STANDBY
600 ekW 750 kVA
60 Hz 1800 rpm 480 Volts
Caterpillar is leading the power generation
marketplace with Power Solutions engineered
to deliver unmatched flexibility, expandability,
reliability, and cost-effectiveness.
Image shown may not
reflect actual package.
FEATURES
FUEL/EMISSIONS STRATEGY CAT ® C18 ATAAC DIESEL ENGINE
• Low Fuel consumption • Utilizes ACERT™ Technology
• Reliable, rugged, durable design
DESIGN CRITERIA • Field-proven in thousands of applications
• The generator set accepts 100% rated load in one worldwide
step per NFPA 110 and meets ISO 8528-5 transient • Four-stroke-cycle diesel engine combines
response. consistent performance and excellent fuel
economy with minimum weight
UL 2200 / CSA - Optional
• Electronic controlled governor
• UL 2200 listed packages
• CSA Certified CAT GENERATOR
Certain restrictions may apply. • Matched to the performance and output
Consult with your Cat® Dealer. characteristics of Cat engines
• Load adjustment module provides engine relief
FULL RANGE OF ATTACHMENTS
upon load impact and improves load acceptance
• Wide range of bolt-on system expansion
and recovery time
attachments, factory designed and tested
• UL 1446 Recognized Class H insulation
• Flexible packaging options for easy and cost
effective installation CAT EMCP 4 CONTROL PANELS
• Simple user friendly interface and navigation
SINGLE-SOURCE SUPPLIER
• Scalable system to meet a wide range of
• Fully prototype tested with certified torsional
customer needs
vibration analysis available
• Integrated Control System and Communications
WORLDWIDE PRODUCT SUPPORT Gateway
• Cat dealers provide extensive post sale support
including maintenance and repair agreements
• Cat dealers have over 1,800 dealer branch stores
operating in 200 countries
• The Cat® S•O•SSM program cost effectively detects
internal engine component condition, even the
presence of unwanted fluids and combustion
by-products
STANDBY 600 ekW 750 kVA
60 Hz 1800 rpm 480 Volts
Fuel • Integral single wall fuel tank base [ ] Manual transfer pump
• Primary fuel filter with integral water separator [ ] Fuel level switch
• Secondary fuel filters
• Fuel priming pump
• Engine fuel transfer pump
• Fuel cooler integral with cooling system*
• Fexible fuel lines
*Not inlcuded with packages without radiators
Generator • Class H insulation [ ] Oversize generators
• Internal excited (IE) [ ] Permanent magnet excitation(PMG)
• Class H temperature rise [ ] Cat digital voltage regulator (CDVR) with kVAR/PF
• R450 voltage regulator with single phase sensing and control
load adjustment [ ] Anti-condensation space heaters
• IP23 Protection [ ] Coastal Insulation Protection (CIP)
[ ] Reactive droop
[ ] Three phase sensing
Power Termination • Power Center houses EMCP controller and [ ] C.B. Shunt trips
power/control terminations (rear mounted) [ ] C.B. Auxiliary contacts
• Circit breaker, IEC compliant, 3-4 pole (100% rated)
• Segregated low voltage wiring termination panel
• IP22 protection
• Bottom cable entry
Governor • ADEM™ A4
SPECIFICATIONS
TECHNICAL DATA
Meets or Exceeds International Specifications: AS1359, Ratings are based on SAE J1349 standard conditions.
CSA, IEC60034-1, ISO3046, ISO8528, NEMA MG 1-22, These ratings also apply at ISO3046 standard conditions.
NEMA MG 1-33, UL508A, 72/23/EEC, 98/37/EC, Fuel rates are based on fuel oil of 35º API [16º C (60º F)]
2004/108/EC gravity having an LHV of 42 780 kJ/kg (18,390 Btu/lb)
Standby - Output available with varying load for the when used at 29º C (85º F) and weighing 838.9 g/liter
duration of the interruption of the normal source power. (7.001 lbs/U.S. gal.). Additional ratings may be available
Average power output is 70% of the standby power for specific customer requirements, contact your Cat
rating. Typical operation is 200 hours per year, with representative for details. For information regarding Low
maximum expected usage of 500 hours per year. Sulfur fuel and Biodiesel capability, please consult your
Standby power in accordance with ISO8528. Fuel stop Cat dealer.
power in accordance with ISO3046. Standby ambients
shown indicate ambient temperature at 100% load which
results in a coolant top tank temperature just below the
shutdown temperature.
DIMENSIONS
Package Dimensions
NOTE: For reference only - do not use for
Length 3910.0 mm 153.94 in installation design. Please contact
Width 1461.0 mm 57.52 in your local dealer for exact weight
and dimensions. (General
Height 2155.7 mm 84.87 in Dimension Drawing #3930335).