Group 3: BSEE -5B – e2 September 27, 2019

Gallarion, Christian
Lumantas, Jericho
Manosa, Matt Anthony
Opiso, Leslie Joy

1) It is a conductor installed on the supply side of a service or within a service equipment enclosure.
 Bonding Jumper, Supply-side
2-3) Give two (2) examples if the use of multiple grounding connection results in objectionable current.
 Discontinue one or more but not all of such grounding connection.
 Change the location of grounding connections.
 Interrupt the continuity of the conductor or conductive path causing the objectionable current
 Take other suitable remedial and approve action.
4-6) Give at least (3) permitted methods in Connection of Grounding and Bonding Equipment.
 Listed pressure connectors
 Terminal bars
 Pressure connectors listed as grounding and bonding equipment
 Exothermic welding process
 Connections that are part of a listed assembly, etc.
7-10) what are the non – conductive coatings?
 Paint
 Lacquer
 Enamel
11-12) Insulated equipment grounding conductors that shall have continuous outer finish that is either
___________ or _____________ color.
 green or
 green with one or more yellow stripes
13) It is where the dc system source is located on the premises, and a grounding connection shall be made.
 On – Premises Source
14-15) The equipment grounding conductor for secondary circuits of instrument transformers and for instrument
cases shall not be smaller than ____________ copper or____________ aluminum.
 3.5 mm2 coper or
 5.5 mm2 aluminum
16) what system that shall be permitted to be either single point grounded or multi-grounded?
 Solidly grounded neutral systems
17) A substation that the grounding system shall be in accordance with Grounding Electrode System and
Grounding Electrode Conductor.
 Alternating – current substation
18) Rating of silicon carbid-type surge arrester shall be not less than ____ percent of rating.
 125%
19) Conductor between “Surge-Arrester. and Line” and “Surge-Arrester. and grounding” connection shall not be
smaller than ___ mm squared copper or aluminum.
 14mm copper or aluminum
20) Size of Equipment Grounding Conductors Table 2.50.6.13 can be found in what page.
 Page 124