4110_ECS Network Topology

EVM II
EVM Energía del Valle de México II
Combined Cycle Power Plant

Owner Contractor

GE Global Parts & Products GmbH


General Electric Global Services GmbH, México Branch
Grid Solutions México S.A de C.V

GE POWER
Gas Power Systems

Project Document Code EMX/00/E/BYB-----EN/DO/001

Title 4110_ECS Network Topology

Identification Number 127T3686

Revision
Revision A 2018-02-21
Date

KKS

Information Class, if applicable, on pg. 1 et sqq


SIZE
B
DWG. NO.
127T3686 SH.
1
REV.
A
REVISIONS
THIS DOCUMENT SHALL BE
REVISED IN ITS ENTIRETY. ALL REV DESCRIPTION DATE ISSUED BY
SHEETS OF THIS DOCUMENT
ARE THE SAME REVISION LEVEL A A1 GCB regrouped with LEC. 2018/02/20 AB
AS INDICATED IN THE REVISION A2 88BT1/88BT2 arrangement.
BLOCK.
A3 Removal of options on edge
panel.
A4 Removal of GSUT/UAT OLTC
A5 Diesel generators IEDS to GT
A6 Addition of VFD to secondary e-
room.
A7 88BT2 in plant scope
A8 Common building name to
ROP-EROOM change.
A9 Link correction for GSUT/UAT
A10 Scope revision for optional
items

EVM II
ECS NETWORK TOPOLOGY

Legend
MDH Network
PDH Network
UDH Network
EDH Network
Profibus Segments GE CLASS II ( INTERNAL NON-CRITICAL )
Irig-B Segments
g
UNLESS OTHERWISE SPECIFIED SIGNATURES DATE GENERAL ELECTRIC COMPANY
Typical Control Scope (See 4108) DIMENSIONS ARE IN INCHES
DRAWN
A. BENOIT 2018-02-20 GE Energy Products
TOLERANCES ON CHECKED
2 PL DECIMALS ± S. HOGG SEE PLM
3 PL DECIMALS ± ENGRG 2018-02-20

C
ANGLES ±
FRACTIONS ± ISSUED ECS Network Topology
COPYRIGHT 2018 GENERAL ELECTRIC COMPANY SEE PLM SEE PLM
FIRST MADE FOR: IPS 1154163
THIRD ANGLE PROJECTION MLI/COST CODE: 4110
APPLIED CAGE CODE DWG NO
PRACTICES

DISTR
B 127T3686

TO
SHEET
GENERAL ELECTRIC COMPANY. SIM TO SCALE RDO CODE : 1 of 23
DT-1N
SIZE DWG. NO. SH. REV.
B 127T3686 2 A

SUMMARY
SHEET NO DESCRIPTION REVISION
2 SUMMARY A
3 ECS NOTES - SH1 -
4 ECS NOTES - SH2 -
5 CONTROL SYSTEM NETWORK OVERVIEW A
6 ENGINEERING/CONTROL ROOM OVERVIEW A
7 MAIN eROOM OVERVIEW A
8 ROP eROOM OVERVIEW A
9 MAIN eROOM - GT11 / ST ECS AND EDGE PANEL TYPICALS A
10 MAIN eROOM - GT12 ECS TYPICALS A
11 ROP eROOM EDGE PANEL TYPICAL A
12 ELECTRICAL MV/LV MOTOR STARTER TYPICALS -
13 ELECTRICAL MV/LV BREAKERS DISTRIBUTION TYPICALS -
14 ELECTRICAL MV/LV DIESEL DISTRIBUTION TYPICAL -
15 EDH TOPOLOGY OVERVIEW A
16 ECS GPGs REDUNDANCY & PDH CONNECTION -
17 ECS GPGs & GPP/TPP TO MASTER CLOCK CONNECTION -
18 MAIN eROOM GT11 MSD IEDs CONNECTIONS TO ECS PANEL SWITCHES A
19 MAIN eROOM GT12 MSD IEDs CONNECTIONS TO ECS PANEL SWITCHES A
20 MAIN eROOM ST MSD IEDs CONNECTIONS TO EDGE PANEL SWITCHES -
21 MAIN eROOM MSD IEDs CONNECTIONS TO BHC12 SWITCHBOARD SWITCHES A
22 MAIN eROOM MSD IEDs CONNECTIONS TO BMC10 SWITCHBOARD SWITCHES -
23 ACRONYMS -

AREA HIGHLIGHTED IN GREY SHOWS TYPICAL CONTROL TEAM SCOPE (DETAILED IN MLI 4108)
Notes here after are given to provide a general overview of the ECS system.
A Vendor ECS dedicated network topology that will detail the owner, type, connections, IP addresses of all the IEDs, switches, concentrator panel
will be provided later during project requisition and will be used for commissioning and maintenance.
Refer to the ECS fact sheet or ECS Manual for further information about ECS system
SIZE CAGE CODE DWG NO
4110
g GENERAL ELECTRIC COMPANY B
127T3686

DISTR
SUMMARY DRAWN A. BENOIT 2018-02-20

TO
ISSUED SCALE SHEET
SEE PLM SEE PLM 2 of 23
SIZE DWG. NO. SH. REV.
B 127T3686 3 -

1. SYMBOL DESCRIPTION: 3. ELECTRICAL DATA HIGHWAY (EDH):


A DOR a) ECS network called Electrical Data Highway (EDH) is unique and common for the complete plant electrical scope
1 CUSTOMER EQUIPMENT (GT/ST/BOP and site common).
2 PARTNER EQUIPMENT
3 EQUIPMENT SUPPLIED FOR GAS TURBINE ORDER b) EDH is composed by several pair of switches (redundant) that are interconnected in one redundant Ethernet ring
4 EQUIPMENT SUPPLIED FOR STEAM TURBINE ORDER topology using multimode fiber optic.
5 EQUIPMENT SUPPLIED FOR GE PLANT ORDER c) EDH covers different protocols such as IEC61850, Modbus TCP and NTP for time synchronization, RSTP for
B CONTROL EQUIPMENT switch to switch communication (Ethernet network redundancy management).
1 TURBINE CONTROL PANEL (TCP) d) EDH interconnects all the electrical Intelligent Electronic Devices (IEDs) supplied by the different electrical teams
2 GE DCS SUPPLIED EQUIPMENT (GE GET, GE Plant and Customer / partner), therefore each electrical team is in charge to define, supply and
3 EXCITER PANEL EX21000e commission their respective IEDs with their associated pairs of switches (One ECS meeting with all electrical
4 LCI PANEL LS21000e teams need to take place at the beginning of the project requisition to summaries the overall scope and define
5 GENERATOR AND TRANSFORMER PROTECTION PANEL the preliminary IED list / EDH routing).
6 E ELECTRICAL CONTROL SYSTEM (ECS)
e) EDH ring has no communication with external networks, same as the Mark Vie UDH network: The ECS signals
7 ML EDH NETWORK SWITCHES (ML3000)
sharing with networks outside the plant will transit through the DCS OPC gateways and DCS cyber security system .
8 IED ELECTRICAL INTELLIGENT ELECTRONIC DEVICES (IED)
f) EDH ring route shall follow the below main rules:
C DISTRIBUTION EQUIPMENT
 Each block should have only one input / output,
1 PACKAGE ELECTRICAL & ELECTRONIC CONTROL CENTER (PEECC)
 Ring shall follow the available cable routes,
2 LV SWITCHBOARD / MCC.
 Number <1> use to be the 1st eRoom of 1st block,
3 BC BC COMPARTMENT
 One exception use to be applied for water Intake that use to be far from the plant and therefore connected
4 DC DC/UPS SWITCHBOARD
as an antenna to the main Ring.
D POWER EQUIPMENT
g) EDH switches shall follow the below main rules:
1 GCB GENERATOR CIRCUIT BREAKER
 Switches shall be always provided in pairs (redundant) and of same type: ML3000 from GE Grid Automation
2 VT VT CUBICLE
 Pair of switches are typically located in each electrical room / building that have more than 5x IEDs,
3 B GPLE - GENERATOR PHASE LEAD ENCLOSURE / GTE - GENERATOR TERMINAL ENCLOSURE
with typically one pair of switches per:
4 G GNTE - GENERATOR NEUTRAL TIE ENCLOSURE
- ECS panel and/or Edge panel for DC, UPS and Other miscellaneous IEDs,
5 NGE NEUTRAL GROUNDING ENCLOSURE
- MV Switchboard and other MV IEDs,
6 EXT EXCITATION TRANSFORMER
- LV Switchboard and other LV IEDs
7 EXCITER COMPARTMENT
(switch optimization shall be based on cable vs distance vs fiber optic converter need).
8 ISO ISOLATION TRANSFORMER
9 LEC / LCIC COMPARTMENT h) HV Switchyard can be integrated by three solutions:
 HV Switchyard IEDs directly connected to EDH in IEC61850 (SCADA by ECS),
2. ECS CONCENTRATORS PANEL(S):  HV Switchyard provided with separate SCADA and external connection to PCS in IEC104/DNP3,
 HV Switchyard provided with no IEDs and connected to PCS in conventional hard wired signals .
a) ECS concentrator panel(s) is a system that process (Synchronize, Collect, Store, Show, Alert, Share) all the signals
i) NCC can be integrated by two solutions:
from/to all the Electrical IEDs connected to the EDH network:
 NCC connection to PCS in IEC104/DNP3,
 ECS performs the advanced monitoring of all the Electrical IEDs as well as the operator initiated command of all
remote controlled electrical distribution breakers and switches.  NCC connection to PCS in conventional hard wired signals.
 ECS only performs the advanced monitoring of all the motor starter Electrical IEDs: control being made through a
second communication by the different Mark Vie over Profibus DP. 4. ELECTRICAL INTELLIGENT ELECTRONIC DEVICES (Electrical IEDs):
b) ECS concentrator panel(s) provided along with each GT is not just GT dedicated: ECS concentrator panel(s) can There are 4 main types of Electrical IEDs connected to the EDH redundant switches, communicating in different protocols
cover full plant scope including GT, ST, Plant BOP and other Customer / Partner plant utility. and using different network redundancies.
c) Each ECS concentrator panel is composed by following main devices : Main types:
 One pair of Ethernet switches of Electrical Data Highway (EDH).
 One to four ECS concentrators (quantity defined per the project specific total quantity of IEDs, one hot/standby
pair of concentrator designed to process 250x IEDs).
 One administrator HMI.
d) ECS concentrator panel(s) are installed in the main eRoom next to the GT GPP and GT Mark Vie
to facilitate the commissioning and maintenance in each eRoom (close to IEDs).
e) ECS concentrator panel(s) is connected to the Electrical Data Highway (EDH) and the Plant Data Highway (PDH).
SIZE CAGE CODE DWG NO
4110
g GENERAL ELECTRIC COMPANY B
127T3686

DISTR
ECS NOTES - SH1 DRAWN A. BENOIT 2018-02-20

TO
ISSUED SCALE SHEET
SEE PLM SEE PLM 3 of 23
SIZE DWG. NO. SH. REV.
B 127T3686 4 -

Typical protocols and redundancies: ECS connection to PDH needs 2x copper Cat-6 F/UTP redundant ports to GT Mark VIe PDH switches (Multimode fiber
possible in option) with following blocked IP addresses.
f) Master hot Concentrator to PDH switch 1: 172.16.203.248,
g) Master hot Concentrator to PDH switch 2: 172.16.203.250,
h) Master stand-by Concentrator to PDH switch 1: 172.16.203.249,
i) Master stand-by Concentrator to PDH switch 2: 172.16.203.251.
Time synchronization:
j) Each ECS concentrators needs one multimode fiber (Irig-b RG58 coaxial single ports depending to the distance to
plant s time server is available as an option).
k) GPGs and main protection IEDs (G60, T60 of GPP) use Irig-B time synchronization as master (more accurate)
and NTP (via Ethernet) as back-Up.
There are 3 types of communication between ECS and DCS which need to be opened and available when using a firewall.
The following table provides the TCP ports using for these communication links.

(1) Depends on the existing capability of the devices: IEC61850 preferred for source time stamp, fail-over redundancy
preferred when operator initiated remote control required, goose messaging preferred in case the device needs to share
information with other IEDs (e.g. Automatic Transfer Scheme) to avoid using conventional hard-wiring between these
IEDs.
(2) Motor starter are controlled by Mark Vie through Profibus DP, therefore the ECS advance monitoring is via single comm .
IEDs to EDH switches are cat-6 F/UTP or multimode Fiber (as per requirements) with following blocked IP address ranges:
a) EDH switches: 172.16.150.001 to 099,
b) Plant Common IEDs: 172.16.150.100 to 255,
c) Block 1 IEDs (GT/ST/HRSG/BOP): 172.16.151.001 to 255,
d) Block 2 IEDs (GT/ST/HRSG/BOP): 172.16.152.001 to 255,
e) Block X IEDs (GT/ST/HRSG/BOP): 172.16.15x.001 to 255.
ECS Concentrator does not have any I/Os nor logic, it communicates through protocol to the different IEDs that have I/Os and
logic.

5. ECS ADMINISTRATOR STATION(S):


a) One administrator HMI is provided and installed within each ECS concentrator panel with 19 rack mounted HMI
screen and keyboard / mouse drawer.
b) ECS administrator HMIs provided along with each GT concentrator panel is not just GT dedicated:
These administrator HMIs are the same and can administrate the full electrical plant scope including GE GT, ST,
Plant BOP and other Customer / Partner plant utility.
c) One optional KVM, directly wired to one of the local administrator HMI computers, and installed in the central control
room or engineering room can be provided as an option to allow on-line remote access to the IEDs
(change IEDs settings).
6. ECS to PCS INTEGRATION:
ECS do not have any additional hardware required in the Central Control Room (CCR), it just needs a redundant connection
to the PDH and to the Network Time Server (IRIG-B).
Connection to PDH is used to exchange following information:
The ECS archived data are plain text files in CSV format and COMTRADE files for Oscillographies.
a) Source time stamp electrical alarms in OPC AE to PCS plant unique alarm management system.
This data is stored in all Administrator workstations in the EDH network but it also needs a storing location available in the
b) Source time stamp other shared signals in OPC DA from / to PCS, Predix or other.
PDH network. Therefore, it is required a network drive with at least 10GB storage capacity to be installed in the PDH network.
c) Auto-retrieve and storage of electrical ftp files (event, historical data, oscillography) in PCS historian.
(e.g. it can be a network shared hard drive or partition of Historian computer).
d) Shared memory with the ECS viewer: ECS viewer being installed In colocation next to Cimplicity PCS viewer
in each Engineering and Operator Workstations (EWS / OWS) with ECS to PCS screen switching capability Network drive directory must be included in 4108.
(installation on site).
SIZE CAGE CODE DWG NO
e) One optional communication such as IEC104, DNP3 can also be added for direct interfacing between electrical IEDs 4110
and HV Switchyard / National Control Center (NCC). g GENERAL ELECTRIC COMPANY B
127T3686

DISTR
ECS NOTES - SH2 DRAWN A. BENOIT 2018-02-20

TO
ISSUED SCALE SHEET
SEE PLM SEE PLM 4 of 23
SIZE DWG. NO. SH. REV.
B 127T3686 5 A

HV SWITCHYARD

Cyber Security

Site Router / Firewall ---- GE-WAN ISP Circuit / HSC

MDH A
MDH B

PDH A
PDH B

MarkVIe
HMIs Gateways Historian EX2100 LS2100 GPGs
Controllers

UDH A
UDH B

Energy Meters MV VFDs LV VFDs Remote I/O Diesel Other Electrical


IEDs IEDs IEDs IEDs synchronizer IEDs IEDs A4

Protection MV Switchboard LV Switchboard Edge Panels Battery Charger Diesel Transformer


Panel IEDs IEDs IEDs IEDs Inverter IEDs Generator IEDs Monitoring IEDs

EDH

IED and ML / or or or or (Each it s own IEDs and Switches as per project DOR)

SIZE CAGE CODE DWG NO


4110
g GENERAL ELECTRIC COMPANY B
127T3686

DISTR
CONTROL SYSTEM NETWORK OVERVIEW DRAWN A. BENOIT 2018-02-20

TO
ISSUED SCALE SHEET
SEE PLM SEE PLM 5 of 23
SIZE DWG. NO. SH. REV.
B 127T3686 6 A

ENGINEERING ROOM CENTRAL CONTROL ROOM

MONITOR Plant Control System MONITOR Plant Control System


Work Stations Work Stations

A10

Note:
ECS does not have any additional hardware in Central Control Room (CCR).
ECS does not have any additional hardware in Engineering room nor ECS Admin KVM. Refer to ECS Note 5.c).
ECS uses same DCS hardware for alarm management, historian, OPC gateways. Refer to ECS Note 6.a) b) c).
ECS viewer software is installed on the same EWS, CRM / OWS. Refer to ECS Note 6.d).
ECS GPGs and main protection panel IEDs are synchronized to same NTP time server. Refer to sheet 16.
SIZE CAGE CODE DWG NO
4110
g GENERAL ELECTRIC COMPANY B
127T3686

DISTR
ENGINEERING/CONTROL ROOM OVERVIEW DRAWN A. BENOIT 2018-02-20

TO
ISSUED SCALE SHEET
SEE PLM SEE PLM 6 of 23
SIZE DWG. NO. SH. REV.
B 127T3686 7 A

MAIN eROOM

MONITOR Plant Control System Mark Vie I/Os


Work Stations See Typical Sh 12

PDH A
PDH B

ECS Panel ML E Edge Panel ML IED ECS Panel ML E

ECS_ADM ECS_ADM
GPGx C650x GPGx
19" Rack 19" Rack
MONITOR MONITOR
GPGx C650x GPGx
ECS BAY ECS
GT11 CONCENTRATOR ST CONTROLLER GT12 CONCENTRATOR
GPP GPP GPP

MV/LV Switchboards And MCCs Motor Starter IEDs

EDH

A10

Note:
GPP/TPP relays connections moved from UDH to EDH.
One ECS panel per GT located next to GT GPP / GT Mark VIe. Refer to ECS Note 2.
Mark Vie controllers and/or Remote IOs have profibus DP connections to the different MV/LV Switchboards and MCCs Motor Starter IEDs.
MV/LV Switchboards and MCCs IEDs have Ethernet connection to EDH network for advance monitoring and breaker control. Refer to ECS Note 4.
- - - (Dotted red line) Represent fail-over redundancy when Goose or Operator initiated remote control required. Refer to ECS Note 4.

SIZE CAGE CODE DWG NO


4110
g GENERAL ELECTRIC COMPANY B
127T3686

DISTR
MAIN eROOM OVERVIEW DRAWN A. BENOIT 2018-02-20

TO
ISSUED SCALE SHEET
SEE PLM SEE PLM 7 of 23
SIZE DWG. NO. SH. REV.
B 127T3686 8 A

A8
ROP E-ROOM

Mark Vie I/Os


See Typical Sh 12

Edge Panel ML IED

A3
C650x
C650x
BAY
CONTROLLER

MV/LV Switchboards And MCCs Motor Starter IEDs

EDH

A10

Note:
Plant Utility Owner provides Edge Panel as required (with EDH pair of switches).
Mark Vie controllers and/or Remote IOs have profibus DP connections to the different MV/LV Switchboards and MCCs Motor Starter IEDs.
MV/LV Switchboards and MCCs IEDs have Ethernet connection to EDH network for advance monitoring and breaker control. Refer to ECS Note 4.
- - - (Dotted red line) Represent fail-over redundancy when Goose or Operator initiated remote control required. Refer to ECS Note 4.

SIZE CAGE CODE DWG NO


A8
4110
g GENERAL ELECTRIC COMPANY B
127T3686

DISTR
ROP eROOM OVERVIEW DRAWN A. BENOIT 2018-02-20

TO
ISSUED SCALE SHEET
SEE PLM SEE PLM 8 of 23
SIZE DWG. NO. SH. REV.
B 127T3686 9 A

MAIN eROOM - ECS CONCENTRATOR PANEL 1 MAIN eROOM - EDGE PANEL

ML3000 ML3000
EDH Ring
GPG Concentrators
C650
ML3000 ML3000

ECS_ADM
19" Rack
MONITOR IDM
Internal Diagnostic Module
Miscellaneous
Common related non-smart
signals digitalization

GT11 GPP/TPP GT11 IO Module IEDs GT11 Other IEDs ST GPP/TPP DC/UPS Swbd, charger, inv. ST/BOP IO Module IEDs ST/BOP Other IEDs

C650
A5 Diesel Generator A5
IO module IO module

Energy Meters A4 Energy Meters


A4

G60s / T60s T60s / T60s

A9
GSUT / UAT A9
GSUT
Monitoring System Monitoring System
Located in Electrical Bay controller Located in Electrical
Compartments for busbar metering Compartments
(e.g. LCIC, GSEC, LEC) Other GT11 and other non-smart (e.g. LCIC, GSEC, LEC) Other ST/BOP
or Equipment JBs Electrical IEDs signal digitalization or Equipment JBs Electrical IEDs
for local non-smart signal for local non-smart signal
digitalization These are some examples digitalization These are some examples

Note:
One ECS concentrator panel is provided along with GT11, and one Edge panel for ST/BOP and located juxtaposed inside eRoom.
Edge panel is provided without administrator HMI.
ECS Concentrator panel switches connects all the GT11 GPP/TPP and other GT11 related miscellaneous IEDs.
Edge panel switches connects all the ST GPP/TPP, DC/UPS and other ST/BOP related miscellaneous IEDs.
The IEDs are connected with Modbus TCP or IEC61850, single or fail-over redundant ports as required. Refer to ECS Note 4.
- - - (Dotted red line) Represent fail-over redundancy when Goose or Operator initiated remote control required. Refer to ECS Note 4.
SIZE CAGE CODE DWG NO
4110
g GENERAL ELECTRIC COMPANY B
MAIN eROOM – GT11 /ST ECS AND EDGE PANEL TYPICALS 127T3686

DISTR
DRAWN A. BENOIT 2018-02-20

TO
ISSUED SCALE SHEET
SEE PLM SEE PLM 9 of 23
SIZE DWG. NO. SH. REV.
B 127T3686 10 A

MAIN eROOM - ECS CONCENTRATOR PANEL 2

ML3000
EDH Ring
GPG Concentrators

ML3000

ECS_ADM
19" Rack
MONITOR IDM
Internal Diagnostic Module

GT12 GPP/TPP GT12 IO Module IEDs GT12 Other IEDs

A5 Diesel Generator
IO module

Energy Meters A4

G60s / T60s

A9
GSUT / UAT
Monitoring System
Located in Electrical
Compartments
(e.g. LCIC, GSEC, LEC) Other GT12
or Equipment JBs Electrical IEDs
for local non-smart signal
digitalization These are some examples

Note:
One ECS concentrator panel is provided along with GT12.
ECS Concentrator panel switches connects all the GT12 GPP/TPP and other GT12 related miscellaneous IEDs.
The IEDs are connected with Modbus TCP or IEC61850, single or fail-over redundant ports as required. Refer to ECS Note 4.
- - - (Dotted red line) Represent fail-over redundancy when Goose or Operator initiated remote control required. Refer to ECS Note 4.

SIZE CAGE CODE DWG NO


4110
g GENERAL ELECTRIC COMPANY B
MAIN eROOM – GT12 ECS TYPICALS 127T3686

DISTR
DRAWN A. BENOIT 2018-02-20

TO
ISSUED SCALE SHEET
SEE PLM SEE PLM 10 of 23
SIZE DWG. NO. SH. REV.
B 127T3686 11 A

A8
ROP eROOM- EDGE PANEL

ML3000
EDH Ring
C650
ML3000

A10

Miscellaneous
Common related non-smart
signals digitalization

Other DC/UPS Swbd, charger, inv. Other IO Module IEDs Other IEDs

C650

IO module
Battery charger(s)
/ UPS inverter(s)

Bay controller Located in Electrical


for busbar metering Compartments
and other non-smart or Equipment JBs Other
signal digitalization for local non-smart signal Electrical IEDs
digitalization
These are some examples

Note:
Other Edge panel(s) use to be added when a significant quantity of non-smart signals remain to be digitalized for plant common and/or other block related area(s) far from eRoom.
Additional Edge panel(s) are defined / supplied by the team that own these non-smart signals (GE / Customer / Partner teams).
The IEDs are connected with Modbus TCP or IEC61850, single or fail-over redundant ports as required. Refer to ECS Note 4.
- - - (Dotted red line) Represent fail-over redundancy when Goose or Operator initiated remote control required. Refer to ECS Note 4.

A8
SIZE CAGE CODE DWG NO
4110
g GENERAL ELECTRIC COMPANY B
127T3686

DISTR
ROP eROOM - EDGE PANEL TYPICAL DRAWN A. BENOIT 2018-02-20

TO
ISSUED SCALE SHEET
SEE PLM SEE PLM 11 of 23
SIZE DWG. NO. SH. REV.
B 127T3686 12 -

MV SWITCHBOARD # LV SWITCHBOARD & MCC # SECONDARY LV SWITCHBOARD # (sub-distribution)

ML3000 ML3000
EDH Ring

ML3000 ML3000

C650 F650 C650 F650 C650


T60 Hard wired control / monitoring
Hard wired control /
monitoring

Bay controller Incomer / Coupler Large Transformer Bay controller Large Bay controller
for busbar metering / Feeder Incomer / Feeder for busbar metering Incomer / Coupler for busbar metering
and other non-smart (differential protection) and other non-smart (also include ATS) and other non-smart
signal digitalization signal, feeder digitalization signal, inomer, feeder
digitalization
(also include ATS)

Note:
ECS have IEC61850 for breaker control and advance monitoring (include oscillo file auto retrieve).
Refer to ECS Note 4.

SIZE CAGE CODE DWG NO


4110
g GENERAL ELECTRIC COMPANY B
127T3686

DISTR
ELECTRICAL MV/LV BREAKERS DISTRIBUTION TYPICAL DRAWN A. BENOIT 2018-02-20

TO
ISSUED SCALE SHEET
SEE PLM SEE PLM 12 of 23
SIZE DWG. NO. SH. REV.
B 127T3686 13 -

Marck Vie
PDP Segment

MV SWITCHBOARD # MV VFD # LV SWITCHBOARD & MCC # LV VFD #

ML3000 ML3000
EDH Ring

ML3000 ML3000
Profibus DP
Profibus DP / IEC61850
IO module IO module

Hard wired
control cmd
F650
Hard wired
M60
control cmd MM300

Small / non-critical Large / Critical VFD driven Small / non-critical Large / Critical VFD driven
MV Motors MV Motors MV Motors LV Motors LV Motors LV Motors
(differential protection) (non-smart starter)

Note:
Mark Vie have Profibus DP connection to control the motors.
ECS have IEC61850 or Modbus TCP for advance monitoring (include oscillo file auto retrieve).
Refer to ECS Note 4.

SIZE CAGE CODE DWG NO


4110
g GENERAL ELECTRIC COMPANY B
127T3686

DISTR
ELECTRICAL MV/LV MOTOR STARTER TYPICAL DRAWN A. BENOIT 2018-02-20

TO
ISSUED SCALE SHEET
SEE PLM SEE PLM 13 of 23
SIZE DWG. NO. SH. REV.
B 127T3686 14 -

ESSENTIAL DIESEL LV SWITCHBOARD

ML3000

ML3000

C650 F650 F650

Hard wired control /


monitoring

Bay controller
Essential Diesel Incomer / Coupler
for busbar metering
/ Feeder
and other non-smart
signal digitalization

Note:
ECS have IEC61850 for breaker control and advance monitoring (include oscillo file auto retrieve)
Refer to ECS Note 4

SIZE CAGE CODE DWG NO


4110
g GENERAL ELECTRIC COMPANY B
127T3686

DISTR
ELECTRICAL MV/LV DIESEL DISTRIBUTION TYPICAL DRAWN A. BENOIT 2018-02-20

TO
ISSUED SCALE SHEET
SEE PLM SEE PLM 14 of 23
SIZE DWG. NO. SH. REV.
B 127T3686 15 A

Below EDH network Topology and Quantity of switches is preliminary.


A second ECS dedicated network topology that will detail the owner, type, connections, IP addresses of all the IEDs, switches, concentrator panel will be provided later during
project requisition and will be used for commissioning and maintenance.
Refer to the ECS fact sheet or ECS Manual for further information about ECS system.

Main eROOM GT12 Sec eROOM ACC eROOM GT11 Sec eROOM ROP eROOM
ML IED and E ML IED ML IED ML IED ML IED
MV VFD /LV MV VFD /LV
ECS Concentrator panel1 ECS Concentrator panel2 Edge Panel Switchboard / Aux LV Switchboard / Aux Switchboard / Aux Edge Panel

MV Switchboard(s) MV Switchboard(s) MV Switchboard(s)

A5 A5

LV Switchboard / MCC(s) LV Switchboard / MCC(s) LV Switchboard / MCC(s)

Patch BOX used for EDH ring Fiber connection from field (input and output): Easy Connection for armored FO cables.

Note: This sheet gives EDH ring Field interconnect details.


ECS network called Electrical Data Highway (EDH) is an Ethernet fiber optic ring topology that is unique for the complete plant GT/ST/BOP and site common.
EDH interconnects all the Ethernet switches that are typically installed in the different MV/LV switchboards or Edge panels located in the different electrical rooms.
All switches to be same type and defined / supplied by the different package owners (GE / Customer / Partner teams).
Refer to ECS Note 3.

SIZE CAGE CODE DWG NO


4110
g GENERAL ELECTRIC COMPANY B
127T3686

DISTR
EDH TOPOLOGY OVERVIEW DRAWN A. BENOIT 2018-02-20

TO
ISSUED SCALE SHEET
SEE PLM SEE PLM 15 of 23
SIZE DWG. NO. SH. REV.
B 127T3686 16 -

MAIN eROOM
PDH A
PDH B
ECS CONCENTRATOR PANEL 1 ECS CONCENTRATOR PANEL 2

GPG Concentrator GPG Concentrator


Hot A
Stand-by B

ML3000 ML3000
EDH Ring

ML3000 ML3000

GPG Concentrator GPG Concentrator


Hot 11 Stand-by 22

GPG Concentrator 19" Rack GPG Concentrator 19" Rack


MONITOR MONITOR
Hot 21 Stand-by 12

ECS_ADM ECS_ADM

Note: This sheet gives PDH interconnect details from ECS concentrators to GT Mark Vie switches.
Master hot/stand-by GPGs A/B compile the slave GPGs data base and provide single interface to OPC gateways / HMI viewer.
Slave hot/stand-by GPG 11/12 process IEDs 001 to 250.
Slave hot/stand-by GPG 21/22 process IEDs 251 to 500.
Refer to ECS Note 3.

SIZE CAGE CODE DWG NO


4110
g GENERAL ELECTRIC COMPANY B
127T3686

DISTR
ECS GPGs REDUNDANCY & PDH CONNECTION DRAWN A. BENOIT 2018-02-20

TO
ISSUED SCALE SHEET
SEE PLM SEE PLM 16 of 23
SIZE DWG. NO. SH. REV.
B 127T3686 17 -

NTP_1
2 x IRIG-B OUTPUT

IRIG-B Distribution Unit


12 x IRIG-B OUTPUT
(6x FO-SM +6x BNC)

1 1

Main eROOM

ECS CONCENTRATOR PANEL 1 ECS CONCENTRATOR PANEL 2

GPG Concentrator GPG Concentrator


Hot A Stand-by B

GPG Concentrator GPG Concentrator


Hot 11 Stand-by 12

GPG Concentrator GPG Concentrator


Hot 21 2 Stand-by 22 2

ST GPP/TPP GT11 GPP/TPP GT12 GPP/TPP


G60/T60 G60/T60 G60/T60

1 Fiber / Coaxial (Both available on GPGs side)


2 Coaxial

Note: This sheet gives IRIG-B interconnect details from master clock to ECS Concentrators and GPP/TPPs.
GPGs are synchronized in IRIG-B.
Main GPP/TPP protection panel IEDs are synchronized in IRIG-B with backup in NTP via GPGs.
Other IEDs with time stamp capability are synchronized in NTP via GPGs. SIZE CAGE CODE DWG NO
4110
Refer to note 6 j) and k). g GENERAL ELECTRIC COMPANY B
127T3686

DISTR
ECS GPGs & GPP/TPP TO MASTER CLOCK CONNECTION DRAWN A. BENOIT 2018-02-20

TO
ISSUED SCALE SHEET
SEE PLM SEE PLM 17 of 23
SIZE DWG. NO. SH. REV.
B 127T3686 18 A

MAIN EROOM

ECS CONCENTRATOR PANEL 1 ML1 Port # IEDs ML2 Port# IEDs


1 C1 (LC) EDH-IN (FO) C1 (LC) EDH-IN (FO)
E
Patch Box Patch Box 2 C2 (LC) EDH-OUT (FO) C2 (LC) EDH-OUT (FO)
EDH Ring
MAIN 3 C3 (LC) SPARE C3 (LC) GT11- GSUT SWITCH
EROOM 4 C4 (LC) SPARE C4 (LC) SPARE
ML3000-1 C E G I
EXTERNAL-IN OTHER ECS 5 D1 (LC) SPARE D1 (LC) SPARE
CONCENTRATOR 6 D2 (LC) SPARE D2 (LC) SPARE
D F H J SWITCHES PANEL 2 SHEET 18 7 D3 (LC) SPARE D3 (LC) SPARE
IDM E 8 D4 (LC) SPARE D4 (LC) SPARE
Internal Diagnostic Module ECS_ADM ML3000-2 9 E1 (RJ45) GPG E1 (RJ45) GPG
19" Rack 10 E2 (RJ45) GPG E2 (RJ45) GPG
MONITOR
11 E3 (RJ45) GPG E3 (RJ45) GPG
GPGs 12 E4 (RJ45) SPARE E4 (RJ45) SPARE
13 F1 (RJ45) PC-ADM F1 (RJ45) PC-ADM
14 F2 (RJ45) IDM F2 (RJ45) SPARE
15 F3 (RJ45) GT11-EPM-1 F3 (RJ45) GT11-EPM-2
16 F4 (RJ45) GT11-G60A GEN F4 (RJ45) GT11-G60A GEN
17 G1 (RJ45) GT11-G60B GEN G1 (RJ45) GT11-G60B GEN
18 G2 (RJ45) GT11–T60U GSUT G2 (RJ45) GT11–T60U GSUT
Patch Box 19 G3 (RJ45) GT11–T60T GSUT G3 (RJ45) GT11–T60T GSUT
Cable By
20 G4 (RJ45) GT11–T60AT UAT G4 (RJ45) GT11–T60AT UAT
21 H1 (RJ45) GT11–T60ET EXT H1 (RJ45) GT11–T60ET EXT
22 H2 (RJ45) GT11–T60IT- ISO H2 (RJ45) GT11–T60IT- ISO
A1
23 H3 (RJ45) GT11-LEC WAGO H3 (RJ45) SPARE
24 H4 (RJ45) SPARE H4 (RJ45) SPARE
25 … … … …

A1

GT11 GPP/TPP GT11 LEC

GENERATOR GSUT UAT EXT ISO AUX PANEL


EPM -1 EPM -2

GT11 GSUT
G60A T60U T60AT T60ET T60IT
WAGO

G60B T60T
GT11 UAT
WAGO TRANSFIX WAGO

Note: This sheet gives MSD IEDs to ECS concentrator panel switches interconnect details.
ML3000 and patch box fiber Connection (FO) are multimode with LC-100 Mb/s type ports. SIZE CAGE CODE DWG NO
4110
IEDs Connections are Cat-6 F/UTP with RJ45 ports.
g GENERAL ELECTRIC COMPANY B
MAIN eROOM GT11 MSD IEDs CONNECTIONS 127T3686

DISTR
DRAWN A. BENOIT 2018-02-20
TO ECS PANEL SWITCHES

TO
ISSUED SCALE SHEET
SEE PLM SEE PLM 18 of 23
SIZE DWG. NO. SH. REV.
B 127T3686 19 -

MAIN EROOM

ML1 Port # IEDs ML2 Port# IEDs


ECS CONCENTRATOR PANEL 2 1 C1 (LC) EDH-IN (FO) C1 (LC) EDH-IN (FO)
Patch Box
E
Patch Box 2 C2 (LC) EDH-OUT (FO) C2 (LC) EDH-OUT (FO)
MAIN 3 C3 (LC) SPARE C3 (LC) GT12-GSUT SWITCH
EDH Ring
EROOM 4 C4 (LC) SPARE C4 (LC) SPARE
ECS ML3000-1 C E G I 5 D1 (LC) SPARE D1 (LC) SPARE
CONCENTRATOR OTHER EDGE PANEL
6 D2 (LC) SPARE D2 (LC) SPARE
PANEL 1 SHEET 17 SWITCHES SHEET 19
D F H J 7 D3 (LC) SPARE D3 (LC) SPARE
IDM E
8 D4 (LC) SPARE D4 (LC) SPARE
Internal Diagnostic Module ECS_ADM ML3000-2 9 E1 (RJ45) GPG E1 (RJ45) GPG
19" Rack
10 E2 (RJ45) GPG E2 (RJ45) GPG
MONITOR 11 E3 (RJ45) GPG E3 (RJ45) GPG
12 E4 (RJ45) SPARE E4 (RJ45) SPARE
GPGs 13 F1 (RJ45) PC-ADM F1 (RJ45) PC-ADM
14 F2 (RJ45) IDM F2 (RJ45) SPARE
15 F3 (RJ45) GT12-EPM-1 F3 (RJ45) GT12-EPM-2
16 F4 (RJ45) GT12-G60A GEN F4 (RJ45) GT12-G60A GEN
17 G1 (RJ45) GT12-G60B GEN G1 (RJ45) GT12-G60B GEN
18 G2 (RJ45) GT12–T60U GSUT G2 (RJ45) GT12–T60U GSUT
Patch Box 19 G3 (RJ45) GT12–T60T GSUT G3 (RJ45) GT12–T60T GSUT
Cable By 20 G4 (RJ45) GT12–T60AT UAT G4 (RJ45) GT12–T60AT UAT
21 H1 (RJ45) GT12–T60ET EXT H1 (RJ45) GT12–T60ET EXT
22 H2 (RJ45) GT12–T60IT- ISO H2 (RJ45) GT12–T60IT- ISO
A1
23 H3 (RJ45) GT12-LEC WAGO H3 (RJ45) SPARE
24 H4 (RJ45) SPARE H4 (RJ45) SPARE
25 … … … …

A1

GT12 GPP/TPP GT12 LEC

GENERATOR GSUT UAT EXT ISO AUX PANEL


EPM -1 EPM -2

GT12 GSUT
G60A T60U T60AT T60ET T60IT
WAGO

G60B T60T
GT12 UAT
WAGO TRANSFIX WAGO

Note: This sheet gives MSD IEDs to ECS concentrator panel switches interconnect details.
ML3000 and patch box fiber Connection (FO) are multimode with LC-100 Mb/s type ports. SIZE CAGE CODE DWG NO
4110
IEDs Connections are Cat-6 F/UTP with RJ45 ports.
g GENERAL ELECTRIC COMPANY B
MAIN eROOM GT12 MSD IEDs CONNECTIONS 127T3686

DISTR
DRAWN A. BENOIT 2018-02-20
TO ECS PANEL SWITCHES

TO
ISSUED SCALE SHEET
SEE PLM SEE PLM 19 of 23
SIZE DWG. NO. SH. REV.
B 127T3686 20 -

MAIN EROOM ML1 Port # IEDs ML2 Port# IEDs


1 C1 (LC) EDH-IN (FO) C1 (LC) EDH-IN (FO)
EXTERNAL-OUT 2 C2 (LC) EDH-OUT (FO) C2 (LC) EDH-OUT (FO)
EDGE PANEL
3 C3 (LC) SPARE C3 (LC) ST-GSUT SWITCH
Patch Box
Patch Box 4 C4 (LC) SPARE C4 (LC) SPARE
EDH Ring 5 D1 (RJ45) EPM D1 (RJ45) ST GSEC WAGO
ML3000-1 C E G I 6 D2 (RJ45) ST-G60A GEN D2 (RJ45) ST-G60A GEN
ECS
7 D3 (RJ45) ST-G60B GEN D3 (RJ45) ST-G60B GEN
CONCENTRATOR
PANEL 2 SHEET 18 8 D4 (RJ45) ST-T60U GSUT D4 (RJ45) ST-T60U GSUT
D F H J
9 E1 (RJ45) ST-T60T GSUT E1 (RJ45) ST-T60T GSUT
10 E2 (RJ45) ST-T60ET E2 (RJ45) ST-T60ET
ML3000-2
11 E3 (RJ45) ST–C650 EDGE E3 (RJ45) ST–C650 EDGE
12 E4 (RJ45) SPARE E4 (RJ45) SPARE
13 … … …. …

Cable By

Cable By

Patch Box

ST GPP/TPP ST GSEC

GENERATOR GSUT EXT AUX PANEL


EPM

ST GSUT
G60A T60U T60ET C650 WAGO

G60B T60T
WAGO TRANSFIX

Note: This sheet gives ST MSD IEDs to Edge panel switches interconnect details.
ML3000 and patch box fiber Connection (FO) are multimode with LC - 100 Mb/s type ports. SIZE CAGE CODE DWG NO
4110
IEDs Connections are Cat-6 F/UTP with RJ45 ports. g GENERAL ELECTRIC COMPANY B
MAIN eROOM ST MSD IEDs CONNECTIONS 127T3686

DISTR
DRAWN A. BENOIT 2018-02-20

TO
SCALE SHEET
TO EDGE PANEL SWITCHES ISSUED SEE PLM SEE PLM 20 of 23
SIZE DWG. NO. SH. REV.
B 127T3686 21 A

ML1 Port # IEDs ML2 Port# IEDs


MAIN EROOM 1 C1 (LC) EDH-IN (FO) C1 (LC) EDH-IN (FO)
2 C2 (LC) EDH-OUT (FO) C2 (LC) EDH-OUT (FO)
BHC12 SWITCHBOARD 3 C3 (LC) SPARE C3 (LC) SPARE
4 C4 (LC) SPARE C4 (LC) SPARE
A2
5 D1 (RJ45) 88BT1 D1 (RJ45) SPARE
EDH Ring 6 … … … …
ML3000-1 C E G I

D F H J

ML3000-2

VFD PANEL

RS485/TCP
converter

A2

MM200

VFD

88BT1

Note: This sheet gives MSD IEDs to BHC12 Switchboard switches interconnect details.
ML3000 and patch box fiber Connection (FO) are multimode with LC type ports.
IEDs Connections are Cat-6 F/UTP with RJ45 ports.
SIZE CAGE CODE DWG NO
4110
g GENERAL ELECTRIC COMPANY B
MAIN eROOM MSD IEDs CONNECTIONS 127T3686

DISTR
DRAWN A. BENOIT 2018-02-20

TO
SCALE SHEET
TO BHC12 SWITCHBOARD SWITCHES ISSUED SEE PLM SEE PLM 21 of 23
SIZE DWG. NO. SH. REV.
B 127T3686 22 A

MAIN EROOM
ML1 Port # IEDs ML2 Port# IEDs
BMC10 1 C1 (LC) EDH-IN (FO) C1 (LC) EDH-IN (FO)
2 C2 (LC) EDH-OUT (FO) C2 (LC) EDH-OUT (FO)
3 C3 (LC) SPARE C3 (LC) SPARE
EDH Ring 4 C4 (LC) SPARE C4 (LC) SPARE
ML3000-1 C E G I 5 D1 (RJ45) 88BT2 D1 (RJ45) SPARE
A2
6 D2 (RJ45) SPARE D2 (RJ45) SPARE
D F H J 7 … … … …

ML3000-2

A7
VFD PANEL

A2

MM300

88BT2

Note: This sheet gives MSD IEDs to BMC10 Switchboard switches interconnect details.
ML3000 and patch box fiber Connection (FO) are multimode with LC type ports.
IEDs Connections are Cat-6 F/UTP with RJ45 ports.
SIZE CAGE CODE DWG NO
4110
g GENERAL ELECTRIC COMPANY B
MAIN eROOM MSD IEDs CONNECTIONS
127T3686

DISTR
DRAWN A. BENOIT 2018-02-20
TO BMC10 SWITCHBOARD SWITCHES

TO
ISSUED SCALE SHEET
SEE PLM SEE PLM 22 of 23
SIZE DWG. NO. SH. REV.
B 127T3686 23 -

AC : Alternative Current. Irig-B : Inter-range instrumentation group time codes-B type.


AVR : Automatic Voltage Regulator. I/O : Input / Output.
BOP : Balance Of Plant. KVM : Keyboard, Video and Mouse.
C650 : GE GA 650 family IED. LCI : Load Commutative Inverter.
CAT-6 : Category 6 cable, is a standardized twisted pair cable for Ethernet . LCIC : GE GPT Load Commutated Inverter (LS2100) Compartment.
CCR : Central Control Room. LEC : GE GPT LCI and Exciter Compartment.
CSV : Comma-Separated Values (simple file format used to store tabular data). LV : Low Voltage.
DC : Direct current. MCC : Motor Control Center.
DCS : Distributed Control System. Modbus TCP: Modbus protocol under Ethernet, secondary protocol used by ECS system.
DOR : Division Of Responsibility. MDH : Monitoring Data Highway
E(x) : Exciter(x) Controller. MV : Medium Voltage.
ECS : Electrical Control System owned by GE GPT Global Electrical Team. NTP : Network Time Protocol.
Edge Panel: ECS remote IO panel(s) equipped with RTU to digitize conventional NCC : National Control Centre.
hardwired IO for ECS integration. OLTC : On Load Tap Changer.
EDH : Electrical Data Highway. OPC DA : Open Platform Communications protocol for Data Access.
eRoom : Electrical room made of a set of steel compartments (similar to a big OPC AE : Open Platform Communications protocol for Alarms and Events.
PEECC). OSM : On Site Monitoring.
eBuilding : Electrical buildlng made of concrete. OWS : Operation Work Station.
EWS : Engineering Work Station. PCS : Process Control System.
FO : Fiber Optic. PDH : Plant Data Highway Network.
FTP : File Transfer Protocol. PEECC : GE GPT Package Electronic and Electrical Control Cabinet.
G60 : GE GA UR family IED, G60 is a protection relay used for generator PDP : Profibus DP (Decentralized Peripherals).
protection. RG58 : Type of coaxial cable used for IRIG-B signal.
GE GA : GE Grid Automation; supplier of the GE IEDs and ECS. RIO : Remote Input / Output.
GHM : Generator Health Monitoring. RSTP : Rapid Spanning Tree Protocol (for preventing loops on Ethernet networks).
GPG : GE Power Gateway. ST : Steam Turbine.
GPP : Generator Protection Panel. LC : Fiber optic connector type.
GSEC : GE GPT Excitation panel (EX2100) compartment. SCADA : Supervisory Control And Data Acquisition.
GSUT : Generator Step-Up Transformer. SW : Ethernet Switch.
GT : Gas Turbine. TPP : Transformer Protection Panel.
GTG : Gas Turbine Generator. UDH : Unit Data Highway.
HMI : Human Machine Interface. UPS : Uninterrupted Power Supply.
HV : High Voltage. VFD : Variable Frequency Drives.
HVAC : Heating, Ventilation and Air Conditioning .
IED : Intelligent Electrical Device .

SIZE CAGE CODE DWG NO


4110
g GENERAL ELECTRIC COMPANY B
127T3686

DISTR
ACRONYMS DRAWN A. BENOIT 2018-02-20

TO
ISSUED SCALE SHEET
SEE PLM SEE PLM 23 of 23