Sie sind auf Seite 1von 2

OTDR report

Job info
Job ID : Reason :
Contractor : NOVKER Operator A :
Customer : Operator B :
Test date : 03-Aug-19 (12:25:48 PM GMT+7:00) File : JB283 to User Unilever-1550.sor

Cable info
Fiber ID : Cable ID :
Location A : Location B :
Cable mfr. : Type :
Subset ID : Color ID :

Link measurements
Span loss : 0.180 dB Avg. splice loss : 0.118 dB
Span length : 0.2597 km Max. splice loss : 0.118 dB
Average loss : 0.694 dB/km Span ORL : <36.82 dB

OTDR trace

dB

25.00

20.00

15.00

23
10.00

5.00

0.00
200 400 600 800 1000 m

Signature : _________________________ Date : 11-Oct-19


EXFO E. O. Engineering Inc. Page 1 / 2
OTDR report
Events table
No. Loc. Event type Loss Refl. Att. Cumul.
(km) (dB) (dB) (dB/km) (dB)

1 0.0000 Launch Level 0.000 0.000


Fiber Section (0.2474 km) 0.060 0.241 0.060
2 0.2474 Non-Reflective Fault 0.118 0.178
Fiber Section (0.0123 km) 0.003 0.206 0.180
3 0.2597 Reflective Fault 0.000 64.9 0.180

Marker info
A : 0.0000 km, 8.987 dB B : 0.0000 km, 8.987 dB
a : 0.0000 km, 8.987 dB b : 0.0000 km, 8.987 dB
A to B distance : 0.0000 km, 0.000 dB A to B ORL : *****
3-pt. reflectance : ***** A to B LSA att. : -0.000 dB/km
4-pt. Ev. loss : 0.000 dB

Test and cable setup


Wavelength : 1550 nm (SM-9µm) Acq. time : 10 s
Filename : JB283 to User Unilever-1550.sor Pulse width : 50 ns
Hardware : Helix factor : 0.00 %
Serial number : Splice loss threshold : 0.100 dB
Software : N/A Reflectance threshold : -40.0 dB
Range : 1.0456 km End-of-fiber threshold : 10.000 dB
IOR : 1.468000
RBS : -80.00

Signature : _________________________ Date : 11-Oct-19


EXFO E. O. Engineering Inc. Page 2 / 2