Concrete cover is assumed to be the rst measure considered to prevent in uences of aggress
the reinforcement steel bars. That is why utmost cautions are needed during concrete cover th
its construction.
Commonly, the thickness of concrete cover is speci ed based on the type of the reinforced con
the environment in which the structure is constructed.
In this article, concrete cover speci cations based on various most commonly used codes will b
https://theconstructor.org/concrete/concrete-cover-specifications/20758/?utm_source=pushengage&utm_medium=push_notification&utm_campaign=… 1/7
1/9/2019 Concrete Cover Specifications for Reinforcement in Different Codes
The speci cation of di erent codes regarding concrete cover is commonly dependent on natur
method of construction, environmental factors around the structure, and quality of concrete u
construction.
Determination of Concrete cover thickness according to the speci cations of the following code
ACI code
European Code
British standard
The ACI code speci es certain condition in which this minimum cover thickness would not be a
it needs to be increased. These conditions include corrosive environment, re protection, and f
For example, for reinforced concrete member subjected to sea water, the ACI code speci es th
concrete cover should be at least 50mm.
It is desired to set minimum thickness of concrete cover as 65mm to account for possible cons
hence make sure that 50mm cover thickness is achieved.
The code allows the use of cover thickness smaller than those provided in Table-1 for precast c
https://theconstructor.org/concrete/concrete-cover-specifications/20758/?utm_source=pushengage&utm_medium=push_notification&utm_campaign=… 2/7
1/9/2019 Concrete Cover Specifications for Reinforcement in Different Codes
Beams, columns
This can be clearly observed in Table-2 that provided minimum concrete cover thickness along
parameters based on the weather condition.
https://theconstructor.org/concrete/concrete-cover-specifications/20758/?utm_source=pushengage&utm_medium=push_notification&utm_campaign=… 3/7
1/9/2019 Concrete Cover Specifications for Reinforcement in Different Codes
Humid
Seawater
Aggressive chemicals
It is proven by number of researchers like Browne et. el. and Van Daver that concrete cover in
structures are less than that speci ed in design.
For example, Browne et. el. reported that average cover thickness of observed structures was 1
25mm that speci ed in the design.
That is why European code states that minimum cover thickness should be increased by permi
deviation which ranges from 5-10mm for cast in situ concrete and 0-5mm for precast concrete
https://theconstructor.org/concrete/concrete-cover-specifications/20758/?utm_source=pushengage&utm_medium=push_notification&utm_campaign=… 4/7
1/9/2019 Concrete Cover Specifications for Reinforcement in Different Codes
According to the British standard thickness of concrete cover is based on weather condition in
structure is constructed. In addition to the concrete strength, and quality of concrete that is de
cement content and water to cement ratio.
Table-3 provides minimum concrete cover thickness determined according to the British stand
30 35 40 45
25 20 20 20
Moderate1 25 20 20 20
Moderate2 — 35 30 25
Hard3 — — 40 30
Very hard4 — — 50 40
Maximum condition5 — — — 60
2 concrete surfaces protected from rain or freezing and concrete under water or concrete adjac
soil
https://theconstructor.org/concrete/concrete-cover-specifications/20758/?utm_source=pushengage&utm_medium=push_notification&utm_campaign=… 5/7
1/9/2019 Concrete Cover Specifications for Reinforcement in Different Codes
5concrete surface exposed to abrasion such as seawater containing solid particles, or moving w
machines or cars
There are three major regions of severe weather condition to which reinforced concrete struct
exposed.
These severe weather conditions include air, splash zone, and immersed in water. The most da
is the splash zone since the structure subjected to seawater and air combination.
ACI 357 provides recommendation regarding cover thickness in severe weather conditions bas
strength, location of structure, and maximum water to cement ratio, see Table 4.
Cover thickn
Location Maximum w/c ratio Minimum concrete strength at 28 days
Reinforced s
Air 0.4 35 50
https://theconstructor.org/concrete/concrete-cover-specifications/20758/?utm_source=pushengage&utm_medium=push_notification&utm_campaign=… 6/7
1/9/2019 Concrete Cover Specifications for Reinforcement in Different Codes
Apart from ACI 357, British standard provides recommendation about the selection of concrete
for private structures.
The determination of concrete cover thickness takes several parameters into consideration for
mixing for each concrete quality, life expectancy of the structure, and chloride di usion factor
https://theconstructor.org/concrete/concrete-cover-specifications/20758/?utm_source=pushengage&utm_medium=push_notification&utm_campaign=… 7/7