TITLE : DATA SHEET FOR HYDRAULIC ON-OFF VALVE

S.No DESCRIPTION
1 Tag No.
2 Line No.
3 Quantity
4 Line Size(ID & OD) & Line Sch.
General
5 Line Material
6 Location
7 Fluid
8 P & ID
Units
9 Flow Rate MMSCFD
10 Design Pressure PSIG
11 Operating Temperature 0
F
12 Shut Off Pressure PSIG
PROCESS 13 Density Kg/m3 & Mol. Wt.
CONDITIONS
14 Viscosity cP
15 Pressure drop (∆p) PSIG
16 Vapour Pressure Pv PSIG
17 Critical Pressure Pc PSIG
18 Max. Allowable Sound Level(dBA) dB
Pipe Line Matl./Size In ASTM A106Gr C
19
LINE Out ASTM A106Gr C
20 Line Insulation / Thickness NA
Valve Body
21 Type Ball
22 Valve Size / Port Size 8"
23 Body Material ASTM A216 WCB
24 End Connection Flanged
25 Flange Face Finish ASME B16.5,8 INCH / 250
VALVE BODY /
BONNET / Bonnet
WETTED PARTS
26 Type of Bonnet *
WETTED PARTS

27 Bonnet Material *
Wetted Parts
28 Ball Material SS 316/*
29 Stem Material SS 316/*
30 Make & Model No. *
31 Rated Travel *
32 Characteristic ON - OFF
33 Balanced / Unbalanced *
34 Rated CV *
35 Cv at Min / Norm / Max *
36 % Open Min / Norm / Max *
TRIM 37 Trim Material SS316
38 Seat Material SS 316
39 Plug Material SS 316
40 Stem Material SS 316
41 Cage / Guide Material SS 316
42 Valve body test As per 2500# ANSI std.
43 ANSI Leakage Class ANSI/FCI 70.2,Class IV
44 Type Mechanical Limit Switch
45 Quantity, Open / Close 2 No's For Close / Open
46 Contact Rating 24 VDC, 5A
LIMIT SWITCHES
47 Enclosure Class & Protection IP 67, Ex d
48 Cable Entry 2 No's, M20 x 1.5
49 Manufacturer & Model No *
51 Quantity 1 No's
52 Filter & Specification Required / 5 Micron Size
53 Gauges 2'' Dial Size
54 Inlet Connection 1/2'' NPT(F)
AIR FILTER 55 Inlet Pressure 4-12 bar
REGULATOR
56 Drain Manual
57 Tubing SS 316
58 Manufacturer *
59 Model *
Notes: * Vendor To Specify
1 Emergency shutdown valve shall be provided with SS316 identification tag, perm
2 Ball Valve shall be firesafe .
3 Tag Plates provided should be of SS 304
4 Tubing to be 3I6 stainless steel.
5 Valve and actuator design must be suitable for installation in any direction.
6 Vendor to furnish Sizing calculations ,Valve opening atMin/Nor/Max,Possibilityo
PAGE NO.

XV-3900
8"-HG-G1-38007
1 No.s
8'' / SCH 120
CS
Gas Injection Compressor Header
HC GAS

Units Max Normal Min


MMSCFD 150 100 50
PSIG 5165
0
F 130
PSIG 5165
250 &19.72
cP 0.0156
PSIG 0
PSIG -
PSIG 671
dB <85
STM A106Gr C / 8" ZONE 60 Hazardous Area Classification Zone 0, Gas Group IIA, T
STM A106Gr C / 8" 61 Type Rotar SA Single Acting Cy
NA 62 Size *
63 Effective Area *
64 On/Off or Modulating ON-OFF (As per EN-1438
65 Valve Action Fail to Close
6 WCB ACTUATOR 66 Max. Allowable Pressure *
67 Min. Pressure Required *
5,8 INCH / 2500 / RTJ 68 Actuator Orientation *
69 Hand wheel Not Required
70 Make & Model No. *
71 Field Indication ( Open / Close) Required
72 Type 3/2 Way Direct operated
73 Power Supply 24 VDC
74 Material Body / Internals SS316
75 Pnumatic Connection 1/2'' NPT(F)
76 Output Signal *
77 Available Air Pressure Max 12 Bar
78 Available Air Pressure Min 4 Bar
79 Pnumatic Connection 1/2'' NPT(F)
80 Tube Size & Material 1/2'' OD SS316, Swagelo
SOV 81 Tube Fitting Material Swagelock
82 Cable Entry M20 x 1.5
83 Coil Insulation Class *
84 Manual Override Required
85 Enclosure Class IP 66
86 Explosion Protection Ex d (Flame Proof)
0# ANSI std. 87 Housing & Mounting Dicast Aluminium , Side
0.2,Class IV 88 Manufacturer *
l Limit Switch 89 Fusible Plug Required
Close / Open 90 Model No *
ESD 91 Make *

0 x 1.5

5 Micron Size

cation tag, permanently attached.

direction.
Max,Possibilityof Flashing & Cavitation
NO.

00
38007
s
120

pressor Header
AS

Min
50
5165
130
5165
250 &19.72
0.0156
0
-
671
<85
Zone 0, Gas Group IIA, T1
Rotar SA Single Acting Cylinder
*
*
ON-OFF (As per EN-14382)
Fail to Close
*
*
*
Not Required
*
Required
3/2 Way Direct operated
24 VDC
SS316
1/2'' NPT(F)
*
12 Bar
4 Bar
1/2'' NPT(F)
1/2'' OD SS316, Swagelock
Swagelock
M20 x 1.5
*
Required
IP 66
Ex d (Flame Proof)
Dicast Aluminium , Side Mounted
*
Required
*
*