Beruflich Dokumente
Kultur Dokumente
Note: The following is a sample of a typical sequence of operation that may be adapted for a
particular project. This is provided as a suggestion on how to write a sequence of operation for a
specific project. The GPEC includes the ability for the operator to select some different
sequences. Consult your Carrier representative if the sample sequence requires alterations.
A. Description:
Primary Chilled Water Pump, Secondary Pump Control and, Secondary Loop Temperature Reset via
Space Temperature and Three-way Mixing Valve.
B. General:
The chilled water system shall be controlled and monitored by a series (as needed) of EMS
compatible, programmable logic, General Purpose Electronic Controllers (GPEC).
Algorithms Schedules
AO — Reset Time Schedule
DO — Permissive Interlock Setpoint Schedules (temperature)
DO — Timeclock
DO — Analog Comparison
2. Occupancy Status:
The occupancy status is determined by the Time Schedule, and may be affected by the DO
Permissive Interlock algorithm.
The AO—Reset algorithm will modulate the three-way mixing valve to maintain a supply water
temperature. The supply water setpoint will be inversely reset based on a space temperature sensor.
Whenever the outside air temperature is above 60°F, the DO—Permissive Interlock algorithm will
enable the primary pump.
The DO—Timeclock algorithm will switch the operation of the secondary chilled water circuit from an
occupied to an unoccupied mode. During the unoccupied mode, the secondary pump will be
disabled. If the zone pump must be cycled on during unoccupied periods to maintain the space
temperature, use the DO—Timeclock with Check algorithm.
Whenever the zone pump is off, the bypass valve will be positioned to isolate the primary circuit. This
is accomplished by using the status point of the secondary pump as a status input for the AO—Reset
algorithm.
E. Sensor Selection:
The sensors required for this application are described below.