UNDER FREQUENCY setting

1. Instant load shedding in all SEBs (TNEB,KSEB,APSEB,KEB)


2. Inter state feeder trip (TNEB&KSEB seperated from APSEB & KEB)
3. Neyveli Local islanding. InTS 2 selected units will come under HL ,remains will feed to bus.
4. Not selected for HL will come under HL through Class C
5. Unit already in HL unit will trip on Class B UnderFreqency protnection.
Low Forward Power Protection (0.5% of 210MW
Reverse Power Protection. (32 G1&G2)
2/32 G1&G2
2/32 Gx
Reverse Power Back up Protection. (2/86TA)
Generator Over Voltage Protection (59 G) 1.1 times of 15 Kv
Generator Over Flux Protection (59 G) 1.5 times of rated
6.6 KV & 0.4 KV U/V TRIP setting
SES LIMITERS
Rotor Current Limiter (Cut In ) At rated Current.
Rotor Current Limiter (Trip) At rated Current.
Stator Current Limiter (cut in )
Setting Time…..(Sec)

48.2 Hz Instant.
47.8 Hz 0.5-1 sec
47.4 Hz 2.8 sec
47.0 Hz 3 sec
47.0 Hz 5 sec
1.05 MW 5 sec
1.05MW
,, 2 sec
,, 5 sec
30sec
16.5 Kv

73% of V

1.1 times
1.5 times
1.1 times