Sie sind auf Seite 1von 18

Supplementary Specification to GIS 30-253 Specification for Field Instruments Rev B02

Table of Contents
Revision History .................................................................................................................................... 4
Related Documents and References ................................................................................................... 4
1. Introduction ................................................................................................................................... 5
2. Supplementary Data ..................................................................................................................... 5
2 Normative References ............................................................................................................. 5
5 Order of Precedence ............................................................................................................... 6
6 General Technical Requirements ............................................................................................ 6
6.1 General .................................................................................................................................... 6
6.2 Hazardous Area Classification ................................................................................................ 7
6.3 Materials .................................................................................................................................. 7
7 Transmitters ............................................................................................................................. 8
7.1 Conventional ............................................................................................................................ 8
7.2 Wireless Transmitters .............................................................................................................. 9
7.3 Foundation Fieldbus ................................................................................................................ 9
8 Temperature Instruments ...................................................................................................... 12
8.1 General .................................................................................................................................. 12
8.2 Thermowells .......................................................................................................................... 12
8.4 Thermocouples ...................................................................................................................... 13
8.6 Temperature Switches ........................................................................................................... 13
8.7 Temperature Transmitters ..................................................................................................... 13
8.8 Filled Thermal Systems ......................................................................................................... 13
8.9 Temperature Gauges............................................................................................................. 14
9 Pressure Instruments............................................................................................................. 14
9.1 General .................................................................................................................................. 14
9.2 Pressure Switches ................................................................................................................. 14
9.3 Pressure and Differential Pressure Transmitters .................................................................. 14
9.4 Pressure Gauges ................................................................................................................... 14
9.5 Diaphragm Seals ................................................................................................................... 14
10 Flow Instruments ................................................................................................................... 15
10.1 General .................................................................................................................................. 15
10.2 Differential Pressure Flow Measurement .............................................................................. 15
10.7 Ultrasonic Flow Meters .......................................................................................................... 15
10.9 Vortex Flow Meters ................................................................................................................ 15
10.14 Flow Element Identification .................................................................................................... 16
11 Level instruments................................................................................................................... 16
11.1 DP Level Transmitters ........................................................................................................... 16
11.5 Displacer Instruments ............................................................................................................ 16
11.7 Tension Wire Float Transmitter ............................................................................................. 16

Document No. EG001-IC-SPE-11-0004 Page 2 of 18 Rev: B01


© BP p.l.c. EG001 Project Internal - Bechtel Confidential
Supplementary Specification to GIS 30-253 Specification for Field Instruments Rev B02

11.13 Level Switches ....................................................................................................................... 16


11.14 Gauge Glass (Reflex/Transparent) ........................................................................................ 17
11.15 Nucleonic Profilers ................................................................................................................. 17
11.16 Load Cells .............................................................................................................................. 17
17 Inspection, Test and Certification .......................................................................................... 17
17.1 Inspection and Test Plan ....................................................................................................... 17
17.3 Equipment Specific Inspection Requirements ....................................................................... 17

Document No. EG001-IC-SPE-11-0004 Page 3 of 18 Rev: B01


© BP p.l.c. EG001 Project Internal - Bechtel Confidential
Supplementary Specification to GIS 30-253 Specification for Field Instruments Rev B02

Revision History
Amendment Revision Amender
Amendment
Date Number Initials
18-DEC-2014 B01 NM Comments Incorporated
07-NOV-2014 A01 DM No Comments from IDC
31-OCT-2014 01 DM First Issue

All previous issues are hereby superseded and are to be destroyed.


NOTES:
Revisions after Rev. A01 are denoted as follows:
By a vertical line in the right-hand margin adjacent to the revised text.
OR
By a triangle symbol for graphics, the revision number being denoted within the symbol
positioned adjacent to the revision.

Related Documents and References

Document Number Document Name


GPO-EN-SPE-30253 Rev B02 GIS 30-253 Specification for Field Instruments

Holds
Hold Number Section Description

Document No. EG001-IC-SPE-11-0004 Page 4 of 18 Rev: B01


© BP p.l.c. EG001 Project Internal - Bechtel Confidential
Supplementary Specification to GIS 30-253 Specification for Field Instruments Rev B02

1. Introduction
This Technical Note is a supplement to BP GIS 30-253 Specification for Field Instruments
Rev B02 dated 03 September 2014.
The purpose of this document is to identify certain specific requirement for the modifications,
deletions and additions to the GIS 30-253 applicable to the West Nile Delta Onshore Gas
Development Project. Where a paragraph in the parent document is required to be amended,
modified or deleted, it will be identified in this document.
The clauses in Section 2 Supplementary Data outline the specific project requirements to be
added, modified or deleted. Paragraphs of GIS 30-253 that are not revised or mentioned in
this document remain applicable.
Following table describes the intent of the instructions used in this supplement:

Instruction Description
Add This supplement’s clause to be added to existing GIS’s
clause/section.
Modify This supplement’s clause to substitute existing GIS’s
clause/section.
Delete Existing clause/section to be deleted from GIS.

2. Supplementary Data
2 Normative References
Company Documents
Add
ASME BPVC Section VIII
Fourth Edition 01, 2010 Pressure Vessels
ASME B31.3, Edition
2008 Process Piping
ASME B16.5, Edition
2009 Pipe Flanges and Flanged Fittings
ASME PTC 19.3 2004 Temperature Measurement Instruments and Apparatus
ASME PTC 19.3 TW
2010 Thermowell Performance Test Codes

EN 837-2, 1997 Pressure Gauges


API RP 551 Process Measurement Instrumentation

Delete
GIS 30-252 Specification for Instrument Tubing and Fittings – Customary Units

Document No. EG001-IC-SPE-11-0004 Page 5 of 18 Rev: B01


© BP p.l.c. EG001 Project Internal - Bechtel Confidential
Supplementary Specification to GIS 30-253 Specification for Field Instruments Rev B02

5 Order of Precedence
Modify
5.a. The order of precedence of the codes and standards quoted in the specifications
shall be:
1. International and local statutory regulations
2. Project data sheets
3. This Specification
4. Project specifications
5. Referenced Company documents
6. Referenced national and international codes

6 General Technical Requirements


6.1 General
Modify
6.1.b Instruments shall be designed for use under the conditions specified in the Basis of
Engineering Design Data EG001-PE-BOD-11-0001.
Delete
6.1.e.2 NEMA 4X in conformance to NEMA 250
Add
6.1.m 6. Inlet/outlet connection size and rating (for in-line devices)
7. Material References (for in-line devices)
8. Instrument Range
9. Device ID (for Foundation™ Fieldbus devices)
Modify
6.1.n Instruments shall be identified with a permanently attached tag number, as specified
on data sheets which shall be on the nameplate or a separate SS tag, attached with SS wire.
Each field mounted instrument shall be identified by a traffolyte nameplate supplied by the
Instrument Installation Contractor, giving the tag number and service. This nameplate shall be
engraved with minimum of 13mm letters with white / black / white (black lettering on a white
background) for PAS duties and red / white / red (white lettering on a red background) for
F&G and SIS duties, and be fixed adjacent to a permanent structure or purpose made
brackets.
Add
6.1.o The degree of protection provided by an enclosure shall be classified in accordance
with IEC 60529.
Field mounted instruments and enclosures for outdoor installation shall have minimum
ingress protection of IP66.
Add
6.1.p In general all field instruments shall be 24V DC loop powered (2-wire) from the ICSS
or respective control system.
Where the instruments require additional power supply (4-wire), they shall be fed with 230V
AC UPS supply.
Inductive devices such as solenoids and relay coils shall have suitably rated suppression
diodes connected directly across the coil.

Document No. EG001-IC-SPE-11-0004 Page 6 of 18 Rev: B01


© BP p.l.c. EG001 Project Internal - Bechtel Confidential
Supplementary Specification to GIS 30-253 Specification for Field Instruments Rev B02

Solenoid coils shall:


• Be direct current operated.
• Have insulation rated for continuous operation at the maximum ambient temperature,
with Class A of IEC 60085 as an overall minimum requirement.
• Be capable of dissipating additional power resulting from a higher than normal supply
voltage during online boost charging of battery systems or have measures to restrict
voltage at solenoid coils.
Shutdown devices, systems, or actuators, as applicable, shall be individually fuse protected.

6.2 Hazardous Area Classification


Modify
In order to prevent electrical apparatus, including electronic process instrumentation, from
becoming a source of ignition in (potential) gas or dust atmospheres, protective measures
shall be taken, based on the hazardous area classification of the particular area in which the
electrical apparatus are being installed. For the electrical apparatus with protection type
certified for use in explosive atmospheres the appropriate safety documentation shall be
provided.
All field instruments shall be certified for use in Zone 1, Gas Group IIB, and Temperature
Class T3 hazardous area in compliance with the requirements of ATEX directive 94/9/EC. The
instrument shall bear the relevant hazardous area compliance mark and certificate number for
the purposes of traceability. This requirement includes instruments installed in non-hazardous
areas such that component variations are kept to a minimum wherever practical.
Wherever possible, all field instruments shall be certified explosion proof (Ex d).
Use of purge protection (Ex p) type equipment shall be avoided wherever possible.
All junction boxes shall be certified increased safety (Ex e).
Cable glands shall be certified to both Ex d and Ex e.
Intrinsically Safe installations shall be segregated from non-intrinsically safe signals in
marshalling cabinets and Unit Control Panels including the field junction boxes and the field
and home run cables.
System reference earthing for multi-core cables shall be implemented at the system cabinet
cable end. Continuity of earth screens shall be ensured in junction/distribution boxes by
means of screen terminals insulated from the metal work (earth).
All field instrumentation shall be certified for use in hazardous area irrespective of whether the
instrument is installed in a safe area or not. This is to avoid duplication of spares and the
possibility of using a noncertified instrument in a hazardous area. The hazardous area
requirements shall be specified on the instrument datasheet.
Delete
6.2.d FM, UL or CSA certification.

6.3 Materials
Modify
6.3.a.1 Suitable for the process and environmental conditions specified, as defined on the
data sheets. All wetted parts shall be minimum 316 stainless steel. Electrical enclosures may
use 316 stainless steel or epoxy coated aluminium. 304 stainless steel shall not be used for
any part.
Add
6.3.g Field panels, located outdoors, shall be made of 316 Stainless Steel. Instruments
which are panel or rack mounted inside buildings shall normally have material according to
the manufacturers standard.

Document No. EG001-IC-SPE-11-0004 Page 7 of 18 Rev: B01


© BP p.l.c. EG001 Project Internal - Bechtel Confidential
Supplementary Specification to GIS 30-253 Specification for Field Instruments Rev B02

Equipment or materials that contain or are coated with any of the following shall be
prominently tagged at openings to indicate nature of contents and precautions for shipping,
storage, and handling:
• Insulating oils
• Corrosion inhibitors
• Antifreeze solutions
• Desiccants
• Chemical substances
• Hydrocarbon substances
Before shipment, a current Material Safety Data Sheet (MSDS) shall be provided for each
substance shipped in or with equipment that may be locally regulated.
Copies shall be affixed in protective envelopes to the outside of the shipment. All chemical
safety data sheets shall fully comply with all local regulations and shall include a statement
that the substance is considered hazardous.
If any products are considered non-hazardous, a statement to that effect shall be included.

7 Transmitters
7.1 Conventional
Modify
7.1.b Field transmitters and positioners shall utilise Foundation Fieldbus (FF) for all signals
in and out of the Process Automation System (PAS), unless a suitable FF capable device
cannot be identified for the particular application. Full diagnostic information shall be available
for operator or technician review from the Human Machine Interface (HMI) and Engineering
Workstations in the Central Control Room (CCR) for all FF devices. FF instruments shall not
be used in Safety Instrumented System (SIS), Fire and Gas System (F&G) and Anti-Surge
Control applications.
Instruments connected to SIS, F&G and Anti-Surge Control shall be hard wired using 4-20mA
signal for analogue loops and 24V DC for digital signals. Transmitters interfaced with 4-20mA
signals shall be HART compatible and be configurable remotely from control room.
Instruments connected to SIS and FGS shall have a safety certificate from TUV, FMEDA or
other independent bodies. For SIS applications, the Proven in use instruments shall only be
used if an independent certified transmitter is unavailable for the specific application. The
Probability of Failure on Demand (PFD) data shall be available for Proven in use instruments
and the data shall be submitted by the instrument vendor for project approval. All HART
diagnostics shall be available from the Engineering Workstations.
Inputs to the SIS shall have separate and dedicated field sensors and final elements. The
physical principle of the process variable measurement may be shared with another loop;
however, the electronic processing must be segregated between the SIS and the PAS. An
example is a single orifice plate that may be used as the primary flow device with two
independent transmitters connected to two separate high and low pressure process taps. PAS
and SIS instruments shall have separate isolation from the process.
Transmitters are preferred to switches, however there may be instances where a switch may
be used; examples are: valve position limit switches and level (vibration) switches.
Current to pressure (I/P) converters, if required, should be from 4-20 mA, to a standard
pneumatic pressure signal, either from 0.2 barg to 1.0 barg, or from 0.4 barg to 2.0 barg.
P/I converters, if required, should be from 0.2 barg to 1.0 barg, or from 0.4 barg to 2.0 barg, to
standard DC electrical signals (for example, 4-20 mA).

Document No. EG001-IC-SPE-11-0004 Page 8 of 18 Rev: B01


© BP p.l.c. EG001 Project Internal - Bechtel Confidential
Supplementary Specification to GIS 30-253 Specification for Field Instruments Rev B02

7.2 Wireless Transmitters


Delete
7.2.a - 7.2.c
Add
Wireless Transmitters shall not be used on this project.
Add

7.3 Foundation Fieldbus


7.3.1 General Requirements
FF devices should meet the minimum following requirements:
• FF certification for passing the Interoperability Test Kit (ITK).
• Clear indication of which revision of ITK shall also be shown.
• Minimum acceptable ITK revision is 4.01.
• View block for all diagnostics and other relevant transmitter and sensor information.
• Support for multiple function blocks. Though desirable, support for multiple function
blocks is also dependent on being host-compatible.
• Backup Link Active Scheduler (LAS) capability.
• Incremental device description (DD) for extra functionality and/or software revisions in
device memory.
• Capable of performing continuous diagnostics, including self-test functions and
providing specific diagnostic information.
• Support for Trend and Alert Function Blocks.
• Preferably, devices should include the entire range of FBs that are user-selectable at
the time of installation (instantiable blocks).
• Field input devices should include the minimum capabilities as illustrated below:

Device type Minimum Suggested


Required

Pressure AI (1) 2nd AI, PID, LAS capability, input


selector, set point ramp generator,
signal characteriser, integrator,
arithmetic calculator, control selector,
splitter.
Temperature AI (2) PID, LAS capability, input selector, set
point ramp generator, arithmetic,
control selector, splitter.
Mass flow density/specific AI (4), PID, LAS capability, set point ramp
gravity, percent solids, arithmetic, generator, calculate, control selector,
and viscosity integrator/ splitter.
totalizer

Vortex flow AI (2) PID, LAS capability, integrator, input


selector, set point ramp generator,
control selector, splitter.

Document No. EG001-IC-SPE-11-0004 Page 9 of 18 Rev: B01


© BP p.l.c. EG001 Project Internal - Bechtel Confidential
Supplementary Specification to GIS 30-253 Specification for Field Instruments Rev B02

Device type Minimum Suggested


Required

Magnetic flow AI (2) PID, LAS capability, integrator,


arithmetic, set point ramp generator,
control selector, splitter.
Ultrasonic flow/level AI (2) PID, LAS capability, input selector,
integrator, set point ramp generator,
control selector, splitter.
Positioner AO (1), PID, DI DO (1).
(2), LAS
capability
PH, reference voltage, AI (3) PID, LAS capability, arithmetic,
and sample temperature. calculate, input selector, set point ramp
generator, control selector, splitter.

Conductivity and sample AI (2) PID, LAS capability, arithmetic,


temperature calculate, input selector, set point ramp
generator, control selector, splitter.

Chromatograph (Note:1) AI (5) (Note:2) AO (1), PID, LAS capability, control


selector, splitter, input selector, set
point ramp, arithmetic, integrator,
calculate.

Paramagnetic and % AI (3) PID, LAS capability, input selector, set


oxygen, sample flow rate, point ramp generator, arithmetic,
sample pressure calculate.

Zirconia and % oxygen, AI (3) PID, LAS capability, input selector, set
combustibles and furnace point ramp generator, arithmetic,
temperature calculate.

Multivariable transmitter AI (1/variable) PID, LAS capability, signal


(min) characteriser, integrator, arithmetic,
calculate, set point ramp generator.

Notes:
1. Due to high number of parameters from chromatograph, this device might be
better suited to HSE interface.
2. Primary and secondary component, oven temperature, sample flow, reference
cell voltage.

7.3.2 Field Device Diagnostics


The following types of diagnostics should be provided:
• Public diagnostics: output device diagnostics that are viewable from any process
control host. They help determine common problems with valve, actuator, and host.
• Advanced diagnostics: full output device diagnostics that determine output device
health without removing it from the line. Advanced diagnostics come in two forms –
dynamic scan and step scan.

Document No. EG001-IC-SPE-11-0004 Page 10 of 18 Rev: B01


© BP p.l.c. EG001 Project Internal - Bechtel Confidential
Supplementary Specification to GIS 30-253 Specification for Field Instruments Rev B02

o Dynamic scan (online or offline method): cycles output device and in one test
collects all parameters for drive signal, dynamic error band, output signal, and output
device signature.
o Step scan (online or offline method): test moves output device in unique
patterns, which help examine device’s action in specific areas of travel. This action
shall be password protected and require approval of a process operator before
implementation.
• Process diagnostics: test that is run as the process is running. This test moves output
device within a range until the process exceeds its configured maximum deviation. It
allows maintenance personnel to compare host action, actuator action, output device
action, and process action. Process diagnostics should provide key information on the
impact that an output device has on the process, including but not limited to:
o Position accuracy.
o Operating resolution.
o Total valve travel.
o Packing friction and hysteresis.
o Static and sliding friction.
o Dead band.

7.3.3 Field Device Specification


Applicable fieldbus data sheets shall be prepared the same as for conventional instruments
but with the additional information required for fieldbus devices.
For FF devices, the required information shall include but not limited to the following:
• Functions block requirements.
• Minimum power required.
• Device current draw (mA).
• Device in-rush current (mA).
• Device (lift off) minimum voltage.
• Block execution time.
• Polarity sensitivity.
• Link active scheduler (LAS) capability.
• Diagnostic requirements.
• Virtual communication relationships (VCRs).
• Device capacitance.
• Fieldbus locator
• Software revisions:
o DD revision.
o CFF revision.
o ITK revision with which device was tested.
Device manufacturer shall also provide information on non-standard or enhanced function
data, and unique vendor diagnostic/advance diagnostic capabilities.

Document No. EG001-IC-SPE-11-0004 Page 11 of 18 Rev: B01


© BP p.l.c. EG001 Project Internal - Bechtel Confidential
Supplementary Specification to GIS 30-253 Specification for Field Instruments Rev B02

7.3.4 Field Device Tagging


Each fieldbus device shall have a unique physical device tag and corresponding network
address.
FOUNDATION™ Fieldbus device tag shall match the Instrument Tag indicated on data
sheet/P&ID.
The device tag is assigned to the device when it is commissioned and (for most device
states); the device retains the tag in its memory when it is disconnected.

7.3.5 Field Device Configuration


Internal software of fieldbus instruments should be configured by the manufacturer, including
at least the following information:
• Serial number.
• Tag name.
Process use description, as specified on the instrument data sheet provided to the
manufacturer.

8 Temperature Instruments
8.1 General
Modify
8.1.c.2 For remote transmitter mountings or direct reading instruments, allowable wire
resistance should be according to the manufacturer.

8.2 Thermowells
Delete
8.2.d.3 Be bored to achieve inside diameter of 6,8 mm (0,27 in) for stepped type.
Modify
8.2.i Thermowell material shall be stainless steel, 316 minimum and for fabricated flanged
or weld-in thermowells 316 L SS shall be specified except where process conditions require
other alloys.
Modify
8.2.o Length of thermowell shall comply with Instrument Process Connection Thermowell
Details EG001-IC-STD-11-0002-001 and the guidance of API RP 551, Section 5.2.3 for
maximum immersion length should not be followed.
The minimum immersion length shall be 50mm for liquid service and 80mm for gas service.
For thermowells installed upstream of rotating equipment, e.g. compressors, the immersion
length shall be limited to 125mm irrespective of pipe size, to prevent endangering the
downstream equipment.
For thermowells installed in columns, reactors, furnaces or vessels the immersion length shall
be in accordance with process requirements.
Delete
8.2.p

Document No. EG001-IC-SPE-11-0004 Page 12 of 18 Rev: B01


© BP p.l.c. EG001 Project Internal - Bechtel Confidential
Supplementary Specification to GIS 30-253 Specification for Field Instruments Rev B02

8.4 Thermocouples
Add
8.4.e All thermocouples should be provided with burnout protection and the temperature of
the cold junction shall be known and compensated for.
Safety and operability shall be considered in selection of burnout protection action. The
burnout selection should be done with following rules:
• In services that are for operator monitoring only and do not affect plant operation (for
example, indications, recordings, or alarms), burnout protection should drive
measured variable readings to plant fault condition.
• For shutdown and control duties, each application should be individually assessed to
ensure sensor, transmitter, or wiring failure modes inherently drives the plant to safe
condition (i.e. low temperature trips and alarms shall be downscale burn-out and high
temperature trips shall be upscale burnout) or that burnout protection initiates action
to protect the plant (for example, switching a controller to “Manual”). For each system,
an alarm on the thermocouple burnout should be included to alert the operator when
important functions trip controls to “Manual”.
• In services that affect plant operation (for example, control loops and trip functions),
the plant should neither trip nor any control malfunction be caused by thermocouple
burnout.
Designs should include detection of sensor failures and measurement circuit wiring faults.
Sensor failures should be alarmed.

8.6 Temperature Switches


Delete
8.6.a - 8.6.d
Add
Temperature switches shall not be used.

8.7 Temperature Transmitters


Add
8.7.g Digital indicators shall have at least a 4 digit display preceded by a plus sign (+) for
above zero temperature values, or a minus sign (–) for below zero temperature values.
For temperature ranges greater than 40°C (100°F), digital indicators shall display
temperatures in thousands, hundreds, tens, and units of degrees.
Digital indicators shall display tenths of a degree for RTD sensors with an accuracy of ±0,1%
for temperature spans of less than 40°C (100°F), or for differential temperature ranges.

8.8 Filled Thermal Systems


Delete
8.8.a - 8.8.d
Add
Temperature switches shall not be used.

Document No. EG001-IC-SPE-11-0004 Page 13 of 18 Rev: B01


© BP p.l.c. EG001 Project Internal - Bechtel Confidential
Supplementary Specification to GIS 30-253 Specification for Field Instruments Rev B02

8.9 Temperature Gauges


Add
8.9.h Preferred ranges for local indicators are shown below:

Temperatur
e range:
–40°C to
80°C
0°C to
120°C
0°C to
200°C
0°C to
400°C

The number of ranges used should be kept to a minimum.

9 Pressure Instruments
9.1 General
Add
9.1.d Pressure instruments shall be capable of withstanding the maximum allowable
working pressure (MAWP) and an over range protection system shall be specified. The
method of over range protection shall be subject to approval by BP.

9.2 Pressure Switches


Add
9.2.a Pressure switches will be used with company approval.

9.3 Pressure and Differential Pressure Transmitters


Add
9.3.k FF differential pressure transmitters shall provide lines pressures as secondary
variables which will be displayed on the HMI graphics together with ∆p value. In this case,
separate pressure transmitters measuring the lines pressures need not be provided.

9.4 Pressure Gauges


9.4.1 General
Add
9.4.1.p If flush mounted, a NPT 1/2 back connection and hinged retaining ring.

9.5 Diaphragm Seals


Modify
9.5.b Remote diaphragm seals should be connected to the pressure instrument by
armoured stainless steel capillary tubing. Tubing should be 300 series stainless steel 3 mm
(1/8 in) OD, and protected by stainless steel spiral wound armour, 6 mm (1/4 in) OD.

Document No. EG001-IC-SPE-11-0004 Page 14 of 18 Rev: B01


© BP p.l.c. EG001 Project Internal - Bechtel Confidential
Supplementary Specification to GIS 30-253 Specification for Field Instruments Rev B02

10 Flow Instruments
10.1 General
Add
10.1.d Flow indication sight glasses shall only be considered for:
• Cooling water.
• Lubricating oil at atmospheric pressure (such as in bearing drain lines).
• Sight glasses in lines that run full of liquid shall have a flow indicator such as a flapper
or ball.
Add
10.1.e Further guidance relating to Flow instrument selection is found within BP Technical
Note for Flow Instruments EG001-IC-TEC-00-1001.

10.2 Differential Pressure Flow Measurement


10.2.2 Differential Pressure Transmitters
Modify
10.2.2.o Orifice plates shall be provided with a tab stamped, or deep engraved, on the
upstream face,
• The word “UPSTREAM”
• Tag number
• Nominal line size
• Rating
• Internal line diameter
• Measured orifice diameter
• Plate thickness
• Plate material
• Plate type

10.2.3 Orifice Flanges


Add
10.2.3,m Orifice bore shall not be less than 6.0 mm.

10.7 Ultrasonic Flow Meters


Modify
10.7.f Clamp-on type may be considered for in certain applications such as extremely
corrosive fluids where sensors are mounted on the pipe. Clamp-on type shall have separately
mounted electronics but shall be supplied with integral cable assemblies ready for installation
with plug and socket terminations.

10.9 Vortex Flow Meters


Add
10.9.f Selection of vortex flow meters should also consider the following:
• The Reynolds number shall be at least 20,000 and the minimum flow velocity shall be
as specified by the manufacturer, in order to achieve reliable measurement.

Document No. EG001-IC-SPE-11-0004 Page 15 of 18 Rev: B01


© BP p.l.c. EG001 Project Internal - Bechtel Confidential
Supplementary Specification to GIS 30-253 Specification for Field Instruments Rev B02

• Vortex flow meters should not be considered for very viscous, waxy or erosive
services.
• Vortex flow meters shall be flanged type. Use of wafer design requires the approval
from Company.
• In selecting a vortex flow meter the following criteria shall be considered in order of
importance:
o Measurement performance (turn-down, minimum measurable flow due to the low
flow cut-off value).
o Pressure drop across the meter.
o Need for pipe reducers.
Add

10.14 Flow Element Identification


The direction of flow shall be clearly indicated on all inline element bodies. Direction arrow
must be a permanent mark cast, forged, stamped, or otherwise permanently attached.
Painted markings are not permitted.

11 Level instruments
Add
For selection of Level Instrument selection is found within BP Technical Note for Level
Instruments EG001-IC-TEC-00-1000.

11.1 DP Level Transmitters


Modify
11.1 DP Level transmitters are used on approval of company. If approved for use, the DP
Level transmitters shall meet the following design requirements unless otherwise specified:

11.5 Displacer Instruments


Delete
11.5.1 - 11.5.2
Add
Displacer instruments shall not be used.

11.7 Tension Wire Float Transmitter


Delete
11.7.a - 11.7.c
Add
Tension wire float instruments shall not be used.

11.13 Level Switches


Delete
11.13.a to 11.13.l
Add
Level switches shall not be used.

Document No. EG001-IC-SPE-11-0004 Page 16 of 18 Rev: B01


© BP p.l.c. EG001 Project Internal - Bechtel Confidential
Supplementary Specification to GIS 30-253 Specification for Field Instruments Rev B02

11.14 Gauge Glass (Reflex/Transparent)


Add
11.14.k Gauge glasses should not be installed on vessels that:
• Use float and tape level gauges.
• Contain extremely viscous liquids.
• Contain solid materials.
Overlap of level gauges shall be 50 mm (2 in) to ensure readability of the level throughout the
required range.
Add

11.15 Nucleonic Profilers


Where there is a multiphase component to the level application, i.e. where sand, emulsions or
foams may be present, nucleonic profiler devices may be considered. Due to their high cost,
nucleonic profilers of this type should only be used where no other instrument options will be
suitable.
These devices are able to profile the content of the vessel and can therefore be used to
provide levels in the vessel excluding for example the foam layer.

Add

11.16 Load Cells


Load cells may be considered on duties where a level measurement of solids is required.

17 Inspection, Test and Certification


17.1 Inspection and Test Plan
Add
17.1.c Check certificate of conformity for all equipment.
• Check that the instruments comply with the specification(s) and data sheet(s)
attached to the material requisition.
• Check of labelling, legal stamping and nameplates.
• Calibration test at operating conditions
• All inline instruments together with all related accessories, when part of supply, shall
be subjected to the following further checks/tests as a minimum:
• Materials Certificates
• Dimensional check as per SUPPLIER issued drawings
• Hydrostatic test in accordance with ASME B31.3
All FF instrument types shall be tested by MAC (Field instrument supplier) for operability with
PAS. If a given FF instrument type has previously been tested it should be confirmed by MAC
(Field instrument supplier) basing on the FF instrument details provided by the SUPPLIER,
and then no additional testing is required.

17.3 Equipment Specific Inspection Requirements


Add
17,3,i SUPPLIER shall provide technicians and materials as required to make
measurements and connections that the Inspector deems necessary to ensure that all
functions and accuracies are according to specifications.

Document No. EG001-IC-SPE-11-0004 Page 17 of 18 Rev: B01


© BP p.l.c. EG001 Project Internal - Bechtel Confidential
Supplementary Specification to GIS 30-253 Specification for Field Instruments Rev B02

Test instruments and equipment, test leads, temporary wiring, tools, etc. shall be made
available by SUPPLIER, as required to permit 100% inspection and testing. All the above
items are to remain the property of SUPPLIER.
SUPPLIER scope shall include all legal requirements for certification of equipment including
hazardous area and material certificates.

Document No. EG001-IC-SPE-11-0004 Page 18 of 18 Rev: B01


© BP p.l.c. EG001 Project Internal - Bechtel Confidential

Das könnte Ihnen auch gefallen