Sie sind auf Seite 1von 47

Wärtsilä Finland Oy Power Plants

Doc no: i
Date: 9-Nov-2006
Page: 1 (47)
Status: APPROVED
Made/Approved: JVA033 / MRI005
Project: PlanVision, WNS-P Design Systems, IN028
Name: Coding of processes
Subject: Coding of processes in Power Plants

CONTENTS

Structure of the code 3


Power transmission system (AEP) 6
Station service system (AES) 8
System grounding (AEG) 10
Instrumentation system (ACI) 11
Process control system (ACP) 12
Operators interface (ACO) 13
Auxiliary Configurations (AAM) 14
Fuel system (AAF) 15
Oily water and Sludge system (AAS) 19
Lube oil system (AAL) 20
Compressed air system (AAC) 22
Cooling system (AAW) 23
Water and Fire water supply system (AAD) 25
Exhaust gas (EG) system (AAE) 28
Component temp control system (AAN) 29
Steam generation system (AHS) 30
Hot water generation system (AHW) 32
Cold water generation system (AHC) 33
Hot air generation system (AHA) 33
Desalination system (AHD) 33
Thermal fluid system (AHT) 34
Selective Catalytic Reduction system (APS) 35
Water injection system (APW) 36
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 2 (47)

Oxidation catalyst system (APO) 37


SO2 removal system (APD) 38
Electrostatic precipitator (APP) 40
Continuous emission monitoring system (APM) 41
Engine driven equipment (ADM) 42
Engine related equipment (ADR) 43
Engine system (ADE) 44
Platforms (ADP) 46
Generating set fastening system (ADF) 47

APPENDIX

Block Diagrams:
Fuel system VPDOC000073
Lube oil system VPDOC000074
Compressed air system VPDOC000075
Cooling system VPDOC000076
Water supply system WDAAA095833
CA & EG systems VPDOC000077
Steam generation system VPDOC000078
Oily water and Sludge system WDAAA037086
SO2 removal system, wet NaOH FGD WDAAA039703
SO2 removal system, wet CaCO3 FGD WDAAA298155
SO2 removal system, dry CaO FGD WDAAA039704
SCR system WDAAA039705
Electrostatic precipitator WDAAA281469
Continuous emission monitoring syst. WDAAA282086
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 3 (47)

Structure of the code


To identify the functionality of units and components in the process and electrical systems, they must be assigned unique codes
consisting of specified letters (L, P) and numbers (N). Each code is divided into four groups.

System code System number Component code Part code

Serial group number 1 2 3 4

Type of character L1 L2 L3 N1 N2 N3 L4 N4 N5 N6 L5 N7 N8

System main group

System code

System code

System number

System number

System number

Component code

Component number

Component number

Component number

Part code

Part number

Part number
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 4 (47)

System codes (1)

System code

1 2 3 4
Serial group number

Type of character L1 L2 L3

System Code (L1-L3) This is the system code as specified in the rest of this document.

System numbers (2)


System number

Serial group number 1 2 3 4

Type of character N1 N2 N3

For processes that are shared by two or more engines:

N1 is 9 (nine).
N2-N3 is consecutive for each unit in the system, starting from 01 (zero-one).
00 (zero-zero) is reserved for piping / cabling.

For enginevise processes:

N1-N2 is consecutive for each engine, starting from 01 (zero-one) for Engine #1.
N3 is consecutive for each unit in the system, starting from 1 (one).
0 (zero) is reserved for piping / cabling.

Examples:
2 Engines 11 Engines 24 Engines

The LT/HT Expansion tank in a project: 011-021 011-111 011-241

The first charge air filters in a project: 011-021 011-111 011-241


The second charge air filters in a project: 012-022 012-112 012-242
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 5 (47)

Component-, Part Coding and Numbering (3,4)


Component code Part code

Serial group number 1 2 3 4

Type of character L4 N4 N5 N6 L5 N7 N8

Component code

L4 Components are grouped for easier identification (L4). The coding follows standard IEC 750 for electric devices,
denoted by [...]. The group codes are:

A [Assemblies, sub-assemblies]
B Tanks, filters, heaters, beams + flexible hose and hose reel [transducers]
C [Capacitors]
D Machines (pumps, compressors, etc.), [binary elements] delay devices, storage devices
E Control panels, [miscellaneous] analogue and binary elements.
F [Protective devices]
G [Generators] Power supplies
H [Signalling devices]
J Plates
K [Relays, contactors]
L Level & limit control / measuring equipment, [inductors] reactors
M [Motors]
N [Analogue microcircuitry]
P Pressure control / measuring equipment, [measuring equipment] testing equipment
Q Flow control / measuring equipment, [switches for power circuits]
R [Resistors]
S [Switches for control circuits, selectors]
T Temperature control/measuring equipment, [transformers]
U [Modulators, converters]
V Valves, [tubes, semiconductors]
W [Transmission paths, wave guides, aerials]
X Vibration control / measuring equipment, [Terminals, plugs, sockets]
Y Electrically operated mechanical devices (e.g. Brakes, clutches, pneumatic valves)
Z Pipelines, [terminations, filters, limiters] hybrid transformers, equalisers.

Component number

N4-N6 These numbers form unique codes for components in the same group. The numbering is consecutive, starting
from 001 (zero-zero-one) for each component.

Part code

L5 Components can be split into parts (L5) when more detailed identification is required.
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 6 (47)

E Elbows
F Flanges
G Gaskets
H Screws
I Insulation
N Nuts
O Rivets
R Reducers
S Supports
T Tees
U Fittings
W Washers
Z Others

Part number

N7-N8 These numbers form unique codes for parts in the same group. The numbering is consecutive, starting from 01
(zero-one) for each part.

Power transmission system (AEP)


Grid connection system (AEPG)
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 7 (47)

AEA Grid transformer switchyard bay

AEM Grid measuring bay

AET Grid power transformer

AEB Grid switchyard outgoing feeder bay

AEE Grid control / protection panels

AEP Grid PLCC system (Power Line Carrier Control)

UAA Grid steel structures

Station main switchgear (AEPM)

BAA Auxiliary cubicle

BAB Tiebreaker cubicle

BAE Genset cubicle

BAM Measuring cubicle

BAO Outgoing cubicle

BAU Grounding cubicle

BAF Block transformer


Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 8 (47)

Station service system (AES)


Low voltage system (AESL)

BFA Load control centre

BFB Auxiliary transformers

BJA Genset control panels

BJB Fuel unit control panels

BJC LFO unloading control panels

BJD HFO unloading control panels

BJE LFO transfer pump control panels

BJF HFO transfer pump control panels

BJG HFO tank control panels

BJH HFO trace heating control panels

BJI Return fuel control panels

BJJ Fuel oil separator unit control panels

BJK Feeder Booster control panels

BJL Feeder unit control panels

BJM Booster unit control panels

BJN Lube oil separator control panels

BJO Lube oil auto filter control panels

BJP Lube oil transfer pump control panels

BJQ Sludge transfer pump control panels

BJR Sludge treatment control panels

BJS Sludge incinerator control panels

BJT Gas compressor control panels

BJU Oily water transfer pump control panels

BJV Sludge loading control panels

BLA Starting air control panels

BLB Control & Working air control panel


Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 9 (47)

BLC Maintenance and water pump control panels

BLD Water treatment control panels

BLE Fire fighting control panels

BLF Heat recovery system control panels

BLG DeSOx system control panels

BLH DeNOx system control panels

BLI Building electrification control panels

BLJ Nozzle temperature control panels

BLK Overhead crane control panels

BLL Workshop control panels

BLM Blackstart control panels

BLN Fire detection control panels

BLO Exhaust gas control panels

BLP Cooling control panels

BLQ Building ventilation control panels

BLR Junction boxes for Gas regulating unit

CJU Emergency stop control panels

DC/UPS power supply system (AESD)

BEY DC unit

BEU UPS unit


Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 10 (47)

System grounding (AEG)

Resistor grounding system (AEGR)


BAN Grounding resistor cubicle

Transformer grounding system (AEGT)


BAZ Grounding transformer
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 11 (47)

Instrumentation system (ACI)

Generating set instrumentation system (ACIE)

Field instrumentation system (ACIF)


Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 12 (47)

Process control system (ACP)


Generating set primary control (ACPG)
CFE Local genset control panel

Generating supervision system (ACPE)

CFC Central control panel, genset section

CJU Emergency stop system

Plant supervision system (ACPP)


CFA Central control panel, common section
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 13 (47)

Operators interface (ACO)

Operators station (ACOO)


CWA Operator’s Station

CWB Remote operator station

Management system (ACOM)


CWF Report station

CWG Maintenance and service station


Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 14 (47)

Auxiliary Configurations (AAM)


MOD Piping configurations
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 15 (47)

Fuel system (AAF)


PFC Fuel system configurations

Heavy fuel oil system (AAFH)


PAA HFO Unloading system
-From truck / barge HFO outlet
-To HFO storage tank inlet

PAB HFO Storage system


-From HFO storage tank inlet
-To HFO storage tank outlet

PAC HFO Transfer system


-From HFO storage tank outlet
-To HFO buffer tank and HFO storage tank (return) inlets

PBA HFO Buffer system, uncleaned


-From HFO buffer tank inlet
-To HFO separator inlet

PBB HFO Separation system


-From HFO separator inlet
-To HFO day tank and HFO buffer tank (return) inlets

PBC HFO Buffer system, cleaned


-From HFO day tank inlet
-To feeder / booster and HFO buffer tank (overflow) inlets

PCA Feeder Booster system


-From booster inlet
-To booster (return) and HFO day tank (return) inlets

PCC Engine supply system


-From booster system outlet
-To booster system (return) inlet

PDA Clean leak fuel collection system


-From engine (clean leak) and automatic filter (flush) outlets
-To return fuel (clean) unit outlet

PDC Clean leak fuel transfer system


-From return fuel (clean) unit outlet
-To HFO buffer tank inlet
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 16 (47)

Light fuel oil system (AAFL)


PAD LFO Unloading system
-From truck / barge LFO outlet
-To LFO storage tank inlet

PAE LFO Storage system


-From LFO storage tank inlet
-To LFO storage tank outlet

PAF LFO Transfer system


-From LFO storage tank outlet
-To LFO buffer tank inlet

PBD LFO Buffer system, uncleaned


-From LFO buffer tank inlet
-To LFO separator inlet

PBE LFO Separation system


-From LFO separator inlet
-To LFO day tank and LFO buffer tank (return) inlets

PBF LFO Buffer system, cleaned


-From LFO day tank inlet
-To booster / pump and filter unit / engine inlet

PCC LFO Engine supply system


-From pump and filter unit inlet
-To LFO day tank (return) inlet

PDA Clean leak fuel collection system


-From engine (clean leak) and automatic filter (flush) outlets
-To return fuel (clean) unit outlet

PDC Clean leak fuel transfer system


-From return fuel (clean) unit outlet
-To LFO buffer tank inlet
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 17 (47)

Gas system (AAFG)


ZAA Gas delivery system (Including gas safety unit)
-From gas truck / barge / pipeline outlet
-To gas compressor / conditioning / regulating unit / pressure reduction unit inlet

ZAB Gas conditioning system


-From gas conditioning unit inlet
-To gas regulating / valve unit inlet

ZAC Gas regulating system


-From gas regulating / valve unit / pressure reduction unit inlet
-To engine gas inlet

ZBA Gas compression system


-From gas compressor inlet
-To gas compressor outlet / gas regulating unit inlet

ZCA High pressure gas system


-From gas compressor outlet
-To engine gas inlet

ZCD Gas compressor cooling


-From gas compressor cooling outlet
-To gas compressor cooling inlet

ZCQ Compressor lubrication system


-From lube oil tank
-To lube oil consumers

ZEA High pressure venting system


-From gas compressor
-To atmosphere / burner

ZEB Venting system


-From low pressure gas systems
-To atmosphere / burner

ZFA Inert gas system


-From inert gas supply / reactor inlet
-To distribution inlet

LPG system (Liquid Pressurised Gas) (AAFP)


ZLA Feeder system
-From LPG truck / barge / pipeline outlet
-To LPG pump unit inlet

ZLB Compression system


-From LPG pump unit inlet
-To distribution system inlet

ZLC Distribution system


-From distribution system inlet
-To engine LPG inlet
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 18 (47)

ZLD Venting system


-From engine / unit venting outlet
-To atmosphere / burner

ZLE Inert gas system


-From inert gas supply / reactor inlet
-To distribution inlet

Orimulsion system (AAFO)


POB Orimulsion storage system
-From Orimulsion storage tank inlet
-To Orimulsion storage tank outlet

POC Orimulsion transfer system


-From Orimulsion storage tank outlet
-To Orimulsion buffer tank inlet and Orimulsion storage tank (return) inlet

PPA Orimulsion buffer system, uncleaned


-From Orimulsion buffer tank inlet
-To separator inlet
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 19 (47)

Oily water and Sludge system (AAS)


DAA Oily water collection system
-From drain pits inside / outside of power house
-To oily water sump

DAB Oily water buffer tank


-From inlet of buffer tank
-To outlet of buffer tank

DAC Dirty leak fuel collection system


-From engine
-To LO separator

DAD Oily water transfer system


-From oily water sump or buffer tank
-To buffer tank / oily water settling tank / oily water treatment unit inlet

DBA Oily water settling tank (in big plants the concept is integrated in DBB)
-From oily water settling tank inlet
-To oily water treatment unit inlet

DBB Oily water treatment unit


-From oily water treatment unit inlet
-To sludge storage tank inlet

DBC Separated water system


-From oily water treatment unit outlet
-To sewage

DDA Sludge collection system


-From workshop
-To sludge storage tank inlet

DDB Sludge storage system


-From sludge storage tank inlet
-To sludge storage tank outlet

DDC Sludge transfer system


-From oily water settling tank outlet
-To sludge storage tank inlet

DDD Sludge loading system


-From sludge and solids tanks outlet
-To sludge truck / barge / incinerator inlet / separator

DDE Sludge Incinerator system


-From sludge incinerator inlet
-To sludge incinerator outlet

DDF Sludge separator system


-From sludge separator inlet
-To concentrated sludge and solids tank
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 20 (47)

Lube oil system (AAL)


QLC Lube oil system configurations

Clean lube oil system (AALN)


QAA Lube oil unloading system
-From truck / barge lube oil outlet
-To clean lube oil storage tank inlet

QAC Lube oil storage system


-From clean lube oil storage tank inlet
-To clean lube oil storage tank outlet

QAE Lube oil transfer system


-From clean lube oil storage tank outlet
-To engine lube oil sump / system tank inlet

Used lube oil system (AALU)


QAB Used lube oil loading system
-From used lube oil storage tank outlet
-To truck / barge inlet

QAD Used lube oil storage system


-From used lube oil storage tank inlet
-To used lube oil storage tank outlet

QAF Used lube oil transfer system


-From engine lube oil sump / system tank outlet
-To used lube oil storage tank inlet

Lube oil maintenance system (AALO)


QAM Lube oil maintenance system
-From engine lube oil sump outlet
-To engine lube oil sump inlet

Main lubricating oil system (AALM)


QBB Lube oil separation system
-From engine lube oil sump / system tank outlet
-To engine lube oil sump / system tank inlet

QBF Engine crankcase venting system


-From engine / system tank venting outlet
-To atmosphere

QEA Main circulation system


-From engine lube oil outlet
-To engine lube oil inlet
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 21 (47)

QEE Gravity lubrication system


-From lube oil main circulation system connection
-To lube oil main circulation system connection

QEP Pre lube oil system


-From engine / system tank outlet
-To lube oil main circulation system inlet

QFA Generator bearing lubrication


-From main circulation system connection
-To engine lube oil sump / system tank inlet

QFB Pump and gearbox lubrication system


-From pump and gearbox lube oil outlet
-To pump and gearbox lube oil inlet

Sealing oil system (AALS)


QZH High pressure sealing oil
-From HP sealing oil unit inlet
-To HP sealing oil unit return inlet

QZL Low pressure sealing oil


-From LP sealing oil unit inlet
-To LP sealing oil unit return inlet
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 22 (47)

Compressed air system (AAC)


TAC Compressed air system configurations

Instrumentation air system (AACC)


TCA Control air compression system
-From control air compressor inlet
-To control & instrumentation air bottle inlet

TCB Control air storage system


-From control air bottle inlet
-To air treatment system inlet

TCC Control air treatment system


-From air treatment system inlet
-To engine / auxiliaries control & instrumentation air inlet

Starting air system (AACS)


TSA Starting air compression system
-From starting air compressor inlet
-To starting air bottle inlet

TSB Starting air storage system


-From starting air bottle inlet
-To engine starting air inlet

Working air system (AACW)


TWA Working air compression system
-From working air compressor inlet
-To working air bottle inlet

TWB Working air storage system


-From working air bottle inlet
-To working air distribution system outlets
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 23 (47)

Cooling system (AAW)


HT cooling water system (AAWH)
VCA Central cooler / radiator system
-From cooler / radiator inlet
-To cooler / radiator outlet

VCH HT circulation system


-From engine HT water outlet
-To engine HT water inlet, when separate HT cooler

VDA HT water preheating system


-From HT water system preheating outlet connection
-To HT water system preheating inlet connection

VEA HT / LT expansion system


-From HT water system expansion outlet connection
-To HT water system expansion inlet connection

LT cooling water system (AAWL)


VCL LT circulation system
-From engine LT water outlet
-To engine LT water inlet, when separate LT cooler

VCP LT water preheating system


-From LT water system preheating outlet connection
-To LT water system preheating inlet connection

VEA HT / LT expansion system


-From LT water system expansion outlet connection
-To LT water system expansion inlet connection

VCG Generator cooling system


-From LT water system outlet connection
-To LT water system inlet connection

Raw water (RW) system (AAWR)


VGA RW transfer system
-From RW transfer unit inlet
-To RW cooling system inlet

VGB RW cooling system


-From RW circulation pump inlet
-To cooling tower outlet (complete circuit)

VGC RW treatment system


- From chemical dosing unit inlet
- To cooling tower circuit
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 24 (47)

Sea water (SW) system (AAWS)


VHA SW circulation system
-From sea chest inlet
-To seawater discharge outlet

VHB SW treatment system


- From treatment unit inlet
- To treatment unit outlet

Engine cell cooling system (AAWC)


VCI Internal system
-From internal system inlet
-To internal system outlet

VCE External system


- From external system inlet
- To external system outlet
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 25 (47)

Water and Fire water supply system (AAD)


Fresh water system (AADT)
VAA FW distribution system
-From water booster unit outlet
-To maintenance water tank / consumer inlet

VBA FW maintenance system


-From maintenance water tank inlet
-To HT / LT water circuit connections

VBB FW treatment system


-From treatment / distillation unit inlet
-To water storage tank inlet

VBC FW storage system


-From water storage tank inlet
-To water storage tank outlet

VBD FW booster system


-From water storage tank outlet
-To water booster unit outlet

VBE FW supply system


-From FW source
-To treatment unit inlet

Fire fighting system (AADF)


VFA Fire fighting water supply system
-From water source
-To fire water tank inlet

VFB Fire fighting storage system


-From fire water tank inlet
-To fire water tank outlet

VFC Fire fighting pumping system


-From fire water tank outlet
-To fire water pump outlet

VFD Fire fighting distribution system (fire main)


-From fire water pump outlet
-To hydrant outlets

VFE Fire fighting sprinkler and water spray systems (“Extended system”)
-From fire main outlet
-To nozzle outlets

VFF Fixed foam systems for fire fighting


-From foam concentrate filling
-To foam nozzle outlet

VFG Gaseous fire fighting systems (CO2, Inergen, FM200, Argon, etc.)
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 26 (47)

-From gas storage/bottles


-To nozzle outlet

VFH Fire fighting water hydrant systems inside Power House (“standpipe” system)
-From fire main outlet
-To hydrant valve outlet

VFI Inert gas blanketing systems for tanks


-From gas storage bottles
-To tank ventilation system outlet
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 27 (47)

Intake air system (AAA)


Charge air (CA) system (AAAC)
NGA Charge air filtering system
-From air filter inlet/atmosphere
-To charger air silencer inlet

NGB Charge air noise reduction system


-From charge air silencer inlet
-To turbocharger inlet

NGC Charge air condense system


-From engine condense outlet
-To drain

NGD Charge air filter oil system


-From charge air filter outlet (oil)
-To charge air filter inlet (oil)

NGE Air preheating system


-From atmosphere
-To charge air filter inlet
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 28 (47)

Exhaust gas (EG) system (AAE)


Engine exhaust gas system (AAEN)

NHA Noise reduction system


-From turbocharger outlet
-To atmosphere

Turbocharger cleaning system (AAEC)

NHC Turbine cleaning system


-From dosing unit inlet
-To turbocharger cleaning connection
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 29 (47)

Component temp control system (AAN)


XAA Nozzle temp control system
-From engine nozzle temp. control oil outlet
-To engine nozzle temp. control oil inlet

XBA Valve seat cooling system


-From cooling water system inlet
-To cooling water system outlet
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 30 (47)

Steam generation system (AHS)


RHC Steam system configurations

Make-up water system (AHSM)


RAA Make-up water treatment
-From station service water system outlet
-To feed water tank inlet

Feed water system (AHSF)


RBA Feed water storage system
-From feed water tank inlet
-To feed water tank outlet

RBB Feed water transfer system


-From feed water treatment unit outlet
-To steam drum feed water inlet

RBC Feed water treatment system


-From feed water tank inlet
-To feed water treatment unit outlet

Steam production system (AHSB)


RCA Steam drum system
-From steam drum inlet
-To steam drum outlet

RCB Steam blow-down system


-From steam drum / boiler pressure relief valve (blow-down) outlet
-To drainage system

RCC Steam boiler system


-From steam drum outlet
-To steam drum inlet

RCE Auxiliary boiler system


-From feed water pump outlet
-To steam header inlet

RCT Steam turbine system


-From steam turbine inlet
-To steam turbine outlet
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 31 (47)

Steam distribution system (AHSD)


RDA Steam header system
-From steam drum or superheater outlet
-To steam consumers and application outlets

RDB Condenser system


-From steam drum outlet
-To feed water tank inlet

RDD Condense return system


-From steam consumers and application outlets
-To feed water tank inlet
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 32 (47)

Hot water generation system (AHW)


Hot water production system (AHWB)
RWA Exhaust gas economiser system
-From EG economiser / furnace inlets
-To EG economiser / furnace outlets

Hot water distribution system (AHWH)


RWH Hot water header system
-From economiser / furnace / heat exchanger outlets
-To consumer and application inlets

RWR Hot water return system


-From consumer and application outlets
-To economiser / furnace / heat exchanger inlets

Hot water pressure system (AHWP)


RWP Water pressure regulation system
-From expansion tank inlet
-To hot water circuit connection
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 33 (47)

Cold water generation system (AHC)


Cold water production system (AHCB)
RKA Energy production system
-From heat source (HT water or steam)
-To chiller (complete circuit)

RKB Absorption chiller system


-From chiller inlets
-To chiller outlets

RKC Chiller cooling system


-From chiller outlets
-To coolers (complete circuit)

RKD Cold water distribution system


-From chiller outlet
-To consumers (complete circuit)

Hot air generation system (AHA)

Desalination system (AHD)


Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 34 (47)

Thermal fluid system (AHT)


Thermal fluid distribution system (AHTF)
ROH Oil header system
-From oil heater outlet(s)
-To consumer and application inlets

ROR Oil return system


-From consumer and application outlets
-To oil heater inlet(s)

Glycol system (AHTG)


GAA Glycol heating system

GBA Glycol unloading system


-From truck glycol outlet
-To glycol storage tank inlet

GBB Glycol storage system


-From glycol storage tank inlet
-To storage tank outlet

GBC Glycol transfer system


-From glycol storage tank outlet
-To maintenance water tank inlet
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 35 (47)

Selective Catalytic Reduction system (APS)


Reagent system (APSA)
YAA Reagent unloading system
-From reagent truck / barge outlet
-To reagent storage tank / silo inlet

YAB Reagent storage system


-From reagent storage tank inlet
-To reagent storage tank outlet

YAC Reagent feeding unit


-From reagent storage tank outlet
-To reagent dosing unit inlet and reagent storage tank (return) inlet

YAD Urea mixing system


-From reagent storage house / silo outlet
-To reagent storage tank inlet

YAE Urea silo


-From silo inlet
-To silo outlet

YCA Reagent dosing unit


-From reagent injection system inlet
-To reagent injector connection in exhaust gas system

YDB Measuring and control system


-From reactor measurement connection
-To all systems and units

Reactor system (APSR)


YBA Reactor with catalytic element
-From reactor inlet
-To reactor outlet

YBB SCR compressed air system


-From sootblower inlet
-To reactor and injection system connections
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 36 (47)

Water injection system (APW)

YWL Low pressure system

YWH High pressure system

YWC Control system

YWI Injection system


Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 37 (47)

Oxidation catalyst system (APO)


CO oxidation system (APOC)
YOC CO oxidation catalyst
-From catalyst inlet
-To catalyst outlet

HC oxidation system (APOT)


YOT THC oxidation catalyst
-From catalyst inlet
-To catalyst outlet

YON VOC oxidation catalyst


-From catalyst inlet
-To catalyst outlet
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 38 (47)

SO2 removal system (APD)


Wet system (APDW)
YSA Absorber
- From absorber inlet
- To absorber outlet or stack outlet (including recycle pumps)

YSB Reagent unloading/storage system


- From truck
- To outlet of storage tank/silo

YSC Reagent feeding system


- From outlet of tank/silo or reagent preparation system
- To inlet of absorber

YSD End-product treatment system


- From absorber
- To outlet of end-product treatment system

YSE End-product storage


- From absorber or end-product treatment system
- To outlet of storage

YSG Oxidation air compressor


- From compressor inlet
- To absorber / end-product treatment system

YSH Waste water treatment system


- From end-product treatment system, outlet
- To sewage system

YSI Water system


- From water inlet / end-product treatment system
- To point of consumption

YSK Reagent preparation system


- From outlet of tank/silo
- To outlet of preparation system

YSL Maintenance and drain system


- From absorber / tank / floor drains
- To absorber

Dry / Semidry system (APDD)


YSP Reactor with bag filter
- From inlet of reactor
- To outlet of bag filter

YSQ CaO unloading and storage system


- From truck
- To outlet of storage tank/silo

YSR CaO feeder system


Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 39 (47)

- From outlet of tank/silo


- To inlet of reactor or slaker

YSS Slaker (if separate otherwise included in YSR)


- From inlet of slaker
- To inlet of reactor

YST Dry end-product storage


- From reactor
- To outlet of storage

YSU End-product conditioning


- From end-product storage
- To outlet of conditioning system

YSV Local fluidisation air fan


- From inlet of fan
- To reactor

Common desulphurisation system (APDC)


YSF Exhaust gas fans
- From inlet
- To outlet

YSM Measuring and control system


Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 40 (47)

Electrostatic precipitator (APP)


YOQ ESP reactor
- From inlet
- To outlet

YOR Fly ash transport and storage system


- From reactor
- To storage system outlet

YOS Fly ash conditioning system


- From storage system outlet
- To conditioning system outlet
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 41 (47)

Continuous emission monitoring system (APM)


YMA Sample gas transport system (extractive system)
-From probe inlet
-To sample gas selection or conditioning unit

YMB Sample gas conditioning unit (including NO2 converter if installed)


-From inlet of conditioning unit
-To analyser or sample gas selection unit

YMC Sample gas selection unit


-From inlet of selection unit
-To conditioning unit or analyser

YMD Analyser
-From analyser inlet
-To sample gas outlet

YME Calibration gas line


-From calibration gas bottle(s)
-To analyser

YMG Compressed / ambient air delivery


Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 42 (47)

Engine driven equipment (ADM)


Electrical power production systems (ADME)
BAG Generator system

Mechanical power production system (ADMM)


SAC Compressor system

SAP Pump system


Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 43 (47)

Engine related equipment (ADR)


SAB Black start unit

SAE Coupling system

SAF Flywheel system

SAG Flexible connections

SAH Turbo charger system

SAK Gearbox

SAO Overhead cranes (civil)

SAS Seal flush system


Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 44 (47)

Engine system (ADE)


Engine equipment (ADEX)
SCA Engine related instrumentation

SEA Engine related electrical equipment

SOA Engine built-on turning gear system

SOB Governor system for engine

SOC Engine built-on temperature sensors

SOI Engine fastening

SOS Engine speed measurement system

SCX WECS control system

Engine exhaust gas system (ADEE)


SNA Engine internal exhaust gas system
-From cylinder outlet
-To turbocharger outlet

Engine charge air system (ADEA)


SNB Engine internal charge air system
-From turbocharger inlet
-To cylinder inlet

Engine fuel oil system (ADEF)


SPA Engine internal fuel oil system
-From engine fuel oil inlet
-To engine fuel oil outlet

Engine lube oil system (ADEL)


SQA Engine internal main lube oil system
-From engine lube oil inlet
-To engine lube oil outlet

Engine sealing oil system (ADEO)


SQC Built-on sealing oil system
-From engine sealing oil inlet
-To engine sealing oil outlet
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 45 (47)

Engine compressed air system (ADES)


STA Engine internal starting air system
-From engine starting air inlet
-To cylinder head connection

STB Engine internal control air system


-From engine control air inlet
-To engine control system devices

Engine cooling system (ADEW)


SVH Engine internal HT system
-From engine HT-water inlet
-To engine HT-water outlet

SVL Engine internal LT system


-From engine LT-water inlet
-To engine LT-water outlet

Engine nozzle temperature control system (ADEN)


SXA Engine internal nozzle temp. control equipment
-From engine nozzle temperature control oil inlet
-To engine nozzle temperature control oil outlet

Engine gas system (ADEG)


SZA Engine internal gas system
-From engine gas inlet
-To engine gas outlet

SZB Built-on LPG system


-From engine gas inlet
-To engine gas outlet
Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 46 (47)

Platforms (ADP)
Maintenance platforms (ADPM)
SME Maintenance platforms for engine

SMT Maintenance platforms for turbocharger


Wärtsilä Finland Oy Power Plants

Doc no: 4V75L0112 i


Date: 9-Nov-2006
Page: 47 (47)

Generating set fastening system (ADF)


Flexible fastening system (ADFF)
SOD Base frame

SOE Elastic mounting

SOF Fixing rail system

SOG Steel spring system

SOH Air spring bellow system

Das könnte Ihnen auch gefallen