Sie sind auf Seite 1von 10

This article has been accepted for publication in a future issue of this journal, but has not been

fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2018.2817585, IEEE
Transactions on Power Systems
IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. ?, NO. ?, OCTOBER 2017 1

Steady-state model of grid-connected photovoltaic


generation for power flow analysis
Rafael Tapia, Student Member, IEEE, Claudio Fuerte-Esquivel, Senior Member, IEEE,
Elisa Espinosa-Juárez, Senior Member, IEEE, and Uriel Sandoval, Member, IEEE

Abstract—A new model of a grid-connected photovoltaic (PV) On the other hand, as a first step in assessing the operation
plant suitable for power flow analysis is proposed in this paper. of grid-connected solar PV plants and the way in which this
Unlike existing models, the proposal departs from the equivalent sort of generation affects the overall operation of an electric
generator representation of the PV plant and is based instead
on the operation and control modes of PV panels and voltage power system, the development of steady-state PV models
source converters (VSC). The resulting set of nonlinear equations suitable for power flow studies is of paramount importance.
is assembled together with the network’s equations to formulate Even though the power flow study is one of the most common
a generalized power flow problem in a unified frame of refe- analyses performed in systems planning and operation [7],
rence, which is efficiently solved by using the Newton-Raphson only a very few solar PV plant models have been proposed for
algorithm. The complementarity condition approach is adopted
for directly including all operation and control mode constraints power flow analysis in [8], [9], and [10]. In all these proposals,
of the PV plant in the power flow formulation, which permits the large-scale PV solar park is represented by one single PV
the simultaneous and automatic handling of limits of all state plant, which in turn is modeled as an equivalent generator. The
variables associated with these constraints during the iterative power injected by this equivalent generator is directly included
solution process. The effectiveness of the proposed method is in a conventional power flow formulation, while an additional
fully demonstrated by numerical examples.
subproblem is formulated for updating the state variables of
Index Terms—Grid-connected PV generation, power flow anal- the PV plant. In this sequential solution process, the main
ysis, voltage source converter, Newton-Raphson algorithm.
differences between these proposals are the way in which the
value of the power injected by the PV plant is determined,
I. I NTRODUCTION as well as how the PV plant state variables are maintained

T HE increased integration of PV generation plants into


the electric power system is a cause for concern for the
power system planners and operators because of its impact
inside limits during the computation of a feasible power flow
solution.
In the coordinated sequential iterative solution process pro-
on the reliable operation of the bulk transmission system. posed in [8], the nodal voltages of the transmission network are
To fully understand this impact, it is necessary to perform determined by a conventional power flow analysis, and a set of
extensive planning and interconnection studies, which in turn nonlinear algebraic equations is then solved for the PV plant’s
enforce the development of proper mathematical models of state variables. The link between both solution processes is the
this type of generation for computer simulation studies. To electric power injected into the grid’s node to which the PV
achieve this objective from a steady-state operation perspective plant is connected, referred to as a point of interconnection
the following is necessary: (1) an approach for extracting the (POI), as well as the voltage magnitude and phase angle at
parameters of each PV panel making up the PV generator this node. The sequential solution process is performed until
and (2) a mathematical representation of the solar PV plant all state variables of the PV plant are within limits. If one of
suitable for steady-state studies that not only consider the these state variables hits one of its limits, it is fixed at the
power exchange between the PV generator and the network, offending limit, and the power flow study is newly performed.
but also the PV generator’s dependency on environmental Regarding the power flow study, the electric power injected
effects. by the PV plant, which is always working at the maximum
In general, there is extensive work reported in the literature power point (MPP), depends on the way in which the POI
for extracting the parameters of the single diode-based circuit is categorized: P Q node or P V node. If the POI is a P Q
model representing the PV panel. These parameters are ob- node, the PV plant injects specified active and reactive powers.
tained by iteratively solving the set of equations representing Otherwise, the PV plant only injects a specified active power,
the nonlinear I-V characteristic of the PV panel [1]–[6], based and the reactive power at the POI is determined by the power
on the values of currents and voltages given in the manufac- flow solution considering a controlled voltage magnitude at
turer’s datasheets under standard test conditions (STC) [1], this node. If this reactive power violates one of its limits, it is
[3], [4]. set at this limit, and a new power flow analysis is performed
R. Tapia, C. Fuerte-Esquivel and E. Espinosa-Juárez are with the Elec- by considering the POI as a P Q node.
trical Engineering Faculty, Universidad Michoacana de San Nicolás de In [9], the inverter’s AC node is treated as an external
Hidalgo, Morelia, Mich., 58000, México e-mail: (rtapia@dep.fie.umich.mx; generation node to the network, which is directly included in
cfuerte@umich.mx; eejuarez@umich.mx).
U. Sandoval is with the National Center for Energy Control, México, e-mail: the conventional power flow formulation by using the nodal
(uriel.sandoval@cenace.gob.mx). power equations at the inverter and POI nodes. The amount of

0885-8950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2018.2817585, IEEE
Transactions on Power Systems
IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. ?, NO. ?, OCTOBER 2017 2

electric power injection depends on the inverter’s control mode modeled in the proposed power flow approach. Hence, a new
and the type of POI at which the PV plant is embedded: P V power flow model for a grid-connected solar PV plant is
node or P Q node. The control mode specified at the inverter’s proposed, where its state variables are simultaneously solved
front end corresponds to a constant nodal voltage (Vinv -ϕinv ) with those associated with the network’s nodal voltages in a
spec
or to a constant power injection (Pinv -Qspec
inv ). When the Newton-based unified frame of analysis. To achieve this goal,
spec spec
inverter is operating in a (Pinv -Qinv ) mode, regardless of the grid-connected PV plant is considered to be composed
spec
the type of POI node, the active power Pinv to be injected of a set of PV panels and a DC-AC interface based on
is given by the short circuit current of the PV array times a voltage source converter (VSC), with their corresponding
the nominal voltage of operation, while the injected reactive mathematical equations integrated in one single model. Since
power Qspec spec
inv corresponds to a specified fraction of Pinv . The photovoltaic energy strongly depends on the weather condi-
(Vinv -ϕinv ) control mode is only possible if the PV plant is tions, both module temperature and solar irradiance are taken
connected to a P V node. In this case, the values of Vinv and into account in the modeling of each PV panel. This permits
ϕinv are obtained before the power flow study by performing considering different values of these variables for a large
a nonlinear analysis based on a specified transfer of active utility-scale solar park. Furthermore, because the VSC permits
power from the inverter to the POI node. Once these values a fast and independent control of active and reactive powers
are obtained, the powers to be injected from the inverter are at the converter’s AC-side terminals, the way in which the PV
directly computed from the power flow equations at its front plant provides a voltage control ancillary service is suitably
end by assuming a linear relationship between ϕinv and the modeled in the proposed approach. In this context, the VSC’s
voltage phase angle at the POI. operative limits are considered as complementarity constraints,
A generic model suitable for single-phase distributed energy which are directly included in the power flow mathematical
resources, which includes PV plants and is intended for the formulation by using the Fischer-Burmeister merit function
analysis of distribution systems, is proposed in [10]. In this [11], which avoids the heuristic adjustment of those limits
proposal, the active and reactive powers exchanged by the volt- during the iterative solution process. Lastly, the maximum
age source converter (VSC) with the grid are specified at given power point tracking (MPPT) control strategy is also directly
set points to perform a conventional power flow study. Since considered in the proposed solution approach by including
the VSC state variables are analytically expressed as functions the equations representing this control in the power flow
of the specified injected power and the voltage magnitude at formulation.
the POI, the values of these variables are computed at each Based on the information mentioned above, the key goal of
iteration of the solution process to check if they are within this work is to provide a fundamentally different, comprehen-
limits. If limit violations exist, new active and reactive power sive and general approach for the analysis of power flows in
set points are analytically determined to return the VSC’s electric power systems containing grid-connected PV plants
state variables inside their corresponding limits before the next in a unified single frame of reference. In this context, the
iteration. A similar checking of limits is performed for the main contributions of the proposed approach are the following:
voltage magnitude at the POI, but the injected power set points i) A new and comprehensive PV plant model is developed
are heuristically calculated in case of a limit violation. This from first principles considering different control modes of
iterative process converges to a feasible power solution when operation; ii) A PV solar park is assumed to be composed
none of the variables exceeds its corresponding limits. of several PV plants, which permits considering different
In general terms, all the sequential methods discussed above collection grid topologies; iii) The power flow approach si-
are rather attractive because their implementation in a power multaneously combines the state variables corresponding to
flow analysis is straightforward, but caution has to be exercised the PV plants composing the PV solar park with the nodal
because an additional set of nonlinear algebraic equations voltage magnitudes and angles of the network in a single
has to be solved to obtain the values of the state variables frame of reference for a unified, iterative solution that retains
associated with one single PV plant. Note that in this type Newton’s quadratic convergence characteristics; iv) Finally,
of solution there is no way of knowing during the iterative operative limits of PV plants’ state variables are automatically
process of the power flow solution whether or not the PV checked and adjusted during the power flow solution process
plant’s state variables are within limits [8] [9]. If there exist by using complementarity constraints. There is no need to have
limit violations of some of these variables, the power injected a special part of the code or to solve another subproblem to
by the equivalent generator representing the PV solar park check limits.
must be newly computed, in some cases in a heuristic way To the best of the authors’ knowledge and belief, the pro-
[10], to perform another power flow study. Since the sequential posed way in which the PV plant is modeled and implemented
solution process must be performed until all state variables for power flow studies is a newly developed concept that has
of the PV plant are within limits, it will yield no quadratic not been previously proposed.
convergence.
Trying to circumvent the problems associated with the II. PV MODELS
sequential approach and the concept of an equivalent gen-
erator reported in [8], [9] and [10], this paper proposes the A. PV panel model
representation of the solar park by several individual PV plants As with several system simulation platforms [2], [3], the
tied to a collector system, and each PV unit is independently single diode model shown in Fig. 1 is used to describe the

0885-8950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2018.2817585, IEEE
Transactions on Power Systems
IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. ?, NO. ?, OCTOBER 2017 3


PV Generator
PV Plant
Fig. 1. PV panel electrical equivalent circuit.
equivalent circuit of a PV panel composed of a set of ns Fig. 2. PV plant system.
series connected PV cells. The PV panel has an equivalent the equivalent circuit representing the PV generator is then
I-V characteristic given by [3]: defined by the parameters given by [2]:
   
V + IRs V + IRs Ieq = Ieq × Npp ∀ eq = sc, ph, 0, dc (6)
I = Iph − I0 exp −1 − , (1)
Vt Rsh
Veq = Veq × Nss ∀ eq = oc, t, dc (7)
where Vt , Iph , I0 , Rs and Rsh are unknown parameters Req = Req × Nss /Npp ∀ eq = s, sh, (8)
defined as follows. Vt is the diode thermal voltage, Iph is
the photocurrent and I0 is the dark saturation current. On the where Nss and Npp are the number of panels connected in
other hand, Rs and Rsh are the series and parallel resistances, series and parallel, respectively, and Idc and Vdc are the current
respectively. and voltage of the PV generator at its DC terminals. Note also
The first three parameters Vt , Iph and I0 are estimated that the diode ideality factor a keeps the same value for the
as reported in [3] based on the values of V and I at the PV generator model [2].
terminals of the PV panel. For this purpose, the values of
(V, I) are taken from the manufacturer’s datasheets at STC III. G RID - CONNECTED PV PLANT MODEL
(25◦ C and 1000W/m2 ) for the following operating modes: The PV generator delivers DC power that is injected into
short circuit (0, Isc ), MPP (Vmpp , Impp ), and open circuit the grid as an AC power through a point-to-point VSC-based
(Voc , 0). Hence, the diode thermal voltage is given by [2], [3]: DC-AC link, as shown in Fig. 2. In this case, the VSC is
kT a operating under a MPPT control mode to maximize the amount
Vt = ns , (2) of power converted from the PV generator. According to [9],
q
the line-to-line three-phase RMS voltage at bus k is expressed
where k is the Boltzmann constant (1.38 × 10−23 J/K), T is by (9), where ma and α are the modulation index and firing
the actual module temperature in K, a is the diode ideality angle of the VSC, respectively:
factor and q is the electron charge (1.6021 × 10−19 C).
The photocurrent Iph is given by (3) as a function of the
p
Vk = 3/8ma Vdc ∠α. (9)
irradiance and temperature
The model also includes a transformer with a series nodal
G
Iph = (Isc + KI ∆T ) , (3) admittance given by Gkk + jBkk = 1/ (RT + jXT ), which
Gn provides a Galvanic insulation [12]. Based on this admittance
where ∆T = T −Tn , Tn is the nominal module temperature in and (9), the active and reactive powers that flow from k to m
K, G and Gn are the actual and nominal irradiance in W/m2 are given by
and KI is the temperature coefficient of Isc . Finally, I0 is 3 p
expressed by Pkm = m2a Vdc 2
Gkk + 3/8ma Vdc Vm
8
Isc + KI ∆T

I0 = , (4) × Gkm cos(α − θm ) + Bkm sin(α − θm ) (10)
exp (Voc + aKV ∆T Vt ) − 1 3 p
Qkm = − m2a Vdc 2
Bkk + 3/8ma Vdc Vm
where Voc is the open circuit voltage and KV its temperature 8 
coefficient. × Gkm sin(α − θm ) − Bkm cos(α − θm ) . (11)
On the other hand, if (1) is applied at the MPP, the
relationship (5) is derived by considering the concept of DC A. VSC’s power balance equation
power P = IV . Hence, the unknown values of Rs and Rsh
The power balance equation through the VSC can be
can be obtained by iteratively solving (1) and (5):
expressed as a function of the power converter’s efficiency
∂P ∂I η, η = Pkm /Pdc [13], and it is given by
= V + I = 0. (5)
∂V ∂V
Pkm = ηPdc = ηVdc Idc . (12)
B. PV generator model The efficiency depends on the inverter power output and
A PV generator is made up by an array of series and remains almost constant for values of output powers above
parallel-connected PV panels that have the same manufactur- 0.3 p.u. [14] such that the efficiency can be set to a fixed
ing characteristics. Based on the structure shown in Fig. 2, value. On the other hand, an explicit relationship between the

0885-8950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2018.2817585, IEEE
Transactions on Power Systems
IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. ?, NO. ?, OCTOBER 2017 4

efficiency and the converter’s output power is given by the 2) PV control mode: This kind of control mode permits the
Jantsch’s model [14]: participation of PV units in ancillary services, such as reactive
Pkm power support and voltage control. This is a requirement in
η= Pnom
, (13) the Mexican grid code for the integration of PV plants at the
Pkm
Pnom + k0 + k1 PPnom
km
+ k2 ( PPnom
km
)2 transmission level [15]. In this control mode, an active power
Pkm is injected into the network, and the voltage magnitude
where Pnom is the converter’s nominal power. The param-
Vm at the POI is controlled at a constant value Vref by
eters k0 , k1 and k2 are computed by (14)-(16) as functions
the VSC. This control is achieved by adjusting the VSC’s
of the converter’s efficiency at 100, 50 and 10% of its rated
reactive power during the iterative solution process based on
output power: ηinv1 , ηinv0.5 and ηinv0.1 [14].
the voltage droop control given by [16]:

1 1 1 1 5 1 ∆g5 = Vm − Vref + Kp Qkm = 0, (21)


k0 = − + (14)
9 ηinv1 4 ηinv0.5 36 ηinv0.1 where Kp represents the voltage droop control setting. Note
4 1 33 1 5 1 that (21) is used for each PV plant that provides reactive power
k1 = − + − −1 (15)
3 ηinv1 12 ηinv0.5 12 ηinv0.1 support for achieving the voltage magnitude control at the
20 1 5 1 5 1 m-th bus [17], [18].
k2 = − + . (16)
9 ηinv1 2 ηinv0.5 18 ηinv0.1 The nonlinear equations that need to be solved to assess
the steady-state operation under this control mode are (17),
B. Basic mismatch equations of the PV plant (18), (19) and (21). Note that in this case the VSC applies
both MPPT and voltage droop control strategies to achieve
The general set of mismatch equations that describes the maximum power and voltage control. Note also that the final
steady-state operation of the PV power plant always considers value of α is relative to the system phase reference, regardless
the basic equations (17) and (19). The MPPT control strategy if the VSC is operating under a PQ or PV control mode.
is represented by (17)-(18), which are derived from (1) and
(5), respectively. The active power flow mismatch equation at
IV. H ANDLING OF THE VSC POWER LIMITS
the AC terminals of the VSC is given by (19):
    The handling of VSC’s power limits is performed by con-
Vdc + Idc Rs sidering either of the following two approaches: i) a switching
∆g1 = Iph − I0 exp −1
Vt approach, which is applied at the end of each iteration of
Vdc + Idc Rs the solution process, or ii) a complementarity constraints
− − Idc = 0 (17)
Rsh approach, where mismatch constraints of power limits are
directly introduced in the power flow formulation. In both
  
I0 Vdc + Idc Rs 1
∆g2 = Idc − Vdc exp + / cases, the dimension of the problem formulation remains
V V R
  t  t  sh unaltered during the solution process, and Vdc , Idc , ma and α
I0 Vdc + Idc Rs Rs
exp + + 1 = 0 (18) prevail as state variables of the PV plant along with additional
Vt Vt Rsh
state variables added by the selected limit checking approach.
∆g3 = ηPdc − Pkm = 0. (19)

On the other hand, the reactive power flow mismatch equation A. Switching approach
to be considered depends on the control mode at which the Our proposal in this approach is to extend the set of
VSC is operating, as described in the next subsection. equations representing the PV plant with mismatch equations
associated with the limit violation of active and reactive
C. VSC’s control modes powers. The number of mismatch equations is one (resp. two)
for the PQ (resp. PV) control mode of operation. Furthermore,
Since the grid-connected PV plant can provide ancillary
one (resp. two) additional state variable is (resp. state variables
services associated with the voltage magnitude control, the
are) added to avoid oversizing the total number of nonlinear
following control modes have been considered for the VSC.
equations associated with the power flow formulation. The
1) PQ control mode: In this control mode the VSC injects limit checking is performed at the end of each iteration once
an active power Pkm according to the network operation the maximum absolute value of the mismatch equations is
conditions and also provides reactive power support. This lower than 1 × 10−3 .
power support depends on the converter’s power factor (pf ) 1) Active power limits: In both control modes, the VSC is
and the injected active power Pkm : operating within limits if ηVdc Idc ≤ Pnom . Hence, (22) must

∆g4 = Qkm − Pkm tan cos−1 (pf ) = 0, (20) be added to the set of equations representing the steady-state
operation of the PV plant, and Pnomsv is an extra state variable
where pf is a fixed value selected within the range of of the problem. In addition, for both operating control modes
pfmin ≤ pflag ≤ pfmax or −pfmin ≤ pflead ≤ −pfmax. (18) is rewritten as (23), where ξs will have a non-null value
The steady-state operation of the PV plant for this control if there exists a limit violation. While the VSC is operating
mode is then obtained by solving the mismatch equations within limits, Pnomsv is a state variable, and ξs is maintained
(17)-(20) for the four state variables Vdc ,Idc ,ma and α. at its null initial value. If the limit violation takes place,

0885-8950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2018.2817585, IEEE
Transactions on Power Systems
IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. ?, NO. ?, OCTOBER 2017 5

Pnomsv is fixed at Pnom , and ξs replaces Pnomsv as a state TABLE I


variable. Note that in this case the values of Vdc and Idc must PV PLANT EQUATIONS UNDER A P Q OPERATION MODE
satisfy ηVdc Idc = Pnom , which implies that the VSC is not Approach State variables Equations
longer operating under MPP mode: WLC Idc , Vdc , ma , α (17), (18) (19), (20)
LCSA Idc , Vdc , ma , α (17), (23) (19), (20)
∆h1 = Pnomsv − ηVdc Idc = 0, (22) Pnomsv or ξs (22)
∆h2 = ∆g2 + ξs = 0. (23) LCCA Idc , Vdc , ma , α (17), (30) (19), (20)
ξc (31)
2) Reactive power limits: The amount of reactive power TABLE II
provided by the VSC depends on the values of Pkm , which PV PLANT EQUATIONS UNDER A P V OPERATION MODE
change during the iterative solution process, and the value of
Approach State variables Equations
pf . For the PQ control mode of operation, the value of pf
WLC Idc , Vdc , ma , α (17), (18) (19), (21)
is specified by the user, which must be selected within the Idc , Vdc , ma , α (17), (23) (19), (21)
ranges defined in Section III-C1; if this value is selected out of LCSA Pnomsv or ξs (22)
limits, however, the pf is automatically fixed at the offending Qvio or Vref (26)
limit. For the PV control mode, the limit value of reactive LCCA Idc , Vdc , ma , α (17), (30), (19), (32)
ξc , va , vb (31), (33), (34)
power that the VSC can either absorb or inject to satisfy
Qmin ≤ Qkm ≤ Qmax is given by (24) or (25), respectively. 2) Reactive power limits: When the VSC is operating in
Hence, the limits’ handling is performed by adding (26) to the PQ control mode, the reactive power limits are handled
the set equations representing the PV plant’s steady-state as explained for the switching approach. On the other hand,
operation. The voltage magnitude control is achieved while the set of equations (32)-(34) is used in the PV control
Qkm is within limits such that Qvio is considered as a state mode to assure that Qmin ≤ Qkm ≤ Qmax when a voltage
variable. Note that if there is no limit violation, Qvio = Qkm at magnitude control is performed based on the voltage droop
the end of the solution process. Otherwise, Qvio is fixed at the control strategy. Note that in this approach (21) is rewritten as
violated limit, and Vref becomes the new state variable such (32):
that the voltage magnitude at the POI is not longer controlled:
 ∆Φ3 = ∆g5 − va + vb = 0 (32)
Qmin = Pkm tan cos−1 (−pfmin ) (24)
q
2
 ∆Φ4 = (Qkm − Qmin ) + va2
Qmax = Pkm tan cos−1 (pfmin ) (25)  
− (Qkm − Qmin ) + va = 0 (33)
∆h3 = Qvio − Qkm = 0. (26) q
2
∆Φ5 = (Qmax − Qkm ) + vb2
B. Complementarity conditions approach  
− (Qmax − Qkm ) + vb = 0. (34)
In general, a complementarity condition is expressed as
ymin ≤ y ≤ ymax ⊥ CL (y) = 0 [19] and states an equilibrium
between the control law CL (y) of the VSC and the rating V. G ENERALIZED POWER FLOW FORMULATION
limits ymin and ymax of its variable y. This complementarity The explicit inclusion of the PV plant model in the power
condition is transformed into the set of nonlinear equality flow problem is accomplished by grouping together the set of
constraints given by (27)-(29), which is directly included in nodal active and reactive power mismatch equations, ∆P and
the power flow formulation. In this case, za and zb are a new ∆Q, and the equations describing the PV plant operation, ∆g,
pair of state variables of the problem that relaxes (27), which ∆h and ∆Φ, such that the generalized power flow problem is
avoids the resultant set of equations associated with the VSC formulated by the set of equations given by (35). In this case,
operation being oversized. Note that (27) is not considered in the PV plant equations are selected according to the VSC’s
the formulation if there is not a control law equation: control mode and the approach used for handling its power
CL (y) − za + zb = 0 (27) limits, as reported in Tables I and II. The abbreviations WLC,
q LCSA and LCCA denote without limit checking, limit check-
2  
(y − ymin ) + za2 − (y − ymin ) + za = 0 (28) ing by using the switching approach and limit checking by
q using the complementarity condition approach, respectively.
(ymax − y)2 + zb2 − (ymax − y) + zb = 0.
 
(29)
T
1) Active power limits: The set of nonlinear equations used f (x) = [∆P ∆Q ∆g ∆h ∆Φ] = 0. (35)
to satisfy ηVdc Idc ≤ Pnom is (30), which was rewritten from The use of augmented equations for the power flow problem
(18), and (31) for both control modes of operation. When the lends itself to a suitable formulation to solve the nodal voltages
PV generator oversteps its limit, the state variable ξc takes a of the network, xnt , and the PV plant state variables, xpvp ,
value different from zero, steering the VSC operation point simultaneously. In this context, the Newton-Raphson method
out of the MPP: is used for obtaining an approximate solution to the nonlinear
∆Φ1 = ∆g2 + ξc = 0 (30) problem f (x) = 0, where x = [xnt xpvp ]T , by solving for
q
2
∆xi in the linear problem J i ∆xi = −f (xi ), where J is
∆Φ2 = ξc2 + (Pnom − ηVdc Idc ) known as the Jacobian matrix. The method starts from an
− [ξc + (Pnom − ηVdc Idc )] = 0. (31) initial guess x0 and updates the solution for all state variables

0885-8950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2018.2817585, IEEE
Transactions on Power Systems
IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. ?, NO. ?, OCTOBER 2017 6

TABLE III A. IEEE-14 test system


PV GENERATOR PARAMETERS
1) Base case: In this case, the conventional generator
STC Conditions (Tn = 25◦ C, Gn = 1000W/m2 ) embedded at bus 6 is replaced by four parallel-connected
System Parameter
PV power plants, Bus6-U1 to Bus6-U4, with their PV gen-
Pmpp Impp Vmpp Npp Nss
erators composed of an array of multiple panels as reported
IEEE-14 test system 12MW 12.3kA 0.97kV 1515 24
in Table III, and the resistors values are Rsh = 10.354Ω
BCSPS 6.2MW 6.3kA 0.97kV 783 24
and Rs = 4.45mΩ. The parameters for each VSC are the
at each iteration i, i.e. xi+1 = xi + ∆xi , until same, with a nominal active power of Pnom = 12.50 MW,
a specified a droop control parameter of Kp = 2 × 10−3 , an efficiency
mismatch tolerance is satisfied: max f (xi+1 ) ≤ T OL.
of η = 98% and power factor limits of 0.95 ≤ pf ≤ 1.
The transformer reactance for all PV units is XT = 0.9
A. State variable initialization per-unit (p.u.). All power plants are operating at the PV
control mode to set the voltage magnitude at the POI node
The generalized power flow problem arrives at the solution at Vref = 1.08 p.u. Similarly, these units operate under the
with local quadratic convergence if proper initial conditions same temperature of 28◦ C but at different levels of irradiance
are given for the set of state variables. The flat initialization as shown in Table IV. The power flow study converged to
of nodal voltages is commonly used in conventional power the same solution in four and six iterations by using the
flow studies [7], while the amplitude modulation ratio ma is switching and complementarity approaches, respectively, as
initialized at 1, and the VSC’s phase angle α is set at 0◦ . shown in Fig. 3. Since no operating limit of the PV units
On the other hand, the initialization of Vdc and Idc is not a was violated, the switching approach was not activated, the
trivial task such that one way of defining their initial values switching approach was not activated. On the other hand,
consists of using the open circuit voltage Voc and short circuit the complementarity approach is always activated during the
current Isc , respectively, which are provided by manufacturer’s iterative process, whereby this approach always takes more
datasheets at STC. Although these values provide a good iterations to obtain convergence when no limit violations have
estimate, this can be improved by selecting initial values of Vdc occurred during the iterative process. Lastly, the final values
and Idc closer to the MPP. This is achieved by first expressing of the state variables associated with each PV unit are given
Idc as an explicit function of Vdc , or vice versa. This explicit in Table IV. Since each unit is operating under different levels
function can be derived from (1) by using the Lambert W of irradiance, the resulting Pdc = Vdc Idc achieved at the MPP
function [20], which results in is also different for each unit.
Rsh (Iph + I0 ) − Vdc Vt

Rs Rsh I0 Table IV also shows the final values of ηPdc , Qkm and
Idc = − W pf for each single PV plant unit. Clearly, unit Bus6-U2 is
Rs + Rsh Rs Vt (Rs + Rsh )
 !) operating closer to its STC: Pdc ∼= Pmpp . On the other hand,
Rsh Rs (Iph + I0 ) + Vdc Bus6-U4 operates with the lowest irradiance, which results in
× exp , (36)
Vt (Rs + Rsh ) the lowest ηPdc = 0.1090 p.u. Note also that all PV units
generate the same amount of reactive power to achieve the
where W {·} refers to the Lambert W function, which cannot specified control of voltage magnitude: Qkm = 0.0225 p.u.
be expressed in terms of elementary functions. Therefore, The reason for this performance is because the voltage droop
the series expansion employed to approximate W {·} is the controller has the same value of Kp for each PV unit. Lastly,
one given in [21]. Based on (36), the dyad of Idc and Vdc the power factor at which each unit is operating is computed
that provides the maximum value of Pdc can be obtained by from (20).
computing a set of values for Idc by varying Vdc from 0 to Voc . 2) Violation of VSCs’ limits: In order to assess the per-
The dyad {Idc , Vdc } associated with the maximum computed formance of the proposed approach when violations exist in
value of Pdc is then selected as an initial value for the state the VSCs’ operation limits, the case study previously reported
variables Idc and Vdc , respectively. was repeated but with the levels of irradiance reported in Table
IV, a temperature of 32◦ C and a control voltage magnitude at
Vref = 1.1 p.u. The same power flow solution was obtained by
VI. C ASE STUDIES
using any of the two proposed approaches for limit checking,
The performance of the proposed approach is evaluated with the state variable values of each PV plant reported in
by using the IEEE-14 bus test system and a real Mexican the last four columns of Table IV. From the analysis of these
71-bus power system. The proposed PV plant model and results, the non-null value of ξ indicates that units Bus6-U1
power flow algorithm were implemented in the MATLAB R
and Bus6-U2 violated their active power limits, i.e. they are no
platform, and the power flow studies were performed with longer operating under MPP, whereby their active powers are
a mismatch tolerance of 10−12 by considering either the fixed at Pnom . On the other hand, units Bus6-U3 and Bus6-U4
switching or complementarity approach. For this purpose, the operate under the MPP mode with values of ηPdc < Pnom .
330W Kyocera KU330-8BCA photovoltaic panel has been All PV plants have also violated their corresponding maxi-
selected with its datasheet given in [22]. The panel’s resistor mum reactive power limit such that all units operate at the PQ
values are Rsh = 652.51Ω and Rs = 280.84mΩ. control mode at a fixed pf of 0.95, with their reactive power

0885-8950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2018.2817585, IEEE
Transactions on Power Systems
IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. ?, NO. ?, OCTOBER 2017 7

TABLE IV
VALUES OF STATE VARIABLES FOR IEEE-14 TEST SYSTEM

PV plant units
Parameters No limits violation Limits violation Limits violation
and T = 28◦ C Constant η T = 32◦ C Constant η T = 32◦ C Jantsch’s model
state variables Unit 1 Unit 2 Unit 3 Unit 4 Unit 1 Unit 2 Unit 3 Unit 4 Unit 1 Unit 2 Unit 3 Unit 4
G (W/m2 ) 990 1000 950 930 1110 1120 970 980 1110 1120 970 980
Vdc (p.u.) 1.8758 1.8761 1.8746 1.8740 1.9930 2.0043 1.8712 1.8715 1.9930 2.0043 1.8712 1.8715
Idc (p.u.) 0.0632 0.0638 0.0606 0.0593 0.0640 0.0636 0.0618 0.0625 0.0640 0.0636 0.0618 0.0625
α (degree) -7.7628 -7.7575 -7.7841 -7.7948 -7.5157 -7.5157 -7.5659 -7.5607 -7.5154 -7.5154 -7.5655 -7.5604
ma 0.9417 0.9416 0.9423 0.9427 0.8985 0.8934 0.9567 0.9566 0.8985 0.8934 0.9567 0.9566
ξs = ξc 0 0 0 0 0.0979 0.1115 0 0 0.0979 0.1115 0 0
Pkm (p.u.) 0.1161 0.1173 0.1114 0.1090 0.1250 0.1250 0.1134 0.1146 0.1250 0.1250 0.1134 0.1146
Qkm (p.u.) 0.0225 0.0225 0.0225 0.0225 0.0411 0.0411 0.0373 0.0377 0.0411 0.0411 0.0373 0.0377
pf 0.9818 0.9822 0.9803 0.9794 0.9500 0.9500 0.9500 0.9500 0.9500 0.9500 0.9500 0.9500
η 0.9800 0.9800 0.9800 0.9800 0.9800 0.9800 0.9800 0.9800 0.9800 0.9800 0.9801 0.9801

0 Switching Case 1
10
Complementarity Case 1
Switching Case 2
-2
Complementarity Case 2
10

-4
10
Maximum mismatch in p.u.

-6
10

-8
10

-10
10

10
-12
Fig. 4. Collection grid topologies.

10
-14
these power flow results with respect to those obtained when
1 2 3 4 5 6 7 8 9
using a constant value of efficiency clearly shows that both
Iteration count
approaches give similar results. This is because of the output
power at the VSCs’ AC terminals.
Fig. 3. Convergence profile for both limit handling approaches. 4) Collection grid topologies: The capability of the pro-
posed approach to simulate different AC collection grid
generation fixed at the offending limit. This limit is calculated topologies is reported in this section. For this purpose, the
for each PV unit by either using (25) for the switching simulation reported in Section VI-A2 when violations of the
approach or the merit function (34) for the complementarity VSC’s operation limits take place has been newly repeated, but
approach. Since this limit’s value depends on the active power it considers the radial, ring and star collection grid topologies
supplied by the corresponding PV plant, units Bus6-U1 and [23]. In the former topology, the four PV units are connected
Bus6-U2 supply the same reactive power generation because to one feeder in one continuous string, as shown in Fig. 4 a).
they have also been fixed at their maximum active power The ring topology derives from the radial topology by adding
Pnom . In this case, the voltage magnitude’s final value at node another feeder on the other side of the string, as shown in
6 was 1.093 p.u. instead of the target value of Vref = 1.1 p.u. Fig. 4 b). Lastly, the star topology is shown in Fig. 4 c) where
Unlike the case study where no limit violations took place, each PV unit is connected to the main collector. In all these
the solution was obtained in seven iterations by using the topologies, each PV unit is operating in the P V control mode
complementarity approach, while two more iterations were to set the voltage magnitude at its corresponding medium volt-
required when the limit checking was carried out by the age bus at Vref = 1.1 p.u. All lines composing the topologies
switching approach. Furthermore, the switching approach was have the same impedance of Zl = 0.01335 + j0.04211 p.u.,
applied by considering truncated adjustments in the state vari- while the same station transformer connecting nodes MV and
ables during the solution of (35) [7]; otherwise, the iterative HV has been considered for all topologies with a reactance
process diverges. The convergence profile of the proposed of XST = 0.25202 p.u. The results obtained for the state
generalized power flow for both limit handling approaches variables of each generator are reported in Table V according
is shown in Fig. 3, where the discontinuity observed in the to the type of AC collection grid topology considered in the
convergence trajectory associated with the switching approach power flow study. The analysis of these results is similar to
is due to the violation of limits. the one described in Section VI-A2.
3) Comparison of efficiency representation: The last simu- 5) Distributed PV generation: In this study, five PV plants
lation where the VSCs violated some of their operating limits of different power capabilities have been embedded in five
has been repeated, but by considering the Jantsch model for different nodes of the system as reported in Table VI. The
representing the efficiency of converters [14]. The results are parameters and control mode of operation associated with each
shown in the last four columns of Table IV. A comparison of PV plant, as well as the power flow solution, are also reported

0885-8950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2018.2817585, IEEE
Transactions on Power Systems
IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. ?, NO. ?, OCTOBER 2017 8

TABLE V
VALUES OF STATE VARIABLES FOR IEEE-14 TEST SYSTEM WITH DIFFERENT AC COLLECTION GRID TOPOLOGIES

PV plant units
Parameters Limits violation T = 32◦ C Limits violation T = 32◦ C Limits violation T = 32◦ C
and Radial configuration Ring configuration Star configuration
state variables Unit 1 Unit 2 Unit 3 Unit 4 Unit 1 Unit 2 Unit 3 Unit 4 Unit 1 Unit 2 Unit 3 Unit 4
G (W/m2 ) 990 1000 950 930 1110 1120 970 980 1110 1120 970 980
Vdc (p.u.) 1.9930 2.0043 1.8712 1.8715 1.9930 2.0043 1.8712 1.8715 1.9930 2.0043 1.8712 1.8715
Idc (p.u.) 0.0640 0.0636 0.0618 0.0625 0.0640 0.0636 0.0618 0.0625 0.0640 0.0636 0.0618 0.0625
α (degree) 0.8819 0.6166 0.0807 -0.6085 -1.0914 -0.8657 -0.9302 -1.1526 -1.3886 -1.3886 -1.4138 -1.0935
ma 0.8999 0.8984 0.9589 0.9533 0.9024 0.8971 0.9614 0.9606 0.9031 0.8981 0.9622 0.9620
ξs = ξc 0.0979 0.1115 0 0 0.0979 0.1115 0 0 0.0979 0.1115 0 0
Pkm (p.u.) 0.1250 0.1250 0.1134 0.1146 0.1250 0.1250 0.1134 0.1146 0.1250 0.1250 0.1134 0.1146
Qkm (p.u.) -0.0210 0.0411 0.0373 0.0377 0.0411 0.0146 0.0205 0.0377 0.0288 0.0288 0.0321 0.0318
pf 0.9861 0.9500 0.9500 0.9500 0.9500 0.9932 0.9840 0.9500 0.9744 0.9744 0.9622 0.9637
η 0.9800 0.9800 0.9801 0.9801 0.9800 0.9800 0.9801 0.9801 0.9800 0.9800 0.9801 0.9801
POI, Vm (p.u.) 1.1 1.0994 1.0957 1.0894 1.0980 1.1 1.1 1.0978 1.1 1.1 1.1 1.1

TABLE VI TABLE VII


PARAMETERS AND STATE VARIABLES FOR PV P LANTS W EATHER CONDITIONS OF PV PLANTS

Parameters PV plant units PV plants at Bus 66 PV plants at Bus 53 PV plants at Bus 50


and Bus 5 Bus 6 Bus 7 Bus 11 Bus 14 G T G T G T
state variables Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 B66 W/m2 ◦C B53 W/m2 ◦C B50 W/m2 ◦C

T (◦ C) 21◦ 30◦ 35◦ 24◦ 26◦ U1 920 34 U1 960 36 U1 975 36


G (W/m2 ) 600 980 1200 700 800 U2 935 34 U2 920 34 U2 980 36
Pnom (MW) 15.5 48.5 7.5 30.5 8.5 U3 970 35 U3 970 36 U3 1140 38
XT (p.u.) 0.3871 0.1237 0.800 0.1967 0.7059 U4 1130 37 U4 1100 38 U4 970 35
Rs (mΩ) 3.55 1.11 7.62 1.78 6.66 U5 980 35 U5 1090 38 U5 1150 38
Rsh (Ω) 8.22 2.58 17.74 4.14 15.53
Control mode PQ PV PQ PV PQ
Vdc (p.u.) 1.8609 1.8735 2.0411 1.8661 1.8703 the nominal power is now Pnom = 6.50 MW. Furthermore,
Idc (p.u.) 0.0478 0.2500 0.0375 0.1115 0.0340 the set of Kyocera photovoltaic panels composing the PV
α (degree) -2.8651 -1.6227 -3.7106 -2.9863 -4.9238 generator, as well as the generator’s characteristics, are given
ma 0.9134 0.9415 0.8538 0.9561 0.9277
in Table III, where the following values of resistances have
ξs = ξc 0 0 0.0975 0 0
Pkm (p.u.) 0.0872 0.4591 0.0750 0.2040 0.0624 been adopted: Rsh = 20.033Ω and Rs = 8.61mΩ. Table VII
Qkm (p.u.) 0.0177 0.1270 0 0.0671 0.0182 shows the weather conditions for each PV plant. Based on
Vm (p.u.) 1.0349 1.0800 1.0686 1.0811 1.0513 this information, two power flow studies have been performed,
pf 0.9800 0.9996 1.0000 0.9500 0.9600 with and without the handling of limits, by considering that
η 0.9801 0.9801 0.9800 0.9802 0.9802
the set of PV plants connected at node B66 are operating
in this Table. This solution indicates that units Bus7-U3 and in the PQ control mode. Similarly, the rest of the renewable
Bus11-U4 violated their active power and reactive power generators are considered to be operating in the PV control
limits, respectively. On the other hand, the rest of PV units mode to control the voltage magnitude at nodes B50 and B53
remain operating within their power limits. at 1.02 p.u. and 1.04 p.u., respectively. Regarding the set of
generators embedded at node B66, units B66-U4 and B66-U5
operate at unity power factor, while units B66-U1, B66-U2
B. 71-bus electric power system and B66-U3 operate at power factors of 0.95, 0.98 and 0.96,
This electric power system shown in Fig. 7, referred to respectively.
as BCSPS, is located on the peninsula of Baja California When no power limits were considered in the power flow
Sur, México, and consists of 71 buses, 44 transmission lines, study, the specified control actions were achieved. On the other
44 two-winding and 3 three-winding transformers [24]. The hand, when limits were checked only the voltage magnitude at
generation portfolio is composed of steam plants, gas turbines node B53 was controlled. In this case, the five units embedded
and internal combustion generators. In 2016, solar energy at this node were able to perform the control action, but
represented 3.1% of the overall region capacity with 32 MW, units B53-U4 and B53-U5 violated their corresponding active
but it is expected that this capacity will increase to 300 MW power limit Pnom . In contrast, all generators embedded at node
by 2031 [25]. This exponential growth is basically defined B50 violated their maximum reactive power limit, and units
by its daily solar irradiance of 8.5 kWh/m2 , which results in B50-U3 and B50-U5 also violated their active power limits.
several requests for integrating solar PV plants from private Lastly, unit B66-U4 operating in PQ control mode has also
utilities. Based on the mentioned above, 15 PV plants have violated its active power limit.
been embedded in the system at 115 kV nodes B50, B53 Figure 5 (a) shows the value of ma for each VSC unit for
and B66, considering five parallel-connected power plants at both case studies. Note that the value of ma became lower
each node, with the parameters of each single VSC similar when the active power limit was violated; this is because
to those reported in Section VI-A. The difference is that the PV plant is no longer operating in the MPP. In addition,

0885-8950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2018.2817585, IEEE
Transactions on Power Systems
IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. ?, NO. ?, OCTOBER 2017 9

B49 B53 B1 B55 B30


B38
(a) ma 34.5 kV
115 kV
L21
115 kV 115 kV
L2
115 kV 13.8 kV

1 C15
L1
T29
C9

Considering power limits SH11


T37 L22
Without power limits L3
B33
13.8 kV
0.95 C17
B58 C11
B52 B40 T40 T31
B7 L29 L30 115 kV
115 kV 34.5 kV
13.8 kV
0.9 D3
L27
B19
L28
T3 13.8 kV
B8 B36
13.8 kV 13.8 kV C20 TG7
0.85 D4 T45 T15 B61
C14 B13
T4 115 kV
B9 T35 13.8 kV
B37 B43
13.8 kV 13.8 kV 34.5 kV T46 B65 TE4
0.8 115 kV SH7
T9
D5 C8 B14
B6 1

B6 2

B6 3

B6 4

B5 5

B5 1

B5 2

B5 3

B5 4

B5 5

B5 1

B5 2

B5 3

B5 4

5
T5 T36 L40
U

U
13.8 kV
6-

6-

6-

6-

6-

3-

3-

3-

3-

3-

0-

0-

0-

0-

0-
B67 L39
TE5
B6

115 kV B29
B2 T10
13.8 kV
(b) pf 115 kV L37
B60
1 C22 L6
L4 T27 T28
115 kV
B10
L7
C1 B54 13.8 kV
B66 B3 115 kV
B44 TE1
115 kV 115 kV L5
0.95 115 kV
T6
B20
L11 L31 4.2 kV
L12

0.9 L34
B22 L13
B57 T16
13.8 kV 115 kV
T18
B11
B32 13.8 kV
C3 L35
13.8 kV
0.85 Considering power limits T19
TE2
B56 SH9 T7
Without power limits 115 kV SH1
C10|
T30
C21 B21
4.2 kV
T20
0.8
B6 1

B6 2

B6 3

B6 4

B5 5

B5 1

B5 2

B5 3

B5 4

B5 5

B5 1

B5 2

B5 3

B5 4

5
T17
U

U
B12
6-

6-

6-

6-

6-

3-

3-

3-

3-

3-

0-

0-

0-

0-

0-
L32 13.8 kV
B6

L33 TE3
B71
T49 B69 B5 T8
230 kV
230 kV 13.8 kV
B64 L41
L25 L24 B51 B39
B15 D1
115 kV 115 kV 34.5 kV
Fig. 5. ma and pf for each unit. TG1
13.8 kV
B31
13.8 kV
L42
T1
C2

T38 C16
T11 B6
B16
13.8 kV
13.8 kV
(a) η *Pdc TG2 L43 L44 D2 T39

0.075 T2 L26
B63 B42
TG3 T12 SH8 B70
Considering power limits 230 kV
115 kV 34.5 kV
B17 B27
0.07 Without power limits 13.8 kV
T47
13.8 kV
T48
T43 C19
TG4 B28
T13 13.8 kV
p.u.

B18 T44
0.065 13.8 kV SH6 L38
B50 B62 B35
TG5 115 kV 115 kV 13.8 kV

C13
0.06 TG6
T14 L17
L16 T33
L9 L23
B68 B4
L18 SH10
115 kV 115 kV
0.055 C23 L10
L14 L15 L19 L20 L36 T34
B41
34.5 kV
B45 B47 B48 B59
1

5
U

115 kV 115 kV 115 kV 115 kV


6-

6-

6-

6-

6-

3-

3-

3-

3-

3-

0-

0-

0-

0-

0-

B46 C18
L8
B6

B6

B6

B6

B6

B5

B5

B5

B5

B5

B5

B5

B5

B5

B5

B24 115 kV T41


13.8 kV
T21 T22 T25 T26 T32 SH12
(b) Qkm C5 SH13 SH15 SH16
T42
0.04 T23 B25 B26 B34
B23 13.8 kV 13.8 kV 13.8 kV
Considering power limits SH3 13.8 kV

0.03 Without power limits T24 SH14


C4 C6 C7 C12

SH2 SH4 SH5


p.u.

0.02

0.01
Fig. 7. Baja California Sur power system.

0
TABLE VIII
R ESULTS FOR THE 5- BUS TEST SYSTEM
1

5
U

U
6-

6-

6-

6-

6-

3-

3-

3-

3-

3-

0-

0-

0-

0-

0-
B6

B6

B6

B6

B6

B5

B5

B5

B5

B5

B5

B5

B5

B5

B5

α ma Vk pf Pkm Qkm
Model [9]
Fig. 6. Active and reactive power generation by PV units. 2.882 0.8426 1.032 0.9942 0.48 0.052
Proposed approach
there was an increment in the voltage value at the DC side of 3.1223 0.8400 1.0240 0.9942 0.48 0.0519
the VSC. For the units that only violated the reactive power
limit (B50-U1,U2 and U4), ma had a slight change. When respect to the models where PV solar parks are modeled by
power limits were not considered, the units B50-U1 to B50-U5 equivalent generators. In accordance to these references, it
worked at a lower pf than allowed for the VSC, as shown is considered that the solar park is composed of one single
in Fig. 5 (b). On the other hand, when these limits were PV plant. Table VIII reports the values of state variables
considered the pf was fixed at the maximum value allowed associated with the PV plant embedded at node 3 of the
for the VSC, and a slight change in the pf of units B53-U1 5-bus test system. A comparison of these results clearly shows
to B53-U5 is accomplished. that the solution obtained by our proposal is similar to the
Figure 6 (a) shows the AC power ηPdc for each unit, where one reported in [9]. A similar conclusion is reached after
it is observed that B66-U4, B53-U4, B53-U5, B50-U3 and comparing the results obtained by our proposed approach with
B50-U5 were fixed at Pnom = 0.065 p.u. Similarly, Fig. 6 (b) respect to those reported in [10], which are shown in Table
shows the reactive power of all PV units involved in the study. IX. Note that the values of the modulation index reported in
When the power limits were not considered, units B50-U1 to Table IV of [10] correspond to the voltage magnitudes at the
B50-U5 were dispatched at the same value, and the voltage AC inverter’s terminal. This was verified by using the set of
magnitude was controlled at the target value. On the contrary, equations (10)-(15) given in this reference.
when limits were checked, the Qkm produced by these units
was imposed according to the generation of active power at a VII. C ONCLUSIONS
fixed pf . In this case, the uncontrolled voltage at bus 50 was
A detailed grid-connected PV power plant model that
VB50 = 1.0132 p.u.
considers both operation and control mode constraints has
been proposed in this paper for power flow analysis. In
C. Comparison to other proposals contrast to the existing methods, the proposed model is directly
The case studies reported in references [9] and [10] have incorporated in a Newton-based power flow program where the
been reproduced in this section to compare our proposal with state variables of the PV plant are combined with the nodal

0885-8950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2018.2817585, IEEE
Transactions on Power Systems
IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. ?, NO. ?, OCTOBER 2017 10

TABLE IX [14] L. Monteiro, I. Finelli, A. Quinan, W. N. Macêdo, P. Torres, J. T. Pinho,


R ESULTS FOR THE 12- BUS TEST SYSTEM E. Nohme, B. Marciano, and S. R. Silva, “Implementation and validation
of energy conversion efficiency inverter models for small pv systems in
Vm ma Vk pf Pmk Qmk the north of brazil,” in Renewable Energy in the Service of Mankind Vol
Model [10] II. Springer, 2016, pp. 93–102.
Unit 1 0.9071 0.9163 0.8997 0.9 0.5345 0.2588 [15] Comisión Reguladora de Energı́a. (2006, April) Criteria of efficiency,
Unit 2 0.9074 0.9166 0.9000 0.9 0.5346 0.2589 quality, reliability, continuity, security and sustainability of the
Unit 3 0.9072 0.9164 0.8998 0.9 0.5345 0.2588 national electrical system: grid code (in spanish). [Online]. Available:
Proposed approach http://www.cenace.gob.mx/Docs/MarcoRegulatorio/AcuerdosCRE/
Unit 1 0.9071 0.9107 0.8997 0.9 0.5345 0.2583 Resoluci\’on%20151%202016%20C\’odigo%20de%20Red%20DOF%
Unit 2 0.9074 0.9110 0.9000 0.9 0.5345 0.2583 202016%2004%2008.pdf
Unit 3 0.9072 0.9108 0.8998 0.9 0.5345 0.2583 [16] W. REMTF, “Wecc power flow modeling guide for pv systems,” Tech.
Rep., November 2010.
voltages of the entire network for a unified iterative solution. [17] K. De Brabandere, B. Bolsens, J. Van den Keybus, A. Woyte, J. Driesen,
and R. Belmans, “A voltage and frequency droop control method for
The complementarity condition approach was used to directly parallel inverters,” IEEE Transactions on Power Electronics, vol. 22,
introduce the set of PV plant constraints in the formulation no. 4, pp. 1107–1115, July 2007.
of the power flow problem, which is rather attractive be- [18] A. Elrayyah, Y. Sozer, and M. Elbuluk, “Modeling and control design
of microgrid-connected pv-based sources,” IEEE Journal of Emerging
cause the check of limits is simultaneously and automatically and Selected Topics in Power Electronics, vol. 2, no. 4, pp. 907–919,
performed for all variables during the iterative power flow Dec 2014.
solution process. A switching approach was also proposed [19] W. Rosehart, C. Roman, and A. Schellenberg, “Optimal power flow with
complementarity constraints,” IEEE Transactions on Power Systems,
for checking limits, where the dimension of the power flow vol. 20, no. 2, pp. 813–822, 2005.
Jacobian matrix remains unaltered during the iterative solution [20] L. H. I. Lim, Z. Ye, J. Ye, D. Yang, and H. Du, “A linear identification
process. Since reliability towards the convergence is of the of diode models from single i–v characteristics of pv panels,” IEEE
Transactions on Industrial Electronics, vol. 62, no. 7, pp. 4181–4193,
utmost concern when using the Newton method, guidelines for 2015.
the suitable initialization of the PV plant state variables have [21] E. Batzelis, I. Routsolias, and S. Papathanassiou, “An explicit pv string
been provided. Lastly, the effectiveness of the proposed model model based on the lambert w function and simplified mpp expressions
for operation under partial shading,” IEEE Transactions on Sustainable
and solution method has been fully validated by numerical Energy, vol. 5, no. 1, pp. 301–312, Jan 2014.
simulations. [22] Kyocera KU330-8BCA High efficiency multicrystal photovoltaic
module. [Online]. Available: www.kyocerasolar.com/assets/001/5667.
R EFERENCES pdf
[23] A. Cabrera-Tobar, E. Bullich-Massagué, M. Aragüés-Peñalba, and
[1] W. Xiao, M. Lind, W. Dunford, and A. Capel, “Real-time identification O. Gomis-Bellmunt, “Topologies for large scale photovoltaic power
of optimal operating points in photovoltaic power systems,” IEEE plants,” Renewable and Sustainable Energy Reviews, vol. 59, pp. 309–
Transactions on Industrial Electronics, vol. 53, no. 4, pp. 1017–1026, 319, 2016.
June 2006. [24] A. M. Romero, “Estabilidad de voltaje en redes con generación eólica,”
[2] A. Chatterjee, A. Keyhani, and D. Kapoor, “Identification of photovoltaic Master’s thesis, Universidad Nacional Autónoma de México, November
source models,” IEEE Transactions on Energy Conversion, vol. 26, no. 3, 2014. [Online]. Available: http://www.ptolomeo.unam.mx:8080/xmlui/
pp. 883–889, Sept 2011. bitstream/handle/132.248.52.100/7095/Tesis.pdf?sequence=1
[3] M. Villalva, J. Gazoli, and E. Filho, “Comprehensive approach to [25] PRODESEN 2017, “Development Program for the National
modeling and simulation of photovoltaic arrays,” IEEE Transactions on Electrical System 2017-2031,” Secretarı́a de Energı́a, Tech.
Power Electronics, vol. 24, no. 5, pp. 1198–1208, May 2009. Rep., 2017. [Online]. Available: http://base.energia.gob.mx/prodesen/
[4] Y. Mahmoud, W. Xiao, and H. Zeineldin, “A simple approach to PRODESEN2017/PRODESEN-2017-2031.pdf
modeling and simulation of photovoltaic modules,” IEEE Transactions
on Sustainable Energy, vol. 3, no. 1, pp. 185–186, Jan 2012. Rafael Tapia Juárez received his B.Sc. in Electronic Engineering from
[5] W. D. Soto, S. Klein, and W. Beckman, “Improvement and validation Instituto Tecnológico de Morelia and his M.Sc. degree from Universidad
of a model for photovoltaic array performance,” Solar Energy, vol. 80, Michoacana de San Nicolás de Hidalgo, México (UMSNH), in 2010 and
no. 1, pp. 78 – 88, 2006. 2013 respectively. He is currently pursuing the Ph.D. degree at the UMSNH
[6] Y. Mahmoud and E. El-Saadany, “A photovoltaic model with re- in the area grid-connected photovoltaic systems.
duced computational time,” IEEE Transactions on Industrial Electronics,
vol. 62, no. 6, pp. 3534–3544, June 2015. Claudio Rubén Fuerte-Esquivel (StM’89, M’94, SM’04) received the Ph.D.
[7] E. Acha, C. R. Fuerte-Esquivel, H. Ambriz-Perez, and C. Angeles- degree from the University of Glasgow, Glasgow, Scotland, U.K., in 1997.
Camacho, FACTS: Modelling and Simulation in Power Networks. John Currently, he is a full-time professor at the Universidad Michoacana de San
Wiley & Sons, 2004. Nicolás de Hidalgo (UMSNH), Morelia, México. Dr. Fuerte-Esquivel is a
[8] W. Yi-Bo, W. Chun-Sheng, L. Hua, and X. Hong-Hua, “Steady-state regular member of the Mexican Academy of Science.
model and power flow analysis of grid-connected photovoltaic power
system,” in 2008 IEEE International Conference on Industrial Technol- Elisa Espinosa Juárez (SM’2017) received the B.E. degree in Electrical
ogy, April 2008, pp. 1–6. Engineering from the Universidad Michoacana de San Nicolás de Hidalgo
[9] S. Ahmed and M. Mohsin, “Analytical determination of the control (UMSNH), México, in 1986, the M.Sc. degree from the Instituto Politécnico
parameters for a large photovoltaic generator embedded in a grid Nacional, México city, México, in 2001, and the Ph.D. degree from the
system,” IEEE Transactions on Sustainable Energy, vol. 2, no. 2, pp. Universidad Politécnica de Madrid (UPM), Spain, in 2006. Currently, she
122–130, April 2011. is a full-time professor with the UMSNH, Morelia, México. Her research
[10] M. Z. Kamh and R. Iravani, “Steady-state model and power-flow analysis interests include power systems, smart grids and power quality.
of single-phase electronically coupled distributed energy resources,”
IEEE Transactions on Power Delivery, vol. 27, no. 1, pp. 131–139, Uriel Sandoval received his B.Sc. (Hons) degree in Electrical Engineering
Jan 2012. in 2013 and his M.Sc. degree in 2015, both from Universidad Michoacana
[11] A. Fischer, “A special newton-type optimization method,” Optimization, de San Nicolás de Hidalgo, México. Since 2015 he has collaborated with
vol. 24, no. 3-4, pp. 269–284, 1992. Manitoba Hydro International as an independent contractor by programming
[12] F. Milano, Power system modelling and scripting. Springer Science & and solving power systems economic problems. In 2015, he joined CENACE
Business Media, 2010. (National Center for Energy Control in México) and currently serves as the
[13] G. Rampinelli, A. Krenzinger, and F. C. Romero, “Mathematical models head of the Power System Modeling Department.
for efficiency of inverters used in grid connected photovoltaic systems,”
Renewable and Sustainable Energy Reviews, vol. 34, pp. 578–587, 2014.

0885-8950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.

Das könnte Ihnen auch gefallen