Restricted Earth Fault Protection shall


(a) be single pole type
(b) be of current/voltage operated high impedance type
(c) have a current setting range of 10-40% of 1 Amp./ have a suitable
voltage setting range
(d) be tuned to the system frequency
21.4. Back-up Over Current and Earth fault protection scheme with high
set feature
(a) Shall have three over current and one earth fault element(s)
which shall be either independent or composite unit(s).
(b) The scheme shall include necessary VT fuse failure relays for
alarm purposes
(c) Over current relay shall
 have directional IDMT characteristic with a definite
minimum time of 3.0 seconds at 10 times setting and have
a variable setting range of 50-200% of rated current
 have low transient, over reach high set instantaneous unit
of continuously variable setting range 500-2000 % of rated
current
 have a characteristic angle of 30/45 degree lead
 include hand reset flag indicators or LEDs.
(d) Earth fault relay shall
 have directional IDMT characteristic with a definite
minimum time of 3.0 seconds at 10 times setting and have
a variable setting range of 20-80% of rated current
 have low transient, over reach high set instantaneous unit
of continuously variable setting range 200-800 % of rated
current
 have a characteristic angle of 45/60 degree lag
 include hand reset flag indicators or LEDs
 include necessary separate interposing voltage
transformers or have internal feature in the relay for open
delta voltage to the relay
21.5. Transformer Overload Protection Relay shall
(a) be of single pole type
(b) be of definite time over-current type
(c) have one set of over-current relay element, with continuously
adjustable setting range of 50-200% of rated current
(d) have one adjustable time delay relay for alarm having setting
range of 1 to 10.0 seconds, continuously.
Tech Specification, Section: CRP Page 23 of 40
C/ENGG/SPEC/CRP REV NO: 08