Sie sind auf Seite 1von 5

Project

By : HK GOMA ENGG & CONSULTANCY No:


1097

Date :07.10.2019 Client: TANVI TECHSOLUTIONS & L& T CONSTRUCTION Doc.No.: 1097/01
1.5 M
Chd : HM Project:PCSCL Subject: CANTILEVER
POLE DBR
Date :07.10.2019 Rev: 0

CONTENTS

Sr Sub Page
Item Description
No section nos
1 Introduction 1
I Structure Description 1
II Material Data 1
2 References 1
3 Loads & Load combinations 2
I Dead Load 2
II Live Load 2
III Wind Load 2
IV Earthquake Load 2
V Primary Load Cases 2
VI Load Combinations 3
4 Design Philosophy 3
5 Analysis & Design 4
6 Check for Overturning 5
7 Design Of Pedestal 5
8 Design of Base plate
9 STAAD File

This document is property of GEC it should not be copied or disclosed without obtaining specific approval from GEC
Project
By : HK GOMA ENGG & CONSULTANCY No:
1097

Date :07.10.2019 Client: TANVI TECHSOLUTIONS & L& T CONSTRUCTION Doc.No.: 1097/01
1.5 M
Chd : HM Project:PCSCL Subject: CANTILEVER
POLE DBR
Date :07.10.2019 Rev: 0

1. Introduction

This document mainly covers Introduction of structure, geometry & loading applied on
structure, analysis methods adopted, design philosophy and reference taken etc.
Project is mainly known as “1.5M CANTILEVER POLE ”. The project site is located near
Ahmedabad, Gujarat

I. Building description

Structure Type:- Pole


Horizontal Member Dimension:- 1.5 m
Pole Height:- 6.0 mtr

II. Material Data

Grade of Structural steel:- 250Mpa (As per IS 2062:2011)


Unit Weight of Structural steel:- 7850 kg/m3
Grade of Concrete:- M-20 (For Foundations)
Grade of Concrete:- M-10 (For PCC)
Grade of Reinforcing Steel:- Fe500 (HYSD bars)

2. References

The design & drawings are developed on the basis of the standard codes and documents and
specified codes used are mention below:

IS 800:2007 Code of practice for general construction in


steel
IS 456:2000 Code of Practice for Plain & reinforced
Concrete
IS 875(Part-1):1987 Design dead loads for building & Structures
IS 875(Part-2):1987 Imposed loads on building & structures
IS 875(Part-3):2015 Wind loads on building & structures
IS 2062:2011 Specification of Structural steel

This document is property of GEC it should not be copied or disclosed without obtaining specific approval from GEC
Project
By : HK GOMA ENGG & CONSULTANCY No:
1097

Date :07.10.2019 Client: TANVI TECHSOLUTIONS & L& T CONSTRUCTION Doc.No.: 1097/01
1.5 M
Chd : HM Project:PCSCL Subject: CANTILEVER
POLE DBR
Date :07.10.2019 Rev: 0

3. Loads & loads combination

This section deals with the loads & load combination adopted for the analysis & design of
structure is mentioned below:

I. Dead Loads (DL)

Dead Load is applied by providing self-weight command in STAAD PRO.

II. Wind load (WL)

Structure is designed for basic wind speed of 39 m/s in accordance with IS: 875(Part-
3).

III. Earthquake load (EQ)

Pole structure is critical towards wind as the structure is light weighed so earthquake
analysis not done.

IV. Primary Load Cases

Dead Load:- DL
Wind Load:- WL (X) in X direction
WL (Z) in Z direction

V. Load Combinations

Service Load Combinations


DL + WL

Strength Load Combinations


1.5DL + 1.5WL
0.9DL+1.5WL
1.2DL+0.6WL

4. Design Philosophy

Generally structure is analysed as frame structure using Staad Pro for the loads and
load combinations mentioned in section 3.0.

This document is property of GEC it should not be copied or disclosed without obtaining specific approval from GEC
Project
By : HK GOMA ENGG & CONSULTANCY No:
1097

Date :07.10.2019 Client: TANVI TECHSOLUTIONS & L& T CONSTRUCTION Doc.No.: 1097/01
1.5 M
Chd : HM Project:PCSCL Subject: CANTILEVER
POLE DBR
Date :07.10.2019 Rev: 0

 All design of RCC members is carried out by Limit state method as per IS:
456-2000.
 All design of Steel structures is carried out as per IS: 800-2007 by Limit stated
method.
 Columns are designed as a Fixed based connection to footings.
 For foundation design net allowable bearing pressure at 2.0 mtr depth from
N.G.L is adopted as 150 kN/M2.

5. Analysis & Design

WIND DETAILS

a) Basic Wind Speed 42 m/sec as per IS 875 (Part 3) – 2015

WIND PRESSURE CALCULATION

Design wind pressure , Pz =0.6 x Vz 2 ……………Clause No 7.2


Where ,
Vz = design wind speed at height z ,in m/sec, Vz = Vb x k1x k2 x k3x k4
Vb = basic wind speed in m/sec
k1 = 0.9……Probability factor (Risk Coefficient) from Clause No 6.3.1
k2 = 1.0……Terrain roughness & height factor from Clause No 6.3.2
k3 = 1.0……Topographic factor from Clause No 6.3.3
k4 = 1.0……Importance factor for cyclonic region from Clause No 6.3.4

Now Calculate Wind Pressure,


Wind Pressure, Pz = 0.6 x Vz 2
= 0.6X(42 X0.9 X 1.0 X 1.0 X 1.0)2
= 0.857 kN/m2

WIND LOAD CALCULATIONS


Wind load on pipe section of 114.3 X 3.65 mm = 0.857 X 0.1143 X3
=0.5877 kN.

Wind load on pipe section of 88.9 X 3.25 mm = 0.857 X 0.0889 X1.5


= 0.114 kN.
Wind load on pipe section of 76.1 X 3.25 mm = 0.857 X 0.0761 X1.5
= 0.0978 kN.
Wind load on pipe section of 33.7 X 3.25 mm = 0.857 X 0.0337 X1.5
= 0.0433 kN.
Wind load on pipe section of 48.3 X 3.25 mm = 0.857 X 0.0483 X1.5
= 0.0620 kN.

This document is property of GEC it should not be copied or disclosed without obtaining specific approval from GEC
Project
By : HK GOMA ENGG & CONSULTANCY No:
1097

Date :07.10.2019 Client: TANVI TECHSOLUTIONS & L& T CONSTRUCTION Doc.No.: 1097/01
1.5 M
Chd : HM Project:PCSCL Subject: CANTILEVER
POLE DBR
Date :07.10.2019 Rev: 0

7 Check for Overturning

Size of Pedestal = 0.65 X 0.65 X1.0 m


Overturning Moment = 1.363 X 1.0 X 1.5 = 2.0445 kNm
Stabilizing moment = (0.65 X 0.65 X1.0 X25+0.699) X0.65/2 =3.6599 kNm
FOS against overturning =3.6599/2.0445 = 1.79

8. Design of Pedestal
Providing min reinforcement = 0.15 % of gross cross section
Required reinforcement area = 0.15X 650 X 650/100 = 634 mm2
Dia of Bar Used = 12 mm
No. of Bar required = 6 no.
Providing reinforcement = 678 mm2> 634 mm2
Provide 8 mm dia stirrup @ 175 mm c/c

This document is property of GEC it should not be copied or disclosed without obtaining specific approval from GEC