CONFIGURATION RET670 (A40)

A VERSION 1.2, SINGLE BREAKER 3-WINDING A

Work Sheet Description

OVERVIEW List of content


W1_AI Analog inputs for winding 1
W2_AI Analog inputs for winding 2
B B
W3_AI Analog inputs for winding 3
DIF_PROT Differential protection function
W1_PROT Protection winding 1
W2_PROT Protection winding 2
W3_PROT Protection winding 3
W2_U Voltage protection winding 2
W2_SYNCH Synchrocheck function winding 2
C C
W3_U0 Residual voltage protection winding 3
TRIP Tripping logic
V_BI Virtual Binary inputs
V_BO Virtual Binary outputs
MEAS Measurement of currents, voltages etc.
LOGIC Signal logic
DREP_AI Disturbance report analog inputs
D
DREP_BI Disturbance report binary inputs D

COMMON General IED functions

E E

Main Application: OVERVIEW, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
1 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

CURRENT CIRCUIT FOR DIFFERENTIAL & REF PROTECTION, WINDING 1 SIDE

A W1_CT_A A
SMAI1
FALSE BLOCK SPFCOUT
W1_IL1
REALZERO DFTSPFC AI3P W1_CT_A_I3P
IL1 AI1
GRP1L1 AI2
TRM_9I_3U_31.CH1 IL2 AI3
GRP1L2 AI4
W1_IL2
IL3 AIN
GRP1L3
IN Optional
TRM_9I_3U_31.CH2 GRP1N
W1_IL3

TRM_9I_3U_31.CH3

B B
W1_INCT_A
SMAI2
FALSE BLOCK AI3P W1_NEUT_CT_A_I3P
Not used AI1
GRP2L1 AI2
Not used AI3
GRP2L2 AI4 W1_NEUT_CT_A_IN
Not used AIN
GRP2L3
IN
GRP2N

C C

CURRENT CIRCUIT FOR BFP & IOC, WINDING 1 SIDE

W1_CT_B
SMAI1
FALSE BLOCK SPFCOUT
W1_IL1
REALZERO DFTSPFC AI3P W1_CT_B_I3P
IL1 AI1 W1_CT_B_IL1
GRP1L1 AI2 W1_CT_B_IL2
TRM_9I_3U_31.CH1 IL2 AI3 W1_CT_B_IL3
GRP1L2 AI4
W1_IL2
IL3 AIN W1_CT_B_IN
GRP1L3
D D
IN optional
TRM_9I_3U_31.CH2 GRP1N
W1_IL3

TRM_9I_3U_31.CH3

E E

Main Application: W1_AI, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
2 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

CURRENT CIRCUIT FOR BACKUP PROTECTION & MEASURING, WINDING 1 SIDE

A A
W1_CT_C
SMAI1
FALSE BLOCK SPFCOUT
W1_IL1
REALZERO DFTSPFC AI3P W1_CT_C_I3P
IL1 AI1
GRP1L1 AI2
TRM_9I_3U_31.CH1 IL2 AI3
GRP1L2 AI4
W1_IL2
IL3 AIN
GRP1L3
IN optional
TRM_9I_3U_31.CH2 GRP1N
W1_IL3

TRM_9I_3U_31.CH3
Note! If IN is not connected in SMT, residual current is calculated and used
B B

CURRENT CIRCUIT FOR BACKUP EF PROTECTION, WINDING 1 SIDE

W1_INCT_C

SMAI2
FALSE BLOCK AI3P W1_NEUT_CT_C_I3P
Not used AI1
C GRP2L1 AI2 C
Not used AI3
GRP2L2 AI4
Not used AIN
GRP2L3
IN
GRP2N

W1_VT
D D
SMAI3
W1_UL1
BLOCK AI3P W1_VT_U3P
UL1 AI1 W1_VT_U1
GRP3L1 AI2 W1_VT_U2
TRM_9I_3U_31.CH10 UL2 AI3 W1_VT_U3
W1_UL2
GRP3L2 AI4
UL3 AIN W1_VT_UN
GRP3L3
TRM_9I_3U_31.CH11 Not used
W1_UL3
GRP3N

TRM_9I_3U_31.CH12

E E

Main Application: W1_AI, Page: 2


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
3 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

CURRENT CIRCUIT FOR DIFFERENTIAL & REF PROTECTION, WINDING 2 SIDE

A W2_IL1 W2_CT_A A
SMAI4
TRM_9I_3U_32.CH1 FALSE BLOCK AI3P W2_CT_A_I3P
W2_IL2 IL1 AI1
GRP4L1 AI2
IL2 AI3
GRP4L2 AI4
TRM_9I_3U_32.CH2 IL3 AIN
GRP4L3
W2_IL3 IN optional
GRP4N

TRM_9I_3U_32.CH3

W2_INCT_A
B SMAI6 B
FALSE BLOCK AI3P W2_NEUT_CT_A_I3P
Not used AI1
GRP6L1 AI2
Not used AI3
GRP6L2 AI4 W2_NEUT_CT_A_IN
Not used AIN
GRP6L3
IN
GRP6N

CURRENT CIRCUIT FOR BREAKER FAILURE PROTECTION & FUSE FAILURE SUPERVISION, WINDING 2 SIDE

C C
W2_IL1
W2_CT_B

TRM_9I_3U_32.CH1 SMAI4
W2_IL2 FALSE BLOCK AI3P W2_CT_B_I3P
IL1 AI1 W2_CT_B_IL1
GRP4L1 AI2 W2_CT_B_IL2
IL2 AI3 W2_CT_B_IL3
TRM_9I_3U_32.CH2 GRP4L2 AI4
W2_IL3 IL3 AIN W2_CT_B_IN
GRP4L3
IN optional
GRP4N
TRM_9I_3U_32.CH3

D CURRENT CIRCUIT FOR BACKUP PROTECTION & MEASURING, WINDING 2 SIDE D

W2_IL1

W2_CT_C
TRM_9I_3U_32.CH1
SMAI4
W2_IL2
FALSE BLOCK AI3P W2_CT_C_I3P
IL1 AI1
GRP4L1 AI2
TRM_9I_3U_32.CH2 IL2 AI3
GRP4L2 AI4
W2_IL3 IL3 AIN
GRP4L3
IN optional
GRP4N
TRM_9I_3U_32.CH3
E Note! If IN is not connected in SMT, residual current is calculated and used E

Main Application: W2_AI, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
4 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

VOLTAGE CIRCUIT FOR FUSE FAILURE SUPERVISION, WINDING 2 SIDE

A A
W2_VT_B
SMAI3
FALSE BLOCK AI3P W2_VT_B_U3P
UL1 AI1 W2_VT_B_U1
GRP3L1 AI2 W2_VT_B_U2
UL2 AI3 W2_VT_B_U3
GRP3L2 AI4
UL3 AIN W2_VT_B_UN
GRP3L3
UN optional
GRP3N

B B

VOLTAGE CIRCUIT FOR VOLTAGE PROTECTION, SYNCHRO CHECK & MEASURING, WINDING 2 SIDE

W2_VT_C
SMAI5
FALSE BLOCK AI3P W2_VT_C_U3P
UL1 AI1
GRP5L1 AI2
C UL2 AI3 C
GRP5L2 AI4
UL3 AIN
GRP5L3
UN optional
GRP5N

D D

E E

Main Application: W2_AI, Page: 2


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
5 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

VOLTAGE CIRCUIT FOR SYNCHRO CHECK, BUS1 WINDING 2 SIDE

A A
W2_BUS1VT_C
SMAI3
FALSE BLOCK AI3P W2_BUS1_VT_C_U3P
UL1 AI1
GRP3L1 AI2
UL2 AI3
GRP3L2 AI4
UL3 AIN
GRP3L3
Not used
GRP3N

Note! Connect the phase used for SC and do corresponding setting in PST
B B

VOLTAGE CIRCUIT FOR SYNCHRO CHECK, BUS2 WINDING 2 SIDE

W2_BUS2VT_C
SMAI6
FALSE BLOCK AI3P W2_BUS2_VT_C_U3P
UL1 AI1
GRP6L1 AI2
C UL2 AI3 C
GRP6L2 AI4
UL3 AIN
GRP6L3
Not used
GRP6N

D D

E E

Main Application: W2_AI, Page: 3


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
6 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

CURRENT CIRCUIT FOR DIFFERENTIAL PROTECTION, WINDING 3 SIDE

A W3_CT_A A
SMAI5
W3_IL1
FALSE BLOCK AI3P W3_CT_A_I3P
IL1 AI1
GRP5L1 AI2
TRM_9I_3U_32.CH4 IL2 AI3
GRP5L2 AI4
W3_IL2
IL3 AIN
GRP5L3
IN optional
TRM_9I_3U_32.CH5 GRP5N
W3_IL3

TRM_9I_3U_32.CH6

B B

CURRENT CIRCUIT FOR BREAKER FAILURE PROTECTION, WINDING 3 SIDE

W3_CT_B
SMAI5
W3_IL1
FALSE BLOCK AI3P W3_CT_B_I3P
IL1 AI1 W3_CT_B_IL1
GRP5L1 AI2 W3_CT_B_IL2
TRM_9I_3U_32.CH4 IL2 AI3 W3_CT_B_IL3
GRP5L2 AI4
W3_IL2
IL3 AIN W3_CT_B_IN
C GRP5L3 C
IN optional
TRM_9I_3U_32.CH5 GRP5N
W3_IL3

TRM_9I_3U_32.CH6

CURRENT CIRCUIT FOR BACKUP PROTECTION & MEASURING, WINDING 3 SIDE

D D

W3_CT_C

SMAI7
W3_IL1 FALSE BLOCK AI3P W3_CT_C_I3P
IL1 AI1
GRP7L1 AI2
IL2 AI3
TRM_9I_3U_32.CH4 GRP7L2 AI4
W3_IL2 IL3 AIN
GRP7L3
IN optional
GRP7N
TRM_9I_3U_32.CH5
W3_IL3

TRM_9I_3U_32.CH6 Note! If IN is not connected in SMT, residual current is calculated and used
E E

Main Application: W3_AI, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
7 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

VOLTAGE CIRCUIT FOR RESIDUAL VOLTAGE PROTECTION, WINDING 3 SIDE

A A
W3_3Uo_VT_C

SMAI8
FALSE BLOCK AI3P W3_UN_VT_C_U3P
Not used AI1
GRP8L1 AI2
Not used AI3
GRP8L2 AI4 W3_3Uo_VT_C_UN
Not used AIN
GRP8L3
UN
GRP8N

B B

C C

D D

E E

Main Application: W3_AI, Page: 2


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
8 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

A 3-W DIFFERENTIAL PROTECTION A

T3WPDIF
W1_CT_A_I3P I3PW1CT1 TRIP T3D1-TRIP
GRP_OFF I3PW1CT2 TRIPRES T3D1-TRIPRES
W2_CT_A_I3P I3PW2CT1 TRIPUNRE T3D1-TRIPUNRE
GRP_OFF I3PW2CT2 TRNSUNR T3D1-TRNSUNR
W3_CT_A_I3P I3PW3CT1 TRNSSENS T3D1-TRNSSENS
GRP_OFF I3PW3CT2 START T3D1-START
TCM1-TCPOS TAPOLTC1 STL1 T3D1-STL1
TCM2-TCPOS TAPOLTC2 STL2 T3D1-STL2
B TCM1-POSERRAL OLTC1AL STL3 T3D1-STL3 B
TCM2-POSERRAL OLTC2AL BLK2H T3D1-BLK2H
FALSE BLOCK BLK2HL1 T3D1-BLK2HL1
FALSE BLKRES BLK2HL2 T3D1-BLK2HL2
FALSE BLKUNRES BLK2HL3 T3D1-BLK2HL3
FALSE BLKNSUNR BLK5H T3D1-BLK5H
FALSE BLKNSSEN BLK5HL1 T3D1-BLK5HL1
BLK5HL2 T3D1-BLK5HL2
BLK5HL3 T3D1-BLK5HL3
BLKWAV T3D1-BLKWAV
BLKWAVL1 T3D1-BLKWAVL1
BLKWAVL2 T3D1-BLKWAVL2
BLKWAVL3 T3D1-BLKWAVL3
IDALARM T3D1-IDALARM
OPENCT
OPENCTAL T3D1-OPENCTAL
IDL1
IDL2
IDL3
IDL1MAG T3D1-IDL1MAG
IDL2MAG T3D1-IDL2MAG
C IDL3MAG T3D1-IDL3MAG C
IBIAS T3D1-IBIAS
IDNSMAG T3D1-IDNSMAG

D D

E E

Main Application: DIF_PROT, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
9 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

TCMYLTC
A A
GRP_OFF YLTCIN URAISE
TCPOS1_TCINPROG TCINPROG ULOWER
TCPOS1_INPUT_ERROR INERR HIPOSAL
TCPOS1_RESET_ERROR RESETERR LOPOSAL
FALSE OUTERR POSERRAL TCM1-POSERRAL
FALSE RS_CLCNT CMDERRAL
FALSE RS_OPCNT TCERRAL
TCPOS1_PARITY_ERROR PARITY POSOUT
TCPOS1_BINPUT_ERROR BIERR CONVERR
TCPOS1_BIT1 B1 NEWPOS
TCPOS1_BIT2 B2 HIDIFPOS
TCPOS1_BIT3 B3 INVALPOS
TCPOS1_BIT4 B4 TCPOS TCM1-TCPOS
TCPOS1_BIT5 B5 YLTCOUT
TCPOS1_BIT6 B6
TCPOS1_MA MA

B B

C C
TCMYLTC
GRP_OFF YLTCIN URAISE
TCPOS2_TCINPROG TCINPROG ULOWER
TCPOS2_INPUT_ERROR INERR HIPOSAL
TCPOS2_RESET_ERROR RESETERR LOPOSAL
FALSE OUTERR POSERRAL TCM2-POSERRAL
FALSE RS_CLCNT CMDERRAL
FALSE RS_OPCNT TCERRAL
TCPOS2_PARITY_ERROR PARITY POSOUT
TCPOS2_BINPUT_ERROR BIERR CONVERR
TCPOS2_BIT1 B1 NEWPOS
TCPOS2_BIT2 B2 HIDIFPOS
TCPOS2_BIT3 B3 INVALPOS
TCPOS2_BIT4 B4 TCPOS TCM2-TCPOS
TCPOS2_BIT5 B5 YLTCOUT
TCPOS2_BIT6 B6
TCPOS2_MA MA

D D

E E

Main Application: DIF_PROT, Page: 2


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
10 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

BREAKER FAILURE PROTECTION, WINDING 1 SIDE

A A
CCRBRF
W1_CT_B_I3P I3P TRBU W1_CB_BFP1-TRBU
FALSE BLOCK TRBU2
W1_CB_TRP1-TRIP START TRRET W1_CB_BFP1-TRRET
FALSE STL1 TRRETL1
FALSE STL2 TRRETL2
FALSE STL3 TRRETL3
FALSE CBCLDL1 CBALARM
FALSE CBCLDL2
FALSE CBCLDL3
FALSE CBFLT

B B
POLE DISCORDANCE PROTECTION, WINDING 1 SIDE

CCRPLD
W1_CT_C_I3P I3P TRIP W1_CB_PD1-TRIP
FALSE BLOCK START
FALSE BLKDBYAR
FALSE CLOSECMD
FALSE OPENCMD
BI_W1_CB_POLE_DISC EXTPDIND
FALSE POLE1OPN
FALSE POLE1CL
FALSE POLE2OPN
FALSE POLE2CL
C FALSE POLE3OPN C
FALSE POLE3CL

D D

E E

Main Application: W1_PROT, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
11 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

INSTANTANEOUS OVERCURRENT PROTECTION, WINDING 1 SIDE

A A
PHPIOC
W1_CT_B_I3P I3P TRIP W1_IOC1-TRIP
FALSE BLOCK TRL1
FALSE ENMULT TRL2
TRL3

TIME OVERCURRENT PROTECTION, WINDING 1 SIDE


B B

OC4PTOC
W1_CT_C_I3P I3P TRIP W1_TOC1-TRIP
GRP_OFF U3P TR1
FALSE BLOCK TR2
FALSE BLKTR TR3
FALSE BLKST1 TR4
FALSE BLKST2 TRL1
FALSE BLKST3 TRL2
FALSE BLKST4 TRL3
FALSE ENMULT1 TR1L1
FALSE ENMULT2 TR1L2
FALSE ENMULT3 TR1L3
FALSE ENMULT4 TR2L1
TR2L2
TR2L3
TR3L1
C TR3L2 C
TR3L3
TR4L1
TR4L2
TR4L3
START W1_TOC1-START
ST1
ST2
ST3
ST4
STL1 W1_TOC1-STL1
STL2 W1_TOC1-STL2
STL3 W1_TOC1-STL3
ST1L1
ST1L2
ST1L3
ST2L1
ST2L2
ST2L3
ST3L1
ST3L2
D ST3L3 D
ST4L1
ST4L2
ST4L3
2NDHARM
DIRL1
DIRL2
DIRL3

E E

Main Application: W1_PROT, Page: 2


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
12 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

RESTRICTED EARTH FAULT PROTECTION, WINDING 1 SIDE

A REFPDIF A
W1_NEUT_CT_A_I3P I3P TRIP W1_REF1-TRIP
W1_CT_A_I3P I3PW1CT1 START W1_REF1-START
GRP_OFF I3PW1CT2 DIROK W1_REF1-DIROK
GRP_OFF I3PW2CT1 BLK2H W1_REF1-BLK2H
GRP_OFF I3PW2CT2 IRES
FALSE BLOCK IN
IBIAS W1_REF1-IBIAS
IDIFF W1_REF1-IDIFF
ANGLE
I2RATIO

B INSTANTANEOUS EARTH FAULT PROTECTION, WINDING 1 SIDE B

EFPIOC
W1_CT_B_I3P I3P TRIP W1_IEF-TRIP
FALSE BLOCK
FALSE BLKAR
FALSE MULTEN

TIME DELAYED EARTH FAULT PROTECTION, WINDING 1 SIDE


C C

EF4PTOC
W1_CT_C_I3P I3P TRIP W1_TEF1-TRIP
GRP_OFF U3P TRIN1
GRP_OFF I3PPOL TRIN2
FALSE BLOCK TRIN3
FALSE BLKTR TRIN4
FALSE BLKST1 TRSOTF
FALSE BLKST2 START W1_TEF1-START
FALSE BLKST3 STIN1
FALSE BLKST4 STIN2
FALSE ENMULT1 STIN3
FALSE ENMULT2 STIN4
FALSE ENMULT3 STSOTF
FALSE ENMULT4 STFW
D FALSE CBPOS STRV D
FALSE CLOSECB 2NDHARMD W1_TEF1-2NDHARM
FALSE OPENCB

E E

Main Application: W1_PROT, Page: 3


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
13 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

A
MINIMA TENSIO PARA ST A

B B

C C

D D

E E

Main Application: W1_PROT, Page: 4


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
14 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

BREAKER FAILURE PROTECTION, WINDING 2 SIDE


A A

CCRBRF
W2_CT_B_I3P I3P TRBU W2_CB_BFP3-TRBU
FALSE BLOCK TRBU2
W2_CB_TRP3-TRIP START TRRET W2_CB_BFP3-TRRET
FALSE STL1 TRRETL1
FALSE STL2 TRRETL2
FALSE STL3 TRRETL3
FALSE CBCLDL1 CBALARM
FALSE CBCLDL2
FALSE CBCLDL3
FALSE CBFLT

B B

THERMAL OVERLOAD PROTECTION, WINDING 2 SIDE

TRPTTR
W2_CT_C_I3P I3P TRIP W2_TTR1-TRIP
FALSE BLOCK START
BI_FORCED_COOLING_THERMAL_OVERLOAD COOLING ALARM1 W2_TTR1-ALARM1
FALSE ENMULT ALARM2 W2_TTR1-ALARM2
BI_RESET_THERMAL_OVERLOAD RESET LOCKOUT
C WARNING C

D D

E E

Main Application: W2_PROT, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
15 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

TIME OVERCURRENT PROTECTION, WINDING 2 SIDE

A A

OC4PTOC
W2_CT_C_I3P I3P TRIP W2_TOC2-TRIP
GRP_OFF U3P TR1
FALSE BLOCK TR2
FALSE BLKTR TR3
BI_W2_BLOCK_BBP_OC_STEP BLKST1 TR4
FALSE BLKST2 TRL1
FALSE BLKST3 TRL2
FALSE BLKST4 TRL3
FALSE ENMULT1 TR1L1
FALSE ENMULT2 TR1L2
FALSE ENMULT3 TR1L3
FALSE ENMULT4 TR2L1
TR2L2
TR2L3
B TR3L1 B
TR3L2
TR3L3
TR4L1
TR4L2
TR4L3
START W2_TOC2-START
ST1
ST2
ST3
ST4
STL1 W2_TOC2-STL1
STL2 W2_TOC2-STL2
STL3 W2_TOC2-STL3
ST1L1
ST1L2
ST1L3
ST2L1
ST2L2
ST2L3
ST3L1
C ST3L2 C
ST3L3
ST4L1
ST4L2
ST4L3
2NDHARM
DIRL1
DIRL2
DIRL3

D D

E E

Main Application: W2_PROT, Page: 2


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
16 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

RESTRICTED EARTH FAULT PROTECTION, WINDING 2 SIDE


A A

REFPDIF
W2_NEUT_CT_A_I3P I3P TRIP W2_REF2-TRIP
W2_CT_A_I3P I3PW1CT1 START W2_REF2-START
GRP_OFF I3PW1CT2 DIROK W2_REF2-DIROK
GRP_OFF I3PW2CT1 BLK2H W2_REF2-BLK2H
GRP_OFF I3PW2CT2 IRES
FALSE BLOCK IN
IBIAS W2_REF2-IBIAS
IDIFF W2_REF2-IDIFF
ANGLE
I2RATIO

B B

TIME DELAYED EARTH FAULT PROTECTION, WINDING 2 SIDE

EF4PTOC
W2_CT_C_I3P I3P TRIP W2_TEF2-TRIP
W2_VT_C_U3P U3P TRIN1
GRP_OFF I3PPOL TRIN2
FALSE BLOCK TRIN3
FALSE BLKTR TRIN4
C BI_W2_BLOCK_BBP_EF_STEP BLKST1 TRSOTF C
FALSE BLKST2 START W2_TEF2-START
FALSE BLKST3 STIN1
FALSE BLKST4 STIN2
FALSE ENMULT1 STIN3
FALSE ENMULT2 STIN4
FALSE ENMULT3 STSOTF
FALSE ENMULT4 STFW W2_TEF2-STFW
FALSE CBPOS STRV W2_TEF2-STRV
FALSE CLOSECB 2NDHARMD W2_TEF2-2NDHARM
FALSE OPENCB

D D

E E

Main Application: W2_PROT, Page: 3


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
17 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

BREAKER FAILURE PROTECTION, WINDING 3 SIDE

A A

CCRBRF
W3_CT_B_I3P I3P TRBU W3_CB_BFP2-TRBU
FALSE BLOCK TRBU2
W3_CB_TRP2-TRIP START TRRET W3_CB_BFP2-TRRET
FALSE STL1 TRRETL1
FALSE STL2 TRRETL2
FALSE STL3 TRRETL3
FALSE CBCLDL1 CBALARM
FALSE CBCLDL2
FALSE CBCLDL3
FALSE CBFLT

B B

THERMAL OVERLOAD PROTECTION, WINDING 3 SIDE

TRPTTR
W3_CT_C_I3P I3P TRIP W3_TTR2-TRIP
FALSE BLOCK START
BI_FORCED_COOLING_THERMAL_OVERLOAD COOLING ALARM1 W3_TTR2-ALARM1
FALSE ENMULT ALARM2 W3_TTR2-ALARM2
BI_RESET_THERMAL_OVERLOAD RESET LOCKOUT
WARNING

C C

D D

E E

Main Application: W3_PROT, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
18 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

TIME OVERCURRENT PROTECTION, WINDING 3 SIDE

A A
OC4PTOC
W3_CT_C_I3P I3P TRIP W3_TOC3-TRIP
GRP_OFF U3P TR1
FALSE BLOCK TR2
FALSE BLKTR TR3
BI_W3_BLOCK_BBP_OC_STEP BLKST1 TR4
FALSE BLKST2 TRL1
FALSE BLKST3 TRL2
FALSE BLKST4 TRL3
FALSE ENMULT1 TR1L1
FALSE ENMULT2 TR1L2
FALSE ENMULT3 TR1L3
FALSE ENMULT4 TR2L1
TR2L2
TR2L3
TR3L1
TR3L2
TR3L3
TR4L1
B TR4L2 B
TR4L3
START W3_TOC3-START
ST1
ST2
ST3
ST4
STL1 W3_TOC3-STL1
STL2 W3_TOC3-STL2
STL3 W3_TOC3-STL3
ST1L1
ST1L2
ST1L3
ST2L1
ST2L2
ST2L3
ST3L1
ST3L2
ST3L3
ST4L1
ST4L2
C ST4L3 C
2NDHARM
DIRL1
DIRL2
DIRL3

TIME DELAYED EARTH FAULT PROTECTION, WINDING 3 SIDE

D D
EF4PTOC
W3_CT_C_I3P I3P TRIP W3_TEF3-TRIP
W3_UN_VT_C_U3P U3P TRIN1
GRP_OFF I3PPOL TRIN2
FALSE BLOCK TRIN3
FALSE BLKTR TRIN4
BI_W3_BLOCK_BBP_EF_STEP BLKST1 TRSOTF
FALSE BLKST2 START W3_TEF3-START
FALSE BLKST3 STIN1
FALSE BLKST4 STIN2
FALSE ENMULT1 STIN3
FALSE ENMULT2 STIN4
FALSE ENMULT3 STSOTF
FALSE ENMULT4 STFW W3_TEF3-STFW
FALSE CBPOS STRV W3_TEF3-STRV
FALSE CLOSECB 2NDHARMD W3_TEF3-2NDHARM
FALSE OPENCB

E E

Main Application: W3_PROT, Page: 2


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
19 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

TIME DELAYED OVER VOLTAGE PROTECTION, WINDING 2 SIDE

OV2PTOV
A W2_VT_C_U3P U3P TRIP W2_TOV1-TRIP A
FALSE BLOCK TR1
FALSE BLKTR1 TR1L1
FALSE BLKST1 TR1L2
FALSE BLKTR2 TR1L3
FALSE BLKST2 TR2 W2_TOV1-TR2
TR2L1
TR2L2
TR2L3
START W2_TOV1-START
ST1
ST1L1
ST1L2
ST1L3
ST2
ST2L1
ST2L2
ST2L3

B B

TIME DELAYED UNDER VOLTAGE PROTECTION, WINDING 2 SIDE

UV2PTUV
W2_VT_C_U3P U3P TRIP W2_TUV1-TRIP
W2_FSD1-BLKU BLOCK TR1
FALSE BLKTR1 TR1L1
FALSE BLKST1 TR1L2
FALSE BLKTR2 TR1L3
FALSE BLKST2 TR2 W2_TUV1-TR2
TR2L1
TR2L2
TR2L3
C START W2_TUV1-START C
ST1
ST1L1
ST1L2
ST1L3
ST2
ST2L1
ST2L2
ST2L3

FUSE FAILURE SUPERVSION, WINDING 2 SIDE


D D

SDDRFUF
W2_CT_B_I3P I3P BLKZ
W2_VT_B_U3P U3P BLKU W2_FSD1-BLKU
FALSE BLOCK 3PH
BI_W2_CB_CLOSED CBCLOSED DLD1PH
BI_W2_CB_MCB_VT_FF MCBOP DLD3PH
BI_W2_DISC_OPEN DISCPOS
W2_CB_TRP3-TRIP BLKTRIP

E E

Main Application: W2_U, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
20 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

A LOSS OF VOLTAGE PROTECTION, WINDING 2 SIDE A

LOVPTUV
INV W2_VT_C_U3P U3P TRIP LOV1-TRIP
FALSE BLOCK START LOV1-START
BI_W2_CB_CLOSED INPUT OUT CBOPEN
W2_FSD1-BLKU VTSU

B B

C C

D D

E E

Main Application: W2_U, Page: 2


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
21 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

SYNCHRO/ENERGISE CHECK, WINDING 2 SIDE

A A

OR
INPUT1 OUT W2_SYN_AUTO_OK
INPUT2 NOUT
FALSE INPUT3
FALSE INPUT4
FALSE INPUT5
FALSE INPUT6
SESRSYN
W2_BUS1_VT_C_U3P U3PBB1 SYNOK W2_SYN1_SYNOK
W2_BUS2_VT_C_U3P U3PBB2 AUTOSYOK W2_SYN1-AUTOSYOK
W2_VT_C_U3P U3PLN1 AUTOENOK W2_SYN1-AUTOENOK
GRP_OFF U3PLN2 MANSYOK W2_SYN1-MANSYOK
FALSE BLOCK MANENOK W2_SYN1-MANENOK
FALSE BLKSYNCH TSTSYNOK
B INV FALSE BLKSC TSTAUTSY B
FALSE BLKENERG TSTMANSY
BI_W2_CB_BUS1_DISC_CLOSED INPUT OUT B1QOPEN TSTENOK
BI_W2_CB_BUS1_DISC_CLOSED B1QCLD USELFAIL
B2QOPEN B1SEL
B2QCLD B2SEL
OR
BI_W2_CB_BUS2_DISC_CLOSED
FALSE LN1QOPEN LN1SEL INPUT1 OUT W2_SYN_MAN_OK
TRUE LN1QCLD LN2SEL INPUT2 NOUT
FALSE LN2QOPEN SYNPROGR FALSE INPUT3
INV FALSE LN2QCLD SYNFAIL FALSE INPUT4
BI_W2_CB_BUS1_MCB_OK UB1OK UOKSYN FALSE INPUT5
BI_W2_CB_BUS2_DISC_CLOSED INPUT OUT FALSE UB1FF UDIFFSYN FALSE INPUT6
BI_W2_CB_BUS2_MCB_OK UB2OK FRDIFSYN
FALSE UB2FF FRDIFFOK
TRUE ULN1OK FRDERIVA
W2_FSD1-BLKU ULN1FF UOKSC
FALSE ULN2OK UDIFFSC
FALSE ULN2FF FRDIFFA
FALSE STARTSYN PHDIFFA
FALSE TSTSYNCH FRDIFFM
FALSE TSTSC PHDIFFM
C FALSE TSTENERG INADVCLS C
INTZERO AENMODE UDIFFME
INTZERO MENMODE FRDIFFME
PHDIFFME
UBUS
ULINE
MODEAEN
MODEMEN

D D

E E

Main Application: W2_SYNCH, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
22 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

TIME DELAYED RESIDUAL VOLTAGE PROTECTION, WINDING 3 SIDE


A A

ROV2PTOV
W3_UN_VT_C_U3P U3P TRIP W3_TRV1-TRIP
FALSE BLOCK TR1
FALSE BLKTR1 TR2 W3_TRV1-TR2
FALSE BLKST1 START W3_TRV1-START
FALSE BLKTR2 ST1
FALSE BLKST2 ST2

B B

C C

D D

E E

Main Application: W3_U0, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
23 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

TRIPLOGIC, WINDING 1 SIDE

A A

TMAGGIO SMPPTRC
T3D1-TRIP INPUT1 OUTPUT1 FALSE BLOCK TRIP W1_CB_TRP1-TRIP
W1_REF1-TRIP INPUT2 OUTPUT2 FALSE BLKLKOUT TRL1
W1_IOC1-TRIP INPUT3 OUTPUT3 TRIN TRL2
W1_IEF-TRIP INPUT4 FALSE TRINL1 TRL3
FALSE INPUT5 FALSE TRINL2 TR1P
FALSE INPUT6 FALSE TRINL3 TR2P
W2_CB_BFP3-TRBU INPUT7 FALSE PSL1 TR3P
W3_CB_BFP2-TRBU INPUT8 FALSE PSL2 CLLKOUT W1_CB_TRP1-CLLKOUT
W2_REF2-TRIP INPUT9 FALSE PSL3
BI_BUCHHOLZ_TRIP INPUT10 FALSE 1PTRZ
BI_PRESSURE_TRIP INPUT11 FALSE 1PTREF
FALSE INPUT12 FALSE P3PTR
FALSE INPUT13 SETLKOUT
FALSE INPUT14 BI_RESET_LOCKOUT RSTLKOUT
B FALSE INPUT15 B
BI_W1_CB_EXT_TRIP INPUT16
W1_TOC1-TRIP INPUT17
W1_TEF1-TRIP INPUT18
W1_CB_PD1-TRIP INPUT19
W2_TOV1-TR2 INPUT20
W2_TUV1-TR2 INPUT21
W3_TRV1-TR2 INPUT22
W1_CB_BFP1-TRRET INPUT23
FALSE INPUT24
FALSE INPUT25
FALSE INPUT26
FALSE INPUT27
FALSE INPUT28
FALSE INPUT29
FALSE INPUT30
FALSE INPUT31
FALSE INPUT32

C C

GT21 = ON TRIP COIL SUPERVISION ACTIVATED

GATE
TRUE INPUT OUT

D D

INV TIMER AND


BI_W1_CB_TCS INPUT OUT INPUT ON INPUT1 OUT W1_CB_TCS_ALARM
OFF INPUT2 NOUT
TRUE INPUT3
W1_CB_TRP1-TRIP INPUT4N

E E

Main Application: TRIP, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
24 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

TRIPLOGIC, WINDING 2 SIDE

A A

TMAGGIO SMPPTRC
T3D1-TRIP INPUT1 OUTPUT1 FALSE BLOCK TRIP W2_CB_TRP3-TRIP
W1_REF1-TRIP INPUT2 OUTPUT2 FALSE BLKLKOUT TRL1
W1_IOC1-TRIP INPUT3 OUTPUT3 TRIN TRL2
W1_IEF-TRIP INPUT4 FALSE TRINL1 TRL3
W1_CB_BFP1-TRBU INPUT5 FALSE TRINL2 TR1P
FALSE INPUT6 FALSE TRINL3 TR2P
FALSE INPUT7 FALSE PSL1 TR3P
W3_CB_BFP2-TRBU INPUT8 FALSE PSL2 CLLKOUT W2_CB_TRP3-CLLKOUT
W2_REF2-TRIP INPUT9 FALSE PSL3
BI_BUCHHOLZ_TRIP INPUT10 FALSE 1PTRZ
BI_PRESSURE_TRIP INPUT11 FALSE 1PTREF
FALSE INPUT12 FALSE P3PTR
FALSE INPUT13 SETLKOUT
FALSE INPUT14 BI_RESET_LOCKOUT RSTLKOUT
FALSE INPUT15
B BI_W2_CB_EXT_TRIP INPUT16 B
W2_TOC2-TRIP INPUT17
W2_TEF2-TRIP INPUT18
W2_TOV1-TRIP INPUT19
W2_TUV1-TRIP INPUT20
W3_TRV1-TR2 INPUT21
W2_TTR1-TRIP INPUT22
W2_CB_BFP3-TRRET INPUT23
BI_TRAFO_OIL_TEMP_TRIP INPUT24
BI_WINDING_TEMP_TRIP INPUT25
LOV1-TRIP INPUT26
FALSE INPUT27
FALSE INPUT28
FALSE INPUT29
FALSE INPUT30
FALSE INPUT31
FALSE INPUT32

C C

GT23 = ON TRIP COIL SUPERVISION ACTIVATED

GATE
TRUE INPUT OUT

INV TIMER AND


BI_W2_CB_TCS INPUT OUT INPUT ON INPUT1 OUT W2_CB_TCS_ALARM
OFF INPUT2 NOUT
D TRUE INPUT3 D
W2_CB_TRP3-TRIP INPUT4N

GATE
TRUE INPUT OUT

INV TIMER AND


BI_W2_CB_TC2 INPUT OUT INPUT ON INPUT1 OUT W2_CB_TC2_ALARM
OFF INPUT2 NOUT
TRUE INPUT3
W2_CB_TRP3-TRIP INPUT4N

E E

Main Application: TRIP, Page: 2


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
25 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

TRIPLOGIC, WINDING 3 SIDE

A A

TMAGGIO SMPPTRC
T3D1-TRIP INPUT1 OUTPUT1 FALSE BLOCK TRIP W3_CB_TRP2-TRIP
W1_REF1-TRIP INPUT2 OUTPUT2 FALSE BLKLKOUT TRL1
W1_IOC1-TRIP INPUT3 OUTPUT3 TRIN TRL2
W1_IEF-TRIP INPUT4 FALSE TRINL1 TRL3
W1_CB_BFP1-TRBU INPUT5 FALSE TRINL2 TR1P
FALSE INPUT6 FALSE TRINL3 TR2P
W2_CB_BFP3-TRBU INPUT7 FALSE PSL1 TR3P
FALSE INPUT8 FALSE PSL2 CLLKOUT W3_CB_TRP2-CLLKOUT
W2_REF2-TRIP INPUT9 FALSE PSL3
BI_BUCHHOLZ_TRIP INPUT10 FALSE 1PTRZ
BI_PRESSURE_TRIP INPUT11 FALSE 1PTREF
BI_WINDING_TEMP_TRIP INPUT12 FALSE P3PTR
BI_TRAFO_OIL_TEMP_TRIP INPUT13 SETLKOUT
FALSE INPUT14 BI_RESET_LOCKOUT RSTLKOUT
B INPUT15
B
FALSE
BI_W3_CB_EXT_TRIP INPUT16
W3_TOC3-TRIP INPUT17
W3_TEF3-TRIP INPUT18
W2_TOV1-TR2 INPUT19
W2_TUV1-TR2 INPUT20
W3_TRV1-TRIP INPUT21
W3_TTR2-TRIP INPUT22
W3_CB_BFP2-TRRET INPUT23
BI_TRAFO_OIL_TEMP_TRIP INPUT24
BI_WINDING_TEMP_TRIP INPUT25
FALSE INPUT26
FALSE INPUT27
FALSE INPUT28
FALSE INPUT29
FALSE INPUT30
FALSE INPUT31
FALSE INPUT32

C C

GT24 = ON TRIP COIL SUPERVISION ACTIVATED

GATE
TRUE INPUT OUT

D D
INV TIMER AND
BI_W3_CB_TCS INPUT OUT INPUT ON INPUT1 OUT W3_CB_TCS_ALARM
OFF INPUT2 NOUT
TRUE INPUT3
W3_CB_TRP2-TRIP INPUT4N

E E

Main Application: TRIP, Page: 3


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
26 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

A A

B B

TMAGGIO
T3D1-TRIP INPUT1 OUTPUT1 TIMER
BI_TRAFO_BUCHHOLZ_TRIP INPUT2 OUTPUT2
BI_TRAFO_GUARD_TRIP INPUT3 OUTPUT3 INPUT ON
BI_TRAFO_OIL_TEMP_TRIP INPUT4 OFF TRIP_86T
BI_TRAFO_PRESSURE_TRIP INPUT5
BI_WINDING_TEMP_TRIP INPUT6
BI_OLTC_BUCHHOLZ_TRIP INPUT7
BI_OLTC_GUARD_TRIP INPUT8
BI_OLTC_OIL_LEVEL_TRIP INPUT9
BI_OLTC_PRESSURE_TRIP INPUT10
BI_RELE_PROT_OLTC_TRIP INPUT11
BI_VALV_PRES_TRIP INPUT12
INPUT13
INPUT14
INPUT15
INPUT16
C INPUT17 C
INPUT18
INPUT19
INPUT20
INPUT21
INPUT22
INPUT23
INPUT24
INPUT25
INPUT26
INPUT27
INPUT28
INPUT29
INPUT30
INPUT31
INPUT32

D D

E E

Main Application: TRIP, Page: 4


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
27 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

TC1_OK_W1_CB
W1 CB
LOCAL_CMD1
BIM_5.BI9 SMBI
SMBI
EXT TRIP EXT TRIP BI_W1_CB_EXT_TRIP
VIn1 BI1 LR-OFF LR-OFF LR-OFF==SMBI
A VIn1 BI1
A
POLE DISC POLE DISC BI_W1_CB_POLE_DISC
W1_CB_CLOSED VIn2 BI2 LR-LOC LR-LOC LR-LOC==SMBI
TCS_W1_CB TCS_W1_CB BI_W1_CB_TCS VIn2 BI2
VIn3 BI3 LR-REM LR-REM LR-REM==SMBI
BIM_3.BI2 CB CLOSED CB CLOSED BI_W1_CB_CLOSED VIn3 BI3
VIn4 BI4 QA1-L-SEL QA1-L-SEL QA1-L-SEL==SMBI
W1_CB_OPEN VIn4 BI4
SPRING UNCH SPRING UNCH BI_W1_CB_SPRING_UNCH
VIn5 BI5 QB1-L-SEL QB1-L-SEL QB1-L-SEL==SMBI
CB OPEN CB OPEN BI_W1_CB_OPEN VIn5 BI5
BIM_3.BI1 VIn6 BI6 QB2-L-SEL QB2-L-SEL QB2-L-SEL==SMBI
MCB FF MCB FF BI_MCB_FAIL_UW1 VIn6 BI6
MCB_UW1_FAIL VIn7 BI7 QB9-L-SEL QB9-L-SEL QB9-L-SEL==SMBI
QB9_OPEN QB9_OPEN BI_W1_QB9_OPEN VIn7 BI7
VIn8 BI8 QC9-L-SEL QC9-L-SEL QC9-L-SEL==SMBI
BIM_3.BI12 QB9_CLOSED QB9_CLOSED BI_W1_QB9_CLOSED VIn8 BI8
W1_QB9_CL VIn9 BI9 QA1-L-OPEN QA1-L-OPEN QA1-L-OPEN==SMBI
Not used Not used VIn9 BI9
VIn10 BI10 QA1-L-CLOSE QA1-L-CLOSE QA1-L-CLOSE==SMBI
BIM_3.BI14 VIn10 BI10
W1_QB9_OP

B B
BIM_3.BI13

W2 CB
SMBI
EXT TRIP EXT TRIP BI_W2_CB_EXT_TRIP
VIn1 BI1
DISC_OPEN DISC_OPEN BI_W2_DISC_OPEN
TC1_OK_W2_CB VIn2 BI2
MCB VT FF MCB VT FF BI_W2_CB_MCB_VT_FF
VIn3 BI3
BIM_5.BI10 MCB BUS1 OK MCB BUS1 OK BI_W2_CB_BUS1_MCB_OK
VIn4 BI4
BUS1 VT SELCT BUS1 VT SELCT BI_W2_CB_BUS1_DISC_CLOSED
W2_CB_CLOSED VIn5 BI5
C C
MCB BUS2 OK MCB BUS2 OK BI_W2_CB_BUS2_MCB_OK
VIn6 BI6
BIM_3.BI6 BUS2 VT SELCT BUS2 VT SELCT BI_W2_CB_BUS2_DISC_CLOSED
VIn7 BI7
CB CLOSED CB CLOSED BI_W2_CB_CLOSED
VIn8 BI8
W2_CB_RD
TCS1_W2_CB TCS1_W2_CB BI_W2_CB_TCS
VIn9 BI9
SPRING UNCH SPRING UNCH BI_W2_CB_SPRING_UNCH
BIM_3.BI7 VIn10 BI10

W1_QC9_OP

BIM_3.BI15
W1_QC9_CL Not used

SMBI
BIM_3.BI16 BLOCK OC BLOCK OC
D TC1_OK_W3_CB W3 CB BI_W2_BLOCK_BBP_OC_STEP D
VIn1 BI1
SMBI BLOCK EF BLOCK EF BI_W2_BLOCK_BBP_EF_STEP
W1_BLQ_SF6 VIn2 BI2
BIM_5.BI12 EXT TRIP EXT TRIP BI_W3_CB_EXT_TRIP W1_ALAR_SF6 W1_ALAR_SF6 BI_W1_CB_ALAR_SF6
VIn1 BI1 VIn3 BI3
TCS_W3_CB TCS_W3_CB BI_W3_CB_TCS BIM_3.BI3 QA1_BLQ_SF6 QA1_BLQ_SF6 BI_QA1_BLQ_SF6
W3_CB_CLOSED VIn2 BI2 VIn4 BI4
CB CLOSED CB CLOSED BI_W3_CB_CLOSED QA2_SPR_UNCH QA2_SPR_UNCH BI_QA2_SPR_UNCH
VIn3 BI3 W2_QA2_LOCAL VIn5 BI5
BIM_3.BI10 SPRING UNCH SPRING UNCH BI_W3_CB_SPRING_UNCH QA2_LOCAL QA2_LOCAL BI_QA2_LOCAL
VIn4 BI4 VIn6 BI6
W2_CB_OPEN BIM_3.BI8
W2_CB_OPEN W2_CB_OPEN BI_W2_CB_OPEN QA1_LOCAL QA1_LOCAL BI_QA1_LOCAL
VIn5 BI5 VIn7 BI7
CB_OPEN CB_OPEN BI_W3_CB_OPEN Not used Not used
BIM_3.BI5 VIn6 BI6 W1_QA1_LOCAL VIn8 BI8
W1_QC9_OPEN W1_QC9_OPEN BI_W1_QC9_OPEN Coupler Clos Coupler Clos BI_Bay_Coupler_Closed
W3_CB_OPEN VIn7 BI7 VIn9 BI9
W1_QC9_CLOSED W1_QC9_CLOSED BI_W1_QC9_CLOSED BIM_3.BI4 Any Bay Trans Any Bay Trans BI_Any_Bay_Transfer_Trip
VIn8 BI8 VIn10 BI10
BIM_3.BI9 Not used Not used
VIn9 BI9
E TC2_OK_W2_CB E
TC2_W2_CB TC2_W2_CB BI_W2_CB_TC2
VIn10 BI10
BIM_5.BI11
Main Application: V_BI, Page: 1
1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
28 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

W3_W1 BI
SMBI
BLOCK OC BLOCK OC BI_W3_BLOCK_BBP_OC_STEP
VIn1 BI1
A A
BLOCK EF BLOCK EF BI_W3_BLOCK_BBP_EF_STEP
VIn2 BI2
Not used Not used
VIn3 BI3
Not used Not used
VIn4 BI4
Not used Not used
VIn5 BI5
Not used Not used
VIn6 BI6
Not used Not used
VIn7 BI7
Not used Not used
BUCCHOLZ_TRIP VIn8 BI8
Not used Not used
VIn9 BI9
BIM_5.BI15 Not used Not used
VIn10 BI10
PRES_SUB_TRIP

B B
BIM_7.BI2
OIL_TEMP_TRIP
TRAFO GUARDS

BIM_7.BI3 SMBI
BUCHHOLZ TRIP BUCHHOLZ TRIP BI_TRAFO_BUCHHOLZ_TRIP
WND_TEMP_TRIP VIn1 BI1
PRESSURE TRIP PRESSURE TRIP BI_TRAFO_PRESSURE_TRIP
VIn2 BI2
OIL_LEVEL_ALM BIM_7.BI4 WNDG TEMP TRP WNDG TEMP TRP BI_WINDING_TEMP_TRIP
VIn3 BI3
OIL TEMP TRIP OIL TEMP TRIP BI_TRAFO_OIL_TEMP_TRIP
BIM_7.BI5 VIn4 BI4
WNDG TEMP AL WNDG TEMP AL BI_WINDING_TEMP_ALARM
OIL_OLTC_ALM VIn5 BI5
OIL TEMP AL OIL TEMP AL BI_TRAFO_OIL_TEMP_ALARM
VIn6 BI6
BIM_7.BI6 OIL LEVEL ALM OIL LEVEL ALM BI_TRAFO_OIL_LEVEL_ALARM
VIn7 BI7
C BUCCHOLZ_ALM C
OIL OLTC ALM OIL OLTC ALM BI_OLTC_OIL_LEVEL_ALARM
VIn8 BI8
BCHLZ_ALM BCHLZ_ALM BI_TRAFO_BUCCHOLZ_ALARM
BIM_7.BI7 VIn9 BI9
Not used Not used
OIL_TEMP_ALM VIn10 BI10

BIM_7.BI8
WINDG_TEMP_AL

BIM_7.BI9

OLTC_OIL_TRIP
OLTC GUARDS
BIM_5.BI14
SMBI
D OIL_LEV_TRIP D
BUCHHOLZ TRIP BUCHHOLZ TRIP BI_OLTC_BUCHHOLZ_TRIP
VIn1 BI1
PRESSURE TRIP PRESSURE TRIP BI_OLTC_PRESSURE_TRIP
BIM_5.BI13 VIn2 BI2
GAS_H_ALM
OIL LEVEL TRP OIL LEVEL TRP BI_OLTC_OIL_LEVEL_TRIP
PRT_OLTC_TRIP VIn3 BI3
OIL LEVEL TRP OIL LEVEL TRP BI_TRAFO_OIL_LEVEL_TRIP
BIM_7.BI10 VIn4 BI4
BIM_5.BI16 PRT OLTC TRIP PRT OLTC TRIP BI_RELE_PROT_OLTC_TRIP
GAS_HH_ALM VIn5 BI5
VALV PRS TRIP VALV PRS TRIP BI_VALV_PRES_TRIP
VALV_PRS_TRIP VIn6 BI6
BIM_7.BI11 GAS H ALM GAS H ALM BI_GAS_HIGH_ALARM
VIn7 BI7
HUMD_H_ALM BIM_7.BI1 GAS HH ALM GAS HH ALM BI_GAS_HIGH_HIGH_ALARM
VIn8 BI8
HUMD H ALM HUMD H ALM BI_MOISTURE_HIGH_ALARM
BIM_7.BI12 VIn9 BI9
HUMD_HH_ALM
HUMD HH ALM HUMD HH ALM BI_MOISTURE_HIGH_HIGH_ALARM
VIn10 BI10
E BIM_7.BI13 E

Main Application: V_BI, Page: 2


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
29 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

FP1_TEST_MODE
LOCKOUT
BIM_5.BI1
SMBI
FAIL_FP2
RESET LOCKOUT RESET LOCKOUT BI_RESET_LOCKOUT
VIn1 BI1
A A
FP1_TEST FP1_TEST BI_FP1_TEST_MODE
BIM_5.BI2 VIn2 BI2
FP2_FAIL FP2_FAIL BI_FP2_INTERNAL_FAIL
FAIL_FP3 VIn3 BI3
FP3_FAIL FP3_FAIL BI_FP3_INTERNAL_FAIL
VIn4 BI4
BIM_5.BI3 FP4_FAIL FP4_FAIL FP4_INTERNAL_FAIL
VIn5 BI5
FAIL_FP4
FF_MCB_SACO FF_MCB_SACO BI_MCB_FAIL_SACO
VIn6 BI6
86T_OPTD 86T_OPTD BI_86T_OPERADO
BIM_5.BI4 VIn7 BI7
Not used Not used
FF_MCB_SACO VIn8 BI8
Not used Not used
VIn9 BI9
BIM_5.BI5 Not used Not used
VIn10 BI10
86T_OPTD

B BIM_5.BI6 B

COMMON INPUT
SMBI
ACTIVE GROUP1 ACTIVE GROUP1 BI_ACTIVE_GROUP1
VIn1 BI1
ACTIVE GROUP2 ACTIVE GROUP2 BI_ACTIVE_GROUP2
VIn2 BI2
CHANGE LOCK CHANGE LOCK BI_CHANGE_LOCK
VIn3 BI3
Not used Not used
VIn4 BI4
ACT TESTMODE ACT TESTMODE BI_ACTIVATE_TESTMODE
VIn5 BI5
C C
RESET LEDS RESET LEDS BI_RESET_LEDS
VIn6 BI6
TEST LEDS TEST LEDS BI_LED_TEST
VIn7 BI7
Not used Not used
VIn8 BI8
Not used Not used
VIn9 BI9
Not used Not used
VIn10 BI10

D THOL INPUTS D
SMBI
FORCED COOL FORCED COOL BI_FORCED_COOLING_THERMAL_OVERLOAD
VIn1 BI1
RESET THOL RESET THOL BI_RESET_THERMAL_OVERLOAD
VIn2 BI2
Not used Not used
VIn3 BI3
Not used Not used
VIn4 BI4
Not used Not used
VIn5 BI5
Not used Not used
VIn6 BI6
Not used Not used
VIn7 BI7
Not used Not used
VIn8 BI8
Not used Not used
VIn9 BI9
E E
Not used Not used
VIn10 BI10

Main Application: V_BI, Page: 3


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
30 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

TCPOS1 CODE
SMBI
BIT 1 BIT 1 TCPOS1_BIT1
VIn1 BI1
A A
BIT 2 BIT 2 TCPOS1_BIT2
VIn2 BI2
BIT 3 BIT 3 TCPOS1_BIT3
VIn3 BI3
BIT 4 BIT 4 TCPOS1_BIT4
VIn4 BI4
BIT 5 BIT 5 TCPOS1_BIT5
VIn5 BI5
BIT 6 BIT 6 TCPOS1_BIT6
VIn6 BI6
Not used Not used
VIn7 BI7
Not used Not used
VIn8 BI8
Not used Not used
VIn9 BI9
Not used Not used
VIn10 BI10

B B

TCPOS1 SIGNAL
SMBI
IN PROGRESS IN PROGRESS TCPOS1_TCINPROG
VIn1 BI1
INPUT ERROR INPUT ERROR TCPOS1_INPUT_ERROR
VIn2 BI2
RESET ERROR RESET ERROR TCPOS1_RESET_ERROR
VIn3 BI3
PARITY ERROR PARITY ERROR TCPOS1_PARITY_ERROR
VIn4 BI4
BINPUT ERROR BINPUT ERROR TCPOS1_BINPUT_ERROR
VIn5 BI5
C C
Not used Not used
VIn6 BI6
Not used Not used
VIn7 BI7
Not used Not used
VIn8 BI8
Not used Not used
VIn9 BI9
Not used Not used
VIn10 BI10

D TCPOS1 MIM D
SMMI
MILLI AMP INP AI1 TCPOS1_MA
VIn1 AI2
Not used AI3
VIn2 AI4
Not used AI5
VIn3 AI6
Not used
VIn4
Not used
VIn5
Not used
VIn6

E E

Main Application: V_BI, Page: 4


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
31 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

TCPOS2 CODE
A A
SMBI
BIT 1 BIT 1 TCPOS2_BIT1
VIn1 BI1
BIT 2 BIT 2 TCPOS2_BIT2
VIn2 BI2
BIT 3 BIT 3 TCPOS2_BIT3
VIn3 BI3
BIT 4 BIT 4 TCPOS2_BIT4
VIn4 BI4
BIT 5 BIT 5 TCPOS2_BIT5
VIn5 BI5
BIT 6 BIT 6 TCPOS2_BIT6
VIn6 BI6
Not used Not used
VIn7 BI7
Not used Not used
VIn8 BI8
Not used Not used
VIn9 BI9
B Not used Not used B
VIn10 BI10

TCPOS2 SIGNAL
SMBI
IN PROGRESS IN PROGRESS TCPOS2_TCINPROG
VIn1 BI1
INPUT ERROR INPUT ERROR TCPOS2_INPUT_ERROR
VIn2 BI2
RESET ERROR RESET ERROR TCPOS2_RESET_ERROR
VIn3 BI3
C C
PARITY ERROR PARITY ERROR TCPOS2_PARITY_ERROR
VIn4 BI4
BINPUT ERROR BINPUT ERROR TCPOS2_BINPUT_ERROR
VIn5 BI5
Not used Not used
VIn6 BI6
Not used Not used
VIn7 BI7
Not used Not used
VIn8 BI8
Not used Not used
VIn9 BI9
Not used Not used
VIn10 BI10

D D

TCPOS2 MIM
SMMI
MILLI AMP INP AI1 TCPOS2_MA
VIn1 AI2
Not used AI3
VIn2 AI4
Not used AI5
VIn3 AI6
Not used
VIn4
Not used
VIn5
Not used
VIn6
E E

Main Application: V_BI, Page: 5


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
32 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

W1_CB_TRIP
W1_CB
SMBO BOM_4.BO1
W1_CB_TRP1-TRIP BO1 CB TRIP
W1_CB_TRP1-CLLKOUT BO2 BO1
A A
W1_CB_TCS_ALARM BO3 TRIP LOCKOUT
BI_W1_CB_CLOSED BO4 BO2
BI_W1_CB_SPRING_UNCH BO5 TCS ALARM
FALSE BO6 BO3
FALSE BO7 CB CLOSED
FALSE BO8 BO4
FALSE BO9 CB SPRING UNC LED.YELLOW13
FALSE BO10 BO5
Not used
BO6
Not used
BO7 AP_CONTROL
Not used
BO8
SMBO W1_CMD_OP
Not used
BO9 QA1-OPEN-EXE==SXCBR BO1 QA1_OPEN_CMD
Not used QA1-CLOSE-EXE==SXCBR BO2 BO1
BO10 QA2-OPEN-EXE==SXCBR BO3 QA1_CLOSE_CMD BOM_4.BO18
BO2 W1_CMD_CL
QA2-CLOSE-EXE==SXCBR BO4
QA3-OPEN-EXE==SXCBR BO5 QA2_OPEN_CMD
QA3-CLOSE-EXE==SXCBR BO6 BO3
B BOM_4.BO17 B
BO7 QA2_CLOSE_CMD
BO4 W2_CMD_OP
INV BO8
BO9 QA3_OPEN_CMD
BI_86T_OPERADO INPUT OUT BO10 BO5
QA3_CLOSE_CMD BOM_4.BO20
BO6 W2_CMD_CL
W2CB_TC1_TRIP
bloqueo 10Kv
W2 CB BO7
Not used BOM_4.BO19
BOM_4.BO5 BO8 W3_CMD_OP
SMBO
Not used
W2CB_TC2_TRIP BO9
W2_CB_TRP3-TRIP BO1 CB TRIP
W2_CB_TRP3-CLLKOUT BO2 BO1 Not used BOM_4.BO22
BO10 W3_CMD_CL
W2_CB_TCS_ALARM BO3 TRIP LOCKOUT
BI_W2_CB_CLOSED BO4 BO2 BOM_4.BO7
BI_W2_CB_SPRING_UNCH BO5 TCS ALARM
FALSE BO6 BO3 BOM_4.BO21
FALSE BO7 CB CLOSED
FALSE BO8 BO4 LED.YELLOW14
QB9-EXE-OP==SCSWI BO9 CB SPRING UNC
QB9-EXE-CL==SCSWI BO10 BO5 BOM_4.BO23
C C
Not used
BO6
Not used
BO7
Not used
BO8 BOM06-BO1
QB9_CLOSE_CMD
BO9
QB9_OPEN_CMD BOM_6.BO1
BO10 BOM06-BO2

BOM_6.BO2

D W3 CB D
SMBO W3_CB_TRIP
W3_CB_TRP2-TRIP BO1 CB TRIP
W3_CB_TRP2-CLLKOUT BO2 BO1
W3_CB_TCS_ALARM BO3 TRIP LOCKOUT BOM_4.BO9
BI_W3_CB_CLOSED BO4 BO2
BI_W3_CB_SPRING_UNCH BO5 TCS ALARM
FALSE BO6 BO3
FALSE BO7 CB CLOSED
FALSE BO8 BO4
FALSE BO9 CB SPRING UNC
FALSE BO10 BO5 LED.YELLOW15
Not used
BO6
Not used
BO7
Not used
BO8
Not used
BO9
E E
Not used
BO10

Main Application: V_BO, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
33 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

A A

B B

C C

D D

E E

Main Application: V_BO, Page: 2


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
34 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

DIFF PROT
SMBO
T3D1-TRIP BO1 TRIP
T3D1-TRIPRES BO2 BO1
A A
T3D1-TRIPUNRE BO3 TRIP RESTRAIN
T3D1-TRNSUNR BO4 BO2
T3D1-TRNSSENS BO5 TRIP UNRES
T3D1-START BO6 BO3
T3D1-IDALARM BO7 TRIP NS UNRES
T3D1-OPENCTAL BO8 BO4
TRIP_86T BO9 TRIP NS SENS
FALSE BO10 BO5
START
BO6
IDIFF ALARM
BO7
OPEN CT ALARM
BO8 TRIP_86T
TRIP_86T
BO9
Not used BOM_4.BO13
BO10

B B

DIFF PROT
SMBO
T3D1-BLK2H BO1 I2 BLOCK
T3D1-BLK5H BO2 BO1
T3D1-BLKWAV BO3 I5 BLOCK
FALSE BO4 BO2
FALSE BO5 BLOCK WAV
FALSE BO6 BO3
FALSE BO7 Not used
FALSE BO8 BO4
FALSE BO9 Not used
GNRL_TRIP BO10 BO5
C C
Not used
BO6
Not used
BO7
Not used
BO8
Not used
BO9 GNRL_TRIP
GNRL TRIP
BO10
BOM_4.BO15

D W1 BFP PROT D
SMBO
W1_CB_BFP1-TRBU BO1 CB TRP BU
W1_CB_BFP1-TRRET BO2 BO1
W1_CB_PD1-TRIP BO3 CB RETRIP
FALSE BO4 BO2
FALSE BO5 CB PD TRP
FALSE BO6 BO3
FALSE BO7 Not used
FALSE BO8 BO4
FALSE BO9 Not used
FALSE BO10 BO5
Not used
BO6
Not used
BO7
Not used
BO8
Not used
BO9
E E
Not used
BO10

Main Application: V_BO, Page: 3


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
35 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

W1 PROT
SMBO
W1_IOC1-TRIP BO1 IOC TRIP
W1_TOC1-TRIP BO2 BO1
A A
W1_TOC1-START BO3 TOC TRIP
W1_TOC1-STL1 BO4 BO2 LED.RED2
W1_TOC1-STL2 BO5 TOC START
W1_TOC1-STL3 BO6 BO3
W1_IEF-TRIP BO7 TOC START L1
W1_REF1-TRIP BO8 BO4
W1_REF1-START BO9 TOC START L2
W1_REF1-DIROK BO10 BO5
TOC START L3
BO6
IEF TRIP
BO7
REF TRIP
BO8
REF START
BO9
REF DIROK
BO10

B B

W1 PROT
SMBO
W1_REF1-BLK2H BO1 REF I2 BLOCK
W1_TEF1-TRIP BO2 BO1
W1_TEF1-START BO3 TEF TRIP
W1_TEF1-2NDHARM BO4 BO2
FALSE BO5 TEF START
FALSE BO6 BO3
FALSE BO7 TEF I2 BLOCK
FALSE BO8 BO4
FALSE BO9 Not used
FALSE BO10 BO5
C C
Not used
BO6
Not used
BO7
Not used
BO8
Not used
BO9
Not used
BO10

D W2 PROT D
SMBO
W2_CB_BFP3-TRBU BO1 BFP TRP BU
W2_CB_BFP3-TRRET BO2 BO1
W2_TOC2-TRIP BO3 BFP RETRIP
W2_TOC2-START BO4 BO2
W2_TOC2-STL1 BO5 TOC TRIP
W2_TOC2-STL2 BO6 BO3
W2_TOC2-STL3 BO7 TOC START LED.RED3
W2_REF2-TRIP BO8 BO4
W2_REF2-START BO9 TOC START L1
W2_REF2-DIROK BO10 BO5
TOC START L2
BO6
TOC START L3
BO7
REF TRIP
BO8
REF START
BO9
E E
REF DIR OK
BO10

Main Application: V_BO, Page: 4


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
36 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

W2 PROT
SMBO
W2_REF2-BLK2H BO1 REF I2 BLOCK
W2_TEF2-TRIP BO2 BO1
A A
W2_TEF2-START BO3 TEF TRIP
W2_TEF2-STFW BO4 BO2
W2_TEF2-STRV BO5 TEF START
W2_TEF2-2NDHARM BO6 BO3
W2_TOV1-TRIP BO7 TEF START FW
W2_TOV1-START BO8 BO4
W2_TUV1-TRIP BO9 TEF START RV
W2_TUV1-START BO10 BO5
TEF 2ND HARM
BO6
TOV TRIP
BO7
TOV START
BO8
TUV TRIP
BO9
TUV START
BO10

B B

W2 SYNCH

SMBO
W2_SYN1_SYNOK BO1 SYNCH OK
W2_SYN1-AUTOENOK BO2 BO1
W2_SYN1-AUTOSYOK BO3 AUTO ENERG OK
W2_SYN1-MANENOK BO4 BO2
W2_SYN1-MANSYOK BO5 AUTO SYNCH OK
W2_SYN_AUTO_OK BO6 BO3
W2_SYN_MAN_OK BO7 MAN ENERG OK
W2_FSD1-BLKU BO8 BO4
FALSE BO9 MAN SYNCH OK
FALSE BO10 BO5
C AUTO OK C
BO6
MAN OK
BO7
FUSE FAILURE
BO8
Not used
BO9
Not used
BO10

W3 PROT
D D
SMBO
W3_CB_BFP2-TRBU BO1 BFP TRP BU
W3_CB_BFP2-TRRET BO2 BO1
W3_TOC3-TRIP BO3 BFP RETRIP
W3_TOC3-START BO4 BO2
W3_TOC3-STL1 BO5 TOC TRIP
W3_TOC3-STL2 BO6 BO3
W3_TOC3-STL3 BO7 TOC START LED.RED4
W3_TEF3-TRIP BO8 BO4
W3_TEF3-START BO9 TOC START L1
W3_TEF3-STFW BO10 BO5
TOC START L2
BO6
TOC START L3
BO7
TEF TRIP
BO8
TEF START
BO9
E TEF START FW E
BO10

Main Application: V_BO, Page: 5


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
37 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

W3 PROT
SMBO
W3_TEF3-STRV BO1 TEF START RV
W3_TEF3-2NDHARM BO2 BO1
A A
W3_TRV1-TRIP BO3 TEF I2 BLOCK
W3_TRV1-TR2 BO4 BO2
W3_TRV1-START BO5 TRV TRIP
FALSE BO6 BO3
FALSE BO7 TRV TR2
FALSE BO8 BO4
FALSE BO9 TRV START
FALSE BO10 BO5
Not used
BO6
Not used
BO7
Not used
BO8
Not used
BO9
Not used
BO10

B B

THERM OVLOAD
SMBO
W2_TTR1-TRIP BO1 W2 THOL TRIP
W2_TTR1-ALARM1 BO2 BO1
W2_TTR1-ALARM2 BO3 W2 ALARM1
W3_TTR2-TRIP BO4 BO2
W3_TTR2-ALARM1 BO5 W2 ALARM2
W3_TTR2-ALARM2 BO6 BO3
FALSE BO7 W3 THOL TRIP
FALSE BO8 BO4
FALSE BO9 W3 ALARM 1
FALSE BO10 BO5
C C
W3 ALARM 2
BO6
Not used
BO7
Not used
BO8
Not used
BO9
Not used
BO10

D D

E E

Main Application: V_BO, Page: 6


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
38 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

DRP SIGNALS
SMBO
A DRP-RECSTART BO1 REC STARTED A
DRP-RECMADE BO2 BO1
DRP-MEMUSED BO3 REC MADE
FALSE BO4 BO2
FALSE BO5 REC MEMUSED
FALSE BO6 BO3
GNRL_START_L1 BO7 Not used
GNRL_START_L2 BO8 BO4
GNRL_START_L3 BO9 Not used
GNRL_START_N BO10 BO5
Not used LED.YELLOW8
BO6
START L1
BO7
START L2 LED.YELLOW7
BO8
START L3
BO9
START N LED.YELLOW9
BO10

B LED.YELLOW10 B

YELLOW LED
SMBO
W1_PROTECTION_TRIP BO1 W1 PROT TRIP
W2_PROTECTION_TRIP BO2 BO1
W3_PROTECTION_TRIP BO3 W2 PROT TRIP
CURRENT_PROT_START BO4 BO2
VOLTAGE_PROT_START BO5 W3 PROT TRIP
BI_TRAFO_GUARD_ALARM BO6 BO3
THERMAL_OVELOAD_ALARM BO7 CURRENT START
SUPERVISON_ALARM BO8 BO4
C TRIP_LOCKOUT BO9 VOLTAGE START C
FALSE BO10 BO5
GUARD ALARM
BO6
THOL ALARM LED.YELLOW11
BO7
SUPERV ALARM
BO8
TRIP LOCKOUT
BO9
Not used
BO10

D D

E E

Main Application: V_BO, Page: 7


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
39 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

RED LED
SMBO
T3D1-TRIP BO1 DIFF TRIP
REF_PROT_TRIP BO2 BO1
A LED.RED1 A
CB_FAIL_TRIP BO3 REF TRIP
CURRENT_PROT_TRIP BO4 BO2
VOLTAGE_PROT_TRIP BO5 CB FAIL TRIP
TRAFO_OLTC_GUARD_TRIP BO6 BO3
FALSE BO7 CURRENT TRIP
FALSE BO8 BO4
FALSE BO9 VOLTAGE TRIP
MECHANICAL_TRIP BO10 BO5
GUARD TRIP
BO6
Not used
BO7
Not used
BO8
Not used
BO9
MECH TRIP
BO10
LED.RED5

B B

COMMON FUNC
SMBO
ACGR-GRP1 BO1 GRP1 ACTIVE
ACGR-GRP2 BO2 BO1
ACGR-SETCHGD BO3 GRP2 ACTIVE
TEST-ACTIVE BO4 BO2
LHMI-LEDSCLRD BO5 SETTING CHGD
FALSE BO6 BO3
FALSE BO7 IN TESTMODE
FALSE BO8 BO4
FALSE BO9 LEDS CLRD
FALSE BO10 BO5
C C
Not used
BO6
Not used
BO7
Not used
BO8
Not used
BO9
Not used
BO10

D COMMON SUPERV D
SMBO
TIME-RTCERR BO1 RTC ERROR
TIME-TSYNCERR BO2 BO1
IES-FAIL BO3 TSYNCH ERROR
IES-WARNING BO4 BO2
DOS-WARNING BO5 INT FAIL
DOS-ALARM BO6 BO3
FALSE BO7 INT WARNING
FALSE BO8 BO4
FALSE BO9 DOS WARNING
FALSE BO10 BO5
DOS ALARM
BO6
Not used
BO7
Not used
BO8
Not used
BO9
E E
Not used
BO10

Main Application: V_BO, Page: 8


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
40 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

CURRENT MEASUREMENT, WINDING 1 SIDE

A CMMXU A
W1_CT_C_I3P I3P IL1
IL1RANG
IL1ANGL
IL2
IL2RANG
IL2ANGL
IL3
IL3RANG
IL3ANGL

CMSQI
W1_CT_C_I3P I3P 3I0
3I0RANG
3I0ANGL
B I1 B
I1RANG
I1ANGL
I2
I2RANG
I2ANGL

CURRENT MEASUREMENT, WINDING 2 SIDE

CMMXU
W2_CT_C_I3P I3P IL1
IL1RANG
C IL1ANGL C
IL2
IL2RANG
IL2ANGL
IL3
IL3RANG
IL3ANGL

CMSQI
W2_CT_C_I3P I3P 3I0
3I0RANG
3I0ANGL
I1
I1RANG
I1ANGL
D I2 D
I2RANG
I2ANGL

E E

Main Application: MEAS, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
41 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

VOLTAGE MEASUREMENT, WINDING 1 SIDE RANGE_XP


RANGE HIGHHIGH
HIGH
NORMAL
A LOW A
LOWLOW
VMMXU VNMMXU
W1_VT_U3P U3P UL12 W1_VT_U3P U3P UL1
UL12RANG UL1RANG AND
UL12ANGL UL1ANGL RANGE_XP
UL23 UL2 INPUT1 OUT LINE_VOTS_LOLO
UL23RANG UL2RANG RANGE HIGHHIGH INPUT2 NOUT LINE_VOLTS_ON
UL23ANGL UL2ANGL HIGH INPUT3
UL31 UL3 NORMAL INPUT4N
UL31RANG UL3RANG LOW
UL31ANGL UL3ANGL LOWLOW

FALSE
RANGE_XP
VMSQI
RANGE HIGHHIGH
W1_VT_U3P U3P 3U0 HIGH
B 3U0RANG NORMAL B
3U0ANGL LOW
U1 LOWLOW
U1RANG
U1ANGL
U2
U2RANG
U2ANGL

POWER MEASUREMENT, WINDING 1 SIDE

CVMMXN
C C
W1_CT_C_I3P I3P S ETPMMTR
W1_VT_U3P U3P S_RANGE
P_INST P ACCST
P Q EAFPULSE
P_RANGE TRUE STACC EARPULSE
Q_INST FALSE RSTACC ERFPULSE
Q FALSE RSTDMD ERRPULSE
Q_RANGE EAFALM
PF EARALM
PF_RANGE ERFALM
ILAG ERRALM
ILEAD EAFACC
U EARACC
U_RANGE ERFACC
I ERRACC
I_RANGE MAXPAFD
F MAXPARD
F_RANGE MAXPRFD
MAXPRRD

D D

E E

Main Application: MEAS, Page: 2


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
42 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

CURRENT MEASUREMENT, WINDING 3 SIDE

A A

CMMXU
W3_CT_C_I3P I3P IL1
IL1RANG
IL1ANGL
IL2
IL2RANG
IL2ANGL
IL3
IL3RANG
IL3ANGL

B B

CMSQI
W3_CT_C_I3P I3P 3I0
3I0RANG
3I0ANGL
I1
I1RANG
I1ANGL
I2
I2RANG
I2ANGL

C C

D D

E E

Main Application: MEAS, Page: 3


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
43 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

TRANSFORMER & OLTC GUARD TRIP & ALARM

A A
OR OR
BI_TRAFO_BUCHHOLZ_TRIP INPUT1 OUT BI_BUCHHOLZ_TRIP W1_CB_TRP1-TRIP INPUT1 OUT GNRL_TRIP
BI_OLTC_BUCHHOLZ_TRIP INPUT2 NOUT W2_CB_TRP3-TRIP INPUT2 NOUT
FALSE INPUT3 W3_CB_TRP2-TRIP INPUT3
FALSE INPUT4 FALSE INPUT4
FALSE INPUT5 FALSE INPUT5
FALSE INPUT6 FALSE INPUT6

OR
BI_TRAFO_PRESSURE_TRIP INPUT1 OUT BI_PRESSURE_TRIP
BI_OLTC_PRESSURE_TRIP INPUT2 NOUT
BI_VALV_PRES_TRIP INPUT3
FALSE INPUT4
B FALSE INPUT5 B
FALSE INPUT6
OR
BI_BUCHHOLZ_TRIP INPUT1 OUT MECHANICAL_TRIP
BI_PRESSURE_TRIP INPUT2 NOUT
BI_TRAFO_GUARD_TRIP INPUT3
OR BI_OLTC_GUARD_TRIP INPUT4
TRAFO_OLTC_GUARD_TRIP INPUT5
BI_TRAFO_BUCHHOLZ_TRIP INPUT1 OUT BI_TRAFO_GUARD_TRIP FALSE INPUT6
BI_TRAFO_PRESSURE_TRIP INPUT2 NOUT
BI_TRAFO_OIL_TEMP_TRIP INPUT3
BI_WINDING_TEMP_TRIP INPUT4
BI_TRAFO_OIL_LEVEL_TRIP INPUT5
FALSE INPUT6

OR
OR
C BI_WINDING_TEMP_ALARM INPUT1 OUT BI_TRAFO_GUARD_ALARM C
BI_GAS_HIGH_ALARM INPUT1 OUT BI_TRAFO_OIL_TEMP_ALARM INPUT2 NOUT
BI_GAS_HIGH_HIGH_ALARM INPUT2 NOUT BI_TRAFO_OIL_LEVEL_ALARM INPUT3
BI_MOISTURE_HIGH_ALARM INPUT3 BI_OLTC_OIL_LEVEL_ALARM INPUT4
BI_MOISTURE_HIGH_HIGH_ALARM INPUT4 BI_TRAFO_BUCCHOLZ_ALARM INPUT5
FALSE INPUT5 INPUT6
FALSE INPUT6

OR
BI_OLTC_BUCHHOLZ_TRIP INPUT1 OUT BI_OLTC_GUARD_TRIP
BI_OLTC_PRESSURE_TRIP INPUT2 NOUT
BI_OLTC_OIL_LEVEL_TRIP INPUT3
BI_RELE_PROT_OLTC_TRIP INPUT4
FALSE INPUT5
FALSE INPUT6

D D

OR
BI_TRAFO_GUARD_TRIP INPUT1 OUT TRAFO_OLTC_GUARD_TRIP
BI_OLTC_GUARD_TRIP INPUT2 NOUT
FALSE INPUT3
FALSE INPUT4
FALSE INPUT5
FALSE INPUT6

E E

Main Application: LOGIC, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
44 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

WINDING 1 PROTECTION TRIP

OR OR
A A
W1_REF1-TRIP INPUT1 OUT INPUT1 OUT W1_PROTECTION_TRIP
W1_IOC1-TRIP INPUT2 NOUT INPUT2 NOUT
W1_IEF-TRIP INPUT3 W2_TOV1-TR2 INPUT3
W1_CB_BFP1-TRBU INPUT4 W2_TUV1-TR2 INPUT4
FALSE INPUT5 W3_TRV1-TR2 INPUT5
W1_CB_BFP1-TRRET INPUT6 FALSE INPUT6

OR
FALSE INPUT1 OUT
W1_CB_PD1-TRIP INPUT2 NOUT
FALSE INPUT3
W1_TOC1-TRIP INPUT4
W1_TEF1-TRIP INPUT5
FALSE INPUT6

B B

WINDING 2 PROTECTION TRIP

OR OR
W2_REF2-TRIP INPUT1 OUT INPUT1 OUT W2_PROTECTION_TRIP
W2_CB_BFP3-TRBU INPUT2 NOUT INPUT2 NOUT
W2_CB_BFP3-TRRET INPUT3 FALSE INPUT3
W2_TOC2-TRIP INPUT4 FALSE INPUT4
W2_TEF2-TRIP INPUT5 FALSE INPUT5
W2_TOV1-TRIP INPUT6 FALSE INPUT6

C OR C
W2_TUV1-TRIP INPUT1 OUT
W3_TRV1-TR2 INPUT2 NOUT
W2_TTR1-TRIP INPUT3
FALSE INPUT4
FALSE INPUT5
FALSE INPUT6

WINDING 3 PROTECTION TRIP

OR OR
D D
W3_CB_BFP2-TRRET INPUT1 OUT INPUT1 OUT W3_PROTECTION_TRIP
W3_CB_BFP2-TRBU INPUT2 NOUT INPUT2 NOUT
W3_TOC3-TRIP INPUT3 FALSE INPUT3
W3_TEF3-TRIP INPUT4 FALSE INPUT4
W3_TTR2-TRIP INPUT5 FALSE INPUT5
W3_TRV1-TRIP INPUT6 FALSE INPUT6

OR
W2_TOV1-TR2 INPUT1 OUT
W2_TUV1-TR2 INPUT2 NOUT
FALSE INPUT3
FALSE INPUT4
FALSE INPUT5
FALSE INPUT6

E E

Main Application: LOGIC, Page: 2


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
45 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

CB FAIL TRIP SIGNALS

OR
A W1_CB_BFP1-TRRET INPUT1 OUT CB_FAIL_TRIP A
W1_CB_BFP1-TRBU INPUT2 NOUT
W2_CB_BFP3-TRRET INPUT3
W2_CB_BFP3-TRBU INPUT4
W3_CB_BFP2-TRRET INPUT5
W3_CB_BFP2-TRBU INPUT6

REF PROTECTION TRIP SIGNALS

OR
W1_REF1-TRIP INPUT1 OUT REF_PROT_TRIP
B W2_REF2-TRIP INPUT2 NOUT B
FALSE INPUT3
FALSE INPUT4
FALSE INPUT5
FALSE INPUT6

CURRENT PROTECTION TRIP & START SIGNALS

OR OR
T3D1-TRIP INPUT1 OUT INPUT1 OUT CURRENT_PROT_TRIP
C W1_IOC1-TRIP INPUT2 NOUT INPUT2 NOUT C
W1_IEF-TRIP INPUT3 FALSE INPUT3
W1_TOC1-TRIP INPUT4 FALSE INPUT4
W1_TEF1-TRIP INPUT5 FALSE INPUT5
W2_REF2-TRIP INPUT6 FALSE INPUT6

OR
W2_TOC2-TRIP INPUT1 OUT
W2_TEF2-TRIP INPUT2 NOUT
W2_TTR1-TRIP INPUT3
W3_TOC3-TRIP INPUT4
W3_TEF3-TRIP INPUT5
W3_TTR2-TRIP INPUT6

D D
OR OR
T3D1-START INPUT1 OUT INPUT1 OUT CURRENT_PROT_START
W1_REF1-START INPUT2 NOUT INPUT2 NOUT
W1_TOC1-START INPUT3 FALSE INPUT3
W1_TEF1-START INPUT4 FALSE INPUT4
W2_REF2-START INPUT5 FALSE INPUT5
W2_TOC2-START INPUT6 FALSE INPUT6

OR
W2_TEF2-START INPUT1 OUT
W3_TEF3-START INPUT2 NOUT
W3_TOC3-START INPUT3
FALSE INPUT4
E FALSE INPUT5 E
FALSE INPUT6

Main Application: LOGIC, Page: 3


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
46 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

VOLTAGE PROTECTION TRIP & START SIGNALS

OR
A W2_TOV1-TRIP INPUT1 OUT VOLTAGE_PROT_TRIP A
W2_TUV1-TRIP INPUT2 NOUT
W3_TRV1-TRIP INPUT3
FALSE INPUT4
FALSE INPUT5
FALSE INPUT6

OR
W2_TOV1-START INPUT1 OUT VOLTAGE_PROT_START
W2_TUV1-START INPUT2 NOUT
W3_TRV1-START INPUT3
FALSE INPUT4
FALSE INPUT5
FALSE INPUT6

B B
THERMAL OVERLOAD ALARM

OR
W2_TTR1-ALARM1 INPUT1 OUT THERMAL_OVELOAD_ALARM
W2_TTR1-ALARM2 INPUT2 NOUT
W3_TTR2-ALARM1 INPUT3
W3_TTR2-ALARM2 INPUT4
FALSE INPUT5
FALSE INPUT6

TRIP CIRCUIT SUPERVISION ALARM


C C
OR
W1_CB_TCS_ALARM INPUT1 OUT TRIP:CIRCUIT_SUPERVSION_ALARM
FALSE INPUT2 NOUT
W2_CB_TCS_ALARM INPUT3
W3_CB_TCS_ALARM INPUT4
FALSE INPUT5
FALSE INPUT6

SUPERVISION ALARM

OR
D TRIP:CIRCUIT_SUPERVSION_ALARM INPUT1 OUT SUPERVISON_ALARM D
W2_FSD1-BLKU INPUT2 NOUT
FALSE INPUT3
FALSE INPUT4
FALSE INPUT5
FALSE INPUT6

TRIP LOCKOUT

OR
W1_CB_TRP1-CLLKOUT INPUT1 OUT TRIP_LOCKOUT
FALSE INPUT2 NOUT
W2_CB_TRP3-CLLKOUT INPUT3
W3_CB_TRP2-CLLKOUT INPUT4
FALSE INPUT5
E FALSE INPUT6 E

Main Application: LOGIC, Page: 4


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
47 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

A A

OR
T3D1-STL1 INPUT1 OUT GNRL_START_L1
W1_TOC1-STL1 INPUT2 NOUT
W2_TOC2-STL1 INPUT3
W3_TOC3-STL1 INPUT4
FALSE INPUT5
FALSE INPUT6

OR
B T3D1-STL2 INPUT1 OUT GNRL_START_L2 B
W1_TOC1-STL2 INPUT2 NOUT
W2_TOC2-STL2 INPUT3
W3_TOC3-STL2 INPUT4
FALSE INPUT5
FALSE INPUT6

OR
T3D1-STL3 INPUT1 OUT GNRL_START_L3
W1_TOC1-STL3 INPUT2 NOUT
W2_TOC2-STL3 INPUT3
W2_TOC2-STL3 INPUT4
FALSE INPUT5
FALSE INPUT6
C C

OR
W1_TEF1-START INPUT1 OUT GNRL_START_N
W2_TEF2-START INPUT2 NOUT
W3_TEF3-START INPUT3
FALSE INPUT4
FALSE INPUT5
FALSE INPUT6

D D

E E

Main Application: LOGIC, Page: 5


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
48 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

A A

SP16GGIO SP16GGIO
FALSE BLOCK FALSE BLOCK
BI_W2_CB_SPRING_UNCH MP#-INPUT1 BI_VALV_PRES_TRIP MP#-INPUT1
IN1 IN1
BI_MCB_FAIL_UW1 MP#-INPUT2 BI_TRAFO_PRESSURE_TRIP MP#-INPUT2
IN2 IN2
BI_FP1_TEST_MODE MP#-INPUT3 BI_TRAFO_OIL_TEMP_TRIP MP#-INPUT3
IN3 IN3
BI_FP2_INTERNAL_FAIL MP#-INPUT4 BI_WINDING_TEMP_TRIP MP#-INPUT4
IN4 IN4
BI_FP3_INTERNAL_FAIL MP#-INPUT5 BI_TRAFO_OIL_LEVEL_ALARM MP#-INPUT5
IN5 IN5
FP4_INTERNAL_FAIL MP#-INPUT6 BI_OLTC_OIL_LEVEL_ALARM MP#-INPUT6
B IN6 IN6 B
BI_MCB_FAIL_SACO MP#-INPUT7 BI_TRAFO_BUCCHOLZ_ALARM MP#-INPUT7
IN7 IN7
BI_86T_OPERADO MP#-INPUT8 BI_TRAFO_OIL_TEMP_ALARM MP#-INPUT8
IN8 IN8
W1_CB_TCS_ALARM MP#-INPUT9 BI_WINDING_TEMP_ALARM MP#-INPUT9
IN9 IN9
W2_CB_TCS_ALARM MP#-INPUT10 BI_GAS_HIGH_ALARM MP#-INPUT10
IN10 IN10
W2_CB_TC2_ALARM MP#-INPUT11 BI_GAS_HIGH_HIGH_ALARM MP#-INPUT11
IN11 IN11
W3_CB_TCS_ALARM MP#-INPUT12 BI_MOISTURE_HIGH_ALARM MP#-INPUT12
IN12 IN12
BI_TRAFO_OIL_LEVEL_TRIP MP#-INPUT13 BI_MOISTURE_HIGH_HIGH_ALARM MP#-INPUT13
IN13 IN13
BI_OLTC_OIL_LEVEL_TRIP MP#-INPUT14 LOCAL_IHM MP#-INPUT14
IN14 IN14
BI_TRAFO_BUCHHOLZ_TRIP MP#-INPUT15 REMOTE_IHM MP#-INPUT15
IN15 IN15
BI_RELE_PROT_OLTC_TRIP MP#-INPUT16 FALSE MP#-INPUT16
IN16 IN16
C C

D D

E E

Main Application: LOGIC, Page: 6


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
49 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

DRPRDRE
DRPOFF
RECSTART DRP-RECSTART
A RECMADE DRP-RECMADE A
CLEARED
MEMUSED DRP-MEMUSED

A1RADR
W1_CT_B_IL1 W1 CT IL1
INPUT1
W1_CT_B_IL2 W1 CT IL2
INPUT2
W1_CT_B_IL3 W1 CT IL3
INPUT3
W1_CT_B_IN W1 CT IN
INPUT4
B W1_VT_U1 W1 VT UL1 B
INPUT5
W1_VT_U2 W1 VT UL2
INPUT6
W1_VT_U3 W1 VT UL3
INPUT7
W1_VT_UN W1 VT UN
INPUT8
GRP_OFF Not used
INPUT9
GRP_OFF Not used
INPUT10

C C

A2RADR
GRP_OFF Not used
INPUT11
W1_NEUT_CT_A_IN W1 CT NEUT
INPUT12
W2_CT_B_IL1 W2 CT IL1
INPUT13
W2_CT_B_IL2 W2 CT IL2
INPUT14
W2_CT_B_IL3 W2 CT IL3
INPUT15
W2_CT_B_IN W2 CT IN
INPUT16
W2_NEUT_CT_A_IN W2 CT NEUT
INPUT17
D D
W2_VT_B_U1 W2 VT UL1
INPUT18
W2_VT_B_U2 W2 VT UL2
INPUT19
W2_VT_B_U3 W2 VT UL3
INPUT20

E E

Main Application: DREP_AI, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
50 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

A3RADR
W2_VT_B_UN W2 VT UN
INPUT21
A GRP_OFF Not used A
INPUT22
GRP_OFF Not used
INPUT23
GRP_OFF Not used
INPUT24
W3_3Uo_VT_C_UN W3 VT UN
INPUT25
W3_CT_B_IL1 W3 CT IL1
INPUT26
W3_CT_B_IL2 W3 CT IL2
INPUT27
W3_CT_B_IL3 W3 CT IL3
INPUT28
W3_CT_B_IN W3 CT IN
INPUT29
GRP_OFF Not used
INPUT30

B B

A4RADR
T3D1-IDNSMAG DIFF IDNS MAG
INPUT31
T3D1-IDL1MAG DIFF IDL1 MAG
INPUT32
T3D1-IDL2MAG DIFF IDL2 MAG
INPUT33
T3D1-IDL3MAG DIFF IDL3 MAG
INPUT34
C C
T3D1-IBIAS DIFF IBIAS
INPUT35
W1_REF1-IBIAS W1 REF IBIAS
INPUT36
W1_REF1-IDIFF W1 REF IDIFF
INPUT37
W2_REF2-IBIAS W2 REF IBIAS
INPUT38
W2_REF2-IDIFF W2 REF IDIFF
INPUT39
REALZERO Not used
INPUT40

D D

E E

Main Application: DREP_AI, Page: 2


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
51 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

B1RBDR
T3D1-TRIP DIFF TRIP
INPUT1
T3D1-TRIPRES DIFF TRIP RES
INPUT2
A A
T3D1-TRIPUNRE DIF TRP UNRES
INPUT3
T3D1-TRNSUNR TRIP NS UNRES
INPUT4
T3D1-TRNSSENS TRIP NS SENS
INPUT5
T3D1-STL1 DIFF STL1
INPUT6
T3D1-STL2 DIFF STL2
INPUT7
T3D1-STL3 DIFF STL3
INPUT8
T3D1-BLK2HL1 DIF I2BLCK L1
INPUT9
T3D1-BLK2HL2 DIF I2BLCK L2
INPUT10
T3D1-BLK2HL3 DIF I2BLCK L3
INPUT11
T3D1-BLK5HL1 DIF I5BLCK L1
INPUT12
B T3D1-BLK5HL2 DIF I5BLCK L2 B
INPUT13
T3D1-BLK5HL3 DIF I5BLCK L3
INPUT14
T3D1-IDALARM IDIFF ALARM
INPUT15
T3D1-OPENCTAL OPEN CT ALARM
INPUT16

C C

B2RBDR
T3D1-BLKWAVL1 DIF BLCKWAVL1
INPUT17
T3D1-BLKWAVL2 DIF BLCKWAVL2
INPUT18
T3D1-BLKWAVL3 DIF BLCKWAVL3
INPUT19
W1_CB_TRP1-TRIP W1 CB TRIP
INPUT20
W1_CB_BFP1-TRBU W1 CB TRBU
INPUT21
W1_CB_BFP1-TRRET W1 CB RETRIP
INPUT22
W1_CB_PD1-TRIP W1 CB PD TRP
INPUT23
BI_W1_CB_EXT_TRIP W1 EXT TRIP
INPUT24
D D
BI_W2_CB_EXT_TRIP W2 EXT TRIP
INPUT25
BI_W3_CB_EXT_TRIP W3 EXT TRIP
INPUT26
BI_W1_CB_SPRING_UNCH W1 CB SPRING
INPUT27
BI_W2_CB_SPRING_UNCH W2 CB SPRING
INPUT28
W1_IOC1-TRIP W1 IOC TRIP
INPUT29
W1_TOC1-TRIP W1 TOC TRIP
INPUT30
W1_TOC1-STL1 W1 TOC ST L1
INPUT31
W1_TOC1-STL2 W1 TOC ST L2
INPUT32

E E

Main Application: DREP_BI, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
52 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

B3RBDR
W1_TOC1-STL3 W1 TOC ST L3
INPUT33
A W1_IEF-TRIP W1 IEF TRIP A
INPUT34
W1_REF1-TRIP W1 REF TRIP
INPUT35
W1_REF1-START W1 REF START
INPUT36
W1_REF1-DIROK W1 REF DIROK
INPUT37
BI_QA1_BLQ_SF6 QA1_BLQ_SF6
INPUT38
W1_TEF1-TRIP W1 TEF TRIP
INPUT39
W1_TEF1-START W1 TEF START
INPUT40
W1_TEF1-2NDHARM W1 TEF I2BLC
INPUT41
W2_CB_TRP3-TRIP W2 CB TRIP
INPUT42
W2_CB_BFP3-TRBU W2 CB TRBU
INPUT43
W2_CB_BFP3-TRRET W2 CB RETRIP
INPUT44
B B
W2_TOC2-TRIP W2 TOC TRIP
INPUT45
W2_TOC2-STL1 W2 TOC STL1
INPUT46
W2_TOC2-STL2 W2 TOC STL2
INPUT47
W2_TOC2-STL3 W2 TOC STL3
INPUT48

C C

B4RBDR
W2_REF2-TRIP W2 REF TRIP
INPUT49
W2_REF2-START W2 REF START
INPUT50
W2_REF2-DIROK W2 REF DIROK
INPUT51
BI_W3_CB_SPRING_UNCH W3 CB SPRING
INPUT52
W2_TEF2-TRIP W2 TEF TRIP
INPUT53
W2_TEF2-START W2 TEF START
INPUT54
W2_TEF2-STFW W2 TEF ST FW
INPUT55
W2_TEF2-STRV W2 TEF ST RV
INPUT56
D D
W2_TEF2-2NDHARM W2 TEF I2BLC
INPUT57
W2_TOV1-TRIP W2 TOV TRIP
INPUT58
W2_TOV1-TR2 W2 TOV TR2
INPUT59
W2_TOV1-START W2 TOV START
INPUT60
W2_TUV1-TRIP W2 TUV TRIP
INPUT61
W2_TUV1-TR2 W2 TUV TR2
INPUT62
W2_TUV1-START W2 TUV START
INPUT63
LOV1-START LOV1 START
INPUT64

E E

Main Application: DREP_BI, Page: 2


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
53 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

B5RBDR
W3_CB_TRP2-TRIP W3 CB TRIP
INPUT65
A W3_CB_BFP2-TRBU W3 CB TRBU A
INPUT66
W3_CB_BFP2-TRRET W3 CB RETRIP
INPUT67
W3_TRV1-TRIP W3 TRV TRIP
INPUT68
W3_TRV1-TR2 W3 TRV TR2
INPUT69
W3_TRV1-START W3 TRV START
INPUT70
W3_TOC3-TRIP W3 TOC TRIP
INPUT71
W3_TOC3-STL1 W3 TOC STL1
INPUT72
W3_TOC3-STL2 W3 TOC STL2
INPUT73
W3_TOC3-STL3 W3 TOC STL3
INPUT74
W3_TEF3-TRIP W3 TEF TRIP
INPUT75
W3_TEF3-START W3 TEF START
INPUT76
B B
W3_TEF3-STFW W3 TEF ST FW
INPUT77
W3_TEF3-STRV W3 TEF ST RV
INPUT78
W3_TEF3-2NDHARM W3 TEF I2BLC
INPUT79
W2_FSD1-BLKU FUSE FAILURE
INPUT80

C C

B6RBDR
W2_TTR1-TRIP W2 THOL TRIP
INPUT81
W3_TTR2-TRIP W3 THOL TRIP
INPUT82
BI_BUCHHOLZ_TRIP BUCHHOLZ TRIP
INPUT83
BI_PRESSURE_TRIP PRESSURE TRIP
INPUT84
BI_WINDING_TEMP_TRIP WNDG TEMP TRP
INPUT85
BI_TRAFO_OIL_TEMP_TRIP OIL TEMP TRIP
INPUT86
BI_WINDING_TEMP_ALARM WNDG TEMP AL
INPUT87
D BI_TRAFO_OIL_TEMP_ALARM OIL TEMP AL D
INPUT88
BI_W1_CB_CLOSED W1 CB CLOSED
INPUT89
BI_W2_CB_CLOSED W2 CB CLOSED
INPUT90
BI_W3_CB_CLOSED W3 CB CLOSED
INPUT91
ACGR-GRP1 ACTIVE GROUP1
INPUT92
ACGR-GRP2 ACTIVE GROUP2
INPUT93
ACGR-SETCHGD ACT GRP CHNGD
INPUT94
TEST-ACTIVE TEST-ACTIVE
INPUT95
FALSE Not used
INPUT96

E E

Main Application: DREP_BI, Page: 3


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
54 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

ACTIVE SETTING GROUP

A A
OR ActiveGroup
BI_ACTIVE_GROUP1 INPUT1 OUT ACTGRP1 GRP1 ACGR-GRP1
FALSE INPUT2 NOUT ACTGRP2 GRP2 ACGR-GRP2
FALSE INPUT3 FALSE ACTGRP3 GRP3
FALSE INPUT4 FALSE ACTGRP4 GRP4
FALSE INPUT5 FALSE ACTGRP5 GRP5
FALSE INPUT6 FALSE ACTGRP6 GRP6
SETCHGD ACGR-SETCHGD

OR
BI_ACTIVE_GROUP2 INPUT1 OUT
FALSE INPUT2 NOUT
FALSE INPUT3 CHNGLCK
FALSE INPUT4
FALSE INPUT5 BI_CHANGE_LOCK LOCK
FALSE INPUT6
B B

LED MONITOR

LEDGEN
OR LocalHMI
FALSE BLOCK NEWIND
BI_RESET_LEDS INPUT1 OUT RESET ACK CLRLEDS HMI-ON
FALSE INPUT2 NOUT BI_LED_TEST LEDTEST RED-S
FALSE INPUT3 YELLOW-S
FALSE INPUT4 YELLOW-F
FALSE INPUT5 CLRPULSE
FALSE INPUT6 LEDSCLRD LHMI-LEDSCLRD

C C

TEST MODE ON/OFF

TIMER
TESTMODE
BI_ACTIVATE_TESTMODE INPUT ON
OFF INPUT ACTIVE TEST-ACTIVE
OUTPUT
D SETTING D
NOEVENT

E E

Main Application: COMMON, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
55 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

A A

ERROR SIGNALS

INTERRSIG
FAIL IES-FAIL
WARNING IES-WARNING
CPUFAIL
CPUWARN

B B
TIMEERR
TSYNCERR TIME-TSYNCERR
RTCERR TIME-RTCERR

DOSFRNT
LINKUP OR
WARNING
ALARM INPUT1 OUT DOS-WARNING
INPUT2 NOUT
INPUT3
C FALSE INPUT4 C
FALSE INPUT5
DOSOEMAB FALSE INPUT6

LINKUP
WARNING
ALARM
OR
INPUT1 OUT DOS-ALARM
INPUT2 NOUT
DOSOEMCD INPUT3
FALSE INPUT4
LINKUP FALSE INPUT5
WARNING FALSE INPUT6
ALARM

D D
FIXED SIGNALS

FXDSIGN
OFF FALSE
ON TRUE
INTZERO INTZERO
INTONE INTONE
INTALONE
REALZERO REALZERO
STRNULL STRNULL
ZEROSMPL ZEROSMPL
GRP_OFF GRP_OFF

E E

Main Application: COMMON, Page: 2


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
56 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

A INTERLOCKING FOR BAY A

ABC_LINE
BI_W1_CB_OPEN QA1_OP QA1CLREL QA1-CLREL==ABC_LINE
BI_W1_CB_CLOSED QA1_CL QA1CLITL QA1-CLITL==ABC_LINE
BI_W1_QB9_OPEN QB9_OP QB9REL QB9-CLREL==ABC_LINE
BI_W1_QB9_CLOSED QB9_CL QB9ITL
FALSE QB1_OP QB1REL QB1-CLREL==ABC_LINE
TRUE QB1_CL QB1ITL
TRUE QB2_OP QB2REL QB2-CLREL==ABC_LINE
FALSE QB2_CL QB2ITL
TRUE QB7_OP QB7REL
FALSE QB7_CL QB7ITL
TRUE QC1_OP QC1REL
B FALSE QC1_CL QC1ITL B
TRUE QC2_OP QC2REL
FALSE QC2_CL QC2ITL
BI_W1_QC9_OPEN QC9_OP QC9REL QC9-CLREL==ABC_LINE
AND BI_W1_QC9_CLOSED QC9_CL QC9ITL
TRUE QC11_OP QB1OPTR QB1_OPTR==ABC_LINE
BI_Bay_Coupler_Closed INPUT1 OUT FALSE QC11_CL QB1CLTR QB1_CLTR==ABC_LINE
TRUE INPUT2 NOUT TRUE QC21_OP QB2OPTR QB2_OPTR==ABC_LINE
TRUE INPUT3 FALSE QC21_CL QB2CLTR QB2_CLTR==ABC_LINE
BI_Any_Bay_Transfer_Trip INPUT4N TRUE QC71_OP QB7OPTR
FALSE QC71_CL QB7CLTR
TRUE BB7_D_OP QB12OPTR QB12_OPTR==ABC_LINE
BC_12_CL QB12CLTR QB12_CLTR==ABC_LINE
TRUE BC_17_OP VPQB1TR VP_QB1_TR==ABC_LINE
FALSE BC_17_CL VPQB2TR VP_QB2_TR==ABC_LINE
AND TRUE BC_27_OP VPQB7TR
FALSE BC_27_CL VPQB12TR VP_QB12_TR==ABC_LINE
LINE_VOTS_LOLO INPUT1 OUT VOLT_OFF
BI_MCB_FAIL_UW1 INPUT2 NOUT VOLT_ON
TRUE INPUT3 TRUE VP_BB7_D
FALSE INPUT4N VP_BC_12
C TRUE VP_BC_17 C
TRUE VP_BC_27
TRUE EXDU_ES
TRUE EXDU_BPB
INV OR TRUE EXDU_BC
TRUE QB9_EX1
INPUT OUT INPUT1 OUT TRUE QB9_EX2
INPUT2 NOUT TRUE QB1_EX1
INPUT3 TRUE QB1_EX2
LINE_VOLTS_ON INPUT4 TRUE QB1_EX3
INPUT5 TRUE QB2_EX1
FALSE INPUT6 TRUE QB2_EX2
TRUE QB2_EX3
TRUE QB7_EX1
TRUE QB7_EX2
TRUE QB7_EX3
TRUE QB7_EX4

D D

E E

Main Application: BAY_INTL, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
57 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

A A
BAY RESERVATION

QCRSV
INTZERO EXCH_IN RES_GRT1 QA1_RES_GRT==QCRSV
QA1-RES-RQ==SCSWI RES_RQ1 RES_GRT2 QA2_RES_GRT==QCRSV
QA2-RES-RQ==SCSWI RES_RQ2 RES_GRT3 QA3_RES_GRT==QCRSV
QA3-RES-RQ==SCSWI RES_RQ3 RES_GRT4 QB1_RES_GRT==QCRSV
FALSE RES_RQ4 RES_GRT5 QB2_RES_GRT==QCRSV
FALSE RES_RQ5 RES_GRT6 QB9_RES_GRT==QCRSV
QB9-RES-RQ==SCSWI RES_RQ6 RES_GRT7 QC9_RES_GRT==QCRSV
FALSE RES_RQ7 RES_GRT8
FALSE RES_RQ8 RES_BAYS RES_BAYS==QCRSV
FALSE BLK_RES ACK_TO_B ACK_TO_B==QCRSV
B FALSE OVERRIDE RESERVED RESERVED==QCRSV B
EXCH_OUT==RESIN RES_DATA EXCH_OUT

RESERVATION INPUTS, INFORMATION FROM OTHER BAYS BAY2 (BUS COUPLER)


BAY2 (BUS COUPLER)

RESIN1
BAY_ACK ACK_F_B
BAY_VAL ANY_ACK
BAY_RES VALID_TX VALID_TX==RESIN
C RE_RQ_B C
V_RE_RQ
EXCH_OUT EXCH_OUT==RESIN

D D

E E

Main Application: BAY_RE, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
58 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

LOGICAL NODE FOR INTERLOCKING


A A

SCILO
QA1-OP-POS==SXCBR POSOPEN EN_OPEN QA1-EN-OPEN==SCILO
QA1-CL-POS==SXCBR POSCLOSE EN_CLOSE QA1-EN-CLOSE==SCILO
TRUE OPEN_EN
QA1-CLREL==ABC_LINE CLOSE_EN

SWITCH CONTROLLER

SCSWI
B FALSE BLOCK EXE_OP QA1-EXE-OP==SCSWI B
PSTO==QCBAY PSTO EXE_CL QA1-EXE-CL==SCSWI
QA1-L-SEL==SMBI L_SEL SELECTED QA1-SELECTED==SCSWI
QA1-L-OPEN==SMBI L_OPEN RES_RQ QA1-RES-RQ==SCSWI
QA1-L-CLOSE==SMBI L_CLOSE START_SY QA1-START-SY==SCSWI
FALSE AU_OPEN POSITION QA1-POSITION==SCSWI
FALSE AU_CLOSE OPENPOS QA1-OPEN-POS==SCSWI
CMD_BLKD==QCBAY BL_CMD CLOSEPOS QA1-CLOSED-POS==SCSWI
QA1_RES_GRT==QCRSV RES_GRT POLEDISC QA1-POLDISC==SCSWI
FALSE RES_EXT CMD_BLK
SY_INPRO L_CAUSE QA1-L-CAUSE==SCSWI
TRUE SYNC_OK XOUT
OR QA1-EN-OPEN==SCILO EN_OPEN POS_INTR
QA1-EN-CLOSE==SCILO EN_CLOSE
BI_W2_CB_CLOSED INPUT1 OUT XPOS1
BI_W3_CB_CLOSED INPUT2 NOUT XPOS2
BI_W1_CB_SPRING_UNCH INPUT3 XPOS3
BI_QA1_BLQ_SF6 INPUT4
BI_86T_OPERADO INPUT5
BI_QA1_LOCAL INPUT6

C C

OR
BI_W1_QB9_OPEN INPUT1 OUT
BI_W1_QC9_CLOSED INPUT2
INPUT3
NOUT CIRCUIT BREAKER
INPUT4
INPUT5
INPUT6

SXCBR
FALSE BLOCK XPOS
FALSE LR_SWI EXE_OP QA1-OPEN-EXE==SXCBR
OR QA1-EXE-OP==SCSWI OPEN EXE_CL QA1-CLOSE-EXE==SXCBR
QA1-EXE-CL==SCSWI CLOSE SUBSTED QA1-SUBSTED==SXCBR
INPUT1 OUT BL_OPEN OP_BLKD QA1-OP-BLK==SXCBR
INPUT2 NOUT BL_CLOSE CL_BLKD QA1-CL-BLK==SXCBR
D INPUT3 UPD_BLKD==QCBAY BL_UPD UPD_BLKD D
INPUT4 BI_W1_CB_OPEN POSOPEN POSITION
INPUT5 BI_W1_CB_CLOSED POSCLOSE OPENPOS QA1-OP-POS==SXCBR
INPUT6 TRUE TR_OPEN CLOSEPOS QA1-CL-POS==SXCBR
FALSE TR_CLOSE TR_POS
FALSE RS_CNT CNT_VAL QA1-CNT-VAL==SXCBR
XIN L_CAUSE QA1-L-CAUSE==SXCBR

OR
BI_W1_QB9_OPEN INPUT1 OUT
BI_W1_QC9_CLOSED INPUT2 NOUT
INPUT3
INPUT4
INPUT5
INPUT6

E E

Main Application: W1_QA1_CON, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
59 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

A A

B B

C C

D D

E E

Main Application: W1_QA1_CON, Page: 2


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
60 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

A A

B B

C C

D D

E E

Main Application: W1_QA1_CON, Page: 3


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
61 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

A A

B B

C C

D D

E E

Main Application: W1_QA1_CON, Page: 4


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
62 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

A A

EXTERNAL LOCAL/REMOTE SWITCH


BAY CONTROL

LOCREM QCBAY
LR-OFF==SMBI CTRLOFF OFF LR_OFF PSTO PSTO==QCBAY
LOCREMCTRL LR-LOC==SMBI LOCCTRL LOCAL LR_LOC UPD_BLKD UPD_BLKD==QCBAY
LR-REM==SMBI REMCTRL REMOTE LR_REM CMD_BLKD CMD_BLKD==QCBAY
PSTO==QCBAY PSTO1 HMICTR1 LHMICTRL VALID LR_VALID LOC
INTZERO PSTO2 HMICTR2 BL_UPD REM
INTZERO PSTO3 HMICTR3 BL_CMD
INTZERO PSTO4 HMICTR4
INTZERO PSTO5 HMICTR5
B INTZERO PSTO6 HMICTR6 B
INTZERO PSTO7 HMICTR7
INTZERO PSTO8 HMICTR8
INTZERO PSTO9 HMICTR9
INTZERO PSTO10 HMICTR10
INTZERO PSTO11 HMICTR11
INTZERO PSTO12 HMICTR12

OR
INPUT1 OUT LOCAL_IHM
INPUT2 NOUT
INPUT3
INPUT4
INPUT5
INPUT6

C C
OR
INPUT1 OUT REMOTE_IHM
INPUT2 NOUT
INPUT3
INPUT4
INPUT5
INPUT6

D D

E E

Main Application: BAY_CON, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
63 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

LOGICAL NODE FOR INTERLOCKING


A A
SCILO
QA2-OP-POS==SXCBR POSOPEN EN_OPEN QA2-EN-OPEN==SCILO
QA2-CL-POS==SXCBR POSCLOSE EN_CLOSE QA2-EN-CLOSE==SCILO
TRUE OPEN_EN
TRUE CLOSE_EN

SWITCH CONTROLLER

SCSWI
B FALSE BLOCK EXE_OP QA2-EXE-OP==SCSWI B
PSTO==QCBAY PSTO EXE_CL QA2-EXE-CL==SCSWI
L_SEL SELECTED QA2-SELECTED==SCSWI
L_OPEN RES_RQ QA2-RES-RQ==SCSWI
L_CLOSE START_SY QA2-START-SY==SCSWI
FALSE AU_OPEN POSITION QA2-POSITION==SCSWI
FALSE AU_CLOSE OPENPOS QA2-OPEN-POS==SCSWI
BL_CMD CLOSEPOS QA2-CLOSED-POS==SCSWI
QA2_RES_GRT==QCRSV RES_GRT POLEDISC QA2-POLDISC==SCSWI
RES_EXT CMD_BLK
SY_INPRO L_CAUSE QA2-L-CAUSE==SCSWI
TRUE SYNC_OK XOUT
QA2-EN-OPEN==SCILO EN_OPEN POS_INTR
QA2-EN-CLOSE==SCILO EN_CLOSE
XPOS1
XPOS2
XPOS3

C C

CIRCUIT BREAKER

SXCBR
FALSE BLOCK XPOS
FALSE LR_SWI EXE_OP QA2-OPEN-EXE==SXCBR
QA2-EXE-OP==SCSWI OPEN EXE_CL QA2-CLOSE-EXE==SXCBR
OR QA2-EXE-CL==SCSWI CLOSE SUBSTED QA2-SUBSTED==SXCBR
FALSE BL_OPEN OP_BLKD QA2-OP-BLK==SXCBR
BI_QA2_LOCAL INPUT1 OUT BL_CLOSE CL_BLKD QA2-CL-BLK==SXCBR
FALSE INPUT2 NOUT UPD_BLKD==QCBAY BL_UPD UPD_BLKD
BI_86T_OPERADO INPUT3 BI_W2_CB_OPEN POSOPEN POSITION
D BI_W2_CB_SPRING_UNCH INPUT4 BI_W2_CB_CLOSED POSCLOSE OPENPOS QA2-OP-POS==SXCBR D
FALSE INPUT5 TR_OPEN CLOSEPOS QA2-CL-POS==SXCBR
FALSE INPUT6 TR_CLOSE TR_POS
RS_CNT CNT_VAL QA2-CNT-VAL==SXCBR
XIN L_CAUSE QA2-L-CAUSE==SXCBR

E E

Main Application: W2_QA1_CON, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
64 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

SCILO
A A
QA3-OP-POS==SXCBR POSOPEN EN_OPEN QA3-EN-OPEN==SCILO
QA3-CL-POS==SXCBR POSCLOSE EN_CLOSE QA3-EN-CLOSE==SCILO
TRUE OPEN_EN
TRUE CLOSE_EN

SCSWI
FALSE BLOCK EXE_OP QA3-EXE-OP==SCSWI
PSTO==QCBAY PSTO EXE_CL QA3-EXE-CL==SCSWI
L_SEL SELECTED QA3-SELECTED==SCSWI
L_OPEN RES_RQ QA3-RES-RQ==SCSWI
L_CLOSE START_SY QA3-START-SY==SCSWI
B FALSE AU_OPEN POSITION QA3-POSITION==SCSWI B
FALSE AU_CLOSE OPENPOS QA3-OPEN-POS==SCSWI
BL_CMD CLOSEPOS QA3-CLOSED-POS==SCSWI
QA3_RES_GRT==QCRSV RES_GRT POLEDISC QA3-POLDISC==SCSWI
RES_EXT CMD_BLK
SY_INPRO L_CAUSE QA3-L-CAUSE==SCSWI
TRUE SYNC_OK XOUT
QA3-EN-OPEN==SCILO EN_OPEN POS_INTR
QA3-EN-CLOSE==SCILO EN_CLOSE
XPOS1
XPOS2
XPOS3

C C

SXCBR
FALSE BLOCK XPOS
FALSE LR_SWI EXE_OP QA3-OPEN-EXE==SXCBR
QA3-EXE-OP==SCSWI OPEN EXE_CL QA3-CLOSE-EXE==SXCBR
QA3-EXE-CL==SCSWI CLOSE SUBSTED QA3-SUBSTED==SXCBR
FALSE BL_OPEN OP_BLKD QA3-OP-BLK==SXCBR
BL_CLOSE CL_BLKD QA3-CL-BLK==SXCBR
BL_UPD UPD_BLKD
BI_W3_CB_OPEN POSOPEN POSITION
BI_W3_CB_CLOSED POSCLOSE OPENPOS QA3-OP-POS==SXCBR
TR_OPEN CLOSEPOS QA3-CL-POS==SXCBR
TR_CLOSE TR_POS
RS_CNT CNT_VAL QA3-CNT-VAL==SXCBR
D XIN L_CAUSE QA3-L-CAUSE==SXCBR D

E E

Main Application: W3_QA1_CON, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
65 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

A SCILO A
QB9-OP-POS==SXSWI POSOPEN EN_OPEN QB9-EN-OPEN==SCILO
QB9-CL-POS==SXSWI POSCLOSE EN_CLOSE QB9-EN-CLOSE==SCILO
TRUE OPEN_EN
TRUE CLOSE_EN

SCSWI
FALSE BLOCK EXE_OP QB9-EXE-OP==SCSWI
PSTO==QCBAY PSTO EXE_CL QB9-EXE-CL==SCSWI
B L_SEL SELECTED QB9-SELECTED==SCSWI B
L_OPEN RES_RQ QB9-RES-RQ==SCSWI
L_CLOSE START_SY QB9-START-SY==SCSWI
FALSE AU_OPEN POSITION QB9-POSITION==SCSWI
FALSE AU_CLOSE OPENPOS QB9-OPEN-POS==SCSWI
BL_CMD CLOSEPOS QB9-CLOSED-POS==SCSWI
QB9_RES_GRT==QCRSV RES_GRT POLEDISC QB9-POLDISC==SCSWI
RES_EXT CMD_BLK
SY_INPRO L_CAUSE QB9-L-CAUSE==SCSWI
TRUE SYNC_OK XOUT
QB9-EN-OPEN==SCILO EN_OPEN POS_INTR
QB9-EN-CLOSE==SCILO EN_CLOSE
XPOS1
XPOS2
XPOS3

C C

SXSWI
FALSE BLOCK XPOS
FALSE LR_SWI EXE_OP QB9-OPEN-EXE==SXSWI
OR QB9-EXE-OP==SCSWI OPEN EXE_CL QB9-CLOSE-EXE==SXSWI
QB9-EXE-CL==SCSWI CLOSE SUBSTED QB9-SUBSTED==SXSWI
BI_W1_CB_CLOSED INPUT1 OUT BL_OPEN OP_BLKD QB9-OP-BLK==SXSWI
BI_W1_QC9_CLOSED INPUT2 NOUT BL_CLOSE CL_BLKD QB9-CL-BLK==SXSWI
INPUT3 BL_UPD UPD_BLKD
INPUT4 BI_W1_QB9_OPEN POSOPEN POSITION
INPUT5 BI_W1_QB9_CLOSED POSCLOSE OPENPOS QB9-OP-POS==SXSWI
INPUT6 RS_CNT CLOSEPOS QB9-CL-POS==SXSWI
D XIN CNT_VAL QB9-CNT-VAL==SXSWI D
L_CAUSE QB9-L-CAUSE==SXSWI

E E

Main Application: W1_QB9_CON, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
66 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

A A

B B

C C

D D

E E

Main Application: W1_QB9_CON, Page: 2


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
67 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

SCILO
A A
QC9-OP-POS==SXSWI POSOPEN EN_OPEN QC9-EN-OPEN==SCILO
QC9-CL-POS==SXSWI POSCLOSE EN_CLOSE QC9-EN-CLOSE==SCILO
OPEN_EN
CLOSE_EN

SCSWI
BLOCK EXE_OP
PSTO EXE_CL
L_SEL SELECTED
L_OPEN RES_RQ
B L_CLOSE START_SY B
AU_OPEN POSITION
AU_CLOSE OPENPOS QC9-OPEN-POS==SCSWI
BL_CMD CLOSEPOS QC9-CLOSED-POS==SCSWI
RES_GRT POLEDISC
RES_EXT CMD_BLK
SY_INPRO L_CAUSE
SYNC_OK XOUT
QC9-EN-OPEN==SCILO EN_OPEN POS_INTR
QC9-EN-CLOSE==SCILO EN_CLOSE
XPOS1
XPOS2
XPOS3

C C

SXSWI
BLOCK XPOS
LR_SWI EXE_OP
OPEN EXE_CL
CLOSE SUBSTED
BL_OPEN OP_BLKD
BL_CLOSE CL_BLKD
BL_UPD UPD_BLKD
D BI_W1_QC9_OPEN POSOPEN POSITION QC9-OP-POS==SXSWI D
BI_W1_QC9_CLOSED POSCLOSE OPENPOS QC9-CL-POS==SXSWI
RS_CNT CLOSEPOS
XIN CNT_VAL
L_CAUSE

E E

Main Application: W1_QC9_CON, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
68 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

A A

B B

C C

D D

E E

Main Application: W1_QC9_CON, Page: 2


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
69 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

VSGGIO
A VSGGIO A
FALSE BLOCK BLOCKED
FALSE BLOCK BLOCKED PSTO POSITION
PSTO POSITION IPOS1 POS1 SRMEMORY
IPOS1 POS1 SRMEMORY IPOS2 POS2
IPOS2 POS2 CMDPOS12 SET OUT
CMDPOS12 SET OUT CMDPOS21 RESET NOUT
CMDPOS21 RESET NOUT AND
AND
TRUE INPUT1 OUT
TRUE INPUT1 OUT TRUE INPUT2 NOUT
TRUE INPUT2 NOUT INPUT3
INPUT3 BI_W1_CB_SPRING_UNCH INPUT4N
BI_W2_CB_CLOSED INPUT4N

VSGGIO
B VSGGIO FALSE BLOCK BLOCKED B
PSTO POSITION
FALSE BLOCK BLOCKED IPOS1 POS1 SRMEMORY
PSTO POSITION IPOS2 POS2
IPOS1 POS1 SRMEMORY CMDPOS12 SET OUT
IPOS2 POS2 CMDPOS21 RESET NOUT
CMDPOS12 SET OUT AND
CMDPOS21 RESET NOUT
AND TRUE INPUT1 OUT
TRUE INPUT2 NOUT
TRUE INPUT1 OUT INPUT3
TRUE INPUT2 NOUT BI_QA2_LOCAL INPUT4N
INPUT3
BI_W3_CB_CLOSED INPUT4N

VSGGIO
C FALSE BLOCK BLOCKED C
PSTO POSITION
VSGGIO IPOS1 POS1 SRMEMORY
IPOS2 POS2
FALSE BLOCK BLOCKED CMDPOS12 SET OUT
PSTO POSITION CMDPOS21 RESET NOUT
IPOS1 POS1 SRMEMORY AND
BI_86T_OPERADO IPOS2 POS2
CMDPOS12 SET OUT TRUE INPUT1 OUT
CMDPOS21 RESET NOUT TRUE INPUT2 NOUT
AND INPUT3
BI_QA1_BLQ_SF6 INPUT4N
TRUE INPUT1 OUT
TRUE INPUT2 NOUT
INPUT3
INPUT4N

D D
VSGGIO
FALSE BLOCK BLOCKED
VSGGIO PSTO POSITION
IPOS1 POS1 SRMEMORY
FALSE BLOCK BLOCKED IPOS2 POS2
PSTO POSITION CMDPOS12 SET OUT
IPOS1 POS1 SRMEMORY CMDPOS21 RESET NOUT
BI_W2_CB_SPRING_UNCH IPOS2 POS2 AND
CMDPOS12 SET OUT
CMDPOS21 RESET NOUT TRUE INPUT1 OUT
AND TRUE INPUT2 NOUT
INPUT3
TRUE INPUT1 OUT BI_QA1_LOCAL INPUT4N
TRUE INPUT2 NOUT
INPUT3
INPUT4N

E E

Main Application: HMI, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
70 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

VSGGIO
FALSE BLOCK BLOCKED VSGGIO
PSTO POSITION
IPOS1 POS1 SRMEMORY FALSE BLOCK BLOCKED
BI_W1_QB9_CLOSED IPOS2 POS2 PSTO POSITION
CMDPOS12 SET OUT IPOS1 POS1 SRMEMORY
A CMDPOS21 RESET NOUT IPOS2 POS2 A
AND CMDPOS12 SET OUT
CMDPOS21 RESET NOUT
TRUE INPUT1 OUT AND
TRUE INPUT2 NOUT
INPUT3 TRUE INPUT1 OUT
INPUT4N TRUE INPUT2 NOUT
INPUT3
INPUT4N

VSGGIO
VSGGIO
FALSE BLOCK BLOCKED
PSTO POSITION FALSE BLOCK BLOCKED
IPOS1 POS1 SRMEMORY PSTO POSITION
IPOS2 POS2 IPOS1 POS1 SRMEMORY
B CMDPOS12 SET OUT IPOS2 POS2 B
CMDPOS21 RESET NOUT CMDPOS12 SET OUT
AND CMDPOS21 RESET NOUT
AND
TRUE INPUT1 OUT
TRUE INPUT2 NOUT TRUE INPUT1 OUT
INPUT3 TRUE INPUT2 NOUT
BI_W1_QB9_OPEN INPUT4N INPUT3
INPUT4N

VSGGIO
FALSE BLOCK BLOCKED
PSTO POSITION
IPOS1 POS1 SRMEMORY VSGGIO
BI_W1_QC9_CLOSED
C IPOS2 POS2 C
CMDPOS12 SET OUT FALSE BLOCK BLOCKED
CMDPOS21 RESET NOUT PSTO POSITION
AND IPOS1 POS1 SRMEMORY
IPOS2 POS2
TRUE INPUT1 OUT CMDPOS12 SET OUT
TRUE INPUT2 NOUT CMDPOS21 RESET NOUT
INPUT3 AND
INPUT4N
TRUE INPUT1 OUT
TRUE INPUT2 NOUT
INPUT3
INPUT4N

VSGGIO
D D
FALSE BLOCK BLOCKED
PSTO POSITION VSGGIO
IPOS1 POS1 SRMEMORY
BI_W1_QC9_OPEN IPOS2 POS2 FALSE BLOCK BLOCKED
CMDPOS12 SET OUT PSTO POSITION
CMDPOS21 RESET NOUT IPOS1 POS1 SRMEMORY
AND IPOS2 POS2
CMDPOS12 SET OUT
TRUE INPUT1 OUT CMDPOS21 RESET NOUT
TRUE INPUT2 NOUT AND
INPUT3
INPUT4N TRUE INPUT1 OUT
TRUE INPUT2 NOUT
INPUT3
INPUT4N

E E

Main Application: HMI, Page: 2


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
71 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

VSGGIO
VSGGIO
FALSE BLOCK BLOCKED
PSTO POSITION FALSE BLOCK BLOCKED
A IPOS1 POS1 SRMEMORY PSTO POSITION A
IPOS2 POS2 IPOS1 POS1 SRMEMORY
CMDPOS12 SET OUT IPOS2 POS2
CMDPOS21 RESET NOUT CMDPOS12 SET OUT
AND CMDPOS21 RESET NOUT
AND
TRUE INPUT1 OUT
TRUE INPUT2 NOUT TRUE INPUT1 OUT
INPUT3 TRUE INPUT2 NOUT
INPUT4N INPUT3
INPUT4N

B B
VSGGIO
FALSE BLOCK BLOCKED
PSTO POSITION
IPOS1 POS1 SRMEMORY
IPOS2 POS2
CMDPOS12 SET OUT
CMDPOS21 RESET NOUT
AND
TRUE INPUT1 OUT
TRUE INPUT2 NOUT
INPUT3
INPUT4N

C C

VSGGIO
FALSE BLOCK BLOCKED
PSTO POSITION
IPOS1 POS1 SRMEMORY
IPOS2 POS2
CMDPOS12 SET OUT
CMDPOS21 RESET NOUT
AND
TRUE INPUT1 OUT
TRUE INPUT2 NOUT
D INPUT3 D
INPUT4N

E E

Main Application: HMI, Page: 3


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
72 / 73
Rev. Modification Rel. date Created by Based on 0 06/06/2015 en
1 2 3 4 5 6 7 8

SP16GGIO
A SP16GGIO BLOCK A
MP#-INPUT1
BLOCK IN1
BI_W1_CB_ALAR_SF6 MP#-INPUT1 MP#-INPUT2
IN1 IN2
BI_QA1_BLQ_SF6 MP#-INPUT2 MP#-INPUT3
IN2 IN3
BI_QA1_LOCAL MP#-INPUT3 MP#-INPUT4
IN3 IN4
BI_QA2_LOCAL MP#-INPUT4 MP#-INPUT5
IN4 IN5
MP#-INPUT5 MP#-INPUT6
IN5 IN6
MP#-INPUT6 MP#-INPUT7
IN6 IN7
MP#-INPUT7 MP#-INPUT8
IN7 IN8
MP#-INPUT8 MP#-INPUT9
IN8 IN9
MP#-INPUT9 MP#-INPUT10
IN9 IN10
B MP#-INPUT10 MP#-INPUT11 B
IN10 IN11
MP#-INPUT11 MP#-INPUT12
IN11 IN12
MP#-INPUT12 MP#-INPUT13
IN12 IN13
MP#-INPUT13 MP#-INPUT14
IN13 IN14
MP#-INPUT14 MP#-INPUT15
IN14 IN15
MP#-INPUT15 MP#-INPUT16
IN15 IN16
MP#-INPUT16
IN16

C C

D D

E E

Main Application: GGIO, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
SE_CASMA_138kV(SAT-SAS) ABB Ltd. Graphical Application Configuration AA1E1Q01A1
Replacing Created by Title Document id.
RET670 MOD
SE_CASMA_138kV(SAT-SAS).Substation.E1.Q01 Approved by Rev. Rel. date Lang.
73 / 73