SERVO VALVE NULL Bias Current Page 1 of 33

from the Maintenance department...


SERVO VALVE NULL Bias Current
Posted by saha on 24 February, 2009 - 11:06 am
For GE Gas turbine Frame 5 controlled by Mark 5 TMR system, what can make the Null Bias current of a Servo
Valve incorrect? In other words if the Null Bias is far from -2.667mA, What should we check to make the null
bias current close to -0.267mA?

Posted by CSA on 25 February, 2009 - 12:40 am


I'm going to split some hairs here (be very, very detailed) and make some corrections to what you're describing.
This topic can't really be covered completely in a forum like this; it's complicated. But, we're going to take a
short swing at the high points.

In the Speedtronic turbine control panel, the error between a servo-valve output's regulator feedback and its
reference is converted into servo current. When the feedback of a regulator is equal to the reference the error is
zero, so zero error would mean zero current. But, if zero current is applied to the servo-valve, the fail-safe
spring in the servo-valve will make the hydraulic actuator move to shut off the flow of fuel or air or steam.

Null bias current is the value of current that is added to the servo-valve output current to overcome the tension
of the fail-safe spring in the servo-valve. So, some amount of current must be added to the output when the
regulator error is zero (when the regulator feedback is equal to the reference) to provide sufficient current to
overcome the fail-safe spring to keep the device in position to maintain a steady flow of fuel or air or steam. In
the Mark V, null bias current is a *fixed* value of current, defined in the I/O Configurator, that is *added* to
the output to overcome fail-safe spring tension.

In the Mark V, servo current is expressed as a percent of full-scale servo current. 100% servo current is equal to
10.0 mA, so 0.1 mA equals 1.0%.

The servo current values you see when the unit is running or when you are manually positioning a device are
almost never the null bias currents. The servo current values you see when the unit is running are the total servo
current being put out by the control processor, *including* the null bias current value. You can't really see the
null bias current portion of the total current that's being applied to the servo coils *unless the feedback is nearly
exactly equal to the reference.* Then and only then is the servo current value being displayed equal to the the
null bias current and only the null bias current.

And this is done by each control processor independent of the others in a TMR control panel. So, if one control
processor thinks the feedback for some device is different than the reference and different than another control
processor's or processors', the total amount of current from the control processor will be different than the
current from the other control processor(s). Each control processor will have the *same amount* of null bias
current added to its output, but each control processor's output can be different if each control processor thinks
its feedback is different than the others'.

When the regulator feedback is different from the reference, then the control processor will adjust its total
current output *which includes the fixed null bias current value* to try to make its feedback value equal to the
reference value. And each control processor is doing this for every servo-valve output. Again, the null bias
current is a fixed value, defined in the I/O Configurator, which is always added to the total current output of
each control processor.

When something like what you are asking about happens, you need to find out what the feedback values are for
all three control processors for the servo output and you will likely find that one or two of them are very
different from the other(s). If all three control processors don't think the feedback is the same and equal to the
reference (the reference should be the same for all three control processors), then each control processor will
adjust its servo output current to try to make its feedback equal to the reference.

For example, consider the GCV servo output. The GCV regulator feedback is the high-selected value of LVDT

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 2 of 33

feedback from the two LVDTs on the GCV. Let's say that <R> thought the GCV position was 57.8% and <S>
thought the GCV position was 55.4% and <T> thought the GCV position was 54.8%, and the reference position
for the GCV was 55.2%, then the servo currents would likely be unbalanced. And probably by a fairly large
amount. <R> might be putting out -3.9% servo current, and <S> might be putting out - 1.9%, and <T> might be
putting out -2.5%. Those values are *not* null bias currents, but each one includes the fixed value of null bias
current which is defined in the I/O Configurator.

In this example, the problem is *not* the fixed null bias current value. The problem is that the three processors
have fairly different ideas about the position of the GCV and each one is trying to move the valve to the
reference position, and they all have to work together (and that means that one or two are trying to overcome
the other) to keep the valve at a steady state position. The bigger the discrepancy in what each control processor
believes the feedback to be, the bigger the discrepancy in the servo output currents (which include the fixed
null bias current value).

Now, let's talk specifically about the null bias current value. Let's say that the value of null bias current defined
in the I/O Configurator and that was downloaded to and being used by all three control processors was 2.667 %
(the Mark V automatically inverts the value in the I/O Configurator!). Further, let's say all the control
processors were indicating a GCV position of 49.7%, the measured position was approximately 49.8%, and the
reference was 50.0% and the three servo currrents were all indicating about -2.9% per control processor, or
thereabouts.

If you changed the null bias current value in the I/O Configurator to approximately 3.0 (which would
correspond to -3.0%; remember: the Mark V automatically inverts the value from the I/O Configurator!),
downloaded that value to all three control processors, and re-booted all three control processors, you'd probably
find that the indicated valve position feedback for all three processors was nearly 50.0%, the measured position
would be about 50.0%, and the servo currents would be almost exactly -3.0% per control processor. In this
case, the amount of current being displayed for each control processor would be nearly equal to the null bias
current amount, because each control processor thought the feedback was nearly identical to the reference
*AND* because the amount of null bias current was exactly equal to what was required to overcome the fail-
safe spring tension.

But it should be clear that unless all three control processors believe their regulator feedback values to be
nearly identical to each other, the servo currents being put out by each control processor will not be the same.
And it has nothing to do with the fixed value of null bias current being applied to the servo-valve output. The
value of current that is displayed when the unit is running is not just the null bias current unless all three control
processors are using nearly the same value of feedback for the device and the feedback is very nearly identical
to the reference.

The amount of null bias current required to overcome the fail-safe spring is actually a range: -0.267 mA, +/-
0.133 mA, or, -0.133 mA to -0.400 mA (-1.33% to -4.00%). So, the actual amount of null bias current required
for a particular servo may be anywhere between -0.133 mA to -0.400 mA and still be within spec. The value of
*null bias current* doesn't have to be exactly equal to -2.667%, but 2.67% is a fairly good value and works for
the majority of servo-valves in use on the majority of GE-design heavy duty gas turbines. About the only time
that null bias servo currents need to be adjusted is for some DLN valves, and even then, it's questionable
whether or not it's really required.

The regulator feedback is compared to the reference 128 times per second, and the total servo current output is
adjusted as necessary to try to make the feedback equal to the reference. *BUT* the value that's shown on any
display or in any VIEW tool capture or output is only updated four times per second. In other words, the value
of servo current written into the control signal database is only updated 4 times per second, even though it
could be changing at the rate of 128 times per second. (I think that's different for Mark V LM panels, by the
way.)

Lastly, the LFBV uses Liquid Fuel Flow Divider Feedback as its primary control feedback and the SRV uses
P2 pressure feedback as its primary control feedback. So, feedback is not always position. Some LFBVs have
LVDTs as another stabilizing element of the control loop.

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 3 of 33

Posted by A. OZTAS on 25 February, 2009 - 11:33 am


In general: Internal mechanical failure in the servo will lead to deviation of null bias current. Possible causes
are, degraded lube oil (clogging of servo ports), wrong calibration of the null bias (maybe you have refurbished
servo valves from none OEM supplier). Although, there is a way to calibrate the null bias, my advice is to
replace it with new one from OEM.

Good Luck...Tempus Fugit...

Posted by CSA on 25 February, 2009 - 4:23 pm


A. Oztas brings up a point I neglected to address. Usually, when I get this question it's related to one single
coil that has a servo current that is out of balance with the others. One cannot *really* fix the problem with a
single control processor's servo current being greatly different from the other two by changing the null bias
current value.

There is only *ONE* fail-safe spring, so changing the null bias value and downloading it to all three control
processors will only mask the problem with the one control processor. Yes, it might lessen the differential
between the three control processor's servo currents, but it's not addressing the problem of why the one
control processor's servo current is out of balance. That is usually related to the feedback for that control
processor being out of balance with the other two control processors.

If all three control processors have basically the same feedback and it's not very equal to to the reference, then
all three control processors will likely be trying to overcome some problem with the servo-valve: clogging or
varnishing of internal components leading to sticky or sluggish operation, worn internal passages or o-rings.

Also, a single open-circuit in one of the three coils of a servo-valve will cause the output currents from the
other two control processors to increase to try to supply the "missing" torque which would have been
produced by the lack of current in the one coil. (Some documentation refers to electro-hydraulic servo-valves
as "torque motors.") Usually, in this case, the difference between the reference and the feedback will also
usually be a little greater than normal.

A. Oztas brings up another issue which has been reported by many sites which have tried to use rebuilt or
refurbished servo-valves. That is, the the fail-safe spring tension usually is not adjusted per GE-design
specifications after refurbishment. Adjusting the spring tension is not an easy task even in a factory or lab.
One needs special equipment to monitor oil flow-rates and volumes in addition to the currents applied to the
three coils. Every time I've seen people try to adjust null bias spring tension on a servo-valve which is in
service, it has resulted in having to replace the servo-valve (that has been said in previous posts here on
control.com, also).

And usually when they're trying to adjust the spring tension, it's an attempt to bring the servo current of one
control processor into line with the others. And that simply can't be done with the adjustment on a single fail-
safe spring.

As I've said before, I'm saving my pennies to buy Moog. These things are so misunderstood and people
replace them so quickly without understanding how they work or what they're capable of that Moog must be
making a fortune because I know of sites that have replaced a single servo-valve several times before fixing
the real cause of the problem. In the process, the once perfectly good servos get dirty and are not handled very
well, and are basically useless after that.

Cha-CHING!

Posted by sd on 25 February, 2009 - 10:07 pm

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 4 of 33

Wonder why my earlier reply is not shown here.


NVM.. let me rephrase it again now.
Well.. I think you observed is actually some optical illusion.. ;)
In AutoCalib page, the value for null bias current is shown in percentage and not in amperes. Which mean that
-2.667mA is actually shown as -0.267%.
Don't worry too much as your servo is still fine;)

Posted by CSA on 26 February, 2009 - 11:15 am


>Well.. I think you observed is actually some optical illusion.. ;)
In AutoCalib page, the value for null bias current is shown in percentage and not in amperes. Which mean
that -2.667mA is actually shown as -0.267%.

From the fourth paragraph of the first response:


In the Mark V, servo current is expressed as a percent of full-scale servo current. 100% servo current is equal
to 10.0 mA, so 0.1 mA equals 1.0%.

-0.267 mA would be represented as -2.67%.

I just looked through several ACALIB.DAT files, from early Mark Vs (with <I>s) and from very late Mark
Vs (with GE Mark V HMIs). None of them had lines to display null bias current.

ACALIB.DAT is an ASCII text file that ACALIB.EXE uses to configure the displays seen in AutoCalibrate
is running. Would you please open that file on you operator interface and copy one of the lines which carries
the words "null bias" and paste it into a response?

My suspicion is that someone found the TCQA RAM address for the null bias current value that gets
downloaded from the I/O Configurator, or someone has re-labeled the servo current line to read "null bias".

Posted by Walter on 13 March, 2009 - 2:26 pm


In the Mark V, servo current is expressed as a percent of full-scale
servo current. 100% servo current is equal to 10.0 mA, so 0.1 mA equals 1.0%.

According to this explination we tried to compare the current servo values on the Mark V screen with the
ones measured directly on the screw of the board. For instance..

For the SRV (as seen on interface)


<R>
Required Position 15,53
Actual Position 99,43
Servo Current -2,50

<S>
Required Position 15,53
Actual Position 99,39
Servo Current -2,21

<T>
Required Position 15,53 %
Actual Position 99,37 %
Servo Current -2,87 %

Then checking in the file TC2kReport and we found the screw number and board to measure the output

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 5 of 33

tension (?) to the servo. That was <R> QTBA screw number 27 and 29. We got -0,4v in <R> ( bearing in
mind that the resistance is 1Kohm would be 0,4mA), is that what should be? That is far different from the
value we get on the screen (-0,25 mA), means that that on the screen is not taking account of the null bias?

or we are measuring in a wrong place?


How can i get in the demand desplay the signal's name of the requiered position since I can not find it in the
Longname.dat.

Thanks very much in advance.

Posted by CSA on 15 March, 2009 - 1:36 am


The first thing I see wrong with this post is that if the required position is 15.53% and the actual position
is 99%, then I would say that something is really, really, really, REALLY wrong with the servo-valve
output. Because, if there is that much difference between the setpoint and the actual, then the control ain't
working. Was the unit running when you were observing these values and taking these voltages?

QTBA-27 & -29 are for servo-valve output #1. There are eight servo-valve outputs from a Mark V. So, I
think the second thing that's wrong with this post is that we don't know if you were looking at the required
position for SVO1 and the feedback for SVO1. In TC2KREPT.TXT, the column labeled "Signal Name" is
the value you need to look up in the CSP and work "backwards" from that to find the reference signal
name.

SVO1 is usually assigned to the Stop/Ratio Valve of a gas fuel system. The reference for the SRV is
usually signal name FPRG and the feedback for the SRV is usually FPG2. You won't find this in
LONGNAME.DAT. You will find it in the CSP.

And, the signal name for the SRV servo current is usually FAGR.

If you want to see what value of null bias current is being applied to a particular servo-valve output, you
need to look in the I/O Configurator for that particular servo-valve output. And, remember that the value
in the I/O Configurator is *inverted* (negative) in the Mark V. (If you see 2.667, the actual value will be -
2.667%, or -0.2667 mA.)

Whatever value of current you see or measure is the total current that's being applied to the servo coil and
includes the value of null bias current that's being applied to the output. If you've been reading this post,
unless the reference and the actual values for the output are nearly identical the value of current you see on
the display will not be the value of null bias current. From the data you provided, the reference and the
actual are *far* from equal.

Tension is another name for voltage, and since this is a DC output, it can have positive and negative
values of voltage (tension) and current. The typical resistance of a servo coil used for a GE-design heavy
duty gas turbine is approximately 1000 ohms, so -4.0 V DC would equate to a servo current of
approximately -0.4 mA. But, any measurement you make would only be an assumption unless you know
the exact value the coil resistance.

Posted by walter/roberto on 17 March, 2009 - 3:43 am


Hello! Here we go again.

First thing, at the moment we took all that data the turbine was runing at base load (MS 6001B MKV
TMR). Since CSA warned us about the wide difference between SRV required and actual position we
went into the old files ( I'd dare to say ever since commissioning) and found out that that error was as
wide as is currently.

Could be that problem related to the inadequate fuel pression supply? According to CSP FPRGOUT

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 6 of 33

must be 248,1 psi at 99.85% TNH , and our actual P2 is approx 223 psi at the same TNH. So, as
FPRGOUT is not reached ( because of the lack of fuel) the valve goes practicaly to 99 % of its position
in order to provide 248,1 psi. Is that possible?
Other doubt is why we get the signals FPRG and FPG2 in psi and not in % as is should be to set the
position?

Stop Ratio Valve.

<R>
Required Position: 15,50 %
Actual Position: 99,79 %
Servo Current: -1,87 %

<S>
Required Position: 15,50 %
Actual Position: 99,57 %
Servo Current: -2,28 %

<T>
Required Position: 15,50%
Actual Position: 99,55%
Servo Current: -1,97%

As we understand in these posts, the servo current we see in the screen is the TOTAL output current to
the servo, ( servo null bias + output current to adjust the error). So, here the output SVO1 servo current
is - 1,87 % for <R> , then our maths don't work out, since the servo null bias current is already -2,667%.
And measuring on the QTBA SVO1 output currrent we get -0,4 mA ( 4%), which would be more logical
( null bias (-0,2667mA) + output current to the servo). Any clue where are we going wrong? Could be
something wrong with the configuration of SRV Autocalibrate display?

Thanks very much again and sorry for our insistence.


Greetings from Argentina.

Posted by CSA on 17 March, 2009 - 3:29 pm


Hello to Argentina, one of the futbol powerhouses of the world!

"Here we go again." Do you mind explaining that comment, please?

You seem to have pieces of the puzzle and the answers, but aren't able to put them all together. If the
gas fuel supply pressure is less than the P2 pressure reference, then the SRV is going to go wide open
to try to get the P2 to be equal to the reference. Since there's approximately a 0.7 barg pressure drop
across the SRV (typically) that would mean that, per the information you provided, the supply pressure
would need to be approximately 258 psig to keep the SRV from opening fully.

You did not provide the gas fuel supply pressure reading upstream of the SRV. What is the supply
pressure? I have seen clogged y-strainers cause high pressure drops, and most units have a y-strainer
just upstream of the SRV. Has it been checked for cleanliness recently? There's not usually a d-p gauge
across the y-strainer, and if you can read the pressure directly upstream of the y-strainer, what is it
versus the gas fuel supply pressure upstream of the SRV?

Some units have some kind of fuel filters upstream of the y-strainer, as well. Some times they are
coalescing filters or just "sock" filters. If they are present, have they been checked? I was at one site
where they said the d-p gauge had never registered any d-p. When the filter canister was opened, the
filter element had been so dirty at some point that it had ruptured and was effectively non-existent.
Someone also commented that they had had exhaust temperature spread problems a couple of years

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 7 of 33

earlier and that the gas nozzle tips were found to be plugged with some kind of stringy material, the
source of which was never identified. Turns out the gas fuel filter was one of those sock-type filters
made of wound stringy material.

I want to warn you: That is a bad condition to be operating the unit in if you ever experience gas fuel
supply pressure spikes or sudden load decreases. When the Speedtronic panel is putting out excessive
current to try to open the SRV it can go into what's deemed "wind-up". Wind-up can take a split-
second to recover from if there is a sudden supply pressure increase or a sudden load decrease ("load
rejection") and the unit can trip on exhaust overtemperature if it's being operated at or near Base Load
when the disturbance occurs because the current has to be reduced at a rate and it might not reduce the
current sufficiently to prevent a "burst" of fuel from being admitted to the combustors.

If your gas fuel supply pressure can never be greater than approximately 260 psig, you may be able to
ask GE or the OES to recalculate the P2 pressure reference curve to allow the SRV to operate in a
controlling region and fashion. But, be prepared to supply them with a recent gas analysis and some
details of the configuration of the gas fuel supply system. They may also ask for P/Ns (part numbers)
of the gas fuel nozzle tips installed in the machine, and if they're not OES equipment, be prepared to
supply the flow characteristics from the vendor or the sizes of the orifices in the nozzle tips. This
information will be necessary to be able to determine if a lower P2 pressure might be possible, and if
so, to calculate a lower P2 pressure reference curve. Also, be prepared to supply all the start-up, warm-
up, and acceleration FSR Control Constants.

Can you find the section of ACALIB.DAT for the SRV (SVO1 or SVO01) and post it to this thread?
You have never told us where you were reading the servo currents from, and if it's from the
AutoCalibrate display then you might be right: There might be a problem with the configuration of
ACALIB.DAT.

Did you put the signals FPRG, FPRGOUT, and FAGR on a Demand Display or on the Logic Forcing
Display and observe them versus the readings you are seeing on the AutoCalibrate Display?

I would submit that you aren't doing anything wrong with the measurements you're taking, but it's
something with the display values or the display that you're reading the values from. Please put the
above signals on a Demand Display or the Logic Forcing Display and tell us what the differences are
between them and the values you are seeing on the AutoCalibrate display, if that's where you're
observing the values from (which, again, you haven't told us).

0.4 mA (or 4%) would be more likely what one would expect to see if the Mark V were driving the
SRV to be more open than the valve could physically travel such as what you are describing.

If you will look at Section 7, I believe, of GEH-6195, of the Mark V Application Manual, you will see
that the SRV regulator uses FPRGOUT as the primary reference and FPG2 for the feedback of the
regulator summing junction. If the two are equal, then the output of the summing junction is zero,
which means the SRV position is equal to what it needs to be to make the P2 pressure equal to the P2
pressure reference. After the primary regulator summing junction, the SRV LVDT feedback is
compared to the output of the summing junction, and if the summing junction output is zero, then no
change to valve position is to be made.

If there is an error between FPRGOUT and FPG2, then that difference will be treated as a requiring a
change to the valve position, and that error will be compared to the current LVDT position feedback
and the servo current will be changed to make the necessary position change to make the P2 pressure
feedback equal to the reference.

The GCV and IGV regulators are "straight" position regulators and the feedback is from the LVDTs
mounted on the device actuators. The LFBV (Liq. Fuel Bypass Valve) reference is a liq fuel flow rate
and the feedback is from the magnetic speed pick-ups on the Liq. Fuel Flow Divider.

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 8 of 33

But I'd really like to understand the, "Here we go again!" comment.

Posted by walter/roberto on 19 March, 2009 - 5:07 am


Hello CSA!, again from the land of football (no soccer) no offence..;) , you are invited to see a
football match whenever you want!

First of all let us explain to you that we did not mean to be impolite writing here we go again , we
just wanted to express that we are here trying with the same topic again, just that.

Talking about gas fuel supply pressure upstream the SRV we have 260 psi what would be pressure
enough. After reading your explanation it seems that is not a gas fuel supply problem. It is more
likely to be a problem on the Autocalibrate display. The servo currents we provided you were taken
from the Autocalibrate Display. Here goes the ACALIB.DAT from the SRV.

PROC Q
SOCKET 1
SVO 1
IOP 21
CARD TCQA
TITLE GAS STOP RATIO VALVE
PERMISSIVE L3ADJ

POSITION_NEG_SAT 100
POSITION_POS_SAT -0,1
POSITION_SCALE (F2 256,0 0,0 2 % )
MAN_SCALE (F2 128,0 0,0 2 % )

LINE01 BTEXT DESCRIPTION <R> <S> <T> UNITS


line 02 data SVO number <D0A 09> (C1)
line 03 data Regulator type <D0A 19> (H1)

LINE 05 DATA LVDT #1 0% cal. Ref. <D0A 60> (F2 6,667 0 3 V rms )
LINE 06 DATA LVDT #1 100% cal. Ref. <D0A 62> (F2 6,667 0 3 V rms )
LINE 07 DATA LVDT #2 0% cal. Ref. <D0A 64> (F2 6,667 0 3 V rms )
LINE 08 DATA LVDT #2 100% cal. Ref. <D0A 66> (F2 6,667 0 3 V rms )
;LINE 09 DATA LVDT #3 0% cal. Ref. <D0A 68> (F2 6,667 0 3 V rms )
;LINE 10 DATA LVDT #3 100% cal. Ref. <D0A 70> (F2 6,667 0 3 V rms )
;LINE 11 DATA LVDT #4 0% cal. Ref. <D0A 72> (F2 6,667 0 3 V rms )
;LINE 12 DATA LVDT #4 100% cal. Ref. <D0A 74> (F2 6,667 0 3 V rms )

LINE 14 DATA LVDT #1 Voltage <D0A 20> (F2 6,667 0 3 V rms )


LINE 15 DATA LVDT #2 Voltage <D0A 26> (F2 6,667 0 3 V rms )
;LINE 16 DATA LVDT #3 Voltage <D0A 32> (F2 6,667 0 3 V rms )
;LINE 17 DATA LVDT #4 Voltage <D0A 60> (F2 6,667 0 3 V rms )

LINE 23 DATA Position at POS Cur Sat. <D0A 10> (F2 256 0 1 % )
LINE 24 DATA Position at NEG Cur Sat. <D0A 12> (F2 256 0 1 % )
LINE 25 DATA Manual control position <D0A 14> (F2 128 0 1 % )

LINE 27 DATA Required Position <D0A 50> (F2 128 0 2 % )


LINE 28 DATA Actual Position <D0A 58> (F2 128 0 2 % )
LINE 29 DATA Servo Current. <D0A 56> (F2 100 0 2 % )

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 9 of 33

LINE 31 STATUS 1 R R STATUS: <D0A 16>


LINE 32 STATUS 1 S S STATUS: <D0A 16>
LINE 33 STATUS 1 T T STATUS: <D0A 16>
LINE 34 DATA Permissive: L3ADJ L3ADJ
LINE 35 DATA Permissive: SPEED <28% (TNH) TNH

Then we compared the signals in the Logic Forcing Dispay to the same ones in the Autocalibrate
Display, and this is what we get:

In Logic Forcing Display: FPRGOUT :248,5 psi; FPG2: 233,5 psi; FAGR: -2,95 %
In Autocalibrate Display: FPRGOUT (required pos): 15,52 %; FPG2( actual pos): 99,65 %; FAGR:-
1,99 % all values in <R>
I found a signal which it seems to be the reference for us, FSGR, which in Logic Forcing Display is
99,59 % and in the Autocalibrate is, as you saw above 99,65%, more closed to the value. Is it maybe
a wrong signal reference we are seeing in the Autocalibrate Display as FSGR? And last but not
least In our second turbine (TG 2) happens exactly the same with the SRV autocalibrate display.

Again thanks very much in advance.

Posted by Ore Rotundo on 19 March, 2009 - 2:23 pm


Hombre,

This is not football, it look like that we are ping ponging Now get back reality.
Quick look to your ACALIB data shows that is standard configuration for a FR5. I wonder whether
your system is HMI or I ? Or is it may be in the past upgraded to HMI? How about the PROM
revisions? If your SRV is operating at 99%, definitely the upstream FG pressure is below the
specifications as given by the OEM. However this should not give the problems that you describe.
There are two options for your problems:
1) DONT use ACALIB for calibration and monitoring purposes. Use the logic forcing display
and/or pre-vote data display.
2) Verify the ACALIB data for your GT and the revisions of the PROMs. Cross check also the
IO_CFG SVOx configuration (stroke 100 % or 128 %)

Remember that you dont necessarily AUTOCLIB display to perform calibration. Just use the basic
calibration procedure.

Docendo Discumus

Posted by CSA on 20 March, 2009 - 12:14 pm


If you've asked this question before on control.com, can you please provide the URL link to the
post?

My bad for making some assumptions (I really try not to do that, but I failed on this one!). I
assumed that you have verified pressure transducer readings against reasonably accurate gauges
and didn't ask you to confirm that. I assumed the P2 pressure transducer(s) (by the way, how many
transducers does the unit have: 1 or 3?) are reasonably well calibrated and that the feedback (input)
is properly scaled in the Mark V. I've assumed the SRV LVDTs have been calibrated properly and
that the valve is physically at or near full open (something we haven't asked, but which we are

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 10 of 33

asking you to visually confirm).

I'm going to try to explain this again: When the servo-valve regulator feedback is equal to the servo
-valve regulator reference, the servo-valve regulator error is zero. When the error is zero, the servo-
valve output current would be equal to zero mA. However, the servo-valve has a spring which, in
the absence of current (zero mA), will drive the device to shut off the flow of fuel or air or steam.
To overcome the spring and to keep the device in a steady-state position such that the feedback is
equal to the reference, a small amount of current is continually added to the servo-valve output (at
all times!). The only time that the current being applied to the servo-valve's coils is equal to the null
bias current value is when the feedback is exactly equal to the reference and no additional current is
required to keep the device in a steady-state position to make the feedback equal to the reference.

Remember: The Moog servo-valves used for GE-design heavy duty gas turbines are polarity-
sensitive devices, meaning that the polarity of the applied DC voltage affects the flow of hydraulic
oil through the servo-valve. With zero current, there is no force (torque) developed by the torque
'motor' in the servo-valve, and the null bias spring will act just like the application of a positive
current, which would be to shut off the flow of fuel or air or steam. When the regulator error is
zero, the output is zero mA, so the null bias current value defined in the I/O Configurator is
continually added to the output. That's what a bias value is: something that's continually added to
something (or subtracted, depending on the application). So, when the error between the reference
and the feedback is zero, the only current being supplied is the null bias current. And, in my
experience with the Mark V, the displayed value of servo current is always the total amount of
current being supplied, which includes the null bias current. Under normal conditions, only when
the error is zero will the amount of current being supplied to the servo be equal to the null bias
value.

Which brings up another question I haven't thought to ask: To your knowledge, has anyone tried to
adjust the null bias spring tension of the SRV servo-valve?

At this time, based on the information you have provided and what you have chosen to provide, I
cannot explain why the SRV servo current is less than what the expected null bias current should
be. I suspect that in an attempt to try to get the SRV into a controlling position that someone has
changed the null bias current value in the I/O Configurator, but, we don't yet (!) know what that
value is. I might also suspect that someone has done something with the TCQC card configuration
jumpers or even something "unique" in the CSP to try to rectify this SRV situation. Not being able
to look at your CSP and card jumpers, we can'tell that.

I am hoping that by answering the GCV questions that we can establish that one servo output is
operating as expected, but I'm asking a question that I don't know the answer to, and I just might
get a great big surprise, but I'm willing to take that chance at this point.

You have *NOT* provided all the information asked of you. Please don't arbitrarily choose what
information you are going to provide or what information you deem to be relevant or necessary.
We're not asking questions to be making you run around needlessly; we're asking because we aren't
on site and can't get the information for ourselves. And because you wrote here asking for help with
an issue, we presume that you are interested in learning something and providing the information
requested to help you resolve your issue. If you don't want to fully participate in the exercise of
solving your issue, then there's no point in continuing this thread.

Specifically:

1) What is the value of null bias current listed in the I/O configurator for SVO1? (Open the I/O
Configurator, and click on the TCQA card, and scroll to the screen for SVO1, and tell us what is
listed in the null bias current field. Exit the card, exit the I/O Configurator, without saving anything,
and you won't disturb any of the I/O Cfgr. settings.)

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 11 of 33

2) Precisely, where are you measuring this 260 psi supply pressure? At the SRV inlet/supply
pressure gauge in the Gas Fuel Compartment, which would be downstream of the y-strainer, or
some place in the gas fuel supply piping upstream of the two units' y-strainers? From a pressure
transducer on the gas fuel supply? From a pressure transducer on a metering tube and orifice in the
gas fuel supply piping upstream of the unit's y-strainers?

3) Has anyone visually checked the y-strainer recently?

4) Are there any filters upstream of the y-strainers, and if so, what is the d-p across the filters and
have they been visually checked recently?

Now, eight new questions:

1) Please confirm the actual, physical position of the SRV is at or near full open.

2) What is the GCV position indication (from the LVDT feedback, usually signal name FSG (Fuel
Stroke-Gas))?

3) What is the value of FSR?

4) What is the value of servo current being applied to the GCV (usually signal name FAG)?

5) What Diagnostic Alarms are active when the unit is running? (Include any locked-out Diag.
Alarms in the list)

6) Please tell us exactly where you're measuring this 260 psi, and is it psig or could it be psia?.
Many GE-design heavy duty gas turbines use a metering tube and orifice flow-meter to measure
gas fuel flow-rate, and the static pressure transducer is usually calibrated in psia, not psig. So, if
you're reading a static pressure transducer for the supply pressure (and this is usually located
upstream of the gas fuel y-strainer), please confirm the calibration and scaling of the input (the
signal name is usually FPG1, sometimes, FPG3).

7) What are the pressures on the three gas fuel pressure gauges in the Gas Fuel Compartment? One
should be SRV inlet ("supply" pressure; one should be Gas Fuel Valve Intervalve Pressure (P2
pressure); and one should GCV discharge pressure, or gas fuel manifold pressure.

8) Sometimes the pressure drop across the SRV is a little higher; sometimes a little lower. But 0.8
bar to 1.3 par is a typical range. Also, can you describe the SRV? Is it in a combined casting with
the GCV or is it a separate valve from the GCV? If it's a separate valve, is it a rotary valve or a plug
valve?

The fact remains, if the SRV is at 99.93% and the P2 pressure reference is 248.5 psig and the actual
P2 pressure is 232.5 psig (and I presume you are reading this from the P2 pressure transducer
feedback on the Mark V operator interface display; can you please tell us what the P2 pressure
gauge reading is?) then there is *not* sufficient flow capacity from your gas fuel supply to achieve
required P2 pressure. It's that simple. There would generally be no other reason for the SRV to be
open so high and the P2 pressure to be lower than the P2 pressure reference.

Now, is the P2 pressure transducer calibrated properly? Is the feedback scaled properly in the Mark
V? If the gauges in the Gas Fuel Compartment are relatively accurate, this would be a good
indication of whether or not the transducer(s) is(are) calibrated properly and the feedback is scaled
properly.

If the P2 pressure gauge in the Gas Fuel Compartment is reasonably accurate and is indicating
roughly the same pressure as the transducer feedback, then there's just not enough supply pressure
and flow capacity to allow the SRV to operate in a controlling range (which should be something

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 12 of 33

less than 99.93% and less than full open). Because, even if the SRV LVDTs are calibrated properly,
the regulator for the SRV is a pressure control loop and it will put the SRV at whatever position it
needs to be at to make the actual P2 pressure equal to the P2 pressure reference, provided there is
sufficient pressure and flow capacity upstream of the SRV to allow the SRV to control the P2
pressure without going full open (and that just doesn't seem to be the case in this instance, for two
turbines).

The reason we're asking about the GCV information is to try to establish that at least one valve is
operating in a properly controlled fashion, and to see what the value of servo current is that is being
applied to that valve when operating in a properly controlled fashion.

FSGR (Fuel Stroke-Gas Ratio) is the typical signal name for the SRV LVDT feedback; it's not a
reference, is the actual feedback.

The only other thing I could think of to cause the SRV to behave as it's being described is that if the
P2 pressure transducer was not properly calibrated or the feedback (input) was not properly scaled,
but I would expect that reasonably accurate gauges would have alerted you to this issue much
sooner.

FPG2 is not the SRV position, and it's not listed in the ACALIB.DAT section you posted. Lines 27,
28, and 29 in the section you copied displays the valve's reference position, actual position, and
servo current, respectively. I can't recall if the reference position is "active" when the unit is
running, or if it's only "active" when the valve is being manually positioned using AutoCalib. (The
answers to the GCV question may help with that!)

FPG2 is the scaled feedback (in psi) from the P2 pressure transducer(s), which should be calibrated
in psig (gauge pressure). If you have more than one P2 pressure transducer, the you can look at the
signal name FPG2 in the Prevote Data Display to see the individual, pre-voted values of the three
feedbacks, and then report them to us, please.

Lastly, the amount of null bias current being applied to the SRV as understood in this thread has
nothing whatsoever to do with the fact that the SRV appears to be at or near full open in an attempt
to control P2 pressure at 248.5 psig. But it can't because the upstream supply pressure and flow
capacity isn't sufficient to be able to do that. That's what the data you have provided to date tells us.
Perhaps the answers you haven't provided and the answers to the new questions will lead us in a
different direction, but it's not really likely. And, it has nothing to do with null bias current.

I agree with Ore Rotundo; the section of ACALIB.DAT that you have provided seems to be fairly
generic.

Please provide all the information requested, and we can try to get to the bottom of your problem,
which, again, should not be related to the null bias current value.

Posted by servo_2001 on 18 March, 2009 - 4:39 pm


I would like to clarify that the answer is not just the OEM as the solution to the problem. To null the servovalve
is the easiest calibration you can perform to a servovalve. Do your homework and you will see that there are
reputable repair facilities that have been repairing these valves for some time. Our company has specialized in
electro-hydraulic servovalves since 1969. We were schooled at Moog on the repair of their valves. Do not let
the OEM make you think they are the only game in town.

Posted by CSA on 19 March, 2009 - 12:19 am


What's missing from your reply? Contact info for your company.

What's also missing from your reply? The fact that adjusting servo null bias springs is best done in a

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 13 of 33

"laboratory" environment, with controlled flow-rates and measuring equipment. It's easy under those
circumstances.

The problems being discussed here are not generally related to null bias spring adjustment, but rather the
methods of applying a null bias current and why they are necessary and how to "measure" them. And how the
currents being applied (including the null bias current) can be out of balance.

Nowhere in this thread did anyone claim that the OEM was the only game in town. There have been other
posts here on control.com which listed firms which refurbish Moog servo-valves. Can you add yours to the
group?

Posted by Mehul on 21 March, 2009 - 6:50 am


Dear CSA,
Here I have concept of NULL Bias, You are requested to confirm the same.

There is good talk on the Null Bias Current for the servo. We can use the drawing of Servo along with
schematic of IGV or GCV-SRV to understand the concept.

For this talk reference, let us take IGV scheme, the IGV is stable at one position 57 deg. By viewing the
scheme of IGV actuating Piston & Cylinder, both side of Piston must be equal pressured, as CSRGVOUT is
CSRGVBAK(for Mark_IV) to keep IGV at 57 deg STABLE.

Now look at the drawing of Servo, to maintain the both sides of piston equally pressurized, the spool should
be at the middle of the bushing(such that it neither allows any port{connected to one side of piston} to
drain nor gives extra pressure to Port{Other side of Piston}). And thus flapper (Feedback Sleeve) should be
at centre and so the armature should be at the centre. And to keep the armature at physical centre position,
amount of current applied, is null bias current.

Consider what would happen, if the spool is not coming back to centre position. Definitely! it will drive the
IGV in either extreme position.

Now consider, the IGV is required to be open to maintain the Exhaust temperature. The Controller will
change the current to servo such that the armature will forces spool to move. The movement of the spool
will be such that one port will be connected to pressure source and at the same time, opens the other port to
the drain. This will create the pressure diff. on both side of piston. Ultimately Piston will move the IGV to
open. At the end, when CSRGVOUT=CSRGVBAK(command=feedback), once again armature is required
to be at to null position i.e. centre position, which is done by providing null bias current by controllers

Similarly the mechanical null bias key has been provided to adjust the armature at centre positon.

Thanks in advance

Posted by CSA on 23 March, 2009 - 8:10 pm


I will confirm all but the last statement about the "null bias key".

If by null bias key you mean a tool to adjust the null bias spring tension, then, absolutely no! No one
should be adjusting the null bias spring tension of a three-coil electro-hydraulic servo-valve, with the
exception of a facility with the appropriate means to do so and verify proper results.

Mehul, I really appreciate your questions, and anyone else's who's reading this thread and has some
interpretation of this concept they wish to confirm. I find this to be one of the most difficult concepts to try
to explain to people, with or without the ability to use diagrams or pictures, which doesn't seem to make
much difference. I am almost desperately searching for the right words and the right means to explain this
to people.

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 14 of 33

I think that one of the things that most people misunderstand about servo-valves as used on GE-design
heavy duty gas turbines is that they are not like the overwhelming majority of most actuator outputs on
most other types of control systems. Instead of an output that's proportional to desired position such as a 4
-20 mA output being at 12 mA for a reference of 50%, this one is proportional to the error between the
reference and the feedback, plus a null bias current. And if the error is zero then the output is zero, plus a
null bias current. If the error is greater than zero, then the output is greater than zero plus a null bias
current.

It gets even more complicated when there's more than one coil in the servo-valve, such as in a TMR
control panel, and each control processor can output a different current and each servo-valve output
includes a null bias current (the same amount of current) to overcome a single spring.

So, to anyone reading this thread, if you have some idea about how to make this any easier to understand,
PLEASE write and let me know. If it would help to try to relate it to some other control system concept or
input or output, that would be great. But, I've been trying for years to put this in simple, understandable
terms, and I've yet to find the right words, with or without pictures.

Posted by Mehul on 26 March, 2009 - 4:59 am


Thanks once again CSA.

Definetly , one MUST NOT adjust spring tension to set null bias current without proper FACILITY .

I mentioned it here to confirm the null bias adjustment device available with the servo.

Otherwise, one should prefer to replace servo & maitaining clean Pall filter other than service,claening,
replacement of spares for servo.

Regarding Servo Valve Maintenance, one of my earlier Comment in "IGV TEMP CONTROL TRIP"
topic.

"Another thing, cleaning the moog servo or replacing the filter, spares of moog servo requires the
extream extream exteram(03 Times)care to be taken for the cleanliness of the tool tackels, oils, Hands of
personals and envoirement at which the servicing is being carried out. So if possible try to replce the
servo, then serviceing the servo."

Posted by CSA on 26 March, 2009 - 2:55 pm


Many electronic manufacturers used to give away small screwdrivers to use to adjust the
potentiometers on printed circuit cards. There used to be a joke that they gave away those
"tweakers" (as they were affectionately called) so that technicians and supervisors would misadjust the
pots and have to call the manufacturer in to readjust the pots.

I often wonder if Moog doesn't include the little hex key/wrench for the same reason.

It's interesting to note that the originator of this thread hasn't replied to the questions asked to try to
help with their issue (which likely isn't related to null bias current, but may be related to a
misadjustment of the null bias spring!).

Posted by Ore Rotundo on 19 March, 2009 - 1:25 pm


Dear Servo 2001

Maybe its good to highlight that, we are not fundamentally promoting the OEM's and one thing is sure that
we are also not getting paid for it to do it! Our intention is to give the control.com community our opinions

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 15 of 33

and suggestions in order to help them out with their technical issues. The servo valve users are plenty and
indeed healthy competition is welcome, such as after market parts. Finally its all about money, in order to
safeguard the reliability of their asset, professional companies will purchase anyway OEM servos. There are
plenty of other GT users who are purchasing repaired parts such as the servo valves. I know some of these GT
users buying reconditioned servos who are complaining after having the servo valve in service less then a
year, believe or not!

Docendo Discumus

Posted by minister on 17 July, 2009 - 9:45 am


I would like to add some more interesting facts and kindly ask for explanation.

We have 4 Frame 5 non-dln turbines running in the island mode. I have found something odd
troubleshooting the moog of one of the machines, that randomly changes its bias causing 3% position error -
temporary solution we use(unit online) is to recalculate new Null Bias measuring coils voltage and having
coil resistance measured before, then downloading the VSVO. This way it's fine for some time, usually until
next start-up. I have to mention, that we have already tried three different Moogs with the same result.

Back to the moog story. The odd thing is that each unit SRV, GCV and IGV servo currents change at the
same time from one stable value to another one (usually by the step of 3, 4 %). The same time error doesn't
change. I have trended hydraulic pressure 96HQ but there is no sign of the event. Also no sign on P125DC
and N125DC. I'm running out of ideas what to trend.

Also polarity has been checked many times so far by confiming that MKVI is able to drive the valve by
each servo coil separetely.

Although it happens on all four units, the event doesn't occure at the same time looking from unit to unit
(see my trends).

Please check the data collected I uploded below:


http://www.speedyshare.com/476835562.html

Do not be surpirsed looking at these trends. One of our machines (G4) also have out of spec, positive Null
Bias, since commisioning by GE (MKVI config value -12, changing moogs didn't help, anyway machine is
controlled correctly.)

Any explanation on the moog servo current changes? Why all units affected?

Posted by CSA on 18 July, 2009 - 2:14 am


You say you have four turbines and you're only having a problem with one. Or at least that's what it
sounds like. Actually, I can't really tell how many units are having the problem now that I re-read the
message.

But, here goes anyway.

You've changed the servos; you say the problem happens with all the servos.

You haven't told us what Diagnostic Alarms are present when this happens, or before this happens.

Do these units have IS barriers?

If you've been reading this thread, you know that the null bias current is the current required to overcome
the null bias spring tension. So, if the current required to overcome the spring tension changes, it would
seem that either something is making the spring tension change or something is causing the coil resistance

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 16 of 33

to change.

Servo valves are about the most misunderstood device I've ever run across. They're nothing more that
electromagnets which produce small amounts of torque. They're just coils of wire through which DC
current is applied; the polarity and magnitude of the current causes the direction and amount of torque to
change. How can they be so complicated? They're not.

The overwhelming cause of "failure" is oil cleanliness and oil temperature. There's just not much more to
them than that. Very tiny, orifice-like passages and clearances which are very susceptible to dirt and
varnishing.

Is there possibly a problem with oil temperature?

I have seen units with the relief valves set improperly, used as the "pressure regulators" for the hydraulic
pump. This causes excessive flow through the hydraulic pump.

The hydraulic system of a GE-design heavy duty gas turbine is basically a static system, meaning that
under steady-state operating conditions there is no flow. There is only flow when a valve or the IGVs are
being commanded to move.

I've also seen units with the hydraulic accumulator not properly in service. This also causes the flow
through the hydraulic pump to be excessive which could be a cause of high oil temperature.

Have you compared all the hardware ("Berg") jumpers on the TSVOs? And all the configuration settings
on the VSVOs? Of the unit with the problem vs. a unit without the problem? What is the dither set to on
the unit with the problems vs. a unit which seems to be running well (not the one with the whacko null
bias value).

It just doesn't seem like the servos can be the problem here, especially if all of them on one unit are
behaving similarly. There's something else that's common to the servos that the problem.

Another couple of months and I should be in a position to make my bid for Moog. The way these things
get changed on a whim, they must be raking in the cash! I just want to buy the GE-design heavy duty gas
turbine line, and I'll be paying my business loan off very early--I'm sure of that.

The 125 VDC battery supply voltage is converted to voltages by the rack power supplies which are then
used by the VSVOs to drive the servos. It wouldn't seem likely that a problem with 125 VDC battery
voltage would manifest itself in the servo outputs.

There's something different about the hydraulic system of that unit. Or, possibly even and, there is some
configuration and/or jumper settings that are not correct. But, for a Moog servo to be changing its null bias
spring tension requiring on-line null bias current changes? That's just pretty not right.

Anyway, that's about all I can think of. To address what I thought the problem was. Now, I'm not so sure.

One thing's for sure though: When I own that piece of Moog, I' won't be contributing to threads like this
on control.com. I know better than to kill the goose that lays golden eggs.

Posted by minister on 18 July, 2009 - 11:42 am


Thank you CSA for your reply.

>You say you have four turbines and you're only having a problem with one. Or at least that's what it
sounds like. <

Actually we have problem with two servos:

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 17 of 33

1. On one machine the SRV changes it's Null Bias mostly after restart (I have greased the stem already
and stroke after many times, result the same, so it's probably not the friction). This Moog creates error
>3%, to avoid trip exceeding 5% value we just downloaded recalculated null bias. This really drops the
error to zero. Because of production I can't just stop the machine to do it off-line. (I'm aware about on-
line software download, but hardware, single VSVO I tried many times with no bad luck).

2. Another machine GCV has positive Null Bias (MKVI RegNullBias =-11.96), and it's not the polarity.

Investigating these two issues I trended all machines and found interesting fact that I shared on previous
post.

>You haven't told us what Diagnostic Alarms are present when this happens, or before this happens. <

The only alarm we have is the increased position error that can lead to turbine trip. Again, it's not the
machine with positive NullBias value.

>Do these units have IS barriers? <

Yes we have the barriers on SRV and GCV (some MTL-7765ac), none for IGV. I have it planned to run
the machine bypassing them, what do you think? Especially, that two other barriers for seismics on the
same machine had failed.

>Is there possibly a problem with oil temperature? <

I'm going to trend all servo currents with oil temperature starting this afternoon. Right now (2:42PM) the
header temperatures are 57 to 58 deg C, outside ambient 46 deg C (air oil cooler).

>I have seen units with the relief valves set improperly, used as the "pressure regulators" for the
hydraulic pump. This causes excessive flow through the hydraulic pump. <

That's another good hint you gave me. I found our technician resetting hydraulic pressure on the PSV
instead of using pump PCV. I will check remaining units.

>I've also seen units with the hydraulic accumulator not properly in service. <

No accumulators here.

>Have you compared all the hardware ("Berg") jumpers on the TSVOs? And all the configuration
settings on the VSVOs? Of the unit with the problem vs. a unit without the problem? <

All TSVO the same (jumpers), all MKVI hardware configs the same (to be sure, I have also compared
m6b with the MKVI).

Dither Amplitude 2.0, Freq 100hz on all Moogs (including IGV), on all units.

The SRV/GCV we have is the old design, containing both valves in one body, don't think we have to
disable the dither as someone posted dither disabling is recommended for new types of valves.

Regards!

Posted by CSA on 18 July, 2009 - 4:39 pm


One more time: The SRV regulator is a pressure loop. Even if the LVDT calibration is WAY off, the
pressure loop is going to put the valve at the position required to make the actual P2 pressure equal to
the P2 pressure reference. It doesn't make any difference if the valve thinks it's at 35.4% and it thinks it
should be at 28.4% or 44.4%, or if it's actually at 31.4% stroke (physical measurement) and it thinks it

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 18 of 33

should be at 37.1% and the LVDT feedback says it's at 35.9%. As long as the actual P2 pressure is
equal to the P2 pressure reference, everything is perfectly okay. When it's not perfectly okay is
when the unit is a TMR panel and the three servo currents are not fairly equal; THAT'S a problem.

I'll bet any amount of money the differential is related to the calibration method of that combined
SRV/GCV assembly.

Would you list the servo gains and null biases for all of the servos? For all of the turbines? A simple
chart:

GT1 GT2 GT3 GT4


Null Bias/Gain Null Bias/Gain Null Bias/Gain Null Bias/Gain
SRV
GCV
IGV

I don't believe you told us if these are TMR or SIMPLEX Mark VI panels; if so, please remind me.

As far as dither goes, my personal belief is that none is needed with most of these legacy-style
actuators.

I have seen barriers cause all manner of strange problems over the years. They appear to be fine, but
they're not. Also, some seem to be temperature and current sensitive when they start "failing."

Posted by minister on 19 July, 2009 - 10:59 am


Dear CSA,

Thank you this time for your reply!

> One more time: The SRV regulator is a pressure loop.


---- snip ----
As long as the actual P2 pressure is equal to the P2 pressure reference, everything is perfectly
okay. When it's not perfectly okay is when the unit is a TMR panel and the three servo currents are
not fairly equal; THAT'S a problem. <

Thanks for reminding that. The above was also mentioned many times on this forum. Although it's
pressure control loop our concern is not to be tripped by position error.

>Would you list the servo gains and null biases for all of the servos? For all of the turbines? A simple
chart:

GT1 GT2 GT3 GT4


Null Bias/Gain Null Bias/Gain Null Bias/Gain Null Bias/Gain
SRV 2.4/1.8 3.9/1.8 3.2/1.8 -11.69/1.8
GCV 3.3/1.8 3.1/1.8 3.3/1.8 2.65/1.8
IGV 2.61/6.8 2.67/6.8 2.82/6.8 3.1/6.8

The way we calibrate these valves is to lift the stem and insert and leave filler gauge to get rid of the
gap between the actuator and valve stem. This way the valve is still closed and LVDT indicates 2.5%
difference from its rest position.

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 19 of 33

Hope this is the way.

> I don't believe you told us if these are TMR or SIMPLEX Mark VI panels; if so, please remind me.
<

TMR, sorry, should have mention that at the beginning.

>I have seen barriers cause all manner of strange problems over the years. They appear to be fine, but
they're not. Also, some seem to be temperature and current sensitive when they start "failing." <

Can I bypass these barriers? I know it's for EEX zone but I do not recall (I'm not 100% sure) seeing
them on 9E turbine in Europe for example.

After trending the servo currents jumps together with Oil Temperature no relation could be observed
(during night when temperature decreases, the frequency of jumps seems to be the same)

Can anyone trend servo currents for at least 12hours to observe if these jump like it happens here? I
do not understand why three servos jump at the same time and it happen on all machines but at
different times. We have running hrs varying from 6000 hrs to 12000 hrs and we have never change
the lube oil. I wonder if these jumps happen anywhere else?

Regards!

Posted by CSA on 19 July, 2009 - 8:09 pm


You have a TMR control system. That means that each control processor has it's own gain and null
bias for each coil of the servo valve.

Can you please list the null bias for each processor for each servo of each turbine?

One thing all manufacturers do is to "copy" functions to similar applications, like the LVDT
position error check. Since the position isn't the problem for the SRV (the inability to control P2
pressure is the problem), do you think it makes sense to use the same settings for the SRV as for,
say, the IGVs or the GCV?

I'm still confused about how the position error can start out at one value (even if it's zero) and then
change when the unit is running. And I'm confused when you say you download new null bias
value(s). Do you download a new value to one processor? Or to all three processors, one at a time?

As MIKEVI says, there might be a problem with one of the processors thinking that the P2 pressure
isn't the same as the other processors, and that would cause that processor to change its current
output and the other processors would have to change theirs to counteract the other. This happens a
LOT, and if you have three P2 pressure transducers and one of them drifts or has a leak or a wiring
problem, that can cause a problem like this.

How many P2 pressure transducers does each turbine have? One or three or ????

Have you trended the P2 pressures for all three processors to see what they're doing before and
after this problem?

When you put the feeler gauges into the gap prior to performing the calibration of the SRV and
GCV, that's to PUT them in their true zero position. When you remove the feeler gauges and the
valve stems drop and the indication goes negative, that's what's SUPPOSED to happen.

The purpose for the gap is to ensure that the valves aren't held open by the actuator bottoming out.
Some places it's called "closed end overtavel". The true zero stroke position for these valves is

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 20 of 33

NOT with the valve stem fully down when the valve is closed; in that position the valve stem is not
touching the bottom of the valve plug.

The true zero stroke position is when the valve is closed and the valve stem is touching the bottom
of the plug, and that's what the feeler gauges do: They keep the valve stem in contact with the
bottom of the valve plug when the valve is closed and ensure that at the end of the calibration
procedure that the valve will return to the same position as when it started (which is one of the
checks that AutoCalibrate performs when run).

The use of barriers is entirely a function of the code and requirements of the country or regulatory
agency where the unit is installed, OR the policy of the company which is operating the unit. There
are thousands of units operating in all manner of applications around the world which do not and
have never had IS barriers installed.

So, only you can decide if you can operate without the barriers. We don't know the application or
the site conditions so we can't tell you to bypass them. We don't know if the IS barriers are installed
on the LVDTs or the servo-valve outputs.

When you're trending oil temperature, you're not trending the temperature of the hydraulic pump
discharge. You're trending the oil temperature of the oil at the inlet to the hydraulic pump.

I really don't understand this whole thing; just when I think I'm getting a handle on it, you say "... I
do not understand why three servos jump at the same time and it happen on all machines but at
different times...." By "three" servos do you mean all the coils of a single servo valve? Or do you
mean all the servos on all the machines? You say it's only on the SRV, but then you say it happens
on three servos on all machines at different time. Is this happening on the SRV of all machines at
different times?

Again, I can't imagine why the null bias spring tension would change during operation, or why the
coil resistance would change during operation. Heat would seem to me to be the most likely cause
for either, but I've never heard of this problem, or a problem described like this.

And, a lot of times that is a part of the problem: Someone attributes an occurrence to this reason or
that reason without any real evidence that this reason or that reason is causing the problem.

You don't know if the coil resistance is changing or if the null bias spring tension is changing.

All you know is that a position error is changing (increasing) and that you can change (reduce) the
position error by changing the null bias current value downloaded to "the Mark VI" and we don't
know if you're downloading the change to one VSVO or to all three VSVOs one at a time.

I would really like to help solve this problem, but, again, every time I think I'm understanding
what's happening then I re-read the posts and I get confused even more.

I really think MIKEVI has suggested a good course of action, and that you need to also trend the P2
pressures of all the processors to try to understand what's happening.

You should be trending the P2 pressure of each processor, the LVDT feedback from both LVDTs
as read by each processor, and the servo current outputs from each processor.

I'm also keenly interested to try to solve the problem with the outrageous null bias current. You say
you've replaced this servo and the new one still behaves the same way???? And you've tested the
servo current polarity under the individual control of each processor for this device (GCV or SRV
or ???) and it will closely maintain the position with only one processor????

I think there's a typo in your chart, because you've previously said that the GCV of one unit is the

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 21 of 33

one with the outrageous null bias. We really need to know what the running servo currents for each
processor are for the servo with the outrageous null bias value.

Are you sure there's not an oil leak somewhere in the actuator of the device which this servo is
installed on?

I apologize if my response seems a little "random" but I'm really baffled by this and at the same
time very interested to solve these problems.

You should know this: On every GE-design heavy duty gas turbine operating anywhere in the
world, there is likely some error in position feedback vs. position reference on one or more servo
outputs. Some more than others. But, they are all running.

And we're only talking about position feedback vs. position reference. I have been to more sites that
have incorrectly calibrated LVDT feedback so that the actual physical position is way off from the
indicated LVDT feedback. And the turbines still run. And run well.

I heard a former colleague say once a long time ago about GE-design heavy duty gas turbine
control, "This ain't rocket science." And he was very correct. If it were rocket science, GE would
have been out of business a long time ago because if every servo output had to operate with zero
error the units wouldn't run. But they do run, and they run very well.

Sure, in a perfect world we'd all like the position error to be zero, and it should be zero. But, it
doesn't have to be zero. What counts is: Is the position error increasing or decreasing?

This has been said many times before on control.com: The value of something today isn't really
informative. It's the value today vs. the value last hour or yesterday or two days ago or one week
ago or one month ago or six weeks ago, and whether or not that value has changed in that time and
how fast it has been changing.

Sure, a L.O. header temperature value of 90 deg C isn't good, but if the unit has been running for
four years with an indicated L.O. Header temperature of 90 deg C, would you say it's been running
incorrectly? Or would you go to find another way to verify that reading?

In your case, the position reference error seems to be changing relatively quickly and then
remaining relatively constant. From what we can understand. Which changes with every reading.

Sorry; I'm both perplexed and intrigued. And, I'm a very literal person (but you couldn't tell that
could you?).

Posted by minister on 20 July, 2009 - 11:49 am


CSA,

thanks for your post. I appreciate your time spent at the computer.

> Can you please list the null bias for each processor for each servo of each turbine?

The NullBias values I gave are the same in each processor for each servo coil (RST). You
confused me a little with this question. Using Toolbox I have (v11.02.09), when I select
Download Configuration, it goes directly to all three VSVO cards, with no possibility of selecting
destination processor (R, S or T). It could be only possible if all three VSVOs are in Simplex
config like for example Thermocouple VTCC cards. To set-up hardware config you only have
one common field, not three separate fields for R/S/T.

To have different NullBias values in each R/S/T card, the only way that comes to my mind is to

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 22 of 33

remove Ethernet cables during download. Have you heard about MKVI having different NullBias
values for coils on the same servo? What is your way to achieve that?
Gains are of course the same for R/S/T as NullBias and the rest of the HW config.
More on that, I confirmed the config with TSM, gain and null bias values are the same in all three
processors.

What I found using TSM checking regulators (command A*pplications -> R*egultors) and then
servos (commands S1 for SRV, S3 for GCV and S4 for IGV) : G1/G2/G4 have parameter FIX 1
and FIX 2 equal to zero (for all three GCV/SRV/IGV servos) and MKVI LVDT Min/Max
(0/100% position) values at LIMIT HI VOLTS and LIMIT LO VOLTS. The G3, the one that
must have had SRV Null Bias corrected after two last restarts has MKVI values of SRV and GCV
LVDT min/max in FIX 1/FIX 2 fields and LIMIT HI VOLTS and LIMIT LO VOLTS are
different by around +-0.100 (FIX 1 + 0.100, FIX 2 - 0.100). IGV is the same as G1/G2/G4. I'm
not sure if you are familiar with this part of TSM. I found it today looking for any unusual thing.
It may be that someone here started the calibration and haven't fix Min/Max value - have no idea.
Can only check on stopped unit. Also TSM has a lot of stuff that can be checked.

> do you think it makes sense to use the same settings for the SRV as for, say, the IGVs or the
GCV? <

For some reason we have it (5% position error trip), I can't think of the situation that this
protection is needed, but as it is know that SRV is fuel gas pressure controlled valve, its LVDT is
used as a feedback for VSVO card (SRV VSVO regulator type is 2_LVPosMax), so loosing the
LVDT the card probably doesn't know how to adjust servo current (what direction to go).
Am I close?

> Do you download a new value to one processor? Or to all three processors, one at a time? <

OK. See the trend I have uploaded below:


http://www.speedyshare.com/470864238.html

The whole story started there


You can see that one day we started having the error. Servo command had to be higher then the
position required to drive SRV to desired position. Suddenly either SRV position increased by
overcoming the friction or the moog current increased for some reason and then MKVI reduced
SRV command and so we got both value (position and command) at the same level. I'm not sure
what was the reason I can only speculate as above (as I said I greased the SRV/GCV stems with
the same result after restart). Then I started my research and found such Moog current step
changes on all machines (but again, on other machines the do not cause an position error). Once
again, on each machine. lets say on GT1, all three moogs SRV/GCV/IGV indicates the step
change at the same time.
Please see the trend I included in my first post. I highlighted each GT set of moogs with different
color.

Again, in my post I wanted to confirm if anyone has ever observed these step changes, I had
mention GT3 servo problem as an origin.
So, If you help me with all my problems I will be very grateful.

>As MIKEVI says ----snip----

>How many P2 pressure transducers does each turbine have? One or three or ????

>Have you trended the P2 pressures for all three processors to see what they're doing before and
after this problem? <

I have just trended P2 (R/S/T) and see nothing (flat lines during the step change that just

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 23 of 33

happened on GT1 and GT3). Will include it in GT3 trend at next start-up.

> When you remove the feeler gauges and the valve stems drop and the indication goes negative,
that's what's SUPPOSED to happen. <

Yes, that's right (the value (negative) is from 3% to 2.5% depending on machine).

>The purpose for the gap is to ensure that the valves aren't held open by the actuator bottoming
out. <

That is exactly how I understand the valve. I'm assuming the gap is for safety if the seat is worn
and no gap the valve will leak. Also the drawing say to check that gap is within desired limits and
if no grind the piston rod to obtain it.

> The true zero stroke position is when the valve is closed and the valve stem is touching the
bottom of the plug, and that's what the feeler gauges do: They keep the valve stem in contact with
the bottom of the valve plug when the valve is closed and ensure that at the end of the calibration
procedure that the valve will return to the same position as when it started (which is one of the
checks that AutoCalibrate performs when run). <

No doubt about it.

>The use of barriers is entirely a ----snip----.

> So, only you can decide if you can operate without the barriers. We don't know the application
or the site conditions so we can't tell you to bypass them. We don't know if the IS barriers are
installed on the LVDTs or the servo-valve outputs. <

Thanks for advice. I will feel more confident doing it.

>When you're trending oil temperature, you're not trending the temperature of the hydraulic pump
discharge. You're trending the oil temperature of the oil at the inlet to the hydraulic pump. <

No other option for me right now.

> I really don't understand this whole thing; just when I think I'm getting a handle on it, you say
"... I do not understand why three servos jump at the same time and it happen on all machines but
at different times...." By "three" servos do you mean all the coils of a single servo valve? Or do
you mean all the servos on all the machines? You say it's only on the SRV, but then you say it
happens on three servos on all machines at different time. Is this happening on the SRV of all
machines at different times? <

Again, as stated the thing above (it's really difficult to me to explain it as English is not my native
language).

What I can trend, is jump/step change up/down/up/down (and so on) of the total current of each
Moog. But I observed looking at card points ServoIOutxNVR/S/T that it happens also in the same
direction on all three coils (second screenshot I attached, you can call it static observation). So, on
one single turbine, the change happens at the same time on all 9 coils (3xSRV, 3xGCV, 3x IGV),
and you can observe the same on all machines but from machine to machine it's not synchronized.
Please see again the trend and color marked GT's.

>Again, I can't imagine why the null bias spring tension would change during operation, or why
the coil resistance would change during operation. Heat would seem to me to be the most likely
cause for either, but I've never heard of this problem, or a problem described like this.

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 24 of 33

>And, a lot of times that is a part of the problem: Someone attributes an occurrence to this reason
or that reason without any real evidence that this reason or that reason is causing the problem.

>You don't know if the coil resistance is changing or if the null bias spring tension is changing. <

I agree, I don't want to risk and disconnect servo coils one by one online. What I found after stop
that the current is different each time (I register in Excel sheet all NullBias calculations), not
resistance. It stays on all machines 1200- 1300ohm on all machines (barriers give additional
resistance, I think I checked that a year ago).

> All you know is that a position error is changing (increasing) and that you can change (reduce)
the position error by changing the null bias current value downloaded to "the Mark VI" and we
don't know if you're downloading the change to one VSVO or to all three VSVOs one at a time. <

All three at one time. Simply calculation, have all three resistance noted before the start last
month, I measure the voltage for each coil separately, divide V/R, summarize all three results and
finally divide by three to get average (negative result must be placed as positive in MKVI config
and so on). This is the GE calculation way given by the ControlSpec and it works (offline :), for
me also online)

>I'm also keenly interested to try to solve the problem with the outrageous null bias current. You
say you've replaced this servo and the new one still behaves the same way???? <

Actually It has been replaced by GE TA, that left it saying it's fine. They just wanted to leave the
place :))))

> I think there's a typo in your chart, because you've previously said that the GCV of one unit is
the one with the outrageous null bias. We really need to know what the running servo currents for
each processor are for the servo with the outrageous null bias value. <

I wrote G4 - on the trend you will find G4\signal - that was the reason I used it instead of GT4.
Affected valve is SRV.

> Are you sure there's not an oil leak somewhere in the actuator of the device which this servo is
installed on? <

I will check, I have to re-read your posts guys and prepare a checklist)

Finalizing the story: you can see that we have two major problems - very high positive null bias
on one machine running relatively good - position error that disappear after start-up or we have to
help it disappears changing NullBias value (we did it last time instead of waiting).

...And one minor that is servos current step changes on all machines that I accidentally
discovered.

It took all day to think about answers also have a headache. Sorry if I messed something again.

Regards

Posted by CSA on 21 July, 2009 - 12:42 am


In the early days of Toolbox, it was possible to download to individual VSVOs. Maybe that's
not the case any longer; I haven't seen a Mark VI in a couple of years.

I have never seen trends like this. My initial reaction is that there is something about/with the IS
barriers, but that's just because I don't have a lot of experience with them and the experiences I

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 25 of 33

have had have not been very good.

As for the friction comment, when I have seen friction on a gas valve (SRV or GCV) the effect
has been that the servo current increases with no change in position until the device "jumps"
usually to a position past the reference and then the current changes to try to drive device back
to the reference with no change in position until it "jumps" to a position past the reference and
this continues and in some cases gets worse. So, the valve behavior was jumpy and erratic. On
either side of the sticky portion of the valve stems, the action was normal. But where the shaft
was worn and scored (on a couple of turbines) or where the cylinder walls were scored (on a
couple of turbines) the behavior was jumpy and erratic.

From what you describe, it seems that the current just "jumps" and without seeing the valve
position feedback at the time the current jumps, it's difficult to say what's happening.

I don't recognize the IS barriers you cited. Have you reviewed the manufacturer's
manuals/documents to see if these are properly applied?

I would like to know how the *circuit* resistance changes when this phenomenon occurs. It
would be very interesting to monitor the voltages of each servo coil and see what happens. A
change in voltage would be indicative of a change in circuit resistance. Would it be possible to
monitor the voltage across the IS barrier and the voltage across the servo coil?

I do NOT believe the servo coil resistance is changing, but I've been wrong before and I'll be
wrong again. I have seen Moog provide some very good troubleshooting assistance when asked
to get involved. I know they are slow to respond, but when they do get involved they are pretty
helpful.

I don't believe the null bias spring tension is changing.

Have you had your Lube Oil tested for contaminants? And agglomeration (I think that's what it's
called)? Some of the newer formulations of turbine lube oils seem to be causing lots of
problems for servos. I think BP has a formulation that has been used successfully by a lot of
heavy duty gas turbine users.

When these jumps in current take place, does the turbine power output change? Does the unit
continue to run normally or does an operator have to make a change to keep the unit running as
desired?

If the AHJ (Agency Having Jurisdiction (thanks for that Phil Corso!)) would permit a test with
the servo IS barriers disconnected it would be very interesting to see what happens.

I'd really like to know what happens to the position feedback at the time the current jumps.

That's about all I can think of.

Posted by CSA on 21 July, 2009 - 10:48 pm


The more I think about this the more I think if you're seeing it on all the servos on all the units
at your site, the one thing that's common to the gas valves is the IS barriers. I also wonder if
they're also affecting the other servo outputs on the VSVO, such as the IGVs.

I did some checking on the MTL site, and it says the MTL7765ac is primarily for high
frequency low voltage applications. Hmmmm..... I also wonder about the resistance readings
you mentioned, which seem much higher than those listed in the tables in Sect. 8 of the manual.

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 26 of 33

Posted by minister on 22 July, 2009 - 5:27 am


CSA,

I had opportunity to shutdown GT1 and found something interesting.


It seems that "jumps" are not caused by the hydraulic part of the system as these also exist
during cool down and after when Auxiliaries are off.

Trend with some description added (trip occured :) ).


http://www.speedyshare.com/748565606.html

Will try today to bypass barriers and trend again.

> It would be very interesting to monitor the voltages of each servo coil and see what happens.
<

The voltage changes for sure, I had usual average value of around -0.320V after last calibration,
then when I started the machine and found the position error, I made another measurement of
coil voltages and as described before recalculated the NullBias and downloaded new VSVO
config (average voltage this time -0.490V).

> I do NOT believe the servo coil resistance is changing, but I've been wrong before and I'll be
wrong again. <

I hope barriers is the reason. Could it be changing MKVI cabinet inside temperature affecting
them? I wonder if it's sync'ed with the cabinet fan switching on/off (I can simply check it by
keeping all fans on for few hours.

> Have you had your Lube Oil tested for contaminants? <

Yes we have it tested, but we are trying to make it more often (monthly). Nothing unusual last
time, let's see next time.

> When these jumps in current take place, does the turbine power output change? <

Nothing unusual I have trended DWATT as well.

> test with the servo IS barriers disconnected it would be very interesting to see what happens. <

Yep, this I will provide soon.


I have to find some extra terminals for barriers bypassing.

Cheers!

Posted by CSA on 22 July, 2009 - 2:17 pm


This is troubleshooting: Understanding the possible causes of a problem and working to
eliminate them one at a time or to narrow the field of possibilities down to a very few.

I think it's very telling that when these "jumps" occur when the turbines are running that there is
no change in power output. The Mark VI is fast enough to maintain steady and stable power
output in the face of whatever is causing the servo current to have to change. And, even if the
position error increases (for whatever reason) the Mark VI is automatically "compensating" and
keeping the turbine operation stable and steady.

You have not provided any information on specifically what's happening to the LVDT feedback

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 27 of 33

when these jumps are occurring, and if the LVDT excitation and/or feedback also have IS
barriers. If so, what is the manufacturer/part number?

And here's where I'm going to suggest that the problem is not the changing servo currents, but
the changing LVDT feedback. You say that the position error changes, and when that happens
the servo current would change to try to maintain the error closer to zero. Right?

Please trend the LVDT feedback as well as the servo current, and the LVDT feedback from
each LVDT would be the best to trend, not the high-selected value. Even when the unit is not
running.

It would be unusual for the Mark VI enclosure temperature to be changing very much. It should
be located in a temperature- and humidity controlled environment, the emphasis is on control.
Are you saying the temperature in the Mark VI panel, or wherever the IS barriers are located,
changes? If so, by how much during the course of the day? Are there fans controlled by
temperature? If so, that's unusual, not unheard of, but not typical.

I think the barriers you listed are considered "passive" devices and don't require bus power, but
the manufacturer instruction book is really unclear on these particular barriers. If they are
powered, where do they receive their power from?

What IS barriers are used for the LVDTs? Do all the LVDTs have IS barriers?

Another possible test would be to take suitably sized 1000 ohm resistors (heat dissipation) and
connecting them directly to the TSVO in place of the barriers and then trending the servo
current. (This would have to be done when the unit is not running.)

If the current still changes, then I would suggest removing the IS barriers from the LVDT
circuits and monitoring the individual LVDT feedbacks and the servo currents.

This also happens sometimes in troubleshooting: The focus gets placed on the effect rather than
the "affect" (the cause). The whole servo regulator loop needs to be considered: the reference,
the feedback, the output.

Let's not drop the theory that the servo barriers may be the problem, but let's not lose sight of
the other possible contributing factors. You have addressed the hydraulic possibility pretty
conclusively. But, servos do get very warm in the environments they are placed in.

Sometimes, the gas valve servos are located at the top of the L.O. reservoir/tank, where the
vapors collect. The L.O. in the tank is hotter than the L.O. header (which is cooled).

The IGV servo is usually located in the turbine compartment, which experiences large
temperature swings during starting, operation, and shutdown.

Posted by minister on 23 July, 2009 - 12:26 pm


Thanks CSA for you input:

Post update:
>You have not provided any information on specifically what's happening to the LVDT
feedback when these jumps are occurring, and if the LVDT excitation and/or feedback also have
IS barriers. If so, what is the manufacturer/part number? <

No barriers at LVDT at all. Summarizing we have only 6 barriers installed for SRV and GCV.

I have used terminal block to bypass the barriers and during last 12 hours "jumps" occurred

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 28 of 33

again. We can exclude IS barriers from servo current change phenomena, but still have to take
them into account for two running units, (position error and high positive null bias).

Let's keep in mind, that the offline unit is the one controlled "perfectly" (only servo current
jumps" are observed). So let's concentrate on servo current jumps.

> And here's where I'm going to suggest that the problem is not the changing servo currents, but
the changing LVDT feedback. You say that the position error changes, and when that happens
the servo current would change to try to maintain the error closer to zero. Right? <

Right. This gave in another suggestion as the error appears some time after restart. It can be
possible that we loose one LVDT by vibrations while running unit (e.g.. loose wiring) or we are
getting the LVDT back by the same reason.

> Please trend the LVDT feedback as well as the servo current, and the LVDT feedback from
each LVDT would be the best to trend, not the high-selected value. Even when the unit is not
running. <

Trend set-up and running. A hint for people that want to trend LVDT's. You have to turn
Monitors on (we have it unused, but I met the feature used on some sites). Select 1_LVposition
as monitor type, select LVDT you want to monitor (see your Regulator), fill in Mn and
MxLVDT1_Vrms with data you have in your Regulator. Keep in mind that Regulators use
usually two LVDT's, and you have to separate them using two Monitors. After the config is
downloaded you will see each LVDT value in VSVO Card Point section under MON1,
MON2....MON12 (depending of your set-up)

> It would be unusual for the Mark VI enclosure temperature to be changing very much. It
should be located in a temperature- and humidity controlled environment, the emphasis is on
control. Are you saying the temperature in the Mark VI panel, or wherever the IS barriers are
located, changes? If so, by how much during the course of the day? Are there fans controlled by
temperature? If so, that's unusual, not unheard of, but not typical. <

We have HVAC unit for the MKVI room so we have quite good environment.
And yes, we have fans controlled by thermostats, I was aware of this as very often we have to
clean cabinet ventilation inlet filters and fan outlet filters from accumulated fine desert sand.
After trending servo currents yesterday afternoon with all of fans running the servo current
phenomena still exists. The average temperature measured using TBTC cold junction is 30 deg
C (IS barriers are mounted on the back side of the cabinet where TBTC are mounted, also fans
are on MKVI terminal board side only)

> I think the barriers you listed are considered "passive" devices and don't require bus power,
but the manufacturer instruction book is really unclear on these particular barriers. If they are
powered, where do they receive their power from? <

Passive barriers.

> Another possible test would be to take suitably sized 1000 ohm resistors (heat dissipation) and
connecting them directly to the TSVO in place of the barriers and then trending the servo
current. (This would have to be done when the unit is not running.) If the current still changes,
then I would suggest removing the IS barriers from the LVDT circuits and monitoring the
individual LVDT feedbacks and the servo currents. <

Will add to the plan.

> Sometimes, the gas valve servos are located at the top of the L.O. reservoir/tank, where the
vapours collect. The L.O. in the tank is hotter than the L.O. header (which is cooled). The IGV

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 29 of 33

servo is usually located in the turbine compartment, which experiences large temperature
swings during starting, operation, and shutdown. <

That's the case we have, valve servos are mounted inside the tank underneath the valve. IGV in
turbine compartment. As the unit will stay some days, temperature should come down and we
will see possible effect on the trend.

After all day trending:


Please find another trends (40ms sample time), this time also one toolbox .trn file.

1) change observed only on GCV/SRV (I was measuring coil resistance a while before it
happened. Resistance stays always the same):
http://www.speedyshare.com/727988916.html
http://www.spee dyshare.com/314203559.html

2) GCV/SRV/IGV jump (see signal description in first file, scale for some signals is different,
color the same)
"Jump" UP
http://www.speedyshare.com/810365505.html
"Jump" DOWN:
http://www.speedyshare.com/340410574.html

I'm trying try do the same with dither off. (As dither is an AC on the DC command signal, can it
induct something in the circuit?):

After switching dither off, I observed that all current signals (SRV R/S/T, GCV R/S/T, IGV
R/R/T) have moved in the middle of the "jump high" and "jump low" servo current values. It's
moved down by 2% from the high value or 2% up from the low value.
Is it coincidence, when the dither amplitude is also 2%?

Please see dither off trend: http://www.speedyshare.com/860219617.html

These 4% current switches seems odd when I have checked servo currents loading the machine
by 1MW (around +2% GCV and SRV) and couldn't even indicate the difference on the trend. If
it's not the coil resistance that changes, is it whole circuit loop resistance I mean inside MKVI
hardware? The dither seems to be the one not explored :)))

Another experiment: On running unit I have gradually changed dither amplitude for GCV from
2.0 to 0.2% (by 0.2 % step) , and observed servo current travelling from -7 % to -5% without
load or position change.

Again, not to confuse you guys, these are trend taken on the offline machine, the machine that
has no problems with position error. I will troubleshoot affected unit ASAP (read when
available after shutdown - software modification needed to trend LVDT's and servo outputs
separately).

At the end of the post, after 4 hrs of trending servos with removed dither I can confirm no jumps
on offline GT so far (have to finish my shift). Tomorrow morning I will updated whether jump
occurred or not.

CSA, please share your thoughts and suggestions for next checks.

Cheers!

Posted by minister on 23 July, 2009 - 6:12 pm

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 30 of 33

I was thinking in my bed about this changes of the servo current. It's not the resistance that
changes, but the voltage and then current had to compensate the change for the servo to do the
same work (Power = U*I = const).

(I recall having sometime unusual higher voltage across coils during NullBias verification, I
think I wrote the value before).

Ok have to go to sleep

Posted by minister on 24 July, 2009 - 3:22 am


Update:

After switching the dither off I haven't observed any more jumps last night.

I'm going to do another experiment, put all three servos on different dither frequency and
amplitude trend. As MKVI fastest sample time is 40ms I should see oscillation at least on
12.5Hz and 25Hz dither trend. I want to check if there is a relation between jumps and dither
frequency.

I suspect that these jumps are just recorded extrema of the oscillation signal when its frequency
is higher than the sample rate. The trending tool gets periodically unsynchronized with the servo
current oscillation generator.

Catch you later.

Posted by minister on 24 July, 2009 - 12:32 pm


Update 2:

I can observe full curve oscillation for servo currents with 12.5 Hz and 33Hz frequency dither.

The 25Hz (40ms) dither as being the same as trend sample could be catched only as shown on
attached the screenshot:

http://www.speedyshare.com/660758165.html

We ll, now I will focus on the other two issues I have here. I will write more when I have a
chance to make more tests on these machines

Regards

Posted by CSA on 24 July, 2009 - 1:08 pm


This explanation would make more sense, especially because there is no upset in the turbine
output when these "jumps" occur.

But what isn't explained is the position error that you reduce by changing the null bias.

I'm not a fan of dither for GE-design heavy duty gas turbine applications. The nature of
operation doesn't really cause the control valves to require dither from my experience, though
I've recently been made aware of some "lore" (because it's not documented anywhere) that there
was non-configurable dither built into the Mark V. But there wasn't any dither in the Mark IV or
earlier Speedtronic panels because the servo outputs were all analog circuits and there wasn't
any dither that I was aware of.

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 31 of 33

GE Trending tools can be misleading, as can any manufacturer's. Technology is great, but,
digital technology has its limits, and this is one of them. An old-fashioned pen-and-ink chart
recorder had its limits as well. In general, and this case is probably a great exception because of
the variable frequency rates for the dither option, the GE Trending tools are pretty good because
the execution rate is not generally higher than the fastest trending rate. But, again, this could be
an exception because of the rate issue. Very highspeed toggling of discrete inputs is also hard to
catch on GE Trending tools.

This explanation also makes more sense because of the repeatable nature of the "jumps". They
never seem to increase or decrease by more than the same amount, at least from the trends
you've sent.

But, the position error, which I haven't really seen a good trend of, is still puzzling.

Posted by minister on 25 July, 2009 - 4:23 am


> But, the position error, which I haven't really seen a good trend of, is still puzzling. <

Please see another trend I found in my collection for the position error.
http://www.speedyshare.com/900781673.html

The error wasn't so high that time and went back to normal by itself. (I only changed NullBias
having the alarm above 3%).
Odd is, the step change is recorded at the same moment, it could be that what caused the error
created also a delay (momentary desync) for trending tool (???)

(what happens during that moment can be seen on this zoomed trend:
http://www.speedyshare.com/585332895.html)

Looking at the trend and step changes, the overall picture is very confusing - that's why I
wanted to raised the step changes issue.
The dither on this machine has been disabled yesterday (machine online).

What I need for my tests is to set-up servo currents and LVDT's to be trended all separately.

Regards

Posted by MIKEVI on 18 July, 2009 - 3:04 pm


Dear Minister,

I offer this suggestion as something to trend, although from your post it is difficult to tell if this is
happening on one gas control valve only or multiple valves. And if the problem is on one unit or multiple
units.

Anyway I had an issue recently with a frame 7ea machine. We were intermittently getting an alarm for
low P2 interstage pressure, at the same time we noted the SRV valve position was erratic. Trending the
position of the SRV in the MKVI confirmed that the SRV valve was not holding a steady position, under
constant load and constant main inlet fuel gas pressure. I trended the SRV servo current known as "fagr"
and found it was erratic during the event. I then trended the individual servo currents from each MKVI
core, in my unit these are called FAGR_R, FAGR_S, and FAGR_T. What I found by running a high speed
trend, 40ms, was that intermittently the "T" core would decide to fight the other 2 cores, it would try to
close the valve. The other 2 cores, "S" and "T" would respond by opening the valve. Then "T" would
decide to go back to normal, and "R" and "S" would have to catch up.

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 32 of 33

I don't know if this will help, but it would be something else for you to check. Please also note that
replacing the VSVO card repaired the problem. Also note that I have seen some sites where the signals
were never added at the card level to be able to trend the servo currents individually. Look at your .m6b
file, under the VSVO card points, for the given regulator you are having trouble with look at the
"ServOut#NVR, ServoOut#NVS, and ServoOut#NVT. If there is no point associated with it, it will say
"not used", if that is the case you will need to create a point for each card point and download before you
can trend the currents individually.

Again this may not be the problem, but it would be something else you can check. Lastly this assumes that
your MKVI is a TMR system, and not a simplex.

Posted by minister on 19 July, 2009 - 9:21 am


Dear MIKEVI

Thank your for reply.


I have read your post about the servo current trend 40ms before. I have this it in my plans but have to
wait for scheduled shutdown to create new signal PINs.

Good idea with testing another VSVO. I realized I have one unused VSVO (R/S/T) and two terminal
boards.

minister

Posted by MIKEVI on 20 July, 2009 - 10:55 am


Minister,

the great thing about GE's control systems are that they have lots of great tools to use for diagnosing
problems. The downside is that all the same tools are not given to all the customers (some .m6b have
pins, some don't etc.) I am not sure where the ball gets dropped, either during commissioning or
straight from Salem. But no matter, we have this forum full of knowledgeable people to take advantage
of. And best of all we have a participant such as yourself that provides the information we need to try
and help solve a problem, and hopefully we all learn something in the process. I wish you continued
luck with your issue, and look forward to you resolving the problem.

Posted by minister on 21 July, 2009 - 3:37 am


MIKEVI

The forum is great thing, I agree with you.


I will update my post if I get any new information.

From Control Engineering magazine...


Related articles from Control Engineering magazine
- National Instruments introduces Wireless Sensor Network Platform
- Industrial network selection advice from Rockwell Automation
- System integrators cite product experience in the 2009 Automation Integrator Guide
- Hydroelectric plant in Hawaii upgrades control system
- National Instruments releases LabView 2009
- Chicago waste water project awards control platform contract to Emerson
- Eurotherm releases EtherNet/IP for EPower SCR power controller

http://www.control.com/thread/1235491574 05/08/2009
SERVO VALVE NULL Bias Current Page 33 of 33

- Wireless Standards
- Dataforth 8B33 signal conditioning module measures true RMS, signal power
- Harting Han-Quick Lock terminals: Reliable, space saving
Above articles copyright 2009 Reed Business Information. Subject to its Terms of Use.

Your use of this site is subject to the terms and conditions set forth under Legal Notices and the Privacy Policy.
Please read those terms and conditions carefully. Subject to the rights expressly reserved to others under Legal
Notices, the content of this site and the compilation thereof is © 1999-2009 Nerds in Control, LLC. All rights
reserved.

Users of this site are benefiting from open source technologies, including PHP, MySQL and Apache. Be happy.

http://www.control.com/thread/1235491574 05/08/2009

Das könnte Ihnen auch gefallen