Beruflich Dokumente
Kultur Dokumente
REGULATIONS
NTE 007/08/00
developer: SC Electrica SA
IN 107/95
Delhi - 2008
Page 1 of 73
NTE 007/08/00
ELECTRICAL
CONTENTS
I. SCOPE 6
55
66
Annexes
U a / U to 18/30 kV 69
Annex 5. Allowable minimum bending radius cable routing and handling 110
Annex 8. Fixed water spray installation for extinguishing the fire by cooling the household wiring
117
Appendix 9. calculationwiring
premises
wiring v entilării
calculation
premises
v entilării
wiring calculation
premises v entilării 119
Annex 10. List of branch of electricity and heat That important cable households
157
Page 2 of 73
NTE 007/08/00
Annex 11. The symbols Used for the description of materials. The symbols Used for electric cables
158
Annex 13. Main Technical Data Necessary to the call for tenders for electric cables
168
Annex 14. Influence on electricity cables control cable, control and telecommunication cables
169
Annex 16. List of National Standards, International and related prescriptions 199
Bibliography 202
Page 3 of 73
NTE 007/08/00
a) Conditions and the Principles of sizing and construction of underground electricity lines;
b) how to install power lines underground and delimitation of protection and safety
II. SCOPE Art. 2. This Legislation Applies to the design and execution of cable power lines with Voltages up to 400 kV Belonging to Operators in the
electricity sector.
a) households in nuclear power cables, except for the traditional (common part to discharge the power station, etc.);
c) Construction households and cable enclosures classified in categories A and B fire hazard (if only contrary to the specific design and Regulations
Obvious accidents or fire hazards persons (see Art. 82); any adjustment to the new PROVISIONS Will make the unit operational initiatives, based on a
technical-economic study.
Art. 5 ( 1) The application of this Legislation is in compliance with all the rules of the electricity and / or related Legislation Sectors, underground lines and Their
Article 6. The normative use GMT ways of mandatory indication of the extents contained PROVISIONS:
Page 4 of 73
NTE 007/08/00
Cause;
- "Is recommended ' Indicates the preferred solution, Which must BE Considered in solving
- "To admit" That Indicates a satisfactory solution CAN BE Applied in particular cases, the
Article 7. For the Purposes of this regulation, terms and expressions defined in the table is Used Below.
Term definition
State of the natural environment or contaminated with Substances Which, operating under
The aggressiveness of the environment Conditions, the effect of corrosion of the metal components constituting the LEC
Coating Consisting of metal wires or metal strips usually designed to protect the cable from
Devices rollers to protect wires and insulators against direct contact with surface of can occure
due to arcing That surge to reduce electromagnetic disturbances and uniform electric field
Written response That Gives the network operator the request of year applicator and positions to
Placement allow the ITS Specifying The proposed site of the objective sought
Strips or wires, usually metal, Applied over the mantle to enable it to withstand
mechanical stress due in particular mechanical withstand internal pressure stress due to
Armor internal pressure particularly
The construction element provided with internal channels for routing cables in theme (for
example, a concrete block "telephone channel" with four cylindrical channels, groups of tubes
Block cable
made of metal, concrete, cement, plastic, etc.)
Page 5 of 73
NTE 007/08/00
Term definition
construction
Cable with more conductors without individual display (eg cable screen collectively)
Non-radial field cable
Cable having the shield around the conductor disposed concentrically with the axis of the
Cable screen Collective
cable
Three lead cable sheathing Cable-phase to each conductor is coated over the insulation and the sheath of lead or
lead alloy
High-voltage cable (110 ÷ 400 kV), medium voltage (6 ÷ 35kV) or low voltage (1 kV Below)
Used for the primary circuits of the plants for the production, transport, distribution and use of
Power cable
electricity, AC or DC
Used in the control cable installation, measure, signaling, blocking, control, protection and
automation service with the voltage of less than 400V. This category includes cables for
ussage
Secondary circuit cable
Legislation for the Purposes of this, this category includes cables for connection to receivers
served THESE facilities or in connection with, if the maximum intensity absorbed current not
Page 6 of 73
NTE 007/08/00
Term definition
Cable for the specimen Taken from it and subject to a fixed time to initiate action Continues
flame to burn ITS own flame propagating to the destruction of the specimen. This cable does not
meet the Requirements of SR EN 60332-1-1: 2005 For cables with thin, Whose section is under
Cable-free flame retardant
Cable, subjected to the action of a flame for a predetermined time to initiate, continue to burn,
nature the flame of ITS own transmission to a fixed length, THEN WAS quenched. The cable must
behavior is Flame retardant cable meet the Conditions for SR EN 60332-1-1: 2005 For Which cables with thin section under
amplitude is sufficient to destroy the organic material in the area of the cable where are the
Fire resistant cable flame is Applied. This cable must Comply with the Requirements of IEC 60 331
Open cable construction removable tile to be mounted (wiring luxuries, usually with the free
space inside STI, provided with the installation and operating space
Cable channel
Category of fire resistance of cable bundles There has three categories of behavior to fire According to the amount of combustible material
- category B It Means of the volume of fuel material of 3.5 liters per meter;
- Category C It Means of the volume of fuel material of 1.5 liters per meter.
Safeguards Installing the cable bundle is set According to the wires of the bundle of cables
Page 7 of 73
NTE 007/08/00
Term definition
50266.
accordance SR EN 50266.
Fire hazard category of a production and storage Meaning That characterize the risk of fire of a room, building or production department and / or
building storage, depending on the Physico-Chemical properties of the material Processed or Stored;
defines five categories of wires, A and B (high fire risk) to E (low fire risk)
Those cases in Which, for technical and economic Reasons, May Apply to the code does not
Exceptional or forced allow a satisfactory solution and With its justification in the project
Construction fitted in cable networks laid in the ground, to be Located sleeves and sleeves
Open design (capped Properly) placed at intervals on the ducts. In order to ease That cables
Home shooting
Is the Link Between the equipment enclosure and the subscriber count
electric column
Device Used to allow expansion of the oil or impregnating material to the ends of the cable
Compressor
conductor cable As part of the cable Whose function is to drive the current
Stranded conductor Consisting of thin wires and assembled it Enough That it CAN BE Used
flexible wire
in the flexible cable
shaped conductor Conductor cross-section of Which is different from a circle
Which cross section of conductor is close to the shape of a sector of a circle
Sector-shaped conductor
That in the interstices of the stranded conductor wires have been Reduced by mechanical
compacted conductor compression, or by drawing a Suitable choice of the shape and disposition of the threads 5)
Wire or cable with a conductor posed parallel to the cable or a cable harness, Which Itself is part
of a closed flow circuit in Which CAN currents induced magnetic field Whose That is opposed to
admissible
maximum
current maximum
current
admissible
duration
admissible
of maximum
duration
current
of The maximum load CAN That support cable without Page 8 of 73
NTE 007/08/00
Term definition
Exceed the maximum permissible working temperature, under sustained at a certain ambient
cable
temperature
distance protection Minimum distance delimiting the protection of energy capacity, from ITS Measured in horizontal
Safe distance The distance the safety delimitază That energy capacity, Measured in the horizontal or vertical
projection Between ITS and the outer limit Nearest point of a facility or building; the safety
It is made up of the conductive layer having the function of the electric field inside the insulation
required configuration. May He, Also Achieving a smooth boundary and help removed insulation
Young metallic shell disposed in the cable and connected to earth, in order to maintain the electric field
Protective screen (the cable) inside it, and / or to protect the cable from external electrical Influences 6)
electrical Influences 6)
Open design laid out overhead cables. if the scaffold is Used for pipe support technology or
Branch Which is the component in the Connection Between the electrical connection and where
are the plants and the columns has mounted electrical overload protection of electric columns
Recess (recess) of the supply line
Cableways:
GMT groupCable
7) possess
groupGMT
7) possess
ways: GMT
Cableways:
group 7) possess
Term definition
- Flows along the same route Between Which separations: walls, etc. Conduit Fire
- streams arranged on both sides of the circulation spaces with a width streams arranged on
both sides of the circulation spaces with a width of 1m, the construction of cables or
technological rooms;
- Flows placed in wells on trestles or cable wires, the distance Between the feeds
It is made up of all cable networks, Including mountings and related installations of lighting,
Household wiring
Networks 8)
Wiring Realities Between the mains connection point and the point of separation Between
The assembly of insulating materials That is part of a cable specific Whose function is to
Cable insulation
withstand voltage
Insulation of a conductor Insulation of the conductor or conductor Applied to screen
Insulation consists of layers of paper impregnated with insulating material year (nomadic,
Impregnated paper insulation nemigratoare, with or without pressure or gas oil, etc.).
maintenance and
Closed room cable surveillance (basements, bridges, tunnels, shafts and cables); do not fall in this category is
Term definition
span cable Opportunities for access to the outgoing cable wires and mechanically protected and sealed
Sleeve fitted with a pressure-resistant fluid Which allows separation of the two wires or
The material (s) use (s) for filling the intervals Between the conductors in the multiconductor
Material (s) of filler
cable
Bundle of cables is a distance of at Least
Separate bundle of cables
0.15M to bundles (groups) of neighboring cable.
Cable enclosed room (ie, bridge, footer, etc.) Normally Located under a control room or under
Closed wiring level
an indoor-type
control room orconnection
under an indoor-type
station 10, 11)connection station 10, 11)
Space circulating in buildings Located on the ground free on at Least two sides laid out
Open wiring level
overhead cables
Which Plate or shell serves to protect the thermal, mechanical or electrical cables against the
spring. When plates is not installed in the ground, non-combustible They must BE
Or front protective
protective front plate
plate or
Open construction, covered by removable plates, Intended to protect the cables Located
Above the floor, Such as to allow passage over the construction and
11 of 73
NTE 007/08/00
Term definition
Grommet cable laid in the same plane (horizontal, vertical or oblique); the cable rack is made up
cables, Made of
combustible
Tank Intended to take the variations in the volume of oil impregnating fluid oil cables
pressure tank
Set of cables for transmission, distribution and industrial Consumers of electricity, and similar
Power grid industrial That Connects Consumers to receivers inside the substation or the
Electrical distribution networks of industrial
transformer's own Consumers
Consumers
two components of the cable, for example, Between the conductor and the insulation
Separator
and Between the insulation and the jacket
Construction That serves to protect against the spread of fire, film, gas and water, Providing the
sealing passage of cables and electrical conductors in the construction elements or wiring
Fire-resistant transverse separation
channel segmentation
Maximum temperature of The maximum value of the temperature of the combined conductor
Characteristics The maximum temperature of the The HIGHEST temperature of the conductor, Which May allow the end of a short, having a
Maximum Operating Voltage The effective value of the maximum voltage phases Between May Page 12 of 73
NTE 007/08/00
Term definition
occure in normal operation at any point of the line, at a time When Some
Which voltage cable has been designed and covered by the operating Characteristics and test
cables. Nominal voltage values is Expressed by U a / U in Which: by U a / U in Which: by U a / U in
Which: by U a / U in Which: by U a / U in which:
- U of It is the nominal voltage (effective value) Between the conductor and the
U = 2 • U a, single-phase AC or DC 14)
Device installed at the end of the cable to Provide electrical connection with other parts of
terminal cable the network and maintain insulation to the point of connection
Terminal end of the cable ensures tightness with respect to the environment and
Protection areas related energy capacity The adjacent energy capacity, or share Thereof, extended in space, Where There has
restrictions on access and system construction; This area is set up to protect energy and
Area safety related energy capacity The adjacent energy capacity, or share Thereof, extended in space, Where There has
avoid endangering people and the environment neighboring property; safe area includes the
protection Page 13 of 73
NTE 007/08/00
Term definition
Common safety area The area WHERE CAN coexist Several Objectives Which They encroaches on each other
JT low voltage
MT medium tension
PT transformation post
SEN National Power System
SR Romanian standard
1) The term core cable is Used in particular to describe the cable is one of
5) French term "en âme Paves" Means of compacted conductor of a particular type of
6)
Metal coatings, fittings and earthed concentric conductors May serve as a shield
- manifold body;
- In urban galleries CAN BE installed virtually all types of network Used in the local underground water, sewage, gas, heat, electricity and
telecommunications networks; in the same network CAN picture gallery of the same type with different functions (arteries or service pipes
Page 14 of 73
NTE 007/08/00
water). There have many examples of Which is pictured Above galleries in any of the types of networks. Technical problems Which arise
as to:
- Municipal Gallery equipment available in terms of loss detection, ensuring temperature, ventilation and thermal insulation Possibility of sections;
- in terms of Importance and measure of fire protection cable households CAN BE: normal; Those That is important in emergency year, canon Significant
result in material damage or casualties; Will the design documentation states the most important cable Which households or premises to adopt
additional fire protection According to the PROVISIONS of Art. 77 ÷ 82 (Annex 9 rooms or objects important That cable households).
10) Spaces WHERE Flows cables is not separated on all sides by elements
construction of technological installations, electric Including, the expression "technological rooms or basements" and not fall into the category of
11) R Etel inside - made in specially arranged for building cables (bridges, tunnels, sewers, basements, wells or
galleries cables) or technological spaces (warehouses, machine rooms, boiler rooms, etc.);
12) R outer Etel - Taken outside the building, namely, on the trestles, on the walls of buildings, earth, fine grooves or
13) Througho the norm, technological rooms Sometimes Were included as "space
Page 15 of 73
NTE 007/08/00
Approval of GO 22/1999 on port and waterway and shipping activities in ports and inland Waterways
Law 528/2002
ANRE Decision Technical rules on delimiting the protection and safety of energy facilities.
61/1999
OMAPM no. Approval of the procedure of Environmental Impact Assessment and issuance of Environmental
860/2002
MAMTF Order no. Approval of methodological guidelines applicable procedural steps Framework for Assessing Environmental Impact
863/2002
Establishing servitudes civil aviation and civil aviation easements Areas (RACR-SACZ)
OMT 119/2003
275/2002
MEC Order no. Approving the technical norms for the design, execution and operation of the natural gas supply I 6
58/2004 supply I 6
MTCT Order no. 176/2005 Approving the Norms for the design, execution and operation checking electrical installations in hazardous
Areas NP 099-04
ANRE Order no. Regulation for establishing solutions for connecting users to public electricity networks
45/2006
ANRE Decision no.
Technical Code of Electricity Distribution Networks
101/2000
Page 16 of 73
NTE 007/08/00
complete with Order 35/2004 Technical Code of the Electricity Transmission Network
ANRE Order no. 4/2007 Technical norm on delimiting the protection and safety related energy capacity, with Amendments
NTE 001/03/00 Standard on the choice of insulation and protection of electric energy installations against surges
NTE 002/03/00 Standard test and measurement systems for protection, control and automation of the Command-electric power
stations and plants
NTE 003/04/00 Standard for construction of overhead power lines with Voltages over 1000V
NTE 005/06 / 00 Standard on calculation methods and elements of safe operation of power installations
NTE 006/06/00 Standard on the compilation of short circuit currents in power networks with voltage Below 1kV
cable networks and expansions predictable to avoid Possible Areas of fire or Areas WHERE integrity tow endangered by mechanical damage by corrosive
It Will Also Provide access to cable installation work, maintenance and intervention in case of fire.
taking into account the development prospects of consumption for the next 3-10 years.
Art.10. Customers Connect solutions is Determined in accordance with the Regulation on establishing solutions for connecting users to public
electricity networks, Approved by Order 45/2006 of ANRE, the Norms for the design and execution of connections and distribution installations with Voltages up
to 1000 V as power units - PE 102 and Norms for design of electrical installations AC own service of power stations and heating - PE 113.
transformer stations and Switchboards as close to consumption centers, based on optimization calculations.
Page 17 of 73
NTE 007/08/00
Art.12. Permanent facilities for connecting future Consumers Will Be Used as much by the manufacturer, since the opening sites. Electrical installations
for organizing sites CAN BE fed from the final cable networks, as provided by Normative for the design and execution of electrical installations with Voltages up to
Art.13. Determination cable section of all categories is based on precise knowledge as power absorbed by Consumers and Coefficients of
V.2. Installations for industrial and similar connecting Consumers Art.14. Connecting to industrial plants and the like
It admits Achieving THESE facilities connecting the LEC, with technical and economic justification in the circumstances:
a) network connections for the transport of power exceeding the carrying capacity of the airline or Whose Implementation Leads to
b) Located in a congested area network, the route Would obstruction of the flow of air, the normal activities or pose danger to personnel;
c) networks Located in Areas of influence of transport systems (electrified railways, Airports) or telecommunications (radio antennas stations, television,
etc.);
e) Located in the network with corrosive or hazardous materials deposition Using overhead lines;
g) network for the connection of the fire extinguishing Several receptors of Fires in the cases provided for by the Regulations in force.
In the Above cases, the distribution network Will Be Carried out, usually by all or part of the cable laying Directly in the ground According to
Art.15. Premises goals, Including the locations of power plants, distribution networks based on Principles is Shown to Art. 14.
In cases arising as Necessary to Achieve the cable distribution networks, the cables is installed, usually Directly into the ground (see Art. 15) or air,
using as support brackets building or construction elements BE checked and related technological installations
Page 18 of 73
NTE 007/08/00
When comparing the solutions in order to establishe the optimum, taking into account the Possibilities for the solution (the type of soil, land available,
the Necessary support arrangement), and with the length of the sections Necessary and depending on the mode of laying. In the case where are the installation of
cables in the building elements to Another destination is not possible, or leads to lengthening the tracks, CAN BE made to the solutions trestles special cable (light
construction and preferably prefabricated) levels open laying cables or other solutions air (suspension ropes, etc.).
Art.16. In justified cases the technical and economical construction is allowed cable channels and Solution Will Be Reached in compliance with Art. 57
and 67.
Art.17. In short portions, When There is danger of mechanical damage (for example, the paths of movement tailboard, etc.), tubes or cables or sources current
circuit in accordance with the installation solutions Referred to in Art. 61, 62.
Art.18. Premises outdoor electric cables laid MUST BE Directly in the ground; CAN take into account GMT solutions:
a) laying the prefabricated cable channels with racks (in the case of large Flows of wires cables);
b) laying the cable racks channels (in the case of large flows from the power cable and of the secondary circuit);
c) routing the combined, in the ground - the power cables in cable channels rastelepentru prefabricated with the secondary circuit, etc.
V.4. 19 The public distribution network. The solutions for Achieving public distribution networks in cities (the air - with the insulated
conductors, or insulated wires, or underground - the cable) is Determined According to the urban solution of the locality, the density of the consumer, the solutions Adopted for
In cases where are the results Necessary to Apply the solution to Achieve the electrical distribution network in underground cables, They pose
Directly into the ground (According to the solutions Referred to in Art. 59 Art. 60) in the tube and blocks the cable (in the case and as provided in Art. 62) or in
urban galleries common to other utilities When the area is Adopted politica solutions (According to common norms on urban galleries).
Page 19 of 73
NTE 007/08/00
Art.20. Cable networks in spaces (rooms) technology is made, usually air, Used
to support
to support
the construction
the construction
Used elements of the halls, platforms and
Shouldn BE avoided as far as Possible, flows from the large number of cables to, showing THESE groups of cables in parallel streams, separated by a
In particular cases, the specific equipment or production line cable routing Requires large flow channels or tunnels, or in the case of expansions in
existing installations Mandates Which the use of cable channels or galleries, the solution Will Be justified for money.
V.4.2. Cable networks in Art.21 electricity production facilities. To Achieve the related cable networks-mounted
electrical power production (eg internal electrical stations, control rooms etc.) observe at Least GMT solutions:
Avoid carrying special designs for electric cables Above premises related electrical installations.
The electrical installations and control chamber with a large volume of plants, respectively, cable connections, Where your Analysis That Can not
Be avoided basements or cable ladder, They Will Be limited in volumes built strictly Necessary to ENSURE the Conditions provided for in this Legislation ( see
Art. 57).
V.5. Regulations on electrical supply lines carrying Art.22. The PROVISIONS of this Legislation Applies to the design of
Low voltage underground power supply lines for supplying electricity to Customers requiring small power range (up to 50 kW) for plant use.
Main parts of the underground electrical connections have proper supply line (cable); recess (recess) of the branch; Electrical column.
Branching CAN BE underground Directly connected to the mains supply, using the sleeve junction, a niche (for buildings with blocks of flats or
apartments Several) or a network for the supply of air to air connections Consumers from CAN BE not made.
Using underground supply lines is required especially in Urban Areas built and systemized, where are air and branching That network airlines has
not Shown.
The main technical Conditions to be Considered in the design of underground power supply lines is:
Page 20 of 73
NTE 007/08/00
a) the cable routing is selected, usually so as to Achieve the Shortest connection in accordance with the existing cable network; Also it AIMS Not
enough access to cables for Possible Further repair works and replacement of cables;
b) the radii of curvature of the cables must not Be Expressed by the minimum outer diameter of the cable;
c) When laying cables for connections with other cables must BE Observed distances prescribed by Regulations;
d) the laying of underground electrical cables in parallel with the conduits must BE sure That minimum horizontal;
e) at the entrance to the laying depth Reduced CAN BE, the short portion (Below 5 m).
f) Undercrossing entry roads and buildings, cables must BE protected in PVC tubes; The tubes must have year inner diameter equal to 1.5 x the outer
g) When laying cables of near buildings, trees, tram tracks, Will Indicated respect the minimum distances in the regulations.
h) Streets in towns Undercrossing Will Be made by fitting the branch cable into a protective tube made of PVC, the length of the bead Which Exceed the
limit of 1 m;
i) the intersection of branch wire cable networks have to preserve the protective Will Vertically distances. Typically, cable branch supratraversa I Will
j) the intersection of the branch cables underground pipe network is Achieved by satisfying GMT vertical spacings:
- h = 500 mm from the fluid conduits and pipes of heating fuel. A distance protection May be Reduced to 25 mm with the
Following Conditions:
- protection of the cable and by the intersection of a 500mm side Thereof, Where the combustible fluid pipes;
- Strengthening the thermal insulation pipes for heating the mill by the intersection of the 1M side Thereof.
At the intersection of the pipeline laid at depths Greater than 1 m, the branch pipes supratraversa Will cable.
k) in the branch cable routing overhead on the network pillars, Will Provide for the cables in the protective tube portion 2 m Above the ground for
protection against mechanical damage; The CAN BE protective tube made of PVC or metal.
Page 21 of 73
NTE 007/08/00
VI.1 Conditions Art.23. Choosing and checking electrical cables has made based on technical-analysis, taking into
Below account information. Annex 12 contains guidelines for Choosing the high voltage cables, elaborated upon SR IEC 60 183 + A1: 1999.
Art.24. In order to supply receivers has Taken into account GMT date:
phase);
d) full service voltage , U m The network (the maximum effective voltage Between phases
Which May occure under normal operating Conditions at any point of the line, at a time When Some)
U m represents the effective value of the high voltage (between phases in the three-phase alternating current) Conditions
Which Which Occurs in normal
operating, at any time and at any point in the network; it excludes transient voltage variations (Such as Those caused by maneuvering the network)
and temporary voltage variations due to abnormal operating Conditions of the network (Such as Those caused by failure or sudden connection of
important tasks);
f) surge;
g) the strength and load Conditions Transported (steady-state, cyclic regimen, load);
l) the consumer.
a) laying mode (outdoor - Exposed to direct solar radiation or, in the ground, Ditches, channels, tubes, etc.);
b) the Thermal Characteristics of the environment (the ambient temperature, ground temperature at the depth of laying specific thermal resistance of the soil, etc.);
c) Move cables or other heat sources (number of wires, the power Transported, the location in space relative to Those sources, etc.);
d) the aggressiveness of the environment (type of soil, laying in water, contact with chemicals, electrolytic corrosion);
f) Other Conditions (Significant unevenness or with vertical lines, the paths of movement tailboard, mechanical stresses).
Page 22 of 73
NTE 007/08/00
a) type cable (reinforced or unreinforced, shielded or unshielded, the radial field or not, etc.)
b) number of conductors
e) reaction to fire
f) the terminal type (outdoor, indoor, nature of the filling material, the risk of atmospheric pollution, etc.)
h) connecting sleeves, junction or stopping (the installation like mechanical protection, chemical, etc.)
i) the ground Conditions (Reinforcements Not enough continuity of the grounding, the grounding mode screens, etc.).
VI.2.1. Article 27 insulation level. The level of insulation of the cable is characterized by the cables of the nominal voltage
values
U),
dielectric
and(U
dielectric
values.
of and U),
values.
and dielectric
values (U
values.
of and values
U), and(U of and
(1) The rated Voltages of the wires has Chosen According to the HIGHEST rated voltage and the voltage of the network, According to Table 1.
If power cables, Shown in the table is for networks That, in case of failure on the ground They are disconnected automatically. It accepts manual
disconnection justified and operation phase to earth a short time strictly Necessary to identify the defective circuit, is known to operate with a grounding reduces
Page 23 of 73
NTE 007/08/00
Table 1.
Rated voltage
Ratedcables.
voltage cables. Table 1.
The mains voltage (phase to phase) Voltage (kV) The rated voltage of the cable,
U o / U (kV) cable, U o / U (kV)
cable, U o / U (kV)
the HIGHEST (kV)
≤1 ≤ 1.2 ≤ 0.6 / 1
6 7.2 3.6 / 6
10 12 6/10
20 24 12/20
30 36 18/30
Which is not subject to the influence of power installations, CAN BE Used cables with rated Voltages lower than Those in Table 1 (column 1) Conditions under
(2) characterizes the surge dielectric cable insulation and has given values in the internal Standards and Regulations product, depending on the
For power cables with nominal Voltages Greater than 1 kV, the insulation withstand level check is made as SR EN 60071 ( standard parts) and
Norms
EN 60071
for the
( standard
electionparts)
of insulation
and Norms
and for
protection
the election
against
of insulation
overvoltage
andelectro
protection against overvoltage electro installations - NTE 001/03/00 .
The dielectric under the influence of the secondary circuit cablurilorde energy installations, check overvoltages induced by coupling of These plants
VI.2.2. Choosing the conductors Art.28. ( 1) power cables is provided with conductive aluminum or copper; specifically
a) Importance circuits supplying receivers (eg installation prevention and firefighting, consumer safety, Such as vital circuits from power stations
or receivers AC DC depending on technological protection, absorbing currents lasting more than 10A etc.) When the cable section (aluminum)
Would
10A currents
have less
lasting
thanmore
10mmthan
2; etc.) When the cable section (aluminum) Would have less than 10 mm 2;
b) circuits supplying receivers in hazardous environments, specific design Requirements Specified in WHERE THESE environments;
Page 24 of 73
NTE 007/08/00
c) Areas outside the rooms or the corrosive medium, Where aluminum is the chemical stability of APPROPRIATE, and only if Can not Be
d) protection of plants or to the neutral Earthing, in the specific cases Standards Referred to in the biggest fan installations.
(2) Cables secondary circuits is provided, with a copper conductor Typically, with GMT
a) the supply circuits of circuit panels operative scundare When the cable section (aluminum) Greater than or equal 10 mm 2;
Greater than 10 mm 2;
b) circuits to power receivers (eg valves, valves, dampers, etc.) provided not only with the local part of the control and automation system or
NOTES. Detachable connection of the cable contacts the aluminum conductors to electrical equipment (machines, devices, end block) is
Achieved by pressing by Means of a resiliently that provides; while keeping the contact pressure (spring washers, spring clips string, etc.).
(3) The cables Used for teleprotection secondary circuit, remote control is provided with
VI.2.3. Choosing and checking conductor cross-section Art.29. Conductors of the cable section is Determined That the
Largest section (economic or technical) resulting from the calculation of sizing and verification of GMT criteria: maximum current duration, the heat from the
1. Technical Election section ( s t) According to the current maximum duration is made in accordance with the manufacturer's cables, depending on
the material of the conductor and insulation, load Conditions, the laying mode, cooling Conditions, etc.
For cables with a rated voltage U a / U up to 18 / 30kV in cases where are prescriptions cable provider is not available, For cables with a rated voltage U a / U
up to 18 / 30kV in cases where are prescriptions cable provider is not available, For cables with a rated voltage U a / U up to 18 / 30kV in cases where are
prescriptions cable provider is not available, For cables with a rated voltage U a / U up to 18 / 30kV in cases where are prescriptions cable provider is not
available, For cables with a rated voltage U a / U up to 18 / 30kV has prescriptions in cases where are not available cable provider, you-can use the
guidelines in Annex 1. Annex 1 It is noted That WAS developed based on the German standard DIN 57 298 Teil 2 / VDE 0298 Teil 2 / 11.79.
2. Technical Section ( s t) conductor cables check the thermal stress due to short circuit currents, According to Instructions 103.
3. Technical Section ( s t) cable conductors to check the voltage at the connection point to the last receiver. The calculation formulas for Determining
Page 25 of 73
NTE 007/08/00
The voltage drop relative to the nominal voltage of use must not Exceed the maximum permitted levels of receivers separation points; 95% the voltage
value of the week must not deviate more than ± 10% of the rated voltage for the consumer.
When designing circuits for electric power plants Higher Than Those allowed given voltage drops Above When starting the engine, but not than the
maximum permitted Higher levels of biggest fan engines, Specified by the manufacturer. If you do not have accurate time calculations CAN BE Considered in a
NOTES. Sags admitted to the motor terminals and low voltage power plants physician has Indicated in Regulations PE 113 and
137. Will
receiver
receiver
circuits
circuits
for secondary
for secondary
verification
verification
Will normally
occure inoccure
normalinoperation
degradedinoperation
degradedmode
mode(for
(forhandsets
handsetspowered
poweredby
bybatteries) and engine starting system;
the voltage drop Will Be Greater than that permitted by the respective receivers.
4. Economic Section ( s ec) Which is the cable section is undergoing economic year optimum mode Corresponding to minimum total cost (Consisting of
operating expenses and capital expenditure-energy Mainly due LOSSES) for the relevant line in the time period of operation.
Determining the economic section of the conductors is made According to the Instructions of the Methodology for Determining the economic
VI.2.3. The choice of insulation Art.30. The choice of insulation cables involves studying and comparing a large number
Such as parameters of time and dielectric performance Regimes thermal behavior over time, fire behavior, Possibilities for bumpy routes mount technology,
Given the experience gained so far, the most common cases, GMT Recommendations has the choice of insulation:
- Insulation polyethylene (PE), preferably cross-linked polyethylene (XLPE), Where the tension cables in the range of (10 to 30 kV).
Choosing other types of insulation for low-voltage cables, particularly due to Conditions (mechanical stress, temperature, fire hazard, etc.) and the
choice of high-voltage cable insulation (110 ÷ 400 kV) shouldn BE review subject to particular technical - economic.
For the secondary circuit wiring insulation is best to choose a synthetic (PVC, PE, etc.).
Page 26 of 73
NTE 007/08/00
VI.2.3. Selection criteria and verification of mechanical cable sheaths Art.31. Connecting cables is fitted with metal
Roller screen or screens metal coatings (eg lead or aluminum sheaths provided for sealing), for if it results Necessary Functions Specified Not enough in the
art. 7.
Thus, power cables of medium and high voltage is provided, Which Typically with metal coatings act as the screen. Common screen wires over
the insulation of the conductor (the non-radial field) CAN USE voltage up to 6 kV.
Power cables, metal screen or metal sheaths act as display Which Will check the thermal effects caused by Ground Fault currents based on
allowable values (and Possibly to the calculation) Indicated for delivery of the cable.
Seal coatings CAN BE Used as neutral conductor in the case of low-voltage networks is guaranteed by the manufacturer for this mode of use, and if
Necessary Provide the equivalent section, According to the Standards in force for the neutral conductor.
VI.3.1. Minimum conductor sections Art.32. Sections, respectively permissible minimum diameters of mechanically
conductors cables routed under normal operating Conditions checked under Art. 27 ÷ 31 (electrical Conditions) has:
a) The power cable, not less than 1.5 mm section 2 in the case of copper conductors and 4 mm 2
b) cables with copper conductors secondary circuit, not less than 1 mm sections 2, with
Following exceptions:
- Conditions WHERE electrical circuits (for example, load, voltage drop) mechanical
(Eg, vibration) or Physico - Chemical Properties (eg, corrosive agents) Require larger section;
- the circuit wires in cable households important lenses (Listed in Annex 9) made with cables having-wire, Where the section is less than 1.5 mm 2; The
use of cables with multiple conductors (stranded), the minimum section is the section is less than 1.5 mm 2; The use of cables with multiple
conductors (stranded), the minimum section is the section is less than 1.5 mm 2; The use of cables with multiple conductors (stranded), is the
minimum section of 1 mm 2;
of 1 mm 2;
- the secondary circuits of current transformers, Where the minimum is 1.5mm section 2;
- circuits operating at Voltages up to 60V service (except preceding paragraph) That allowed minimum 0.5mm diameter wires
- the remote
copper conductors,
control cables
the minimum
with copper
diameter
conductors,
of the conductor
the minimum
Will Be
diameter of the conductor Will Be the remote control cables with
Page 27 of 73
NTE 007/08/00
0.5 mm in the case of cables laid inside buildings only 0.8 mm in the case of cables laid in the ground or in the external piping.
VI.3.2. 33 The mechanical strength of the cable. The mechanical strength of the cable is Located over insulation
The cables or sources routes free of mechanical stress, so as not to require as as a rule, rebar, or external mechanical protection (tubes,
bricks, etc.).
Situations in Which to Provide Additional protection is Necessary to Provide mechanical protection of cables or external mechanical laying cases
occure GMT:
c) laying underwater;
e) subject to remote control cable routing Influences energy installations; Typically THESE Will Be shielded cables;
f) hazardous environments, in the cases Requirements Specified in the specific design of These environments;
g) the WHERE Areas the wiring route is not marked (for example, in crowded urban systems and isolated Areas routes). Using armored
The cables reinforced with year outer shell of PVC, namely the secondary circuit and the low voltage and the average voltage provided to the metallic
screen connected to earth over each insulated conductor (cable with radial field) CAN BE laid Directly on the ground, without additional mechanical protection
(tubes, bricks, etc.), if They are guaranteed by the provider cable laying and thus has not to be subjected to mechanical Likely particular of the type in letters a ÷ g
In places subject to vibrations (eg road bridges or railways) do not contain lead sheath cables UNLESS They are guaranteed by the supplier for
this way of laying (if valves with additives lead to vibration That Prevent recrystallization).
NOTES. Additional mechanical protection of the core reinforced cables Used in alternating current, When the required results Will Be Achieved by external
VI.3.3. Mechanical stresses in case of short Art.34. Requirements for mechanical short circuit Efforts
It has:
Page 28 of 73
NTE 007/08/00
a) if cables with more conductors, the peak values of short circuit current must not Exceed the values guaranteed by the manufacturer;
b) in the case of the air laid core cables, due to the electro Efforts That CAN BE
Between CAN DEVELOP phase conductors and cables cause major movements and brutal Will take APPROPRIATE fasteners.
The distances Between the fixing points of the cables is Determined by the electrodynamic Efforts Between the cables and the nature of the insulation,
as Described in Appendix 3. The fixing members must BE of insulating material, and if They are made of metal must not form closed loops around cables and
VI. 4.1. Article 35 Conditions for reaction to fire. Conditions for reaction to fire electric cables Used to the Objectives
recommended to Those Specified in SR EN 60332 (standard parts) SR EN 50266 (standard parts) and IEC 60 331 (standard parts).
Cables with flame retardant, but laid in a bundle does not Satisfy the condition required by the SR EN 50266 (standard parts), CAN BE Used for indoor wiring
levels closed (in tunnels, basements, bridges) levels open wiring and technology in basements, That condition on the cross separation to limit the spread of fire
In exceptional cases, justified to allow the use of cables with flame retardant, provided proper treatment of the outer wrapper (eg Which color coating
increases resistance to fire, with sand or other Suitable cover materials of cables in channels).
Cables must ENSURE temporary installations under fire Will Be drawn from category "Fire Resistant."
3. When routing the ground or water, does not require statements regarding particular Conditions
If the tracks is continuous in construction, the portion of free laying cables must meet the Conditions Shown in Paragraphs a) or b) Above.
VI. 4.2. 36. Laying in aggressive soils. When routing the cables aggressive soils CONTAIN That Will Be protected by the
Page 29 of 73
NTE 007/08/00
VI. 4.3. Art.37 laying in high temperature environments. When routing in environments with elevated Temperatures in
Areas of technological equipment, Where Permanently Exceeds the ambient temperature + 40 ° C (Measured in the vicinity of Flows of wires) and Can
VI. 4.4. Art.38 laying in sun-Exposed areas. When routing cables in outdoor (on the trestles, on the construction) in
Sun-Exposed Areas, cables shouldnt year BE outer shell made with resistant to sunlight (for derating, as Shown in Appendix 1).
VI. 4.5. 39. Laying on uneven trails important. When laying on uneven trails important vertical or inclined, is Used, preferably, the dry-insulated cables (or
When it is economically justified technical and cables CAN BE Used with mass impregnated paper insulation nemigratoare). Impregnated paper insulated
cables with mass migration, technical and economical justified When CAN BE Used only if the maximum difference of level route does not Exceed the limits
For cases where are missing time from manufacturer of cables, it is permissible to use the maximum permitted level difference values Indicated
in Annex 4.
VI. 4.6. Laying the tracks with different backgrounds Art.40. Choosing and checking cables passing through Areas with
different Environmental Conditions (temperature, vibration, hazardous, different aggressiveness, etc.) is made after the Conditions of the hardest, UNLESS it is
Possible technical and economically justifiable and results tronsonarea Environmental Conditions That pose Differentiated by respective cable sections.
In cases where are only Cooling Conditions different it is assumed That the sizing to be done after the cooling Conditions of the route longest When
the high temperature zone is not more than 10 m but not more than 20% of the total length of the cable (if the cable is posing in the ground and a short portion in
VI. 4.7. Specific Conditions cables Art.41 secondary circuit. ( 1) Determination of the number of conductors: secondary circuit wiring conductors do not
Provide backup in the case of four-wire cables for serving cable to Including any individual receivers (motors, valves, dampers, etc.); in other cases, the wires
Page 30 of 73
NTE 007/08/00
The backup is normalized resulting from Adoption of a number of cable wires (or pairs or quads of wires remote control) immediately Higher than the number
Separate circuits for the various facilities (cell aggregates, etc.) must use separate cables. An exception to this situation Provision GMT WHERE Will
1. circuitry designed for a range of installations performing the same function (for example, circuits for protection loops food bar, lock loops, etc.);
2. Indirect control circuits (stage service Below 60 V voltage) or the secondary circuit of choice for a group of plants (the main circuit);
a) home-grown (mutual coupling circuits Between the same cable); avoiding, Where Possible, Bringing together in the same cable operating at
Voltages Below circuits 60V and above, Because of the danger to induce capacitive coupling or inductive electrical voltage to the proper
functioning of disrupted facilities (especially static switchgear telemăsură). To reduce disturbance of domestic origin politica When to adopt
solutions, however, have Chosen the APPROPRIATE cables with shielding groups and Suitable circuits,
Energy installations in the vicinity of Dangerous induce secondary circuit voltage installations CAN cables or personnel by capacitive coupling,
inductive or resistive (electrically). To reduce the induced voltage in the secondary circuit cables placed in the enclosure Near the power plant (for example,
the high-voltage stations 110 ÷ 400 kV) has Taken GMT steps:
cable conductors of different polarity (current-way scroll) Belonging to the same circuit;
d) the avoidance of parallel tracks along the length of large power installations.
high voltage electrical equipment or power lines must have Located near BE Chosen Voltages induced and checked the coupling (inductive, capacitive,
resistive) According to STAS 832 Instructions for designing and pilot cables. coupling (inductive, capacitive, resistive) According to STAS 832 Instructions for
designing and pilot cables. coupling (inductive, capacitive, resistive) According to STAS 832 Instructions for designing and pilot cables.
Page 31 of 73
NTE 007/08/00
Art.42. Choice of cables in places with electric power train in DC must consider the danger of corrosion by stray currents. This danger arises cables
with metallic screen, especially nearby stations WHERE recovery ie cables is Near current return paths from the rail to the negative terminal of the charger.
Consequently, THESE BE shouldnt Areas avoided with metallic screen cable routing. Also, avoid laying cables parallel with the metal shield
DC traction.
If, for Reasons of energy is mandatory or systematization street routing the cables with metal screen in Areas Above, it has Taken THEN the Measures
provided for in the Requirements for the corrosion protection of buried metallic structures (NORM I 14 and STAS 7335 - standard parts) and only use PVC
sheathed cables or other material resistant to structures (NORM I 14 and STAS 7335 - standard parts) and only use PVC sheathed cables or other material
resistant to structures (NORM I 14 and STAS 7335 - standard parts) and only use PVC sheathed cables or other material resistant to structures (NORM I 14 and STAS
7335 - standard parts) and only use PVC sheathed cables or other material resistant to structures (NORM I 14 and STAS 7335 - standard parts) and only use
PVC sheathed cables or other material resistant to the environment.
VII.1 43. Conditions. Installation of cables solution (in air, in soil, in tubes or on special tracks) Determined is based on the
Achieving rules for various types of networks (Indicated in the previous chapter).
44. Objectives In households energy cables separate cables for each of functionally object (blocks or power units, power transformers in power stations,
The cables have powered up each separate object or device for Preventing and extinguishing is disposed in separate streams Belonging to the
It is allowed to flow in the same wiring group Corresponding to two or more separate items, while the back-up supply cables in separate streams
That has laid Belonging to the primary power supply. In THESE cases, if There Is The Possibility of a local operation, the secondary circuit common picture flow
CAN cables portions of the places of local and central control point.
Art. 45. Recommended cable routing of wires, Including Those related to systems and devices for Preventing and Fighting Fires Those Within the
streams separate from the power cables and carrying of separate streams for different voltage energy cables.
If the development of separate streams is not possible, groups of cables in the previous paragraph May be arranged in the same flow (rack,
Page 32 of 73
NTE 007/08/00
GMT cases:
b) at the ends of the cable path with a nominal voltage of 6 kV and higher, Regardless of the type of cable;
c) at the ends of the low voltage cable entry impregnated paper insulation. For reservations, SHALL BE That provided the
minimum length:
a) the sleeves, the required length of the sleeve restoration twice, respectively;
b) the terminal, the length of time required to restore one of the terminal Concerned.
c) in three-phase circuits ENSURE a symmetrical distribution of the loads on the three phases, and the Implementation Used Not enough That technology is the
e) does not fit the individual cables in the ferromagnetic tube and the armature is not embedding in the concrete forming closed loops around each phase;
f) the air-laid cables and fixing parts to check the electrodynamic stresses in case of short circuit in accordance with Art. 34;
g) where are the high capacity of the transport ENSURE has more connections Used in parallel, using sections having lengths identical cables;
group together is three-phase cables different groups Will Be Belonging to the distance Between Them; WHERE Will each group proceed
h) a rule, the metal screens of the cable link Between Them and the ground at both ends. Exceptions have cases where are
screens is not thermally stable currents single-phase short circuit, When admitting Linking Them to the ground only at one end, provided That, in this case,
Voltages to ground induced screen at the other end - under normal and short - does not Exceed the According to STAS 2612 permissible values.
If, by grounding the screen at one end Voltages induced screen to ground at the other end it beyond the permissible values SHALL BE Adopted
solution grounding screen at both ends, taking Measures to ENSURE ITS thermal stability (choice of cables with a more marked section of the screen,
Art.48. Minimum bending radius of the cables, Which must BE Observed When handling and restraint Shown by the manufacturing plant.
Page 33 of 73
NTE 007/08/00
design and execution of electrical installations with Voltages up to 1000 V and 1500 V DC - I 7 and the Norms design relay protections and electrical automation
a) non-combustible layers (masonry, concrete, plaster of at Least 1cm thick envelope of asbestos or at of least 0, 5 cm thick) with a width Which Exceeds by at Least 3 cm
b) The cables have installed on the combustible material element (eg. metal brackets, etc.) wiring at distances of least 3 cm from the fuel material.
Art.51. Cable installation is after being mounted and painted metal construction has made all ground connections and WHERE Were Necessary made
in accordance with signaling circuits extinguishing installations and related facilities, the Latter must BE Able running startup to household wiring.
In cable households, welding work or open fire runs only on hot work permit.
After laying cables, politica works is not admitted except in cases of strict NECESSITY and taking additional Measures of protection.
Art.52. Conducting cable drum and laying Their only while the ambient temperature is Higher than the minimum limits Specified in Standards and
If the cable is Necessary Temperatures deployment and at lower than Indicated by factories supplying cables must BE heated.
Art.53. The specific energy cable installation tension of 110 kV, 220 kV, 400 kV, for example: the mounting distance, Approaches and Intersections
with other pipes and fittings, transpositions, etc., is Determined by the directions of the manufacturer and the rules for the calculation of the influence of the
power line.
Art.54. Earthing conductor and protective coatings for metal cables (ensuring continuity path), and the metal supporting construction is
recommended to
Page 34 of 73
NTE 007/08/00
Comply
SR
recommended
HD 637
SR EN
S1:That
61140:
2004.
theIt2002
Earthing
is recommended
andof
SRthe
HDcable
637
Thatsheaths
S1:
the2004.
Earthing
at Itboth
isof
recommended
ends.
the cable sheaths
That at
theboth
Earthing
ends.ofComply
the cable
SR sheaths
EN 61140:
at both
2002ends.
and Comply
SR HD 637
SR EN
S1: 61140:
2004. It2002
is and
VII.2.1. 55. prescribed distance. When Installing cables in air is standardized GMT categories of distance: distance from the bearing and for fixing the cables,
the distances laying on racks, walls and floors, distance on the lanes of the circular spaces of installation, distance to protect the mechanical distances
technological installations.
(1) The distances of the bearing and fixing the cables Between two successive distances has the bearing points of the cables to be
horizontally mounted, respectively, for fixing the vertical mounting has Chosen According to the Characteristics of cables in accordance with the
Table 2. The
maximum distance
maximum
of the
distance
bearings
of and
the bearings
mountingand
of the
mounting
cables.of the cables. Table 2. The
Distance (cm)
cable type
horizontal installation vertical mounting
unreinforced 50 100
Armed 80 150
Notes. It is believed the cables That Vertically mounted angle at year Greater than 45 0 horizontal.
(2) Distances laying on racks, on walls and floors, recommended in terms of charging cables, Which is Considered to be eliminated Influences technical
interrelations Between power cables laid on racks, walls, floors or bottom channels, as well as the alignment order Thereof It has as Shown in Fig. 1.a, Fig. Figure
If the space available does not allow for cable routing THESE distances, distances Reduced Adopted May be, until the minimum values Indicated in
Fig.1.b, Fig.2.b, respectively Fig. 3.b, with a reduction in the energy charging Corresponding cable (see Appendix 1, Tables A.1.22 and A.1.23).
Cables Belonging to different groups each user or voltage (power circuit That side) is usually placed on different Cables Belonging to different groups
each user or voltage (power circuit That side) is usually placed on different racks, the racks recommended order of alignment of the same rack as the one in
Fig. 1. All the different racks is usually placed, and flame retardant cables with admitted being laid inside buildings, as Indicated in Art. 35, letter a.
If cables with flame retardant, Determining the number of cables in the rack (in a bundle) take into account the category fits the cable harness
That Used
Page 35 of 73
NTE 007/08/00
(A, B, C) According to the standard Determined SR EN 50266 ( standard side); Used cable by cable Indicated category (A, B, C) According to the
standard Determined SR EN 50266 ( standard side); Used cable by cable Indicated category (A, B, C) According to the standard Determined SR EN 50266
( standard side); Indicated category Used by cable provider cable (see Art. 66 letter h.).
In cases required, to allow location on the same rack, wall or floor cable tension and different uses (for example power cables of different Voltages or
power cables and cables of secondary circuits), and the groups of cables with different behavior from flame propagation, while the cables Between the respective
b) A = 15 cm - where are the groups of wires with and without flame retardant. It is permissible to reduce the
a) Large Flows of cables When you-can take effective isolation or separation of groups of cables;
c) Whose Flows through cables do not cross over wires 10A maximum current term. Laying in layers of power cables or power cables with wires or cables
a) The maximum currents not exceeding lasting power cables conductors 10A
b) where are required, short (less than 2m) Regardless of the values of the current through the power cable, provided Between the layers to interleave
the refractory 30 min. (3) horizontal and vertical distances to walkways production facilities must not Be lower than Those Shown in Fig. 4.a.
To manufacture the cables CAN BE installed only in places where are free There is danger of mechanical damage by objects Handled devices
In environments with explosion or fire with the Will Comply THESE PROVISIONS to specific environments. Circulated in cable construction (galleries,
bridges or underground cables) dimensions of walkways Will usually not lower than Those BE Shown in Fig. 4.b; the protection and safety of LEC in cases
In uncirculated cable construction (channels, trestles, etc.). Above the spaces and the walkways (cables installed in ceilings, etc.) must BE ensured
minimum separation / Indicated in Fig. 4.c) for laying and maintenance of cables. The protection and safety of LEC mounted uncirculated cable construction and
(4) When passing cables through the floor (inside mounting) or at the transition from ground to air (the outdoor installation), the cables must BE protected
Page 36 of 73
NTE 007/08/00
a) 0.5 m in space technology, and the use of armored cables in Areas without danger of mechanical damage (for example, power stations or at Least
spaced 0.75 m of walkways rooms Technology Fig. 4.a), the use unarmored cables;
b) Technological Areas 2 m or spaces in danger of mechanical damage (for example, at distances of less than 0.75 m from the walkways - see Fig. 4.a) in
the case unarmored cables, as well as outside the enclosure (for example , power line poles). It is recommended That the passage through the floor to be
done without the protective tube, Where the machinery is connected to the mechanical protection of cables provides Them (for example, connection of
(5) safety distances to the installation of production facilities has LEC technology in
VII.2.2. Rules for installation inside the building Article 56. Cable installation inside buildings (technical rooms,
warehouses, traffic, etc.), except in special cable constructions is treated to Art. 57 Shall be in accordance with the PROVISIONS of Article 20, Article 43 ÷
a) placing cables has politica That it is Possible to intervene for maintenance and in case of fire and damage, avoiding making large cable
b) the cables is installed, usually on the shelves, walls, protective tubes, in gutters and pipes or process units in the terms of Art. 55; The choice of
horizontal trails is recommended to use protected Areas under bridges and platforms, and to Vertically strap-protected Areas around the poles;
c) the premises technology in Areas WHERE occure May leaks from fuel, fuel oil or other fluid, do not build trunking under the floor Areas outside
THESE CAN BE trunking set, taking Measures to avoid fluid penetration into the laying of the cables;
d) have cables installed in rooms combustible technological That is circulating fluids (oil pump stations, oil households, etc.) must serve
1. The cables is installed, usually in protective tubes or placed under the floor surface to Prevent the ingress of fluids steps;
2. CAN BE Used reinforced cables if They are Approved for laying in environments with danger of explosions and There is danger of mechanical
Page 37 of 73
NTE 007/08/00
3. The cables passing through walls and floors of rooms are sealed with insulation and fire resistant fluid does not leak into adjacent spaces.
e) laying cables in Areas with solid fuel is preferably sealed Deposits drains (secondary circuit cable tray, tubes for power cables); if it adopts open
f) the technological channels or galleries Which the CAN BE cables mounted Exclusively plants serving the galleries or channels (for example, valves,
actuators, valves, pumps, transmission measurements, signaling, etc.) or for installations served by Those channels or galleries; the cable out of
NOTES: For cables of 110 kV, 220 kV, 400 kV observe the cable provider.
Page 38 of 73
NTE 007/08/00
g) a secondary circuit installation cable, the PROVISIONS of Norms for the interior design of telecommunications installations in civil
h) storage and circulation space Directly Avoids the leads serves not Consumers in THESE spaces; in case this is not possible, it is Necessary to
Take Measures to protect against bumps and mechanical damage, and if There is danger of fire take Measures to guard against the effect of
a Possible fire by sheathing elements combustible having resistance wires at Least 1.5 hours ; cable protection against Fires in warehouses is
not necessary if the Deposits is provided with automatic signaling and firefighting.
VII.2.3. Rules for installation in special cable constructions Art.57. Cable installation in buildings specially designed
for cables (bridges, basements, galleries, canals, wells, bridges etc.) is made in accordance with Article 16, Art. 21, Art. 43 ÷ 54, Art. 55 indicating:
a) in attics and basements of wires, cables or cable channels or sources on racks, walls or floors, in the Latter APPROPRIATE houses with mechanical
protection (via the cable bridge); attics and basements cables CAN BE installed only lighting systems, ventilation, signage and fire fighting Directly serving
1. The string clamps and connection terminals of the combustible or non-combustible Hardly material (with RI ≥ 2 According to the STAS
4002, wherein R is the resistance of the filament According to the SR ISO 181: 1998);
3. The current paths or switchgear, cables separated by the electric arc resistant construction;
4. The service for compressed air piping or electrical equipment for testing of fixed fire extinguishing water;
b) channels and galleries (tunnels) of wires, cables or cable channels or sources on racks;
Page 39 of 73
NTE 007/08/00
Secondary circuit cables and the remote control circuit installed in the CAN BE channels and layers without racking. The cables CAN BE fitted with shelves and
the bottom of the channel, but not the channels depths of 1m and a free portion not serving for access during installation and maintenance.
concentric neutral power and unarmored cables to Which access is prevented (eg
a) minimum distance from the walkways to the manufacture racks on both sides
Shelves on one side
NOTES: It is assumed
assumed reduction
local reduction of the width
of local
of 0.8m. but no
Under the,
under the 0.6m, 0.6m the length
walkways.
(Cm) 25 30 50
free.
c) a minimum of installation (the channels in the scaffold and circulation spaces Above)
Page 40 of 73
NTE 007/08/00
Table 3. Safety
distances to technological
distances to
installations
technological
of LEC
installations of LEC Table 3. Safety
Nr.
Remarks
Intersections Approaches
books. Name of technological installation minimum distance, cm
1 cold≤ reservoirs
fluid
40 fluid
t (t ≤reservoirs
40 (cold(tfluid
≤ 40reservoirs
cold or reinforced metal pipe
combustible 50 100
of C)
thermal
ducts with
rules respectively.
NOTES. The distances given in section. 4 does not Apply to the inlet of the supply cables for the plant in question.
Channels and galleries cables CAN BE installed only installations required (if applicable) lighting, ventilation, signage and fire fighting Directly serving
the respective construction and ducts of air for servicing electrical equipment or for testing of fixed quenched with water (THESE pipes is mounted in the channels
In exceptional cases, it CAN BE mounted only on the portion of pipe crossing technology, with Measures to protect the cables; both mounting flanges is
prohibited, taps and fittings for measuring devices, paths, and perform welding on pipelines crossing technological area; Fluid fuel pipes by placing Them Will Be
protected in conduit.
Page 41 of 73
NTE 007/08/00
VII.2.4. Installation Rules Art.58 air outside the building. Installing aerial cables outside buildings, premises energy
Objectives,
is Carried out in accordance with Art. 15 to 18 and Art. 55, taking into account
specifications to be do next.
1. Laying overhead cables in enclosures energy Objectives of can make building elements with destination other than
installation cables (for example, in or on the side of bridges and walkways, walls of buildings, common on trestles with other technological installations pipes,
etc.), but it is checked - in terms of mechanical and fire hazard - if Suitable for the purpose, or specially designed for laying cable construction (trestles with cable
If conduits on joint booms, Will Provide Measures to protect cables routed under the right piping, valves, drains and flanges, as well as the cable
sleeve area.
The cables laid in tubes with flammable fluids SHALL BE protected against leakage of fluid over the entire length of the coexistence.
Avoid feeding ducts vital Consumers around Some buildings Which Affect Flows wire CAN cables. If You Can route THESE cables with wires avoid
approaching the building, it is Necessary to ENSURE a minimum of protection against the effects of any nature - Determined based computing - or adopt special
2. When routing the specially designed construction, is provided at the overpass traffic routes, and transmission gauges in the area firefighting vehicles
Necessary gauge (4.2 m high and 3.5 m wide). At the intersection with LEA estacadelor guard devices mounted in line to preventive Possible drop in the
3. Earthing of the supporting Using the CAN BE done the metal parts of the construction, except pipelines carrying flammable fluids.
4. If Whose cables route goes from the ground on poles of power lines or walls mechanically protects cables According to Art. 55, para. (4) aiming to be
placed away from Areas of movement and, as far as Possible from the action of sunlight; in the case of cables with outer shell fuel year, it is cleaned of
combustible protective material (jute, asphalt) and the then protected against corrosion by coating. At the bottom of the column, provides a cable is by laying curled
or looped.
Cable installation in open wiring levels (as defined in Art. 7) May be subject to the Following Conditions:
b) laying cable distances and distances of movement and assembly Will Be Those laid down in Art. 55.
Page 42 of 73
NTE 007/08/00
VII.3.1. Art.59 prescribed distance. ( 1) The distances in the cable-laying trenches is Shown Below.
Depth
normal
is usually
ofConditions
laying
less than:
" H it" is
Under
usually
normal
less than:
Conditions
Depthitofislaying
usually
"Hless
" Under
than: Depth
normalofConditions
laying " H it" Under
Laying CAN BE Reduced depth to 0.5 m in the inside of connections and transformer stations, on short portions (Below 5 m) on the cable entry to
The depth of the laying of cables in parallel tracks or in the overhead lines of intersection with the 110 ÷ 750 kV CAN BE Increased (up to 1.5 m), it
Horizontal clearances " IT " Between cables laid in the same trench or trenches Between separate cables is laid in horizontal clearances " IT " Between
cables laid in the same trench or trenches Between separate cables is laid in horizontal clearances " IT " Between cables laid in the same trench or the trenches
Between separate cables laid is not less than the minimum values given in Table 4. Table 4. Safe distance in cm of power cables Cables horizontally to not
less than the minimum values given in Table 4. Table 4. Safe distance in cm of power cables to cables laid horizontally in the ground
Energy: 1-20 kV 10 1) 7 3) 50 2)
Notes:
1)
Above if parallelism with 1 kV power cables, distances is set or check the calculations of influence under STAS
832.
(2) safety distances electricity cables laid in the ground to various networks,
Will not Be buildings or objects Those generally lower than Indicated in Table 5.
VII.3.2. Laying down rules in Art.60. The cables or sources on the ground in accordance with Art. 18 ÷ 20 Art. 43 Art. 53
Page 43 of 73
NTE 007/08/00
1. The cables or sources in the grooves Between two layers of sand of about 10 cm each, over Which
putting a warning device (for example, warning tapes, and / or warning signs) and the result of digging the ground (Which Bodies removed all cause damage to
It is assumed sheathing of the trench with soil Processed (selected in the surface layer of the slope, so That the grain does not Exceed 30 mm, without
stones, rocks or other foreign Bodies) and compacted by tamping until we Obtain a thickness of 10 to 15 cm smooth surface without cracks; Also warning device
a) in cases where are additional mechanical protection is required (see Art. 33);
b) in the case of the wiring grooves profiles floor (between the layers of conductors);
It Avoids the cable routing layers (levels) did it Because of thermal Influences, and the intervention of the lower wires Subsequent difficult. It is
permissible to adopt this method of laying on the basis of technical and economic justification (Including thermal calculation), the then the solution is clear That
Between cables of different Voltages and Between the medium voltage cables (same voltage) laid in the same trench at spaced up to 10 cm (see
Table 4) is mounted spacers (for example, plastic, rubber) Located on the route at intervals Not enough Between wires prescribed minimum distances.
2. cities and residential Areas, cable networks have usually laid on the carriageable roads (under Sidewalks) or under certain Conditions in the green
Areas in residential districts. The cables laid on the carriageway of the street must have Adequate mechanical protection.
The order of laying power cables under Sidewalks, buildings from side Towards the road (keeping distances Specified in Art. 60) is:
After laying, the cable network plan of the locality or industrial premises, Will necessarily move any route changes to the project.
Page 44 of 73
NTE 007/08/00
61. Depth of laying underground pipes or cables must BE blocks based on locally Conditions.
VII.4.2. Rules for Installing cables in tubes or cables Article 62 blocks. ( 1) The choice of the installation of cables in tubes is usually in the sections in Which Not
a) avoid selling works of Sidewalks, roadway or other paved or concrete surfaces for any Further intervention;
As Shown, Installing the tubes is usually Used for remote control and telecommunications connections in places and traffic routes for Undercrossing by
power cables.
The number of tubes Will Be Determined taking into account the development prospects of cabling in the area.
Also, the leads of the ground through the walls of buildings, channels, galleries Will Be protected by tube embedded in construction.
Cables with different functions (for example: energy secondary circuits, telecommunications) is installed in different tubes.
It is assumed to be installed in the same tube the cables serving the same device or receiver, and if They are provided with the electromagnetic
compatibility (EMC).
It is forbidden to install cables in the same tube That mutual backup or supplying equipment or receivers That each backup.
(2) Each of Them is Chosen tube material in the case, taking into account the guidelines GMT:
a) thermoplastic tubes (PVC) Will Be Used in most cases due to the multiple current Advantages That you present: Mechanical Characteristics
good, low friction, corrosion resistance, low cost delivery Opportunities significant lengths;
b) pipes or concrete blocks, concrete or other similar material has a coefficient of friction Greater the risk of damage to the outer sheath of the
cable; You Can use special measures, the relatively short portions of Several cables in section;
c) steel or cast iron pipes to be Used in special cases with very high mechanical stress; Does not Require a notch protection.
Page 45 of 73
NTE 007/08/00
Due to the nature of the tube does not install magnetic pole cable Belonging to a single phase in the tube (see also Art. 47).
(3) The diameter of the tube had to allow extraction of the cable without the risk of influenza. The ratio of the diameter of the tube and the outer diameter of the cable must Also BE:
a) less than 2.8 - the carriage of the pulling single-phase three wires in the same tube;
(4) the route in the tube (length, changes direction, radii of curvature) should not lead to harmful tensile cord During stretching.
Calculation Methods shooting effort and traction values allowed for different cable types is given in Annex 6.
a) Between Them connecting pipes must burrs or rough BE Achieved without leading to damage to the cable.
b) in the case of traffic routes subtraversării, it is Necessary to Provide mechanical strength and stability; That check the tubes has installed
c) the ends of the tubes must BE closed, with the interposition, if unarmored cables, cable year Between the elastic layer and the sealant material.
VII.5.1. Installation of cables under Art.63 water. When Installing cables in water meet GMT
Requirements:
1. Undercrossing rivers, Waterways, hydraulic channels, lakes, etc., must BE cables laid in Areas subject to as little erosion;
2. Cable routing prohibited in the piers, berths in ports with transhipment ports for parking or wintering ferries boats and barges,
3. Cable installation must BE on the bottom so That the bottom portions of the rough water does not remain suspended cables; Sandbanks, sand
ceilings, stone Thresholds and other underwater obstacles on the route must They must BE BE avoided or arranged in trenches or passages;
Table 5.laid
cables Safety
in thedistances
ground or
ofobjects
cables to
laidvarious
in the network
ground or
structures.
objects to various network structures. Table 5. Safety distances of
Page 46 of 73
NTE 007/08/00
)
Water and sanitation 0.5 *) 0.25 * At depths than the minimum distance is 0.6m
1
1.5m.
Pipelines, canals
2
The distances has Measured to the edge of the heat channel. They CAN
steam 1.5 0.5
3
BE Reduced by 50% the action of thermal protection of the cable (for
)
* The distance May be Reduced to 0.25 M in the case to protect the
combustible cables in tubes by the addition intersection entire length of 0.5 m on each
1.0 0.5 *)
liquids side.
)
* If the tubes to protect the cables, the distance is Increased to:
4
gas;
)
* * Typically, the gas Above. Otherwise, either the pipe or cable
gas 0.6 *) 0.25 **)
(Typically, the last installation or sources) into the protective tube
length
0.8 m from each side of the intersection. The tube Will Be provided
Page 47 of 73
NTE 007/08/00
)
Water and sanitation 0.5 *) 0.25 * At depths than the minimum distance is 0.6m
1
1.5m.
Pipelines, canals
2
The distances has Measured to the edge of the heat channel. They CAN
steam 1.5 0.5
3
BE Reduced by 50% the action of thermal protection of the cable (for
)
* The distance May be Reduced to 0.25 M in the case to protect the
combustible cables in tubes by the addition intersection entire length of 0.5 m on each
1.0 0.5 *)
liquids side.
)
* If the tubes to protect the cables, the distance is Increased to:
4
gas;
)
* * Typically, the gas Above. Otherwise, either the pipe or cable
gas 0.6 *) 0.25 **)
(Typically, the last installation or sources) into the protective tube
length
0.8 m from each side of the intersection. The tube Will Be provided
8
isolated neutral The distance is measured from extreme LEA conductor
1÷1÷
20kV 20kV
1 ÷ or treated 1.0 - (protection horizontal). Secondary circuits for cables and
LEA
110
÷
400kV
110
÷÷400
400kV
kV 110 neutral down 5.0 -
Page 48 of 73
NTE 007/08/00
)
Water and sanitation 0.5 *) 0.25 * At depths than the minimum distance is 0.6m
1
1.5m.
Pipelines, canals
2
The distances are measured to the edge of the heat channel. They can
steam 1.5 0.5
3
be reduced by 50% the action of thermal protection of the cable (for
)
* The distance may be reduced to 0.25 M in the case to protect the
combustible cables in tubes by the addition intersection entire length of 0.5 m on each
1.0 0.5 *)
liquids side.
)
* If the tubes to protect the cables, the distance is increased to:
4
gas;
)
* * Typically, the gas above. Otherwise, either the pipe or cable
gas 0.6 *) 0.25 **)
(typically, the last installation or sources) into the protective tube
length
0.8 m from each side of the intersection. The tube will be provided
crossing angle
minimum crossing
60 a angle 60 a
(Recommended 75 a ÷ 90 a).
Page 49 of 73
NTE 007/08/00
)
Water and sanitation 0.5 *) 0.25 * At depths than the minimum distance is 0.6m
1
1.5m.
Pipelines, canals
2
The distances are measured to the edge of the heat channel. They can
steam 1.5 0.5
3
be reduced by 50% the action of thermal protection of the cable (for
)
* The distance may be reduced to 0.25 M in the case to protect the
combustible cables in tubes by the addition intersection entire length of 0.5 m on each
1.0 0.5 *)
liquids side.
)
* If the tubes to protect the cables, the distance is increased to:
4
gas;
)
* * Typically, the gas above. Otherwise, either the pipe or cable
gas 0.6 *) 0.25 **)
(typically, the last installation or sources) into the protective tube
length
0.8 m from each side of the intersection. The tube will be provided
11 factory 1 1*)
)
* Minimum angle of crossing 75 a. The cables will Minimum angle
of crossing 75 a. The cables will Minimum angle of crossing 75 a. The
cables will be protected in tubes to limit the area of expropriation
Electrified railways
12 SNCFR 3 2*)
Page 50 of 73
NTE 007/08/00
)
Water and sanitation 0.5 *) 0.25 * At depths than the minimum distance is 0.6m
1
1.5m.
Pipelines, canals
2
The distances are measured to the edge of the heat channel. They can
steam 1.5 0.5
3
be reduced by 50% the action of thermal protection of the cable (for
)
* The distance may be reduced to 0.25 M in the case to protect the
combustible cables in tubes by the addition intersection entire length of 0.5 m on each
1.0 0.5 *)
liquids side.
)
* If the tubes to protect the cables, the distance is increased to:
4
gas;
)
* * Typically, the gas above. Otherwise, either the pipe or cable
gas 0.6 *) 0.25 **)
(typically, the last installation or sources) into the protective tube
length
0.8 m from each side of the intersection. The tube will be provided
* ) The safeguards
13 ) - Idem, but at least 3m.
factory 1.5 *) * * for
)
cable *
Electrified railway
)
* it admits - Crossing 10m cable needle
or return **)
reduction to 3m based
)
Water and sanitation 0.5 *) 0.25 * At depths than the minimum distance is 0.6m
1
1.5m.
Pipelines, canals
2
The distances are measured to the edge of the heat channel. They can
steam 1.5 0.5
3
be reduced by 50% the action of thermal protection of the cable (for
)
* The distance may be reduced to 0.25 M in the case to protect the
combustible cables in tubes by the addition intersection entire length of 0.5 m on each
1.0 0.5 *)
liquids side.
)
* If the tubes to protect the cables, the distance is increased to:
4
gas;
)
* * Typically, the gas above. Otherwise, either the pipe or cable
gas 0.6 *) 0.25 **)
(typically, the last installation or sources) into the protective tube
length
0.8 m from each side of the intersection. The tube will be provided
* ) )
15 Paths 0.5 *) 1**) Measured from the curb * * Measured in the axis of
sidewalk exceed
(into the border protection,
0.5m.
(into the
Page 52 of 73
NTE 007/08/00
)
Water and sanitation 0.5 *) 0.25 * At depths than the minimum distance is 0.6m
1
1.5m.
Pipelines, canals
2
The distances are measured to the edge of the heat channel. They can
steam 1.5 0.5
3
be reduced by 50% the action of thermal protection of the cable (for
)
* The distance may be reduced to 0.25 M in the case to protect the
combustible cables in tubes by the addition intersection entire length of 0.5 m on each
1.0 0.5 *)
liquids side.
)
* If the tubes to protect the cables, the distance is increased to:
4
gas;
)
* * Typically, the gas above. Otherwise, either the pipe or cable
gas 0.6 *) 0.25 **)
(typically, the last installation or sources) into the protective tube
length
0.8 m from each side of the intersection. The tube will be provided
crossing 60 a
(Recommended 75 a ÷ 90 a).
) ) )
16 Electrical cables (including * 0.5 **) * See Table 4 * * it admit
on a
Page 53 of 73
NTE 007/08/00
)
Water and sanitation 0.5 *) 0.25 * At depths than the minimum distance is 0.6m
1
1.5m.
Pipelines, canals
2
The distances are measured to the edge of the heat channel. They can
steam 1.5 0.5
3
be reduced by 50% the action of thermal protection of the cable (for
)
* The distance may be reduced to 0.25 M in the case to protect the
combustible cables in tubes by the addition intersection entire length of 0.5 m on each
1.0 0.5 *)
liquids side.
)
* If the tubes to protect the cables, the distance is increased to:
4
gas;
)
* * Typically, the gas above. Otherwise, either the pipe or cable
gas 0.6 *) 0.25 **)
(typically, the last installation or sources) into the protective tube
length
0.8 m from each side of the intersection. The tube will be provided
crossing.
4. The passage places the cable under water, on both sides, be provided with reserve length of at least 10 m to routing in rivers or at least 30 m when
Page 54 of 73
NTE 007/08/00
5. In places where bed and bank erosion are subject to be taken against unveiling cable during ice flow during floods by strengthening banks
7. The underwater cable entry must be marked on the sides of parts (terminals) signaling ;.
8. wiring lines with voltages above 1 kV, which poses in the water is determined and security area having a width of 200 m (100 m each from each side
a) setting piers for ships and barges, throwing anchors and fishing nets, fish land distribution;
The protection and safety (common) for cable crossings under rivers, lakes and waterways, must be marked with lighting and (agreed with the
9. The safety distance between cables with voltages below 110 kV is 250 mm.
10. The cable installation solution in water is determined by the depth of the opening and crossing, as shown in Fig. 5.
a. Undercrossing waterways, rivers and canals with shallow b. Undercrossing rivers (rivers) navigable depths
On waterways, where the works are carried out periodically widening of the bottom thereof, the ropes down to a fixed proportion of river transport
organizations.
VII.5.2. Installation of cables in the galleries of the water of the hydraulic installation 64.. When installing cables in the galleries of
1. It is considered galleries are galleries with permanent or accidental water in the water (flood);
2. If water gallery is not allowed hydraulic cable routing where current is too strong and could create mechanical stress on the cables
Page 55 of 73
NTE 007/08/00
3. The cable routing is allowed in water galleries is possible to check only if their points of suspension, the empty manifold; connecting sleeves
4. The water passing through the walls of the gallery, the cables are provided with special sealing devices (pipes gland or other similar
devices).
5. The galleries are constantly under water, gripping the cable with the clamps on the walls is protected against corrosion; not allowed racks
6. galleries who may be accidentally underwater cable routing can be done on consoles or racks, as well as other routes, and with the same
installation; where they are likely to find moving water, are expected to route cables consolidation;
VII.5.3. Installations in galleries and central access to underground wells or other underground power plants
Art.65. Cable installation in galleries and central access to underground wells or other underground power plants comply with the following
provisions:
1. Install connecting cables in underground power plants or other power plants underground is usually in galleries cables for this purpose (in
accordance with the provisions of Art. 57); allows installation of cables and galleries access (car, pedestrian or vehicular and pedestrian),
the public access tunnels or shafts access protection measures indicated below.
a) in the galleries for access to trucks and the car and the pedestrian access is not permitted unless their route the cable installation is
separated from the road, with protective walls or membranes resistant to mechanical action and heat (1.5 hours) or that the path is protected
from mechanical damage; if the realization of these separations, installation, observe the Art. 55;
b) galleries for access of persons are allowed to install cables, observing indicated in Art. 55, provided that, if the drift (a section gallery)
exceeds 100 m, width of space traffic in addition to consoles racks will be about 1500 mm.
Page 56 of 73
NTE 007/08/00
3. tunnels or other similar spaces with public access cable routing is allowed only if taking additional protective measures (eg cable laying alcoves
necessary separation of cables with wire mesh etc.); in the case of large flows of cables laid in areas where there is danger of fire, and
provide protection (closing) by resistant elements 1.5 hours if the space provided is not automatic signaling installations or installations
fighting fire.
4. The shafts of the stairs or lift access, allows the installation of cables in the racking is specially designed for this purpose and action of the
Page 57 of 73
NTE 007/08/00
VIII.1.1. 66. Conditions. Making cable households must meet the following general conditions:
1. Construction (rooms) networks and cable households are projected taking into account future enlargements; it is recommended that in situations
that are not predictable extensions, constructions provide additional routing cables provided 15% of the original.
2. The size of each room the cable is determined, as a rule, so as not to exceed:
- -surface
underground
bridgesarea
and of
cables;
underground
700 msurface
2 - bridges
cables;
areaand
of
surface
7underground
00 marea
2 - bridges
of 7
cables;
00and
m 2 surface
underground
- bridgesarea
and of
cables;
700 m 2
- length of 100 m - the cable tunnels and galleries (for each section);
From the above provisions exception tunnels, galleries and shafts for hydro underground cables, whose length or height is not standardized. It
is accepted that the cable basement is divided into spaces no more than 2000 m 2,
than 2000 m 2,
and in exceptional cases, justified at most 4000 m 2. Cable basement with an area greater than 2000 m 2 They and in exceptional cases, justified at
most 4000 m 2. Cable basement with an area greater than 2000 m 2 They and in exceptional cases, justified at most 4000 m 2. Cable basement with an
area greater than 2000 m 2 They and in exceptional cases, justified at most 4000 m 2. Cable basement with an area greater than 2000 m 2 They and in
exceptional cases, justified at most 4000 m 2. Cable basement with an area greater than 2000 m 2 They are provided with additional access routes for
fire intervention cars.
3. The cable constructions (bridges, basements, shafts and tunnels) are separated from other spaces adjacent the non-combustible elements with the
4. Galleries (tunnels), wells and bridges cables must be accessible only to staff servicing electrical equipment.
Page 58 of 73
NTE 007/08/00
Table 6.
3 Outwards
Note 3) Outwards
( conformable
( conformable
Note 3) Note
Outwards
3) ( conformable 1 h 30 ' 1 h 30 ' abnormal
Notes:
1) Limit fire resistance elements separation premises wiring to the premises without
fire hazard will be adopted by density heat load in the room cable, important adjacent areas and danger to human fire hazard will be adopted by density
heat load in the room cable, important adjacent areas and danger to human life.
2) Vertical piping portions (pits) or highly inclined are provided at their ends with closing fire resistant minimum of 1 hour and 30 minutes. In addition, wells
- with the exception of hydraulic underground facilities - will be provided with transverse separations at each level, but not less than the m, fireproof
30 minutes, that will completely obstruct the section. Access to the premises openings (doors, hatches) will be protected with fire resistant Clemente
least 30 minutes.
3) If the outdoor construction or installation distances are imposing conditions other than those in the table, will be met specific requirements
5. Construction cable (the spaces assets) must be provided with at least two access points. The number and arrangement of the access is determined
such that the length of the path from anywhere in the room to an outlet does not exceed 50 m, with the exception of tunnels, galleries and shafts
of the power hydraulic underground to which of the access roads, as a rule, only at the ends.
One of the access ways, namely that serves to exhaust through the roof can be achieved through the trap door or hatch or directly to the
outside, possibly to a fire escape. Make one is allowed access roads in the following cases:
Page 59 of 73
NTE 007/08/00
6. prohibit the construction of roadways and manholes in areas where there is danger of flooding water, fuel, oil or other fluids.
7. Doors cable constructions are made of non-combustible materials (metal) with fire resistance limit according to Art. 66, letter c) above; door opening
is made in the normal evacuation indicated in the project (see also Art.
85). In order to facilitate evacuation from buildings cable outlet doors are provided with closures that do not require locking key inside the
8. streams containing flame retardant cables, which bundle does not satisfy the conditions of the SR IEC 332-3, the fire-resistant transverse
separations provide at least 20 minutes to limit the propagation of flame, spaced at more than 25 m and branches of major flows.
It is assumed transverse separations giving up the above-mentioned provision, if other measures are provided against flame propagation (for example, coverage
Against the spread of fire transverse separations are provided in all wires in the same wire cross-section of flow and is designed according to
standard details.
9. openings for passing cables through ceilings, floors and walls, including those provided for extensions will be sealed in order to prevent the spread
of flames, smoke or gas passage. Limit of fire resistance of the seal gaps must be at least equal to the item go. In the cable protection goals will
10. As a general rule, in compliance to the wire (except some crosses) minimum distances between racks of cables under Art. 55 is not
recommended installing slabs between racks, which prevent normal cooling cables, reduce spraying efficiency, if the fire extinguishing water
11. take steps to avoid any leakage of oil penetration of the cable in the apparatus containing a higher amount of oil 60 kg drum and at a distance of
less than 5 m between the edge of the channel and the axis of the collecting device, retention thresholds accidental oil leaks, bulges channels
etc.
12. The cable construction shall ensure necessary space for surveillance, maintenance and intervention in case of fire; from case to case, and
provides special facilities of space for firefighting or machine access areas of intervention
Page 60 of 73
NTE 007/08/00
fire (see also Art. 79); during installation and operation, prohibiting these spaces can be filled with any equipment or materials installation
or operation.
13. The commissioning of an objective must be in operation all installations for lighting, ventilation, fire and related household fire alarm cables;
14. The special cable constructions in which water seepage can occur, especially with increased aggression must be provided with drainage
VIII.1.2. Fitting galleries (tunnels) and Article 67 cable channels. The arrangement of galleries (tunnels) and cable
1. Install cables in the cable galleries and will be subject to the distances specified in Art. 55 of the rules set out in Art. 57, letter b.
2. industrial recommend using standard-size cable channels; the cable can be prefabricated in the area where this is possible and economically
(long sewers); the cable prevents the depths, widths greater than 1200
mm.
3. The control cable and control cable can be constructed of prefabricated channels with racks, the cables are laid in layers.
4. Typically, wiring channels are not built in the interior of cells and in medium and high voltage distribution panels and cabinets for low-voltage or the
command and control; the cable is usually placed in front of or behind the cell, the panels or cabinets; the cable entry of the channels in these
protective tubes is mounted by the lower walls of the channel or channels through the bypass and through the slots; all the passages are sealed
Arrays made of non-combustible material encapsulated and serving equipment racks with a single primary circuit, can be placed over the
It allows placement of wiring channels in cells and panels partially, provided that a good separation between the cells (panels) and cable channel
by fire-resistant floors, with cable troughs well sealed against the spread according to Art. 66 lit. i.
5. Cover plate design cable channels are taken into account the following requirements:
Page 61 of 73
NTE 007/08/00
a) plates must withstand the loads that occur in normal operation in the area; for the transport of heavy parts, there will be
c) weight plates and their construction must allow easy handling by one man or, exceptionally, by two people; in the case of very
large channel widths (more than 1.2 m) to allow the weight of the plates to be larger (up to 120 kg), provided provision of handles
for manipulation and a light tiles (up to 30 kg) at intervals maximum 15 m for controls and rapid intervention.
6. In the case of cable channels that are built outdoors and are located above the groundwater level (ground) to allow the bottom of the canal to be
7. galleries (tunnels) and the cable situated under the groundwater level (ground) must have walls and erasers of a waterproof or
waterproof material.
8. aprons channels, galleries, and wiring blocks should have a drainage slope in the direction of at least
0.5%; erasers not have thresholds, protrusions or other similar structural obstacles that weighed leaks, ventilation or hinder the free
movement of personnel.
9. objectives placed underground galleries cables should not be used in order to circulate the required ventilation air spaces other than
VIII.1.3. Fitting cable bridges and basements Art.68. to attics and basements cable arrangement to meet the
following requirements:
1. Cable installation in attics and basements wiring is in compliance with distances set out in Art. 55 of the rules of Art. 57, letter a.
2. In order to achieve, in the basement of bridges and cables, the cables separate streams, the streams may provide separation between
the walls of the fire resistance of not less than 1.5 hours.
Page 62 of 73
NTE 007/08/00
3. In order to avoid agglomerations flows out of the cable areas of cables bridges, it is preferable that a sufficient number of pits, holes and
VIII.1.4. Fitting wells Art.69 cables. The arrangement of cables wells following rules shall
apply:
1. It is recommended that wells cables that pass through different levels to be fitted with doors Enterprise beside each level (see also Art. 66
c).
2. Within wells cables at the door visitation, install mounting platforms sheet ribbed slatted or concrete.
3. The free space for the installation should be at least 700 mm, measured horizontally.
4. In the case of wells that have no access to each level and the distance between the two doors of access exceeds 6 m, is mounted for
vertical access ladder intervention fixed to the inner walls of the well.
1. homes for pulling cables into the tubes must be made of brick or concrete; where there are more than 10 cables, cable entry from designated
cables or pipes in the ground can be achieved in homes dug directly into the ground and then filled with impermeable clay.
2. Lids cable homes must comply pregnancy can occur normally cover (special situations will be executed consolidation).
3. floor furnished home has a well manifold collecting groundwater and those from heavy rains; also large cable homes have provided a drain
installation.
equipped with:
b) emergency lighting for further work for intervention and evacuation. Emergency lighting for further work set out
in control rooms, power stations, relay cabinets, Diesel group and other rooms with receivers, the building is special
Page 63 of 73
NTE 007/08/00
cable.
Emergency lighting for intervention provided in places with integrated valves, valves and controls, and control of facilities or equipment to be operated
Emergency lighting evacuation lighting provides access points and evacuation in case of accidental extinguishing of normal lighting.
If galleries (tunnels) and cable wells, except the underground hydropower plants, it is recognized that instead of lighting safety outlet to use portable
battery lamps.
VIII.2.2. Supply voltages for luminaires Art.72. Supply voltage luminaires are indicated in STAS 2612, depending on the
type of lighting (fixed, portable), the location lighting of the seriousness of the installation site and the safeguards provided against electric shock.
VIII.2.3. The average lighting Art.73. The average level of lighting must comply with the
following rules:
b) Emergency lighting:
VIII. 2 .4. Art.74 lighting control. Six lighting control must make the following rules:
a) for lighting normal working order is made outside spaces, galleries or cable wells, usually near the entrance to these rooms;
Page 64 of 73
NTE 007/08/00
VIII. 3.1. Article 75 ventilation technology. The design of ventilation technology is in accordance to regulations for
If it adopts the solution Ventilation Technology by leaving open doors between different departments wiring is necessary if fire to automatic control
closing (for example, signals received from fire detectors installed in the area or by triggering fuse links).
In rooms and galleries cables have adequate ventilation cables so as not to exceed, fully-term maximum working temperature conductors indicated in
Maximum ambient temperature is determined based on technical and economic calculation, taking into account the part of the cost increase cable
conductor cross-section calculation ambient temperature is exceeded by 30 a C, and on the part of the cost increase cable conductor cross-section
calculation ambient temperature is exceeded by 30 a C, and on the part of the cost increase cable conductor cross-section calculation ambient temperature
is exceeded by 30 a C, and on the other hand the cost of the ventilation system. The maximum ambient temperature will typically be greater than 40 a C. other
hand the cost of the ventilation system. The maximum ambient temperature will typically be greater than 40 a C. other hand the cost of the ventilation
system. The maximum ambient temperature will typically be greater than 40 a C.
VIII. 3.2. Art.76 emergency ventilation. In closed special cable constructions such as: tunnels, basements or attics of armored cables (no windows) that have a
range greater than 700 m 2 and footers or cable ladders (windows) of the free armored cables (no windows) that have a range greater than 700 m 2 and footers or
cable ladders (windows) of the free armored cables (no windows) that have a range greater than 700 m 2 and footers or cable ladders (windows) of the free area
greater than 10400 m 2, devices are prescribed discharged directly to the outside of the tower and hot gases area greater than 10400 m 2, devices are prescribed
discharged directly to the outside of the tower and hot gases area greater than 10400 m 2, devices are prescribed discharged directly to the outside of the tower
and hot gases resulting fire. The devices must have a free surface of the aggregate at least 0.2% of the area or compartment space.
In cases arising as necessary both technological ventilation system and the failure, this can be achieved in a single ventilation system to ensure
Ventilation is provided, usually in a natural way in the case in which, due to its location spaces for cables or paths or exhaust, will provide for the
installation of a mechanical ventilation installations carried out as the temperature of the gas to be discharged in case of fire ( fans will be located outside the
premises served).
If the ventilation system is common to several rooms linked together technology, will take measures to prevent the spread of fire or smoke from one
room to another. Order mechanical ventilation should be from outside the room cable through buttons located near the entrances to the room and the control
room.
Fan power cables to pose hazard warning so as to not be affected by a possible fire in the rooms which they serve.
Page 65 of 73
NTE 007/08/00
IX. CABLE EQUIPMENT WITH HOUSEHOLD APPLIANCES AND EQUIPMENT AND FIRE PREVENTION
IX.1. Criteria cable households equipped with means and facilities for prevention and firefighting
Article 77. Provide the means and facilities for preventing and extinguishing fires in household wiring is differentiated, following the
provisions of general rules for fire protection and standards of equipment having stars importance of the objectives, serviced and concentration of
cables in the corresponding space, taking into account provisions of this chapter.
78. In normal rooms cable is provided, in accordance with departmental equipment fire following means and facilities and fire prevention:
b) fire hydrants, the objectives set fire to plumbing, wiring located outside premises; Discharge pipes used for fire-fighting hydrant cable
Art.79. In closed rooms cable (Art. 7) of the major farms provide in addition to the means and facilities referred to in Art. 78 and the following:
a) automatic fire signaling systems: for premises wiring with areas greater than 2,000 m 2, to provide direct
communications links, telephone or radio next to the room to the room where the fire alarm panel.
b) special facilities blanking flows cables; applies to streams of combustible cable having more than 3.5 l / m. In rooms with cables with an area
greater than 2000 m 2 must ensure the possibility firefighting intervention vehicles. rooms with cables with an area greater than 2000 m 2 must ensure the
possibility firefighting intervention vehicles. rooms with cables with an area greater than 2000 m 2 must ensure the possibility firefighting intervention
vehicles.
Art.80. In justified cases, the bridges cables under control rooms of major cable households can provide only the original means of extinguishing (fire
extinguishers) and quenching with water to hydrate (with special fire-fighting installations) when the following conditions are met:
b) local service is provided to continue or resume work safely stop times of the machines.
Page 66 of 73
NTE 007/08/00
If the bridge cables are steel structures (columns, beams) unprotected fire must be provided a fixed fire extinguishing water spray, so as to
avoid damage to these structures (maximum temperature 300 a C). extinguishing water spray, so as to avoid damage to these structures (maximum
temperature 300 a C). extinguishing water spray, so as to avoid damage to these structures (maximum temperature 300 a C).
Art.81. In technological spaces in the cable routing and air outside the building, setting means and facilities for preventing and extinguishing fires in
electrical cables is given and those established for the remaining installations in spaces.
Levels open estacadele cable and installations shall be equipped with means for preventing and extinguishing referred to in Art. 78, letter and letters of b.
Article 82. Households cable running to the technical reasons can not be applied strictly the provisions of this regulation, on preventing and
extinguishing fires may continue to operate or be put into operation only with the following measures:
a) application in mechanical separation cables cross the streams cables under the limit laid down in Art. 66, letter H;
b) protection of the cable against the spread of flame according to Art. 35 lit. a and 66 letters H;
c) households have cable running with prevention and firefighting, provided the rules for prevention and firefighting
- PE 009.
IX.2. Art.83 signaling installations. Automatic fire signaling systems is achieved with smoke detectors and temperature;
The temperature detectors provide only if they are not normal operating conditions smoke detectors.
Art.84. Central signaling is placed, where appropriate, civil fire band or in a room where there is always personal touring and service which is in charge
Article 85. From the room it can put up the central signaling and civil fire alarm ensures automatic and performs uplink via telephone, radio or other
means.
IX.3. Special firefighting installations 86. In cable households carry out the following types of special equipment for
firefighting:
Page 67 of 73
NTE 007/08/00
b) foam extinguishing installation with high coefficient extenders (over 400: 1); in the case of small streams of cables placed concentrated on the floor
or on the wall, you can use the foam to the average extenders;
c) extinguishing
extinguishing systems
systems withwith carbon
carbon dioxide
dioxide in the in the space
space volumevolume limited;
limited; the use ofthe usesolutions
other of other solutions prevention and firefighting households cables
can be taken on a case by case basis only with the court's tutelary of the owner and only where those solutions have an efficiency technical,
Art.87. Commissioning of the Switches is usually manually (locally and / or remotely) only after verifying correct signaling the beginning of fire and
Extinguishing installations are so designed as to ensure their commissioning by service personnel in a time that usually does not exceed five minutes
from time signaling the beginning of the fire and to start fighting operation.
Article 88. Commissioning of the plant is outside the premises affected, namely in places that are safe for service personnel or specially
arranged for this purpose. For installations extinguishing foam provides possibilities of connection to the water supply system and the electrical energy for
Power cords generators or sources on separate tracks of wiring space or spaces protected.
Power cords pumps serving fixed installations extinguishing water spray is posing in compliance with the norms concerning the design and execution
Art.89. Of the number of generating foam and sizing of water is such as to ensure filling of the foam to the whole cable compartment in a time usually
not exceeding 5 minutes, where justified, namely in basements or attics large cable, it is recognized that this time is no more than 10 minutes.
Article 90. In construction there are provided compressed air installations, it is recommended that attempts prophylactic fixed installations extinguishing
water spray to make compressed air in those spaces for cables and electrical equipment containing such admitted to Art. 57 lit. to or situated above a room with
electrical equipment.
Art.91. Means first responders and fire hydrants. Cable household endowment means of first responders and hydrants shall be in accordance with
Page 68 of 73
NTE 007/08/00
X.1. Article 92 terminals and sleeves. Terminals and sockets must provide cable protection against ingress of moisture
Article 93. Terminals and sockets for connection and extension cables must withstand the test voltages prescribed cable.
c) the electrical continuity of the metal sheath and the lead sheath and the conductor (aluminum or copper);
In the case of cable joints impregnated paper insulation, cable insulation dried, measures must be taken to prevent the penetration of the cable
It is recommended that the connection sleeves per 1 km of newly built cable with a voltage of 1-30 kV, to a maximum of 4 pieces; a larger
number of sockets (up to 6 pieces) shall be allowed only subject to approval from the company operating the line in cable.
Article 95. Cable splicing controls permitted only in the following cases:
a) the length of the route is longer than the respective cable manufacturing;
Article 96. Electric cables laid in the ground, located in the vicinity of the sleeves, it must be protected from their location at a minimum distance of 25
cm; it is necessary to decrease this distance, the closer to the sleeves cables must be protected by bricks, concrete slabs, etc.
Not carried out, usually in basements sleeves, cable bridges, technological premises, warehouses and other high fire risk areas; requiring power cables
to junction manşonează outside of these areas or protect the junction portion of the mechanical and fire-resistant elements (minimum 30 minutes).
X.2. Cable Markers Article 97. Cables laid out in rooms, channels, galleries, bridges and wells cables are marked with
identification tags at the ends, crossing a cable to another building at Cross other cables etc. Cables laid in earth marks the route, every ten meters.
Page 69 of 73
NTE 007/08/00
Article 99. Labels for cables are made of lead, plastic, copper or aluminum (the material is chosen according to the laying) and must bear them:
- voltage (kV);
- laying year.
Article 100. All connecting sleeves or branch and terminals must be equipped also with identification tags.
Article 101. Underground cable routes are marked by landmarks marking surface or marker plates on buildings when the drawings, ducts can not be
The distance between the terminals marked trails straight outside the areas inhabited areas is 100 m.
Marking the terminal changes direction of road crossings and intersections with other underground sewers (cables, fluid lines, etc.).
Cable terminals are fixed laterally at 0, 8m of its axis, the cable-oriented inscription plate.
102. Marking and repair of cable networks in settlements is in accordance with STAS 9570/1.
103. Marking of cables to waterways river crossings: wires have to be spotted on both sides by plates visible indicator for navigators.
At the crossing of a track, locating the cables are signposts on both sides thereof.
X.3. 104 cable testing. Attempts cable reception or intermediate steps before assembly, are as indicated cable provider
(standards, internal standards, specifications, etc.); tests after installation and during operation are made according to the norm of tests and measurements
XI. Environmental protection measures Art. 105. Design, construction, refurbishment and maintenance of electrical cable lines are taken to reduce negative
environmental lines.
Page 70 of 73
NTE 007/08/00
f) electromagnetic field;
g) Undercrossing water;
i) waste disposal;
Art. 107. Documentation for making LEC must contain all necessary data and information, including management and monitoring plan will include mitigation
a) electromagnetic;
b) physically;
c) the chemical;
d) mechanical;
e) sound;
f) visually;
g) a mental disorder;
h) socio-economic etc.
on the environment both during release route, construction, operation / maintenance and decommissioning them in order to obtain the environmental license. The
documentation will be treated at the request of the beneficiary, and the requirements of its own procedures.
Page 71 of 73
NTE 007/08/00
BIBLIOGRAPHY
1. Clarke, DJ, Soth, IP Cross bonding single core power cables. BICC, London, 1975.
2. Lang, V. L'échauffement des des Lignes aériennes conducteurs cables. In: Bull. of
ASE, no. 14, 1956, p. 631-641.
3. Endrenyi. J., Murllie, Mc. Determination courant de l'intensity admissible dans les
conducteurs numérique par simulation of charge, although Conditions atmosphériques et du vieillissement often conducteurs. CIGRE 1968, Rapport
conducteurs.
23-04. CIGRE 1968, Rapport 23-04.
4. Gorub, IC, Woll, EF Load Capabitity of Bare ACSR and All-Aluminum Conductor
based on Long-time Outdoor Temperature Rise Tests. IEEE Trans. STEP vol. 82 no.
12, 1963, p. 73-82.
5. Davis, MW Nomographic computation of the ampacity rating of aerial conductors.
IEEE Trans. Apparatus und Power Systems, Vol. PAS, 89, pp. 387-399, Mart., 1970.
6. VDE 0103 / 1.61. Leitsätze of Bemessung Starkstromanlagen von und auf mechanische
termische Kurzschlussfestigkeit.
7. Goossens. RF Rapport sur les travaux du Comité d'études no. 2. (á haute tension cables). CIGRE-ref. 233 1964.
8. THE Calculation du courant admissible steady dance en les cables (facteur of charge
100%). Recomandation from Electrotechnique International Commision (IEC), Publication 287 1969 Bureau of IEC,
Geneva.
9. Nehet, John H. Procedures for calculating the temperature yise of buried cable and pipe
cables for sinusoidal and rectangular loss cycles. AIEE Transactions, Vol. 72, pt. III (June 1953), pp. 541-545; 535; 539-560.
10. Buller. FH Woodrow, CA. Load factor-Hour equivalent values compared. In: Electrical
World, vol. 92, no. 2, 1928, pp. 59-60.
permanent (facteur of charge 100%). Suisse Geneve 1969 avec modification No. 1 avril 1971 modification No. 2 avril
1972.
13. Jocteur, R., Osly, M. Recherche et developpement en France dans le domaine des cables haut
16. Sufrim, M., Iszák, E., Dabija D. - Fire safety cables households
industrial enterprises. Technical Publishing House, Bucharest, 1984;
17. Meculescu, M., Diana G. Methods for calculating the maximum admissible current transmission lines
Bucharest, 1960.
19. Iacobescu, Gh. saddle. Electrical networks. Problems. Didactic and Pedagogic, Bucharest, 1975
20. Ionita. Georgeta, Bucea, Gh. Installation and operation of high voltage power cables.
Technical Publishing House, Bucharest, 1979.
21. Siemens Memoratorul electrical engineer. translation from German language adaptations to
conditions in Romania. Technical Publishing House, Bucharest, 1975.
22. Baciu, A., Laszlo T. Operation and repair of electrical networks. Bucharest: technical
1969.
23. Militaru, P., Peter, N. Considerations and proposals for the calculation of the thermal stability
circuit conductors and devices. Sixth Session of scientific-technical Institute for Studies and Power Engineering. 5-7. XII, 1966, vol. I, p. 55-80.
24. Avramescu A. Temperaturabhangigkeit von der wakren spezifischen warm und Leitungskupfer
Page 72 of 73
NTE 007/08/00
25. Avramescu A. Heating the aluminum short-circuit conductors. in: Studies and researches
energy, no. 3, 1953.
26. Avramescu A. Adiabatic heating conductors of copper, aluminum and silver. Studies and
energy research, no. 3-4, 1955.
27. Cruceru C. theoretical and experiments on determination
temperature power cables operating under variable load. The works ICPE, no. 24, 1970.
30. Curelaru, Al. Problems stations and networks. Writing Romanian, Craiova, 1979.
31. Pietrăreanu, E. Agenda electrician. Bucharest, Technical Publishing House, 1986.
32. Arhipov, NK Calculation of short circuit currents. Bucharest, Technical Publishing. 1958.
33. Racoţi, E. Table and diagrams for the calculation of the conductors. Bucharest, Technical Publishing, 1988.
34. Ionita Georgeta, Mazilu, Gh. 1-220kV underground electric lines. Directory computing and
design. Technical Publishing House, 1990, Bucharest.
35. Iacobescu, Gh., Iordanescu I, Eremia, M., Ţenovici, R., Dumitriu, C. - Electrical networks.
Problems. Bucharest, Didactic and Pedagogic 1977.
36. Iacobescu, Gh., Iordanescu I, Eremia, M., Toader, C., Ţenovici, R., Dumitriu, C. - networks
electric. Bucharest, Didactic and Pedagogic 1981.
37. Mircea I. - Installation and equipment. Theoretical and practical guide. Second Edition. publishing house
38. Angelescu, M. - Urban utility networks. Didactic and Pedagogical RA Bucharest, 1996.
Page 73 of 73