projects from V4 to V7
Siemens
SIMATIC WinCC Industry
Online
https://support.industry.siemens.com/cs/ww/en/view/44029132 Support
This article is taken from the Siemens Industry Online Support. The terms of use
stated there apply (www.siemens.com/nutzungsbedingungen).
Security Siemens provides products and solutions with industrial security functions that
infor- support the secure operation of plants, systems, machines and networks.
mation In order to protect plants, systems, machines and networks against cyber
threats, it is necessary to implement – and continuously maintain – a holistic,
state-of-the-art industrial security concept. Siemens’ products and solutions only
form one element of such a concept.
Customer is responsible to prevent unauthorized access to its plants, systems,
machines and networks. Systems, machines and components should only be
connected to the enterprise network or the internet if and to the extent necessary
and with appropriate security measures (e.g. use of firewalls and network
segmentation) in place.
Additionally, Siemens’ guidance on appropriate security measures should be
taken into account. For more information about industrial security, please visit
http://www.siemens.com/industrialsecurity.
Siemens’ products and solutions undergo continuous development to make them more
secure. Siemens strongly recommends to apply product updates as soon as available and
to always use the latest product versions. Use of product versions that are no longer
supported, and failure to apply latest updates may increase customer’s exposure to cyber
threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security
RSS Feed under http://www.siemens.com/industrialsecurity.
© Siemens AG 2019 All rights reserved
Conversion
Conversions affect parts of a project. This happens, for example, when changing to
a new service pack. Here, for example, only the WinCC Runtime images or the
libraries have to be converted.
1.2 Compatibility
Please observe the compatibility of SIMATIC WinCC with the used operating
system incl. Service Pack, Step7 and other SIMATIC products.
An overview for the compatibility of SIMATIC WinCC V5, V6 and V7 can be found
under the following link.
© Siemens AG 2019 All rights reserved
https://support.industry.siemens.com/cs/ww/en/view/64847781
Note If you want to migrate a WinCC project from another time zone to a newer
SIMATIC WinCC version, it is absolutely necessary to set the time zone on the
migration computer to the time zone from which the project originates.
In WinCC, the UTC time is used in the databases. Errors may occur in the
calculation of this time if the time zone is set incorrectly.
Note You can use the scheduler function of the "Windows Backup" to create a daily or
weekly backup of the WinCC project.
The backups can also be placed on external data carriers or network drives.
A log file is created for each backup.
The runtime data in the WinCC project folder "ArchiveManager" are also
archived.
The following graphic shows which intermediate steps you have to take to migrate
WinCC projects from previous versions.
Note Experience has shown that some customer projects cannot be upgraded with
version leaps from their history. Here an upgrade from version to version is
useful, from V6 > V7.0 > V7.2 > V7.5
With the WinCC Migrator you have the possibility to upgrade projects from version
3.x to the current version v7.5. Due to software and compatibility some
intermediate steps are necessary. These can be found in the following table up to
version 7.5. The upgrade from V6 is shown again in detail in the following pictures.
Table 1-2
WinCC current version Upgradeable to version
V3.x V4.02 SP3
V4.02 SP3 V5.0 SP2 or 5.1 SP2
V5.0 SP2 or 5.1 SP2 V6.0 SP1-4 or V6.2 SP2-3
© Siemens AG 2019 All rights reserved
WinCC V6.0
WinCC V6.2
WinCC V7.0
WinCC V7.0 SP1
© Siemens AG 2019 All rights reserved
WinCC V7.0
WinCC V7.2
WinCC V7.3 SE
WinCC V7.4
WinCC V7.5
WinCC V7.0
WinCC V7.2
WinCC V7.3 SE
WinCC V7.4
WinCC V7.5
© Siemens AG 2019 All rights reserved
6. Migration testing
7. Adjusting the project
Note Migrated projects need to be tested. The system operator himself is responsible
for proper functioning!
Note The WinCC V3 licenses are still valid in SIMATIC WinCC V4.
Activities
• Compiling all functions
• Generate header anew
• Open Picture Tree Manager and exit with Save.
• Under the menu item "Options", "Recalculate collective display hierarchy completely
when saving" must be set.
WinCC system messages (without using the Basic Process Control option)
• Some new WinCC system messages were inserted and already existing system
messages were adapted in text and number.
• In order to receive these extensions/corrections in the system message window, the
system messages of existing projects must be re-imported.
• Proceed as follows:
• Start the Alarm Logging editor.
• Select "WinCC system messages..." from the "Tools" menu.
• In the "WinCC System Messages" dialog box activate "Create new system
messages, overwrite existing ones".
• Click the "Create" button.
Table 2-2
No. Procedure
1. Converting the "Global Library"
In the Control Center, open the context menu of the Graphics Designer and
activate the entry "Convert Global Library".
2. Converting the Project Library
Open the context menu of the Graphics Designer in the Control Center and
activate the entry "Convert project library".
3. Converting Graphic Images
In the Control Center, open the context menu of the Graphics Designer and
activate the entry "Convert images".
4. Split Screen Wizard
In the Control Center, open the context menu of the Split Screen Wizard in Base
Data and activate the "Open" entry.
5. Alarm Logging Wizard
In the Control Center, open the context menu of the Alarm Logging Wizard and
activate the "Open" entry.
No. Procedure
6. Converting the user archive
The conversion of the user archive is accomplished in two steps:
• Converting the archive structure
• Converting the runtime data
Requirements
Link to online support
© Siemens AG 2019 All rights reserved
Note Further information on permitted special characters can be found in the system
overview under "Configuring with WinCC" > "Not permitted characters".
Note The SIMATIC WinCC V3 and V4 licenses are also valid in V5!
No. Procedure
3. Converting the Global Library
• In WinCC Explorer, open the context menu of the Graphics Designer and activate
the entry "Convert Global Library".
© Siemens AG 2019 All rights reserved
No. Procedure
5. Converting images
• In WinCC Explorer, open the context menu of the Graphics Designer and activate
the entry "Convert Images".
• Confirm the message that the trend and alarm controls will be replaced.
© Siemens AG 2019 All rights reserved
• All images of the WinCC project will be converted to the new version.
No. Procedure
7. Converting User Archives
• Converting the archive structure:
• Start the editor "User Archive" in the WinCC Explorer.
• In the "Convert old archives" dialog box, select the user archive to be converted and
start the conversion with the "Convert" button.
• Exit the dialog window with the "Close" button after the conversion has been
completed.
• Save the converted archive structure.
No. Procedure
8. Display in Runtime
• If data of a correctly imported user archive is not displayed in Runtime, then the
configuration data must be linked again:
• Open the Graphics Designer.
• Reconnect the table controls to the user archive.
• Save the image.
9. User archives (before WinCC V4.02)
• The conversion of user archives created with WinCC older than V4.02 is not
possible if the archive and field names are longer than 20 characters at the same
time.
• For problems related to converted user archives, it is recommended to create user
archives with WinCC version V5.1 SP2.
10. Persistence
• A persistence configured in the tag logging is not transferred during conversion. The
persistence must be newly configured in the converted project.
11. Split Screen Wizard
• In WinCC Explorer, open the context menu of the Split Screen Wizard in Base Data
and activate the "Open" entry.
© Siemens AG 2019 All rights reserved
No. Procedure
13. If you have used the Basic Process Control option in an existing project, the following
steps are necessary to convert the project:
• Using the Split Screen Wizard.
• Using the Alarm Logging Wizard.
• Converting the Global Library.
• Converting the Project Library.
• Converting Graphic Images.
• Open Tag Logging and exit with Save.
• Open Picture Tree Manager and exit with Save. Under the menu item "Options",
"Recalculate collective display hierarchy completely when saving" must be set.
14. If it is a multi-user project with multi-client connections, all packages on the servers
should be deleted, recreated and reloaded on the multi-clients.
runtime database.
• This has changed the name of the database tool "isql.exe". The new name is
dbisqlc.exe.
• While WinCC is accessing a database, the parameter DSN=DataSourceName must
be used when calling dbisqlc.
• A call using a C program can look as follows:
ProgrammExecute (dbisqlc -q -b -c " uid=dba; pwd=sql; dsn=CC_test_01-04-
18_14:41:11R" select * from msarclong; output to c:\deldelde.txt)
Note You can only convert images and libraries from one WinCC version to the next
main versions. For example, if you want to convert images from WinCC V5.0
SP2 to V6.2, you must first convert the images to WinCC V5.1, then to WinCC
V6.0, and then to WinCC V6.2.
© Siemens AG 2019 All rights reserved
WinCC V6.2 provides the Project Migrator for this purpose which automatically
migrates the project's configuration data, Runtime data and swapped data.
Installation
No. Procedure
1. Start the installation DVD of WinCC V6.2.
2. Select “SQL Anywhere Studio 7" from the "Other Software" menu. Follow the
instructions in the Sybase SQL Anywhere 7 setup.
3. Upon request, insert the installation CD for WinCC V5.0 SP2 or WinCC V5.1 into the
CD drive.
© Siemens AG 2019 All rights reserved
4. If you have activated the autorun function in your operating system, the inserted CD
will be started. The started autorun program of WinCC V5 is not required for the
migration. Close the program with "Exit".
5. Click the "Repeat" button in Sybase Setup. Sybase SQL Anywhere 7 is installed.
6. Restart the computer.
You must upgrade the existing authorizations if you have received WinCC as
upgrade from V5.x to V6.2. The same is applicable to authorizations of
communication drivers and WinCC options.
Upgrade to WinCC V6
After an upgrade from WinCC V5 to WinCC V6 only one V6 license is available.
This license is not recognized by WinCC V5.
© Siemens AG 2019 All rights reserved
New licenses
If you have configured more than 512 archive variables in your project, you will also
need a license for archive tags starting with WinCC V6.
Note If an upgrade license is used, the authorizations for WinCC V5.x are converted to
V6.2 licenses when upgrading to WinCC V6.2.
License upgrade
Upgrade the licenses in the Automation License Manager from version 5 to version
6.
Table 4-2
No. Procedure
1. Insert the Powerpack License Key disk.
2. Start the Automation License Manager using the Start menu. In the navigation
window, select the drive where the license to be upgraded is located. Select this
license from the table.
3. Select menu instruction "License Key" > "Upgrade...". The upgrade process is
started.
4. The upgrade process concludes with the transfer of the upgraded license to the
local drive.
Note Update licenses for the options redundancy, user archive and server are
included in the update packages RC and RT.
Note The migration of a project can only be started once. Only swapped data can be
migrated subsequently.
Table 4-4
No. Procedure
1. Check the following setting in Windows Explorer prior to the start of the Migrator
© Siemens AG 2019 All rights reserved
Project:
In the menu "Tools" > "Folder Options" > "View", in the area "Advanced Settings", the
check box for "Hide File Name Extensions for Known File Types" must not be
activated.
2. Open "Simatic" > "WinCC" > "Tools" > "Project Migrator" in the operating system Start
menu. Project Migrator opens with the "CCMigrator - Step 1 of 3" start window.
No. Procedure
3. Select the project directory, in which the V5 project is located by clicking on the button.
The "Configuration data" check box is already activated in the "Select the desired data"
area.
Select all data to be migrated. If available, you can also select the path of your backup
archives. These will then also be migrated to the new WinCC version.
4. Click on "Continue". The "CCMigrator - Step 3 of 3" window opens. The Project
© Siemens AG 2019 All rights reserved
5. If migration was successfully completed, the Project Migrator sends the following
message: "Data was successfully migrated."
Click "OK" to close the dialog.
You can use the Project Migrator to migrate runtime data, configuration data and
Note outsourced runtime data individually!
Adapt the setting for "SIMATIC Logon" in the user administration as required.
• Enter the User Archives option in the startup list of the WinCC computer properties
The following standard print jobs and layouts can no longer be used in WinCC V6.2:
• @Report Alarm Logging RT Revolving archive (print job)
• @Report Alarm Logging RT Sequence archive (print job)
• @alrtfoa.RPL (layout)
• @alrtuma.RPL (layout)
Use the following print jobs and respective layouts instead:
• @Report Alarm Logging RT ShortTerm archive New (print job)
• @Report Alarm Logging RT Sequence archive New (print job)
• @CCAlgRtShortTermArchive.RPL (layout)
• @CCAlgRtSequenceArchive.RPL (layout)
Note During migration, the Runtime data and exported data are saved in a common
database.
When the migration has finished, the Project Migrator displays the message:
• "Migration has finished with errors.
See <Pfad>\CCMigrator.txt file for details."
Cancelation of Migration
• When the migration is canceled, migration can be restarted after clearing the fault. Do
not use the project containing the faulty migrated project, but a copy of the backup.
Diagnosis files of the Project Migrator
• CCMigrator.txt
• DTSPackages.log
• The diagnostic files are located in the project directory.
Diagnostics file for converting pictures
• When you convert images, WinCC logs error messages and warnings in a log file
named CONVERT.LOG.
• The file CONVERT.LOG can be found in the graphics directory "GraCS" of the current
WinCC project.
Differences to V5.1
© Siemens AG 2019 All rights reserved
Differences to V5.1
• There is no additional license required for the option package Basic Process Control.
• The option package Video is omitted.
• DBStartEngine
• DBStopEngine
New functions
The following functions are new in WinCC V6.0 or higher:
• DBDataBaseAttach
• DBDataBaseDetach
• MldRegisterMsgEx
• MldUnRegisterMsg
If channels are used in the migrated project which are no longer supplied with the
material supplied, the corresponding process tags are not displayed in the tag
management following the migration.
When the tag management is subsequently opened for the first time, a dialog
appears prompting the user to install the driver. The relevant recommendations are
explained in the Chapter "Differences Between predecessor versions and WinCC
V6.2".
The process tags can be reconfigured prior to the migration. Move the process
variables to another communication driver, e.g. OPC. However, you must adjust
the addressing for all moved process variables.
The process tags can be more efficiently reconfigured using the WinCC
Configuration Tool. The "Connections/Groups" sheet in the File Manager can be
used to create connections under a different communication driver. Use the "Tags"
sheet to readdress the process tags and adapt the properties.
The following channels are no longer supplied for WinCC V6.2:
• Allen Bradley DH DH+ DH485
• Allen Bradley Serial DF1
• Applicom Multi Protocol Interface
• GE Fanuc SNP SNPX
• Mitsubishi FX
• Modbus Protocol Suite
• Modbus Serial
• SIMATIC S5 PMC Ethernet
• SIMATIC S5 PMC Profibus
• SIPART
Note OPC can be used, for example, as an alternative. Some channels are supported
as add-ons. Further information can be found in the section "Differences
between WinCC V5 and WinCC V6" in the WinCC Information System.
VBA code
Backup the "@GLOBAL.PDT" file before installing WinCC V6.2. The file contains
your global VBA extensions, for e.g. some menus. The file is replaced when you
install WinCC V6.2.
Procedure
1. Navigate to the <WinCC installation directory\bin> and copy the file
"@GLOBAL.PDT " to another directory.
2. Install WinCC V6.2.
3. Copy the file "@GLOBAL.PDT" from your storage directory to
<WinCCInstallationsverzeichnis\Templates >
4. Migrate the WinCC project.
© Siemens AG 2019 All rights reserved
Note:
The installation notes, when installing V7.5
The released operating systems for SIMATIC WinCC V7.x can be found in the online
support under the following link:
https://support.industry.siemens.com/cs/ww/en/view/64847781.
Pictures may only be converted when they do not contain "Unknown Objects".
"Unknown Objects" are picture objects whose associated object server is not
installed, e.g. unregistered ActiveX Controls.
Once images have been saved or converted with WinCC V7.5, it is no longer
possible to open the images with the previous version of WinCC.
Conversion of the pictures and libraries cannot be undone. A downwards
© Siemens AG 2019 All rights reserved
conversion of WinCC V7.5 images back into WinCC V6.x images is not possible.
If you select a picture that is not converted, it can lead to faulty WinCC operation.
Note Pay attention to conversion functions from strings to floating point numbers and
© Siemens AG 2019 All rights reserved
Requirements
• WinCC V7.2 Update 7 (With Update 7 the language settings for already
migrated C-Scripts can be changed.) or V7.2 Update 7 must be installed.
• WinCC runtime is finished.
Note If you use an upgrade license, when upgrading to WinCC V7.5, the
authorizations for WinCC (<= V6.0 SP2) are converted to V7.5 licenses.
If you have purchased a WinCC Upgrade Package V6.x, then upgrade your
licenses with the included Powerpack License Disk with Upgrade License. Your
existing licenses will be upgraded to WinCC V7.0 licenses.
© Siemens AG 2019 All rights reserved
Table 5-2
Step Procedure
1. Insert the USB stick of WinCC in the USB port.
2. Start the Automation License Manager using the Start menu. In the navigation
window, select the drive where the license to be upgraded is located.
Select this license from the table.
3. Select menu instruction "License Key" > "Upgrade...". The upgrade process is
started.
4. The upgrade process concludes with the transfer of the upgraded license to the
local drive.
5. V7 licenses can be used for V6.2 and V6.0 SP3/4.
• V7.0 archive licenses can only be used on V6.2.
• Archive licenses V6.2 can be used on V7.0.
6. Upgrades are available from:
• V6.0 SQL 2000 ➔ V7.0 SQL Server 2005 SP2
• V6.2 SQL 2005 SP1 ➔ V7.0 SQL Server 2005 SP2
• No direct upgrade V5 ➔ V7
Table 5-3
Station Update Order number Description
SIMATIC WinCC RT Upgrade V7.3, from
V6.2 to V7.3, for SIMATIC WinCC
6AV6381-2AA07-3AX4 Runtime (RT)
Runtime (RT)
incl. Drivers, Server, Redundancy, User
Archive, Connectivity Pack, Connectivity
Server Station
V6.2 →
V7.3 SIMATIC WinCC RC Upgrade V7.3, from
V6.2 to V7.3, for SIMATIC WinCC
Runtime & 6AV6381-2AB07-3AX4 Runtime & Configuration (RC)
Configuration
(RC) incl. Drivers, Server, Redundancy, User
Archive, Connectivity Pack, Connectivity
Station
Upgrade
Client SIMATIC WinCC Runtime Client Upgrade
Client RT-
V6.2 → 6AV6381-2CA07-3AX4 from V6.2 to V7.3 for SIMATIC WinCC RT
V7.3 Version, Clients
V6.2 -> V7.3
Table 5-4
Station Update Order number Description
SIMATIC WinCC RT Upgrade V7.5, from
Upgrade V7.2/7.3 to V7.5, for SIMATIC WinCC
© Siemens AG 2019 All rights reserved
Pictures and libraries may also be converted manually and individually by selecting
the following function in the pop-up menu of Graphics Designer in WinCC Explorer:
• Convert project library
• Convert global library
• Converting images
Notes • Only convert images and libraries if the runtime is not active.
• Implement the conversion for multi-user systems on the server.
• The conversion of pictures during migration may not be interrupted.
• Conversion of pictures and libraries will be canceled after 18 hours.
• If an error occurs during conversion of pictures and libraries using the Project
Migrator, the migration will not be interrupted. The Project Migrator writes an error
message in a diagnostics file and processes the next components. When the
migration is complete, the Project Migrator reports the error (see section 5.6).
© Siemens AG 2019 All rights reserved
48Table 5-5
No. Procedure
1. Open "Siemens Automation > Simatic > WinCC > Tools > Project Migrator" in the
start menu of the operating system. Project Migrator opens with the "CCMigrator
- Step 1 of 2" start window.
© Siemens AG 2019 All rights reserved
2. Use the button to select the project directory in which the V6 project is located.
Select the *.mcp file.
No. Procedure
3. Click the button "Migration". The Project Migrator starts the migration and checks
off all steps of the project, which have been migrated.
© Siemens AG 2019 All rights reserved
The "CCMigrator - Step 2 of 2" window opens. Project Migrator displays the
migration steps. The Project Migrator indicates the estimated migration duration:
"Estimated Migration Duration: XX hour(s) XX minute(s)". This specification is
only a rough guideline value. The migration of a project may take several hours.
No. Procedure
4. If migration was successfully completed, the Project Migrator sends the following
message: "Data was successfully migrated."
© Siemens AG 2019 All rights reserved
When the migration is canceled, migration can be restarted after clearing the fault. Do not
use the project containing the faulty migrated project, but a copy of the backup.
The Project Migrator creates two diagnostics files:
• CCMigrator.txt
• DTSPackages.log
The diagnostics files are stored in the project directory of the migrated projects. The files
can be viewed in any text editor.
CCMigrator.txt
The "CCMigrator.txt" file contains general information: Project name, project type,
type of migrated data, start and end of migration. If the migration was successful,
the file contains the message: "Migration succeeded.".
If an error occurs during migration, the Project Migrator writes an error message in
the file. Details are provided in the "DTSPackages.log" file.
Diagnostics file
The Project Migrator saves the "MigratorLog.txt" diagnostics file to the directory of
© Siemens AG 2019 All rights reserved
the migrated project. You can view this file in any text editor.
The file contains the following general information:
• Project name
• Project type
• Type of migrated data
• Start and end of migration
If an error occurs during migration, the Project Migrator writes an error message in
the file.
Note:
The installation notes, when installing V7.5
The released operating systems for SIMATIC WinCC V7.x can be found in the online
support under the following link:
https://support.industry.siemens.com/cs/ww/en/view/64847781.
How can the .NET Framework 3.5 be installed on SIMATIC IPCs under Windows 10 or
Windows Server 2012? (e.g. for WinCC TIA Portal, STEP 7 TIA Portal or WinCC V7):
https://support.industry.siemens.com/cs/de/en/view/109745988
Pictures may only be converted when they do not contain "Unknown Objects".
"Unknown Objects" are picture objects whose associated object server is not
installed, e.g. unregistered ActiveX Controls.
Once images have been saved or converted with WinCC V7.5, it is no longer
possible to open the images with the previous version of WinCC.
Conversion of the pictures and libraries cannot be undone. A downwards
© Siemens AG 2019 All rights reserved
conversion of WinCC V7.5 images back into WinCC V6.x images is not possible.
Note Do not upgrade images and scripts from previous versions by opening and
saving them in the editors "Graphics Designer" and "Global Script", but convert
the project data beforehand.
Output versions
You can upgrade the following versions directly to WinCC V7.2
• WinCC V7.0
• WinCC V7.0 SP1
• WinCC V7.0 SP2
• WinCC V7.0 SP3
Target versions
WinCC V7.2
Required software
Table 5-6
Product Order number Note
WinCC V7.5 https://eb.automation.sie
and the latest mens.com/
available Update
Microsoft SQL Server Included in WinCC V7.5.
2016 SP2
© Siemens AG 2019 All rights reserved
Output versions
You can upgrade the following versions directly to WinCC V7.5
• WinCC V7.2
• WinCC V7.3 SE
• WinCC V7.4
• WinCC V7.4 SP1
Target versions
You can migrate a WinCC project on any computer on which you have installed
WinCC V7.5. The standard installation scope of WinCC V7.5 also includes the
WinCC Project Migrator.
Use Project Duplicator to copy the configuration data of the project to the migration
computer. For information on copying projects, refer to the "Working with projects"
> "Copying and duplicating projects" section in the WinCC Information System.
The code page settings of projects that you want to migrate in a single step must
be uniform.
Note WinCC Archive licenses are version independent since WinCC V6.2, i.e. they
can also be used with a higher WinCC version.
WinCC channel "OPC UA": Changed project planning as of WinCC V7.4 SP1
As of WinCC V7.4 SP1, you completely configure the OPC UA channel in the
WinCC Configuration Studio. In tag management, the OPC UA connections are
created parallel to the OPC channel.
When you use OPC UA in a WinCC project that was created with WinCC prior to
V7.4, the connections and tags are automatically migrated with the project. Adhere
to the following sequence if you have exported WinCC OPC UA tags:
1. Import the exported WinCC OPC UA tags.
2. Migrate the WinCC project.
User Archive
WinCC Configuration Studio replaces the functionality of WinCC ConfigurationTool
and WinCC Archive ConfigurationTool.
Note Update licenses for the options redundancy, user archive and server are
included in the update packages RC and RT.
© Siemens AG 2019 All rights reserved
Table 6-3
Station Update Order number Description
SIMATIC WinCC RT Upgrade V7.5, from
V7.2/7.3 to V7.5, for SIMATIC WinCC
Runtime (RT)
Runtime (RT) 6AV6381-2AA07-5AK3
incl. Drivers, Server, Redundancy, User
Archive, Connectivity Pack, Connectivity
Server Station
V7.2/7.3 →
V7.5 SIMATIC WinCC RC Upgrade V7.5, from
V7.2/7.3 to V7.5, for SIMATIC WinCC
Runtime & Runtime & Configuration (RC)
Configuration 6AV6381-2AB07-5AK3
(RC) incl. Drivers, Server, Redundancy, User
Archive, Connectivity Pack, Connectivity
Station
SIMATIC WinCC Runtime Client Upgrade
Client from V7.2/7.3 to V7.5 for SIMATIC WinCC
V7.2/7.3 → Client Update 6AV6381-2CA07-5AK3 RT Clients
V7.5 incl. Drivers, User Archive, Connectivity
Pack, Connectivity Station
7 Appendix
7.1 Service and support
Industry Online Support
Do you have any questions or need assistance?
Siemens Industry Online Support offers round the clock access to our entire
service and support know-how and portfolio.
The Industry Online Support is the central address for information about our
products, solutions and services.
Product information, manuals, downloads, FAQs, application examples and videos
– all information is accessible with just a few mouse clicks:
support.industry.siemens.com
Technical Support
The Technical Support of Siemens Industry provides you fast and competent
support regarding all technical queries with numerous tailor-made offers
– ranging from basic support to individual support contracts. Please send queries
to Technical Support via Web form:
www.siemens.com/industry/supportrequest
© Siemens AG 2019 All rights reserved
Service offer
Our range of services includes the following:
• Plant data services
• Spare parts services
• Repair services
• On-site and maintenance services
• Retrofitting and modernization services
• Service programs and contracts
You can find detailed information on our range of services in the service catalog
web page:
support.industry.siemens.com/cs/sc
Phone:
support.industry.siemens.com/cs/ww/en/sc/2067
© Siemens AG 2019 All rights reserved