall be suitable for 35KA (ICS) breaking capacity.

iii. All ACB's shall be suitable for 50 kA ( Icu=Ics=Icw for 1 sec.)

iv. 415 / 110 V suitable rating control transformer shall be provided for aux. Control supply

v. Wiring with space heater, thermostat and control MCB’s shall be provided for all vertical sections
of main LT panel.

vi. All outgoing MCCB’s feeders shall be provided with built-in microprocessor release unit with
earth fault protection and time delay.

vii. All incoming as well as outgoing feeders shall have pad locking facility.

viii. Suitable danger board shall be provided.

ix. All bus bar section / backside panels shall have pad locking facility and hinged type door.

x DG controller with AMF, auto synchronising and auto load sharing features and shall be of
Cummins / Woodword / DEIF or equivalent make with following features:
a) Contol features shall be as per details given under clause 3.6.23.3 of technical specification
when both AMF as well as synchronisation functions are required. When only AMF function is
required, refer clause3.6.23.2.
b) Protection
Engine - over spped, under speed, speed/frequency mismatch, excitation failure
Generator - Over load, short circuit, reverse power, unbalance load, inst. Over current. event
recorder
c) Measurement - LCD display for Generator line and phase voltages, generator line currents,
Mains line and phase voltages, Bus voltages, kwh, kvarh, running hours

d) Gennral - Auto/Manual/OFF mode, soft keys for speed raise lower and frequency raise lower
(required for manual mode). Configurable discrete alarm inputs, configurable discrete outputs

e) Communication - CAN bus for engine, RS 485 + open protocol for BMS

DG AMF CUM AUTO SYNCHRONIZATION AND AUTO LOAD SHARING PANEL as described above. Set 1 1,578,000.00 5,000.00 1,583,000.00 1,583,000.00

2.0 SAFETY EQUIPMENT


RATE
SR.NO ITEM DESCRIPTION UNIT QUANTITY AMOUNT
SUPPLY INSTALLATION TOTAL

Supply and fixing in position the approved “Shock Treatment Charts” written in Hindi, English &
2.1 Nos 1 1,500.00 100.00 1,600.00 1,600.00
Local language. These charts shall be framed and covered with glass.

2.2 Supply and fixing in position the fire extinguishers carbon-di-oxide type 4.5 Kgs capacity. Nos 1 4,500.00 200.00 4,700.00 4,700.00

Supply and fixing in position 1000 mm wide rubber mat of 415 V grade as per electricity rules and
2.3 Meter 22 650.00 50.00 700.00 15,400.00
as per IS 15652 upto latest amendment.

Supply of fire buckets 3 nos. in each set duly filled with fine sand and fixed on an angle iron frame
2.4 as per requirement of local authorities. Fire buckets shall be painted red from outside and white Nos 1 500.00 50.00 550.00 550.00
from inside with additional handle at the bottom.

Factory Testing shall be considered as per the below format and shall be for 2 Nos. 750 KVA DG
3 Sets.

Factory testing shall be as per below format


Idle run: 05 mins
50% load: 30 mins Job 1 55,000.00 55,000.00 55,000.00
75% load: 30 mins
100% load: 30 min
110% load: 1 Hours.

TOTAL AMOUNT 1,660,250.00


C. EARTHING INSTALLATION (FOR DG SETS)

Rates shall also include the following :

1 All fixing accessories such as brass saddles, brass screws rawl plugs etc.

2 Jointing by rivetting and brazing after rivetting.

3 Cutting chases holes and making good the same wherever required.

4 Efecting adequate and proper interconnections.

5 Use of copper thimbles.

6 Earthing system shall comply to IS:3043-1987.

7 All earthing pits shall be interconnected.

8 All equipment motors, DB’s, panels to be connected on either ends (double earthing) with suitable strip / wires.

RATE
SR.NO ITEM DESCRIPTION UNIT QUANTITY AMOUNT
SUPPLY INSTALLATION TOTAL
C. EARTHING INSTALLATION (DG SETS)

Supply and fixing of following bare copper/GI , tapes /


1 wires including all necessary fixing accessories and
efecting connections as per specifications.

1.1 30 x 6 mm thick copper tape. RM 800 850.00 50.00 900.00 720,000.00

1.2 50 x 6 mm thick GI tape. RM 800 380.00 50.00 430.00 344,000.00

Providing and laying of 600 x 600 x 3.15 mm thick tined


copper electrode, with 2 Nos 50 x 6 mm copper strips
from earth electrode to inspection chamber, 50 mm dia
medium class GI pipe, CI funnel with 20 gauge GI wire
mesh, concrete chamber 1000 x 500 mm with concrete
2 base C I heavy duty manhole cover with frame painted No. 4 8,500.00 1,000.00 9,500.00 38,000.00
with bitumastic paint and packing with mixtures of
charcoal and common salt around plate electrode
including digging of pit upto permanent moisture level and
as per soil condition but not less than 3 meters and back
filling as required.

Providing and laying of 600 x 600 x 3.15 mm thick GI


electrode, with 2 Nos 50 x 6 mm GI strips from earth
electrode to inspection chamber, 50 mm dia medium
class GI pipe, CI funnel with 20 gauge GI wire mesh,
concrete chamber 1000 x 500 mm with concrete base C I
3 heavy duty manhole cover with frame painted with No. 4 4,500.00 1,000.00 5,500.00 22,000.00
bitumastic paint and packing with mixtures of charcoal
and common salt around plate electrode including
digging of pit upto permanent moisture level and as per
soil condition but not less than 3 meters and back filling
as required.

Supply and laying of GI pipe under road / paved area


4 crossing etc. including excavation back filling ramming and
making good.

4.1 50 mm dia pipe. RM 0 3,000.00 100.00 3,100.00 -

4.2 100 mm dia pipe. RM 0 3,200.00 100.00 3,300.00 -

4.3 150 mm dia pipe. RM 50 450.00 20.00 470.00 23,500.00

TOTAL AMOUNT 1,147,500.00


D. CABLES AND CABLE TRAYS

The rate shall also include the following :

1 Providing all fixing accessories such as clamping devices nuts, bolts and screws.

2 Wherever the cables are of aluminium and bus bars of copper bimetallic lugs shall be used.

3 All cable shall be laid with one diameter gap.

4 All cables shall be IS approved.

5 Double compression glands

6 Fire retardent paint one meter on both side of wall penetration and at termination as per specifications.

7 Burried LT cables to be laid atleast 750 mm below ground.

RATE
SR.NO ITEM DESCRIPTION UNIT QUANTITY AMOUNT
SUPPLY INSTALLATION TOTAL
D. CABLES AND CABLE TRAYS

Supplying & laying of following 1100 volt grade XLPE insulated


PVC inner sheathed and FRLS PVC outer sheathed aluminium
conductor armoured cables as per specification in existing
1 trenches, cable trays, ducts, clamped to wall with suitable
clamps including, saddles fixing bolts, connecting testing and
commissioning.

1.1 3.1/2 core 400 sq. mm RM 0 1850.00 150.00 2,000.00 -

1.2 3.1/2 core 300 sq. mm RM 275 1050.00 50.00 1,100.00 302,500.00

1.3 3.1/2 core 240 sq. mm. RM 0 1150.00 150.00 1,300.00 -

Supplying & laying of following 1100 volt grade XLPE insulated


PVC inner sheathed and FRLS PVC outer sheathed copper
conductor armoured cables as per specification in existing
2 trenches, cable trays, ducts, clamped to wall with suitable
clamps including, saddles fixing bolts, connecting testing and
commissioning.

2.2 4 core 10 sq. mm. RM 0 500.00 50.00 550.00 -

2.3 4 core 6 sq.mm RM 0 480.00 50.00 530.00 -

2.4 3 core 6 sq.mm RM 0 400.00 50.00 450.00 -

2.5 3 core 10 sq.mm RM 0 380.00 50.00 430.00 -


RATE
SR.NO ITEM DESCRIPTION UNIT QUANTITY AMOUNT
SUPPLY INSTALLATION TOTAL

Supply,laying,testing and commissioning of following 1100 volt


grade FRLS PVC insulated PVC sheathed multistranded 24 AWG
fully annealed stranded tinned copper conductor armoured
shielded control cables with 100% Flexfoil of
3 aluminum/polyester with 25% overlap, foil facing out stranded
tinned copper drain wire laid on cable trays, existing trenches,
burried cables including the cost of providing identification
tags,route markers etc. complete as per specification and as per
site requirements.

3.1 27C x 2.5 sqmm shielded Multistrand CU armoured Control Mtrs 75 50.00 20.00 70.00 5,250.00
Cable.

3.2 12C x 2.5 Sqmm shielded Multistrand CU armoured Control Mtrs 75 380.00 20.00 400.00 30,000.00
Cable.

3.3 10C x 2.5 Sqmm shielded Multistrand CU armoured Control Mtrs 75 50.00 20.00 70.00 5,250.00
Cable.

3.4 4C x 2.5 sqmm shielded Multistrand CU armoured Control Cable. Mtrs 75 100.00 20.00 120.00 9,000.00

3.5 4C x 2.5 Sqmm Multistrand CU armoured Control Cable. Mtrs 75 100.00 20.00 120.00 9,000.00

3.6 3C x 2.5 Sqmm Multistrand CU armoured FR PVC insulated Mtrs 75 122.00 20.00 142.00 10,650.00
Control

3.7 3C x 1.5 sqmm shielded Multistrand CU armoured Control Cable. Mtrs 75 50.00 20.00 70.00 5,250.00

3.8 2C x 6 Sqmm Multistrand CU armoured Control Cable. Mtrs 75 70.00 20.00 90.00 6,750.00

3.9 3C x 6 Sqmm Multistrand CU armoured Control Cable. Mtrs 75 50.00 20.00 70.00 5,250.00

3.10 30 Low resistance / Amie braided cable for temp. scanner (30 Mtrs 75 50.00 20.00 70.00 5,250.00
Core)

Cable end termination of the following XLPE insulated PVC inner


sheathed and FRLS PVC outer sheathed aluminium /copper
4 conductor armoured cables of 1100 volt grade including
supplying and fixing of bimettalic crimping lugs, double
compression glands with earthing.

4.1 3.1/2 core 400 sq. mm. Aluminium Cable Nos. 0 1850.00 150.00 2,000.00 -

4.2 3.1/2 core 300 sq. mm.Aluminium Cable Nos. 16 800.00 50.00 850.00 13,600.00

4.3 3.1/2 core 240 sq. mm. Aluminium Cable Nos. 0 1150.00 150.00 1,300.00 -

4.4 4 core 10 sq. mm copper cable Nos. 0 500.00 50.00 550.00 -

4.5 4 core 6 sq. mm copper cable Nos. 0 500.00 50.00 550.00 -


RATE
SR.NO ITEM DESCRIPTION UNIT QUANTITY AMOUNT
SUPPLY INSTALLATION TOTAL
4.6 3 core 10 sq. mm Copper Cable Nos. 0 480.00 50.00 530.00 -

4.7 3 core 6 sq. mm copper cable Nos. 0 400.00 50.00 450.00 -

4.8 27C x 2.5 sqmm shielded Multistrand CU armoured Control Nos 8 50.00 20.00 70.00 560.00
Cable.

4.9 12C x 2.5 Sqmm shielded Multistrand CU armoured Control Nos 10 200.00 20.00 220.00 2,200.00
Cable.

4.10 10C x 2.5 Sqmm shielded Multistrand CU armoured Control Nos 8 50.00 20.00 70.00 560.00
Cable.

4.11 4C x 2.5 sqmm shielded Multistrand CU armoured Control Cable. Nos 8 200.00 20.00 220.00 1,760.00

4.12 4C x 2.5 Sqmm Multistrand CU armoured Control Cable. Nos 10 50.00 20.00 70.00 700.00

4.13 3C x 2.5 Sqmm Multistrand CU armoured FR PVC insulated Nos 10 200.00 20.00 220.00 2,200.00
Control

4.14 3C x 1.5 sqmm shielded Multistrand CU armoured Control Cable. Nos 8 50.00 20.00 70.00 560.00

4.15 2C x 6 Sqmm Multistrand CU armoured Control Cable. Nos 8 50.00 20.00 70.00 560.00

4.16 3C x 6 Sqmm Multistrand CU armoured Control Cable. Nos 8 50.00 20.00 70.00 560.00

4.17 30 Low resistance / Amie braided cable for temp. scanner (30 Nos 8 50.00 20.00 70.00 560.00
Core)

Supply and installation of following RCC (NP-2 class) Hume pipe


under paved areas, including providing 75 mm thick cement
5 concrete all around pipe 1:3:6 (1 cement, 3 coarse sand
and 6 crushed stone aggregate).

5.1 150 mm dia ID RM 0 2800.00 2000.00 4,800.00 -

5.2 200 mm dia ID RM 0 3200.00 2000.00 5,200.00 -

Providing and fixing of the following size medium class GI pipe


6 sleeves.

6.1 100 mm. dia. RM 0 2800.00 2000.00 4,800.00 -

6.2 150 mm. dia. RM 0 3500.00 2000.00 5,500.00 -

Supply and fixing of factory fabricated Hot dip galvanzied GI


ladder & perforated type cable trays, with radial bends,
7 suspenders and supports as per specification and of the
following sizes.

7.1 1000 mm wide ( Ladder cable tray) RM 0 3800.00 200.00 4,000.00 -


RATE
SR.NO ITEM DESCRIPTION UNIT QUANTITY AMOUNT
SUPPLY INSTALLATION TOTAL

7.2 750 mm wide ( Ladder cable tray) RM 110 1050.00 200.00 1,250.00 137,500.00

7.3 600 mm wide ( Ladder cable tray) RM 0 2100.00 200.00 2,300.00 -

7.4 300 mm wide ( Perforated cable tray) RM 110 250.00 25.00 275.00 30,250.00

7.5 150 mm wide ( Perforated cable tray) RM 50 200.00 50.00 250.00 12,500.00
TOTAL AMOUNT 598,220.00
ANNEXURE :
NON COMPREHENSIVE AMC CHARGES
Note : All Costs to be calculated considering running of 150 hours per DG per year @ 75 % Efficiency.

SR.NO. ITEM DESCRIPTION UNIT QUANTITY RATE AMOUNT


A Non Comprehensive AMC Charges

AMC Charges after 2 years warrantee period. AMC shall be non comprehensive. All
Consumables shall be in Client' scope. 1 visit per month shall be required. This is in
addition to emergency visits required on an "as and when" basis. No separate
amount shall be payable for carrying out A, B and C tests. Cost of Lube Oil
Replacement, Cost of Consumable shall be extra as as per actuals

A.1 1st Year (after Warrantee of 2 years ) Nos. 2 14,000.00 28,000.00


A.2 2nd Year Nos. 2 15,000.00 30,000.00
A.3 3rd Year Nos. 2 15,000.00 30,000.00
TOTAL AMOUNT 88,000.00
750 KVA DG SET AND AUXILIARY EQUIPMENT DATA SHEET
Project
Client
Package : DG Package
Date :

Sr. No. Description Employers Requirement


1 ENGINE
1.1 Rating 750 KVA Excluding Auxiliary LOAD
Minimum Engine Rating
Altitude (m) 11 Mtrs above mean sea level
Air humidity
Air Temperature (°C)
Minimum 28.3
Average 35
Maximum 45
Prime rating Duty at specified ambient
Duty air temperature of 40°C
Standard BS 5514 and ISO 3046
10% over the prime rating. In 12 hours
1.2 Overload Capacity for one hour of continuous running.
1.3 Governor Electronic Type
1.4 Starting
Method Electric
No. of auto starts 4
Selectivity Auto/Manual/Test
1.5 Cooling System
Heat Exchanger Yes
1.6 Exhaust System
1 no. or more as required residential
Silencer duty
1 no. for each exhaust pipe near the
Flexible Connection engine
Scrubber Nil
1.7 Safety Controls & Instruments
Over Speed Governor Trip @ 20% over normal
a. Audible & Visible Alarm
Two point Thermostat b. Trip Engine with trip indication
Lub Oil Temperature Audible & visible alarm
Low Oil Pressure Trip Engine
Fuel Level Low Audible & visible alarm
Oil pressure Guage Yes, required
Thermometers for Lub Oil Yes, required 2 nos.
Water Pressure Guage Yes
Hour Counter Yes, required
1.8 Sundry Fittings
Anti Vibration mounts Yes
1.9 Manufacturer
1.10 Model no.
1.11 Type of Engine
1.12 Engine rating – Prime (minimum) KWe
1.13 Engine Rating- Stanby (minimum) kWe
1.14 Operating Duty
1.15 Operating speed RPM
1.16 Over speed trip RPM
1.17 Design life Hours
1.18 No. of cylinders and arrangement nos
1.19 Cylinder bore x stroke mm x mm
1.20 Total piston displacement volume m3
1.21 No. of stroke per cycle
1.22 Compression ratio ratio
1.23 Enclosure IP54
1.23 Fuel oil System
a Fuel oil storage tank capacity Litre
b Fuel oil transfer pump
c a. Type and number
b. Capacity LPM
c. Head MLC
d. Drive motor power kW
Is the system complete with strainer, valves,
1.24
fittings, unloading hoses etc.
1.25 Engine Cooling
a Method of cooling provided Radiator Cooled
b Details of cooling system provided
c Heat Rejection to Cooling System kW
1.26 Exhaust System
a Silencer
b Piping construction detail
c Exhaust piping diameter mm
d Back pressure kPA
e Exhaust gas flow rate CFM
f Heat rejected to exhaust system kW
g Exhaust temperature (Max) Deg C
1.26 Radiators
a Entering coolant temperature Deg C
b Leaving coolant temperature Deg C
c Fan capacity & Static pressure CFM
d Make and Model
2 ALTERNATOR
2.1 Rating at 40 deg. C
Continuous Duty 750 KVA Excluding Auxiliary LOAD
Emergency Duty 10% over load for 1 hour in 12 hours
2.2 Minimum Efficiency 95%
2.3 Enclosure IP - 23(IEC) & IS 4691
2.4 Winding Class F
2.5 Cooling IC 01 IS - 6362
Brush less exciter with rotating diode
2.6 Excitation System assembly
2.7 Over Speed (%) 120

Max 20% dip on application of full load


2.8 Transient Response & Response Voltage Dip at stated P.F. and recovery in 20 cycles

2.9 Sustained short circuit Min. 300%


FLC for 3 sec.
2.10 Terminal Box Suitable for cable
2.11 Insulation (Rotor winding)
a a. Type of insulation
b b. Class of insulation
2.12 Automatic Voltage Regulator
a Make
b Type
c Voltage Regulator Range
d Degree of protection
2.13 Control & Relay Panel
a Make
b Type
c Dimension
3 FUEL OIL FACILITY

990 litres complete with over flow,


3.1 Day Tank (3mm MS) drain, filter and guage glass etc.

3.2 Piping From day tank to engine set


4 DIESEL GENERATOR SET
4.1 Auto Synchronization Yes
4.2 Auto Load Sharing Yes

Maximum Time Between blackout and power


4.3 15 TO 20 sec
restoration

I. DIESEL GENERATOR SET


(A) DIESEL ENGINE
1 Make
2 Model
3 Specification to which it conforms
4 Type and make
5 BHP rating
6 Method of starting
7 Type of cooling
8 Type of governor
9 Type of fuel
10 Type of lubricating oil
11 No. of stroke and cylinder
12 Fuel Consumption in Ltr/Hrs
12.a Fuel consumption in Ltr/ Hr. at full load (100%
Load)
12.b Fuel consumption in Ltr / Hr. at 75% Load
12.c Fuel consumption in Ltr / Hr. at 50% Load
12.1 KWH Units Generation/Ltr.
12.1a KWH Units/Ltr @ 100% load
12.1b KWH Units/Ltr @ 75% load
12.1c KWH Units/Ltr @ 50% load

13 Voltage regulation from no load to full load ±1%

Speed regulation from 0.8 PF to unity power


14 ±4%
factor
15
Qty of Replacement of lubricating oil (ltr)
16
Replacement of lubricating oil ( nos of hrs for
each replacement for each DG sets.)For 1st ,
2nd ,& 3rd time
17
Air Filter (nos of hrs for replacement for each
DG sets.)For 1st , 2nd ,& 3rd time
18
Fuel Filter (nos of hrs for replacement for each
DG sets.) For 1st , 2nd ,& 3rd time

(B) ALTERNATOR
1 Specification to which it conforms IS-4722/B55000
2 Type and make
3 Output in KVA (continuous) 750 KV
4 Power factor 0.8 PF lag
5 Class of insulation Class F
6 RPM 1500
7 Voltage grade 415
8 Temperature rise CLASS H
9 Degree of protection IP-23
APPROXIMATE WEIGHT OF DIESEL
(C) GENERATOR SET
DIMENSION (L x W x H) OF DIESEL
(D) GENERATOR SET
MENT DATA SHEET

Vendor Confirmation
BATTERY CHARGER DATA SHEET
Project
Client
Package : DG Package
Date :
SPECIFICATIONS
A. Battery Charger Parameters Client Requirement
1 Nominal Output Voltage (Volt) 24 Volt DC
2 Nominal Current (Amp) 30 Amp
3 Ouput Voltage Range (V)

4 Input Supply Single phase 240V ± 10% 50Hz ± 5%


5 Switch ON current soft start without inrush current
6 Transformer galvanically isolated
7 Input power factor (typical) [cos ϕ] ≥ 0.99 ( 0.97 with 25 % load)
8 Noise and Ripple <2% specified at full load and without battery connected.
Total harmonic distortion (at 100 %
9 load) [%]
≤3

Static Voltage Regulation


± 10% for 230 Volt AC input voltage variation and 5% AC input
10 frequency variation and ± 2% for 0-100% DC load variation
11 Dynamic Voltage 5% for load variation of 10% to 100% or 100% to 10%
12 Current Regulation ± 1%

Input Circuit Breaker, Charger Output Circuit Breaker, Charger Current


Protection Limit, Dual Battery Current Limit, AC Surge Suppression, Short Circuit
Protection, Reverse Battery Polarity Protection.
13

Mains Fail, Charger Fail, DC High, DC Low, Under/Over Voltage Trip,


Earth Fault, Low Elec-trolyte, Battery Disconnected, Battery Fail,
Alarms
Battery Over Temperature, Blown Fuse, Common Alarm Relay,
Common Alarm Buzzer *All alarms are user programmable*
14

Charger Voltage, Charger Current, Load Voltage, Load Current, Battery


1 Charge/Discharge Current, Battery 2 Charge/Discharge Current,
Metering
Battery Temperature, Battery Initial Impedance Battery Capacity,
Battery Capacity Ratio,*Meter accuracy 1%*
15
Potenantial Free Contacts
Voltage - free contacts for all alarms, Battery test facility, 3 Stage
16 diode voltage limiter, DC distribution board
17 Serial Communication protocol RS485, Modbus
18 Start up time [sec] 30
19 Efficiency [%] 95% depending on nominal voltage and power rating
19.1 100 % load

19.2 50 % load

20 Temperature Compensation Programmable 3 - 6 mV / Cell / °C


21 Audible Noise < 55 dB
22 Limp Home Feature Continuous operation in the event of control failure
23 Revert to Factory Settings Reinstates all original factory settings
Float voltage with automatic charging
24 and [V/cell]
2.23 – 2.3
Boost voltage with automatic charging
24.1 and [V/cell]
2.3 – 2.4

Voltage tolerance (without batteries)


24.2
24.2a static [%] ±1
24.2b dynamic 0 % to 100 % ± 10
24.2c dynamic 100 % to 0 % ± 10
25 Current tolerance [% ± 1, rectifier is short circuit proof
26 Heat dissipation in [kW]

26.1 100 % load (float charging)

26.2 10 % load (float charging)

27 General Specifications

27.1 Required air flow volume [m3/h]

27.2 Ambient temperature [°C] 0 – 45, daily average ≤ 35


27.3 Rel. Humidity [%] 30– 95 without condensing
27.4 Installation height [m] upto1000 above sea level without derating
27.5 Power derating over 1000 m [%] app. 4.5 per 500 m
27.6 Power derating over 40 °C app. 11 per 5 °C

Enclosure design
Free standing enclosure with 2mm thick CRCA sheet confirming IP 42
27.8 protection
27.9 Paint finish Siemens Grey /RAL 7032, powder coat finish
Dimensions (width x depth x height)
27.1 [mm]
27.11 Weight [kg]

27.12 Cable entry Top or Bottom As per site requirement


Recommended number of lead acid
27.13 cells
27.14 Battery Charger Warranty in years
(Yr)
27.15 Standards AS 1955, AS 3000, AS 3100 AS 4044, AS 2069
Charging characteristic float / boost /
27.16 equalize
IU in acc. DIN 41773
Vendor Confirmation
BATTERY DATA SHEET
Project
Client
Package : DG Package
Date :

A.
Battery Charger Parameters Client Requirement

1 Make As per approved list


2 Model To be given by bidder
3 AH Capacity ( 15% ageing As per recommendation of battery
factor) manufacturer.
4 Type of Battery
5 Cell voltage
6 Number of Cells
7 PF considered for battery
calculation
8 Battery Voltage
9 Lead content in battery
10 Overall dimensions of battery
rack / Stand in (mm)
11 Battery Life in Hours (Hrs)
12 Battery Warranty in years (Yr)
T

Vendor Confirmation