DESIGN OF PRECAST WALL PANEL 

PROJECT: SMDC LIGHTRESIDENCES 
LOCATION : PIONEER‐EDSA 
DESIGN CRITERIA: 

STRUCTURAL MATERIALS: 

1. Concrete Strength 
Precast Wall Panel           20.68 Mpa (3000 psi) 
 
2. Reinforcing Steel 
Deformed Reinforcement 
a.1 Ø12mm or larger        Grade 60 (414 Mpa) 
a.2 Ø 10 mm or smaller      Grade 40 (275 Mpa) 

WIND LOADING PARAMETERS: NCSP 2001 5TH EDITION 

As Component and Cladding Structural Element 

EXPOSURE CATEGORY:   B 

HEIGHT OF STRUCTURE :   ± 142 m 

MEAN STRUCTURE HEIGHT:   ± 142 m 

IMPORTANCE FACTOR, Iw:   1.00        (STANDARD OCCUPANCY) 

WIND ZONE:       ZONE II

DESIGN WIND VELOCITY:   2.00 kPh 

INTERNAL PRESSURE COEFFICIENT, GCPi =   ± 0.18 

P = q G Cp – qh(GCpi);  q = 47.3x10‐6 Kz Kzt V2 Iw 

NSCP 2001 FIG. 207.8 
 
DESIGN ANALYSIS OF PRECAST WALL PANEL 11TH TO 49TH (Design Applicable to Lower 
Floor) 

11P‐3 (smallest panel) 

WALL SIZE:       W = 3.56 B = 3.04 

EEFECTIVE WIND AREA:  10.82 sq. m    (Note: Window area Included) 

GCp = ‐1.1 ; GCp = 0.5            

APPLYING FORMULAS FROM THE DESIGN CRITERIA: 

GCPi:  +0.18;  GCp:  ‐1.1;    P1 = ‐3.75 kPa 

GCPi:  ‐0.18;  GCp:  ‐1.1;    P2 = ‐2.76 kPa 

GCPi:  +0.18;  GCp:   0.5;    P3 = 0.93 kPa 

GCPi:  ‐0.18;  GCp:   0.5;    P4 = 1.97 kPa 

Pressure Design Load = ‐3.75 kPa 

Consider 1m Strip of the Precast Wall 

Loading (Lateral): 

ω = 3.75 (1.0) = 3.75 kN/m 

PRECAST WALL DESIGN: 

THICKNESS: 100mm  L (unsupported) = 2.6m (3.1m floor ht, beam depth 0.5m) 

ALLOWABLE DEFLECTION = 2600mm / 360 

             = 7.22mm 

ACTUAL DEFLECTION = 5ωL4 / 384EI 

Igross     = 83333333.33 mm4 

Ieffective   = 41666666.67mm4 

ACTUAL DEFLECTION  = 2.51mm < 7.22mm    OK 

 
REINFORCEMENT DESIGN (Due To Lateral Load) 

M max = 1.7(ωL2/8) = 5.4 kN‐m per meter 
Mu  = 5.40 KN/m  ULT  Rn  2.4 
fc’  = 20.68 MPa  ρmin ver  0.0015 
fy  = 414.00 MPa  ρact  0.0063 
Strip  = 1000.00 mm  ρmax  0.0160  0.75ρbal 
thk  = 100.00 mm  ρbal  0.0214 
cover  = 50.00 mm  ρmin hor  0.0025 
Bar Ф ver  = 12.00 mm 
Bar Ф h0r  = 10.00 mm  ρver  0.0063 
each 
d'  = 50.00 mm  125.00 
As hor  (min)  face 
β1  = 0.85  As vert  312.92 
each 
    As vert min  75.00  face 
VERTICAL BARS 
Continous Bar  12.00 
As vert  312.92 
S cont  300.00  As equivalent  376.99sq.m  >    312.92sq.m   OK 
 

USE Ø 12 Reinforcing Bar Spaced at 300 mm o.c. 

USE Ø 12 Temperature Bar Spaced at 300 mm o.c.  

PRECAST CONNECTION 

DOWEL DEVELOPMENT AT EACH POINT OF ANCHORAGE  

(dowel spacing to match precast mesh) 

Factors for use in the Expressions of determining Required Development Lengths for 
deformed bars  and Deformed Wires in Tension 

4.1‐ACI 318 (2010 edition) Page 408R‐29 

α = 1.0; reinforcement location factor 

β = 1.0; coating factor 

αβ = 1.0 < 1.7 

γ = 0.8; reinforcement size factor 

λ= 1.0; concrete weight factor (normal weight) 

c = 1.5 in. 
 

To limit the probability of a pullout failure, ACI 318 requires that: 
 

1.5 0
2.4 2.5 
0.625

(Assume Ktr = 0) 

EQN (4‐2) 

3 fy 3 60000
34 
40 √f c c Ktr 40 √3000 2.4
db

34  

21.25 540  

312.92
540 448.22 450  
376.99

 
DESIGN ANALYSIS OF PRECAST WALL PANEL 11TH TO 49TH (Design Applicable to Lower 
Floor) 

11P‐5 (Largest Panel) 

WALL SIZE:    W = 6.29   B = 3.04 

EEFECTIVE WIND AREA:  19.12 sq. m    (Note: Window area Included) 

GCp = ‐1.05 ; GCp = 0.45             

APPLYING FORMULAS FROM THE DESIGN CRITERIA: 

GCPi:  +0.18;  GCp:  ‐1.05;    P1 = ‐3.57 kPa 

GCPi:  ‐0.18;  GCp:  ‐1.1;    P2 = ‐2.52 kPa 

GCPi:  +0.18;  GCp:   0.45;    P3 = 0.78 kPa 

GCPi:  ‐0.18;  GCp:   0.45;    P4 = 1.83 kPa 

Pressure Design Load = ‐3.57 kPa 

Consider 1m Strip of the Precast Wall 

Loading (Lateral): 

ω = 3.57 (1.0) = 3.57 kN/m 

PRECAST WALL DESIGN: 

THICKNESS: 100mm  L (unsupported) = 2.6m (3.1m floor ht, beam depth 0.5m) 

ALLOWABLE DEFLECTION = 2600mm / 360 

             = 7.22mm 

ACTUAL DEFLECTION = 5ωL4 / 384EI 

Igross     = 83333333.33mm4 

Ieffective   = 41666666.67mm4 

ACTUAL DEFLECTION  = 2.38mm < 7.22mm    OK 

 
REINFORCEMENT DESIGN (Due To Lateral Load) 

M max = 1.7(ωL2/8) = 5.12 kN‐m per meter 
Mu  = 5.40 KN/m  ULT  Rn  2.28 
fc’  = 20.68 MPa  ρmin ver  0.0015 
fy  = 414.00 MPa  ρact  0.0059 
Strip  = 1000.00 mm  ρmax  0.0160  0.75ρbal 
thk  = 100.00 mm  ρbal  0.0214 
cover  = 50.00 mm  ρmin hor  0.0025 
Bar Ф ver  = 12.00 mm 
Bar Ф h0r  = 10.00 mm  ρver  0.0059 
each 
d'  = 50.00 mm  125.00 
As hor  (min)  face 
β1  = 0.85  As vert  295.37 
each 
    As vert min  75  face 
VERTICAL BARS 
Continous Bar  12.00 
As vert  295.37 
S cont  300.00  As equivalent  376.99sq.m  >    295.37sq.m   OK 
 

USE Ø 12 Reinforcing Bar Spaced at 300 mm o.c. 

USE Ø 12 Temperature Bar Spaced at 300 mm o.c.  

PRECAST CONNECTION 

DOWEL DEVELOPMENT AT EACH POINT OF ANCHORAGE  

(dowel spacing to match precast mesh) 

Factors for use in the Expressions of determining Required Development Lengths for 
deformed bars  and Deformed Wires in Tension 

4.1‐ACI 318 (2010 edition) Page 408R‐29 

α = 1.0; reinforcement location factor 

β = 1.0; coating factor 

αβ = 1.0 < 1.7 

γ = 0.8; reinforcement size factor 

λ= 1.0; concrete weight factor (normal weight) 

c = 1.5 in. 
 

To limit the probability of a pullout failure, ACI 318 requires that: 
 

1.5 0
2.4 2.5 
0.625

(Assume Ktr = 0) 

EQN (4‐2) 

3 fy 3 60000
34 
40 √f c c Ktr 40 √3000 2.4
db

34  

21.25 540  

295.37
540 423.09 450  
376.99