Document No.

MOBILECT POWER CORPORATION


Date of Test
RELAY TEST REPORT Feb . 16,2019
Client Name CIP II Powerp Corp. Page No.
Address Bacnotan, La Union

Location/ Substation 30 MVA ,69/13.8 kV


Ct. Pri./Ct. Sec 600/5 ,1500/5
Relay Type P632
Serial Number
Test Instr ument Used PONOVO

III. RELAY FUNCTIONAL/TRIP TEST


1.0 T2WPDIF:1 - Transformer Differential Protection
1.1 Pick Up Test
HV Side LV Side
Phase Function Remarks
Pick Up Drop Out Pick Up Drop Out
A Id 0.41 0.81 Okay
B Id 0.41 0.81 Okay
C Id 0.41 0.81 Okay
1.2 INST PU
Phase I Time (sec) Remarks

A 16.734 0.03 Okay


B Okay
C Okay
1.3 Stability Test
Current xIn (in
Phase HV Side (in Amps) LV Side (in Amps) Status
Amps)
ABC 100% 2.092 4.184 No Trip
ABC 200% 4.184 8.367 No Trip
ABC 300% 6.275 12.6 No Trip
1.4 Slope Test
HV Side Start (in LV Side Start (in LV Expected Curr (in
% Bias Point Id Trip Time (in sec)
Amps) Amps) Amps)
100% 2.092 4.184 0.00 3.138 0.0365
150% 3.292 4.184 0.00 0.0306

ACCEPTANCE TESTED BY CHECKED/NOTED BY WITNESSED BY


SIGNATURE
NAME HERBERT S. OTEDA JOE ARLIN C. DIVINAGRACIA
COMPANY MOBILECT POWER CORP
DATE
Document No.

Date of Test
Feb . 16,2019
Page No.

Remarks

Okay
Okay
Okay

Trip Time (in sec) Remarks

0.0365 Okay
0.0306 Okay

WITNESSED BY
Document No.
MOBILECT POWER CORPORATION
Date of Test
RELAY TEST REPORT Feb . 16,2019
Client Name CIP II Powerp Corp. Page No.
Address Bacnotan, La Union

Location/ Substation
Panel /Circuit 69 kV ,bus
Relay Type
Serial Number 2010076337
Test Instr ument Used PONOVO

1.0 BUS DIFFERENTIAL TEST DATA


1.1 TAP SETTINGS
Phase TEST TAP AS FOUND AS LEFT Remarks

A 68 V 68 V 68 V Okay
B 68 V 68 V 68 V Okay
C 68 V 68 V 68 V Okay
1.2 CALIBRATION
Phase Test tap PU Time (sec) Remarks

A 67V 66.3 V 0.0082 Okay


B 67 V 66.3 V 0.0187 Okay
C 67 V 66.3 V 0.0113 Okay

ACCEPTANCE TESTED BY CHECKED/NOTED BY WITNESSED BY


SIGNATURE
NAME HERBERT S. OTEDA JOE ARLIN C. DIVINAGRACIA
COMPANY MOBILECT POWER CORP
DATE
Document No.

Date of Test
Feb . 16,2019
Page No.

WITNESSED BY
Document No.
MOBILECT POWER CORPORATION
Date of Test
RELAY TEST REPORT 16-Feb-19

Client Name CIP II POWER Corp. Page No.


Address Bacnotan, La Union

Location/ Substation CONTROL ROOM


Panel /Circuit HOLCIM OC/EF (P123)
Relay Type MICOM
Test Instr ument Used

I. RELAY DATA
MADE AREVA 10605
TYPE MICOM 123
Serial Number 2206530
CONTROL PWR SUPPLY 48-125Vdc

II. RELAY SETTINGS


AS FOUND AS LEFT
I> I>> Ie> I> I>>
TAP 0.33xIn 4.0xIn 0.1xIn TAP 0.33xIn 4..0xIn
TIME DIAL IDMT DMT IDMT TIME DIAL IDMT DMT
CURVE TYPE IEC SI - IEC SI CURVE TYPE IEC SI -
TMS 0.22 70ms 0.025ms TMS 0.22 70ms

III. RELAY PICK UP TEST


AS FOUND AS LEFT
in Amps I> I>> Ie> in Amps I> I>>
PICK UP 1.81 20.00 0.55 PICK UP 1.81 20.00
DROP OUT DROP OUT
RESULTS RESULTS

IV. RELAY TIMING TEST


AS FOUND AS LEFT
% Multiple of Pick Time (sec) % Multiple of Pick Time (sec)
up I> I>> Ie> up I> I>>
110% 0.0920 110% 0.0920
120% 0.0911 120% 0.0911
150% 3.8065 0.4542 150% 3.8065
200% 2.2272 0.2722 200% 2.2272
300% 1.4034 0.1753 300% 1.4034
400% 1.1105 0.1425 400% 1.1105
500% 0.9574 0.1248 500% 0.9574
V. REMARKS

VI. ACCEPTANCE TESTED BY CHECKED/NOTED BY WITNESSED BY

SIGNATURE

NAME
COMPANY
DATE
Document No.

Date of Test
16-Feb-19

Page No.

3)

LEFT
Ie>
0.1xIn
IDMT
IEC SI
0.025ms

LEFT
Ie>
0.55

LEFT
Time (sec)
Ie>

0.4542
0.2722
0.1753
0.1425
0.1248
WITNESSED BY
Document No.
MOBILECT POWER CORPORATION
Date of Test
RELAY TEST REPORT 16-Feb-19

Client Name CIP II POWER Corp. Page No.


Address Bacnotan, La Union

Location/ Substation CONTROL ROOM


Panel /Circuit CIP II OC/EF (P123)
Relay Type MICOM
Test Instr ument Used

I. RELAY DATA
MADE AREVA 10605
TYPE MICOM 123
Serial Number 2206531
CONTROL PWR SUPPLY 48-125Vdc

II. RELAY SETTINGS


AS FOUND AS LEFT
I> I>> Ie> I> I>>
TAP 1.0xIn 16.0xIn 0.3xIn TAP 1.0xIn 16.0xIn
TIME DIAL IDMT DMT IDMT TIME DIAL IDMT DMT
CURVE TYPE IEC SI - IEC SI CURVE TYPE IEC SI -
TMS 0.07 10ms 0.025ms TMS 0.07 10ms

III. RELAY PICK UP TEST


AS FOUND AS LEFT
in Amps I> I>> Ie> in Amps I> I>>
PICK UP 5.53 80.00 1.65 PICK UP 5.53 80.00
DROP OUT DROP OUT
RESULTS RESULTS

IV. RELAY TIMING TEST


AS FOUND AS LEFT
% Multiple of Pick Time (sec) % Multiple of Pick Time (sec)
up I> I>> Ie> up I> I>>
110% n/a 110% n/a
120% n/a 120% n/a
150% 1.2315 0.4522 150% 1.2315
200% 0.7214 0.2725 200% 0.7214
300% 0.4583 0.1764 300% 0.4583
400% 0.3652 0.1412 400% 0.3652
500% 0.3149 0.1246 500% 0.3149
V. REMARKS

VI. ACCEPTANCE TESTED BY CHECKED/NOTED BY WITNESSED BY

SIGNATURE

NAME
COMPANY
DATE
Document No.

Date of Test
16-Feb-19

Page No.

LEFT
Ie>
0.3xIn
IDMT
IEC SI
0.025ms

LEFT
Ie>
1.65

LEFT
Time (sec)
Ie>

0.4522
0.2725
0.1764
0.1412
0.1246
WITNESSED BY
Document No.
MOBILECT POWER CORPORATION
Date of Test
RELAY TEST REPORT 16-Feb-19

Client Name CIP II POWER Corp. Page No.


Address Bacnotan, La Union

Location/ Substation
Panel /Circuit
Relay Type
Test Instr ument Used

I. RELAY DATA
MADE
TYPE
Serial Number GE MII
CONTROL PWR SUPPLY

II. RELAY SETTINGS


AS FOUND AS LEFT
I> I>> Ie> I> I>>
TAP 0.33 x In 4xIn 0.1 x In TAP 0.33 x In 4xIn
TIME DIAL TIME DIAL
CURVE TYPE CURVE TYPE
TMS TMS

III. RELAY PICK UP TEST


AS FOUND AS LEFT
in Amps I> I>> Ie> in Amps I> I>>
PICK UP 1.72 20.00 0.53 PICK UP 1.72 20.00
DROP OUT DROP OUT
RESULTS RESULTS

IV. RELAY TIMING TEST


AS FOUND AS LEFT
% Multiple of Pick Time (sec) % Multiple of Pick Time (sec)
up I> I>> Ie> up I> I>>
110% 0.0776 110% 0.0776
120% 0.0739 120% 0.0739
150% 3.6067 0.4673 150% 3.6067
200% 2.1156 0.2744 200% 2.1156
300% 1.3441 0.1827 300% 1.3441
400% 1.0540 0.1190 400% 1.0540
500% 0.9113 0.1077 500% 0.9113
V. REMARKS

VI. ACCEPTANCE TESTED BY CHECKED/NOTED BY WITNESSED BY

SIGNATURE

NAME
COMPANY
DATE
Document No.

Date of Test
16-Feb-19

Page No.

LEFT
Ie>
0.1 x In

LEFT
Ie>
0.53

LEFT
Time (sec)
Ie>

0.4673
0.2744
0.1827
0.1190
0.1077
WITNESSED BY