Pathfinder
Air-Cooled Single-Screw Chiller/Heat Pump
Super-high-efficiency series Model: UAY105-UAY348
Cooling capacity: 393 kW–1334 kW
Heating capacity: 400 kW–1312 kW
Overview
Air-cooled water chiller/hot water units are the central air conditioning units with air as the cold (hot) source, and water as
the heat transfer medium. The units need no additional equipment room, cooling tower, cooling pump, or cooling pipe and
can be mounted on the building roof and outdoors. The heat pump units can provide heat as a hot water boiler. This series
of units are applicable to various environments, such as hospitals, hotels, factories, and office buildings.
As the first designer and manufacturer of large air-cooled heat pump units, DAIKIN has been committed to technical
improvement and innovation and leads the development of the air-cooled heat pump technology. For the consideration of
environment protection and energy saving, DAIKIN applies the advanced technology to the latest ultra-efficient air-cooled
heat pump units. By using the R134a environment-friendly refrigerant, this series of units have a full-load COP of over 3.2.
This value is higher than the energy saving product certification standard, which makes them one of the most efficient,
energy-saving, and quiet environmental-friendly air conditioning units. Moreover, DAIKIN has built a large 1600 kW full
performance lab to ensure the quality and performance of the units.
Test
9601019 EMS 80362 7644 CNAS L0778
Specification
UAY 105 ST 3 - F AA E
Export
Refrigerant code:
3: R134a
Product type:
ST: Standard
105: Cooling capacity code
2
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Features
■ The most advanced efficient single-screw compressor Easy installation and simple maintenance
is adopted. The compressor can perform stepless
adjustment within the range of 10% to 100%
■ Flexible installation without additional equipment
room, cooling tower, or cooling pump.
workload at maximum. Compared with the traditional
compressors, this compressor has wider adjustment
■ The electric system of the units is integrated with the
master unit, so an additional electric control cabinet is
range and higher efficiency.
■ The temperature of outlet water is stable. The output
■
not required.
An intelligent control system monitors and controls the
ability meets the workload demand of the construction
system. The units can regulate the output based on the operating status of the units and indicates the fault
actual workload and maintains high efficiency when cause for the convenience of maintenance.
running at partial workload. In addition, the accurate Accurate control and reliable operation
adjustment of the energy and water temperature
brings more comfortable experience to customers. ■ An advanced electrical expansion valve enables the
units to control the refrigerant flow accurately, adapt
Required load Compressor load
to various working conditions, and perform multiple
control functions.
load (%)
load (%)
Cooling
Cooling
Temperature of outlet
Temperature of outlet
Time Time
3
DAIKIN Air-Cooled Screw Chiller/Heat Pump
■ The temperature of outlet chilled water is accurate to ■ Compressors start up one by one with a low startup
0.5°C. In addition, various sensors in the system can current, to reduce the impact on the power grid.
transmit various kinds of signal data to the controller ■ Multiple protection functions ensure safe operation of
to implement timely protection for the unit components the units.
and ensure more reliable operation.
■ The mechanism of tree-level password protection
ensures safe operation of the units and prevents
misoperations of non-professional personnel.
The units adopt the new-generation DAIKIN controller Micro Tech III. This controller integrates the heat pump applications
and technologies of DAIKIN of more than 40 years and is equipped with programmable software. This enables compressors
and fans to reach the highest COP.
Main components
Built-in controller
■ Control type: PLC programmable
■ Operation language: Chinese/English
■ Screen display: LCD display
■ Operating environment: Temperature: -20°C~60°C
Relative humidity: < 90%.
4
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Features
DAIKIN leads the single-screw compressor technology. ■ Low operation sound and vibration
The Semi-hermetic compressor features high efficiency, DAIKIN single-screw compressor can balance the
energy saving, quiet operation, few moving components, load completely during its operation. Therefore, the
and long service life. vibration can be ignored because the noise value is
lower than the industrial standard. The compressor
■ Few moving components does not contact with any metal during compression
DAIKIN single-screw compressor consists of only five so that no high frequency noise is generated. The
moving components: a screw rotor, two star wheels, special-shaped air discharge cavity helps eliminate
and two energy adjustment slide valves. The screw noises effectively.
rotor is a six-tooth aluminum coated steel component.
The star wheel is an eleven-tooth component made of ■ Unique star wheel and rotor design
high-strength composite material. The star wheel of DAIKIN single-screw compressor
is made of special materials that can avoid metal
■ Long duration and high reliability engagement between the star wheel and rotor.
The star wheels made of high-strength composite The small engagement gap and low engagement
material can ensure the accuracy and the minimum resistance implement “zero gap" engagement. The
gap and guarantee operation without wear and tear. unique oil supply system that uses the oil pressure
The oil injection and liquid injection design of the difference function enables more efficient sealing,
compressor minimizes air superheat and eliminates lubrication, and cooling of the compressor. In this way,
the possibility of oil and refrigerant decomposition due the engagement resistance is further reduced and the
to superheat. efficiency of entire units is improved.
Options
5
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Model Unit UAY-FAAE ST3 105 125 150 175 204 245 291 348
kW 393 459 573 667 786 918 1146 1334
Nominal Cooling Capacity
x104kcal/h 34 39 49 57 68 79 99 115
Compressor Power Input (Cooling) kW 95.9 119.0 145.0 172.3 191.8 238.0 290.0 344.6
kW 400 459 571 656 800 918 1142 1312
Nominal Heating Capacity
x104kcal/h 34 39 49 56 69 79 98 113
Compressor Power Input (Heating) kW 100.4 114.6 141.6 171.2 200.8 229.2 283.2 342.4
Power Supply 380V/3N~/50Hz
Capacity Steps 10%-100% 5%-100%
Type R134a
Refrigerant Curcuit No. 1 2
Flow Control EXV
Type Semi-hermetic Single-screw
Quantity 1 2
Compressor
Startup Star Delta
Cooling Liquid Injection Cooling
Air-side
Heat Type Crossed Fin and Tube
Exchanger
Type Efficient Spiral Axial Fan
Quantity n 10 10 12 14 20 20 24 28
Fan
Air Flow x10 m /h
4 3
18.0 18.0 21.6 25.2 36.0 36.0 43.2 50.4
Motor Power Input kW 20.0 20.0 24.0 28.0 40.0 40.0 48.0 56.0
Type Shell and Tube Heat Exchanger
Water Flow Rate
m3/h 68 79 99 115 135 158 197 229
(Cooling)
Water-side Water Flow
m3/h 69 79 98 113 138 158 196 226
Heat Rate (Heating)
Exchanger Water Resistance kPa 67 67 79 67 62 64 48 61
Connection Pipe
inch 6 8 10
(OD)
Maximun WPD MPa 1.0
Length mm 5530 5530 6480 7380 10860 10860 12690 14490
Unit
Width mm 2260
Dimensions
Height* mm 2460
Transport kg 5250 5450 6080 6810 10210 10610 11870 13230
Weight
Operation kg 5080 5400 6000 6730 9840 10540 11740 13370
6
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Model Unit UAY-FBAE/FBBE ST3 105 125 150 175 204 220 245 266 291
kW 352 448 583 659 703 794 891 935 1029
Nominal Cooling Capacity
×104kcal/h 30 39 50 57 60 68 77 80 88
Compressor Power Input (Cooling) kW 98.0 123.1 162.1 179.3 194.3 218.1 243.8 260.1 284.5
kW 352 452 577 660 696 793 905 929 1029
Nominal Heating Capacity
×104kcal/h 30 39 50 57 60 68 78 80 88
Compressor Power Input (Heating) kW 104.1 122.5 155.8 170.1 183.1 210.4 246.7 259.9 279.1
Power Supply 380V/3N~/50Hz
Capacity Steps 10%~100% 5%~100%
Type R134a
Refrigerant Curcuit No. 1 2
Flow Control EXV
Type Semi-hermetic Single-screw
Compressor Startup Star Delta
Cooling Liquid Injection Cooling
Air-side Heat
Type Crossed Fin and Tube
Exchanger
Type Efficient Spiral Axial Fan
Quantity n 6 8 10 12 12 14 16 16 18
Fan 4 3
Air Flow x10 m /h 10.8 14.4 18.0 21.6 21.6 25.2 28.8 28.8 32.4
Motor Power Input kW 12.0 16.0 20.0 24.0 24.0 28.0 32.0 32.0 36.0
Type Shell and Tube Heat Exchanger
Water Flow Rate
m3/h 61 77 100 113 121 137 153 61/100* 177
(Cooling)
Water-side Water Flow
m3/h 61 78 99 114 120 136 156 61/99 177
Heat Rate (Heating)
Exchanger Water Resistance kPa 58 75 68 70 76 62 72 58/68 74
Connection Pipe
inch 4 5 6 4/5 6
(OD)
Maximun WPD MPa 1.0
Length mm 3730 4630 5580 6480 6480 7380 9060 9710 9960
Unit
Width mm 2260
Dimensions
Height* mm 2460 2425 2460
Transport kg 3650 4500 5450 5880 6000 6710 8780 8310 9690
Weight
Operation kg 3470 4330 5250 5680 5870 6550 8490 8530 9420
7
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Model Unit UAY-FBAE/FBBE ST3 300 348 355 380 390 400 415 424 450
kW 1107 1166 1242 1325 1362 1406 1453 1497 1588
Nominal Cooling Capacity
×104kcal/h 95 100 107 114 117 121 125 129 137
Compressor Power Input (Cooling) kW 302.4 324.3 341.4 360.9 373.6 388.6 397.4 412.4 436.2
kW 1112 1154 1237 1319 1356 1392 1453 1489 1586
Nominal Heating Capacity
×104kcal/h 96 99 106 113 117 120 125 128 136
Compressor Power Input (Heating) kW 292.6 311.5 325.9 337.9 353.2 366.3 380.5 393.6 420.9
Power Supply 380V/3N~/50Hz
Capacity Steps 5%~100%
Type R134a
Refrigerant Curcuit No. 2
Flow Control EXV
Type Semi-hermetic Single-screw
Compressor Startup Star Delta
Cooling Liquid Injection Cooling
Air-side Heat
Type Crossed Fin and Tube
Exchanger
Type Efficient Spiral Axial Fan
Quantity n 20 20 22 24 24 24 26 26 28
Fan 4 3
Air Flow x10 m /h 36.0 36.0 39.6 43.2 43.2 43.2 46.8 46.8 50.4
Motor Power Input kW 40.0 40.0 44.0 48.0 48.0 48.0 52.0 52.0 56.0
Type Shell and Tube Heat Exchanger
Water Flow Rate
m3/h 77/113 201 100/113* 228 113/121 121/121 113/137 121/137 137/137
(Cooling)
Water-side Water Flow
m3/h 78/114 198 99/114 227 114/120 120/120 114/136 120/136 136/136
Heat Rate (Heating)
Exchanger Water Resistance kPa 75/70 78 68/70 83 70/76 76/76 70/62 76/62 62/62
Connection Pipe
inch 4/5 6 5/5 8 5/6 6/6 5/6 6/6 6/6
(OD)
Maximun WPD MPa 1.0
Length mm 11510 10890 12460 12690 13360 13360 14260 14260 15160
Unit
Width mm 2260
Dimensions
Height* mm 2425 2460 2425 2460 2425
Transport kg 9460 10600 10450 11460 10950 11060 11680 11790 12520
Weight
Operation kg 9750 10300 10780 11180 11380 11560 12110 12290 13020
8
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Model Unit UAA-FBAE ST3 105 125 150 175 204 220 245 291 348 380 400 450
kW 370 449 586 663 717 802 898 1035 1172 1326 1434 1604
Nominal Cooling Capacity
×104kcal/h 32 39 50 57 62 69 77 89 101 114 123 138
Compressor Power Input
kW 103.5 122.5 158.7 177.3 192.1 214.6 245.0 281.2 317.4 354.6 384.2 429.2
(Cooling)
Power Supply 380V/3N~/50Hz
Quantity 1 2
Compressor
Startup Star Delta
Cooling Liquid Injection Cooling
Air-side Heat
Type Crossed Fin and Tube
Exchanger
Type Efficient Spiral Axial Fan
Quantity n 6 8 10 12 12 14 16 18 20 24 24 28
Fan Air Flow x104m3/h 10.8 14.4 18.0 21.6 21.6 25.2 28.8 32.4 36.0 43.2 43.2 50.4
Motor Power
kW 12.0 16.0 20.0 24.0 24.0 28.0 32.0 36.0 40.0 48.0 48.0 56.0
Input
Type Shell and Tube Heat Exchanger
Water
Flow Rate m3/h 64 77 101 114 123 138 154 178 202 228 247 276
(Cooling)
Water-side
Water
Heat kPa 58 75 68 70 76 62 72 74 78 83 61 79
Resistance
Exchanger
Connection
inch 4 5 6 8
Pipe (OD)
Maximun
MPa 1.0
WPD
Length mm 3530 4430 5380 6280 6280 7180 8660 9560 10490 12290 12290 14090
Unit
Width mm 2260
Dimensions
Height* mm 2460
Transport kg 3170 4040 4920 5330 5450 6180 7850 8750 9620 10440 10680 12100
Weight
Operation kg 3070 3930 4810 5220 5420 6100 7700 8590 9430 10270 10640 11990
unit installation manual, certificate, warranty application form, spring shock absorber,
Stand Aceessories
water flow switch
9
DAIKIN Air-Cooled Screw Chiller/Heat Pump
11
DAIKIN Air-Cooled Screw Chiller/Heat Pump
12
DAIKIN Air-Cooled Screw Chiller/Heat Pump
13
DAIKIN Air-Cooled Screw Chiller/Heat Pump
14
DAIKIN Air-Cooled Screw Chiller/Heat Pump
16
DAIKIN Air-Cooled Screw Chiller/Heat Pump
17
DAIKIN Air-Cooled Screw Chiller/Heat Pump
18
DAIKIN Air-Cooled Screw Chiller/Heat Pump
19
DAIKIN Air-Cooled Screw Chiller/Heat Pump
UAY105SR3 Input power (kW) 89.7 93.0 96.3 98.0 100.1 104.2 108.3 112.4 116.5 118.6 121.1 126.1 131.0
UAY125SR3 Input power (kW) 112.6 116.8 121.0 123.1 125.7 130.9 136.0 141.2 146.4 149.0 152.1 158.3 164.6
UAY150SR3 Input power (kW) 148.3 153.8 159.3 162.1 165.5 172.3 179.1 185.9 192.7 196.1 200.3 208.5 216.7
UAY175SR3 Input power (kW) 164.1 170.2 176.3 179.3 183.1 190.6 198.1 205.7 213.2 217.0 221.5 230.6 239.7
UAY204SR3 Input power (kW) 177.8 184.4 191.0 194.3 198.4 206.5 214.7 222.9 231.0 235.1 240.0 249.9 259.8
UAY220SR3 Input power (kW) 199.6 207.0 214.4 218.1 222.7 231.8 241.0 250.2 259.3 263.9 269.4 280.5 291.6
Note: The inlet/outlet water temperature on the air conditioning side corresponding to the capacity variation parameters on the heat
recovery side is 12°C/7°C.
20
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Dimensions
Super-high-efficiency series
UAY105ST3-FAAE
5530 2260
1 5
2460
4
2
3
395
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)
4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)
5 Control cabinet
Unit: mm
UAY125ST3-FAAE
5530 2260
1
4 5
2460
2
3
427
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)
4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)
5 Control cabinet
Unit: mm
21
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Dimensions
Super-high-efficiency series
UAY150ST3-FAAE
6480 2260
1
5
2460
2
4
3
427
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)
4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)
5 Control cabinet
Unit: mm
UAY175ST3-FAAE
7380 2260
1
5
2460
2
4
427
3
3262 2142 2225
7200
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)
4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)
5 Control cabinet
Unit: mm
22
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Dimensions
Super-high-efficiency series
UAY204ST3-FAAE
10860 2260
1
5
2460
427
10730
4 3 2
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)
4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)
5 Control cabinet
Unit: mm
UAY245ST3-FAAE
10860 2260
1 5
2460
465
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 8" (OD219.1 mm)
4 Size of outlet water pipe of the evaporator 8" (OD219.1 mm)
5 Control cabinet
Unit: mm
23
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Dimensions
Super-high-efficiency series
UAY291ST3-FAAE
12690 2260
2460
5
465
2225
3510 7248
12530
4 3 2
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 8" (OD219.1 mm)
4 Size of outlet water pipe of the evaporator 8" (OD219.1 mm)
5 Control cabinet
Unit: mm
UAY348ST3-FAAE
14490 2260
1
5
2460
540
2225
3130 8791
14330
4 3 2
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 10" (OD273 mm)
4 Size of outlet water pipe of the evaporator 10" (OD273 mm)
5 Control cabinet
Unit: mm
24
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Dimensions
High-efficiency series
UAY105ST3-FBAE
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 4" (OD114.3 mm)
4 Size of outlet water pipe of the evaporator 4" (OD114.3 mm)
5 Control cabinet
Unit: mm
UAY125ST3-FBAE
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 4" (OD114.3 mm)
4 Size of outlet water pipe of the evaporator 4" (OD114.3 mm)
5 Control cabinet
Unit: mm
25
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Dimensions
High-efficiency series
UAY150ST3-FBAE
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 5" (OD139.7 mm)
4 Size of outlet water pipe of the evaporator 5" (OD139.7 mm)
5 Control cabinet
Unit: mm
UAY175ST3-FBAE
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 5" (OD139.7 mm)
4 Size of outlet water pipe of the evaporator 5" (OD139.7 mm)
5 Control cabinet
Unit: mm
26
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Dimensions
High-efficiency series
UAY204ST3-FBAE
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)
4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)
5 Control cabinet
Unit: mm
UAY220ST3-FBAE
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)
4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)
5 Control cabinet
Unit: mm
27
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Dimensions
High-efficiency series
UAY245ST3-FBAE
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)
4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)
5 Control cabinet
Unit: mm
UAY291ST3-FBAE
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)
4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)
5 Control cabinet
Unit: mm
28
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Dimensions
High-efficiency series
UAY348ST3-FBAE
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)
4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)
5 Control cabinet
Unit: mm
UAY380ST3-FBAE
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 8" (OD219.1 mm)
4 Size of outlet water pipe of the evaporator 8" (OD219.1 mm)
5 Control cabinet
Unit: mm
29
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Dimensions
UAY266ST3-FBBE
9710 2260
400
4
1 3
2
2425
8 5
562
452
3023 3822 7 500 6 2396 1941 3471
9500
1 Condenser
2 Evaporator
3 Main unit’s control cabinet
4 Auxiliary unit’s control cabinet
5 Size of inlet water pipe of the main unit’s evaporator 4"(OD114.3 mm)
6 Size of outlet water pipe of the unit’s evaporator 4"(OD114.3 mm)
7 Size of inlet water pipe of the auxiliary unit’s evaporator 5"(OD139.7 mm)
8 Size of outlet water pipe of the auxiliary unit’s evaporator 5"(OD139.7 mm)
Unit: mm
UAY300ST3-FBBE
11510 2260
400
4
1 3
2
2425
8 5
504
406
11300
1 Condenser
2 Evaporator
3 Main unit’s control cabinet
4 Auxiliary unit’s control cabinet
5 Size of inlet water pipe of the main unit’s evaporator 4"(OD114.3 mm)
6 Size of outlet water pipe of the unit’s evaporator 4"(OD114.3 mm)
7 Size of inlet water pipe of the auxiliary unit’s evaporator 5"(OD139.7 mm)
8 Size of outlet water pipe of the auxiliary unit’s evaporator 5"(OD139.7 mm)
Unit: mm
30
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Dimensions
UAY355ST3-FBBE
12460
400 2260
4 1 3
2
2425
8 5
475
475
2937
2295 3960 7 500 6 3234 1752
12200
1 Condenser
2 Evaporator
3 Main unit’s control cabinet
4 Auxiliary unit’s control cabinet
5 Size of inlet water pipe of the main unit’s evaporator 5"(OD139.7 mm)
6 Size of outlet water pipe of the unit’s evaporator 5"(OD139.7 mm)
7 Size of inlet water pipe of the auxiliary unit’s evaporator 5"(OD139.7 mm)
8 Size of inlet water pipe of the auxiliary unit’s evaporator 5"(OD139.7 mm)
Unit: mm
UAY390ST3-FBBE
13360 2260
4 400
1 3
2
2425
8 5
510
468
1 Condenser
2 Evaporator
3 Main unit’s control cabinet
4 Auxiliary unit’s control cabinet
5 Size of inlet water pipe of the main unit’s evaporator 5"(OD139.7 mm)
6 Size of outlet water pipe of the unit’s evaporator 5"(OD139.7 mm)
7 Size of inlet water pipe of the auxiliary unit’s evaporator 6"(OD168.3 mm)
8 Size of outlet water pipe of the auxiliary unit’s evaporator 6"(OD168.3 mm)
Unit: mm
31
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Dimensions
UAY400ST3-FBBE
13360
400 2260
4
1
3
2
2425
8
5
500
510
510
13100
1 Condenser
2 Evaporator
3 Main unit’s control cabinet
4 Auxiliary unit’s control cabinet
5 Size of inlet water pipe of the main unit’s evaporator 6"(OD168.3 mm)
6 Size of outlet water pipe of the unit’s evaporator 6"(OD168.3 mm)
7 Size of inlet water pipe of the auxiliary unit’s evaporator 6"(OD168.3 mm)
8 Size of outlet water pipe of the auxiliary unit’s evaporator 6"(OD168.3 mm)
Unit: mm
UAY415ST3-FBBE
14260 2260
400
4 1 3
2
2425
8 5
392
360
14000
1 Condenser
2 Evaporator
3 Main unit’s control cabinet
4 Auxiliary unit’s control cabinet
5 Size of inlet water pipe of the main unit’s evaporator 5"(OD139.7 mm)
6 Size of outlet water pipe of the unit’s evaporator 5"(OD139.7 mm)
7 Size of inlet water pipe of the auxiliary unit’s evaporator 6"(OD168.3 mm)
8 Size of outlet water pipe of the auxiliary unit’s evaporator 6"(OD168.3 mm)
Unit: mm
32
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Dimensions
UAY424ST3-FBBE
14260 2260
400
4 1 3
2
2425
5
8
392
392
2412 1340 2225
2940 2412 7 500 6
14000
1 Condenser
2 Evaporator
3 Main unit’s control cabinet
4 Auxiliary unit’s control cabinet
5 Size of inlet water pipe of the main unit’s evaporator 6"(OD168.3 mm)
6 Size of outlet water pipe of the unit’s evaporator 6"(OD168.3 mm)
7 Size of inlet water pipe of the auxiliary unit’s evaporator 6"(OD168.3 mm)
8 Size of outlet water pipe of the auxiliary unit’s evaporator 6"(OD168.3 mm)
Unit: mm
UAY450ST3-FBBE
15160
400 2260
4 1 3
2
2425
8 5
392
392
14900
1 Condenser
2 Evaporator
3 Main unit’s control cabinet
4 Auxiliary unit’s control cabinet
5 Size of inlet water pipe of the main unit’s evaporator 6"(OD168.3 mm)
6 Size of outlet water pipe of the unit’s evaporator 6"(OD168.3 mm)
7 Size of inlet water pipe of the auxiliary unit’s evaporator 6"(OD168.3 mm)
8 Size of outlet water pipe of the auxiliary unit’s evaporator 6"(OD168.3 mm)
Unit: mm
33
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Dimensions
High-efficiency series
UAA105ST3-FBAE
3530 2260
1 5
2460
2
4
365
3
1536 1244
3400 2225
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 4" (OD114.3 mm)
4 Size of outlet water pipe of the evaporator 4" (OD114.3 mm)
5 Control cabinet
Unit: mm
UAA125ST3-FBAE
4430 2260
1 5
2460
2
4
365
3
2486 1244 2225
4300
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 4" (OD114.3 mm)
4 Size of outlet water pipe of the evaporator 4" (OD114.3 mm)
5 Control cabinet
Unit: mm
34
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Dimensions
High-efficiency series
UAA150ST3-FBAE
5380 2260
1 5
2460
4 2
395
3
2450 1353
5200 2225
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 5" (OD139.7 mm)
4 Size of outlet water pipe of the evaporator 5" (OD139.7 mm)
5 Control cabinet
Unit: mm
UAA175ST3-FBAE
6280 2260
1 5
2460
4 2
395
3
3000 1320
2225
6100
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 5" (OD139.7 mm)
4 Size of outlet water pipe of the evaporator 5" (OD139.7 mm)
5 Control cabinet
Unit: mm
35
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Dimensions
High-efficiency series
UAA204ST3-FBAE
6280 2260
1 5
2460
2
4
427
3
2412 1340
2225
6100
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)
4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)
5 Control cabinet
Unit: mm
UAA220ST3-FBAE
7180 2260
1 5
2460
2
4
427
3
2412 2163
7000 2225
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)
4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)
5 Control cabinet
Unit: mm
36
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Dimensions
High-efficiency series
UAA245ST3-FBAE
8660 2260
1 5
2460
4
427
2412 5467
3 2 8530 2225
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)
4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)
5 Control cabinet
Unit: mm
UAA291ST3-FBAE
9560 2260
1 5
2460
4
427
3262 5371
9430 2225
3 2
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)
4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)
5 Control cabinet
Unit: mm
37
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Dimensions
High-efficiency series
UAA348ST3-FBAE
10490 2260
1 5
2460
4
427
3262 6271
10330 2225
3 2
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)
4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)
5 Control cabinet
Unit: mm
UAA380ST3-FBAE
2260
12290
1
2460
5
4
465
2360 7302
2225
12130
3 2
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 8" (OD219.1 mm)
4 Size of outlet water pipe of the evaporator 8" (OD219.1 mm)
5 Control cabinet
Unit: mm
38
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Dimensions
High-efficiency series
UAA400ST3-FBAE
12290 2260
1 5
2460
4
465
3210 7297
12130 2225
3 2
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 8" (OD219.1 mm)
4 Size of outlet water pipe of the evaporator 8" (OD219.1 mm)
5 Control cabinet
Unit: mm
UAA450ST3-FBAE
14090 2260
1 5
2460
4
465
3210 8197
13930 2225
3 2
1 Condenser
2 Evaporator
3 Size of inlet water pipe of the evaporator 8" (OD219.1 mm)
4 Size of outlet water pipe of the evaporator 8" (OD219.1 mm)
5 Control cabinet
Unit: mm
39
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Dimensions
UAY105SR3-FBAE
1 Condenser
2 Control cabinet
3 Evaporator
4 Size of inlet water pipe of the evaporator 4"(OD114.3 mm)
5 Size of outlet water pipe of the evaporator 4"(OD114.3 mm)
6 Heat recovery exchanger
7 Size of outlet water pipe of the heat recovery exchanger 3"(OD88.9 mm)
8 Size of inlet water pipe of the heat recovery exchanger 3"(OD88.9 mm)
Unit: mm
UAY125SR3-FBAE
1 Condenser
2 Control cabinet
3 Evaporator
4 Size of inlet water pipe of the evaporator 4"(OD114.3 mm)
5 Size of outlet water pipe of the evaporator 4"(OD114.3 mm)
6 Heat recovery exchanger
7 Size of outlet water pipe of the heat recovery exchanger 3"(OD88.9 mm)
8 Size of inlet water pipe of the heat recovery exchanger 3"(OD88.9 mm)
Unit: mm
40
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Dimensions
UAY150SR3-FBAE
1 Condenser
2 Control cabinet
3 Evaporator
4 Size of inlet water pipe of the evaporator 5"(OD139.7 mm)
5 Size of outlet water pipe of the evaporator 5"(OD139.7 mm)
6 Heat recovery exchanger
7 Size of outlet water pipe of the heat recovery exchanger 3"(OD88.9 mm)
8 Size of inlet water pipe of the heat recovery exchanger 3"(OD88.9 mm)
Unit: mm
UAY175SR3-FBAE
1 Condenser
2 Control cabinet
3 Evaporator
4 Size of inlet water pipe of the evaporator 5"(OD139.7 mm)
5 Size of outlet water pipe of the evaporator 5"(OD139.7 mm)
6 Heat recovery exchanger
7 Size of outlet water pipe of the heat recovery exchanger 4"(OD114.3 mm)
8 Size of inlet water pipe of the heat recovery exchanger 4"(OD114.3 mm)
Unit: mm
41
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Dimensions
UAY204SR3-FBAE
1 Condenser
2 Control cabinet
3 Evaporator
4 Size of inlet water pipe of the evaporator 6"(OD168.3 mm)
5 Size of outlet water pipe of the evaporator 6"(OD168.3 mm)
6 Heat recovery exchanger
7 Size of outlet water pipe of the heat recovery exchanger 4"(OD114.3 mm)
8 Size of inlet water pipe of the heat recovery exchanger 4"(OD114.3 mm)
Unit: mm
UAY220SR3-FBAE
1 Condenser
2 Control cabinet
3 Evaporator
4 Size of inlet water pipe of the evaporator 6"(OD168.3 mm)
5 Size of outlet water pipe of the evaporator 6"(OD168.3 mm)
6 Heat recovery exchanger
7 Size of outlet water pipe of the heat recovery exchanger 4"(OD114.3 mm)
8 Size of inlet water pipe of the heat recovery exchanger 4"(OD114.3 mm)
Unit: mm
42
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Foundation drawing
Super-high-efficiency series
UAY105ST3-FAAE / UAY125ST3-FAAE
Installation foundation
Base of the unit A B C
Electric control cabinet
A B C
UAY150ST3-FAAE
Installation foundation A B C
Base of the unit
A B C
UAY175ST3-FAAE
Installation foundation
A B C D
Base of the unit
A B C D
43
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Foundation drawing
Super-high-efficiency series
UAY204ST3-FAAE / UAY245ST3-FAAE
Installation foundation
Base of the unit
Unit: mm
UAY291ST3-FAAE
Installation foundation
Base of the unit
Electric control cabinet
Distribution of
shock absorber
Unit: mm
UAY348ST3-FAAE
Installation foundation
Base of the unit
Unit: mm
44
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Foundation drawing
UAY105ST3-FBAE
Installation foundation
Base of the unit A B
2525
2065
2225
Distribution of
shock absorber
A B
230
150
3600
3900
UAY125ST3-FBAE
Installation foundation
Base of the unit A B C
Distribution of
shock absorber
A B C
700
230
1500 1600
150
150
4500
4800
UAY150ST3-FBAE
Installation foundation
Base of the unit A B C
2525
2225
Distribution of
shock absorber
A B C
1300
230
1500 1300
150
150
5400
5700
45
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Foundation drawing
High-efficiency series
UAY175ST3-FBAE / UAY204ST3-FBAE
Installation foundation
Base of the unit A B C
2525
2065
2225
Distribution of
shock absorber
A B C
230
1050 2100 2100
150
150
6300
6600
UAY220ST3-FBAE
Installation foundation
Base of the unit A B C D
2525
2225
Distribution of 2065
shock absorber
A B C D
1400
230
150
7200
7500
UAY245ST3-FBAE
Installation foundation
A B C D E F
Base of the unit
Distribution of
shock absorber
A B C D E F
1778 1200
150
150 1500
8930
9230
Unit: mm
46
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Foundation drawing
High-efficiency series
UAY291ST3-FBAE
Installation foundation
A B C D E F
Base of the unit
2525
2225
2065
Distribution of
shock absorber
A B C D E F
230
1778 1500 1500
150
150
9830
10130
UAY348ST3-FBAE
Installation foundation
Base of the unit A B C D E F
2525
2225
2065
Distribution of
shock absorber
A B C D E F
230
1311 1900 1500 1778 1500
150
150 1500
10730
11030
UAY380ST3-FBAE
Installation foundation
A B C D E F
Base of the unit
Distribution of
shock absorber
A B C D E F
150 2101
150
12530
12830
47
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Foundation drawing
UAY266ST3-FBBE
2169
2525
2185
2225
Distribution of
shock absorber
A B c b a
170
178
150
3600 5400
9500
9800
Unit: mm
UAY300ST3-FBBE
2225
2525
2185
Distribution of
shock absorber
A B C c b a
150
178
4500 6300
11300
11600
Unit: mm
48
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Foundation drawing
UAY355ST3-FBBE
2225
2525
2169
Distribution of
shock absorber
A B C c b a
178
150
5400 6300
12200
12500
Unit: mm
UAY390ST3-FBBE
2225
Distribution of
shock absorber
A B C c b a
150
6300 6300
13100
13400
Unit: mm
49
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Foundation drawing
UAY400ST3-FBBE
2525
2169
2225
Distribution of
shock absorber
A B C D E F
178
150
6300 6300
13100
13400
UAY415ST3-FBBE
2225
Distribution of
shock absorber
A B C d c b a
150
6300 7200
14000
14300
Unit: mm
50
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Foundation drawing
UAY424ST3-FBBE
2525
2169
2225
Distribution of
shock absorber
A B C d c b a
178
150
6300 7200
Unit: mm
UAY450ST3-FBBE
2525
2169
Distribution of
shock absorber
A B C D d c b a
150
7200 7200
14900
15200
51
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Foundation drawing
High-efficiency series
UAA105ST3-FBAE
Installation foundation
Base of the unit A B
2525
2225
2065
Distribution of
shock absorber
A B
230
150
3400
3700
UAA125ST3-FBAE
Installation foundation
Base of the unit A B C
2225
Distribution of
shock absorber
A B C
150
4300
4600
UAA150ST3-FBAE
Installation foundation
Base of the unit A B C
Electric control cabinet
2065
2525
2225
Distribution of
shock absorber
A B C
150
5200
5500
52
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Foundation drawing
High-efficiency series
UAA175ST3-FBAE
Installation foundation
Base of the unit A B C
2525
2065
2225
Distribution of
shock absorber
A B C
230
150
6100
6400
UAA204ST3-FBAE
Installation foundation
Base of the unit A B C
2525
2065
2225
Distribution of
shock absorber
A B C
150
6100
6400
UAA220ST3-FBAE
Installation foundation
Base of the unit A B C D
Electric control cabinet
2525
2225
2065
Distribution of
shock absorber
A B C D
150
7000
7300
53
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Foundation drawing
High-efficiency series
UAA245ST3-FBAE
Installation foundation
A B C D E F
Base of the unit
Electric control cabinet
Distribution of
2525
2225
2065
shock absorber
A B C D E F
230
150
8530
8830
UAA291ST3-FBAE
Installation foundation
A B C D E F
Base of the unit
Electric control cabinet
Distribution of
2525
2225
2065
shock absorber
A B C D E F
150
9430
9730
UAA348ST3-FBAE
Installation foundation
A B C D E F
Base of the unit
shock absorber
A B C D E F
150
10330
10630
54
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Foundation drawing
High-efficiency series
UAA380ST3-FBAE
Installation foundation
A B C D E F
Base of the unit
Electric control cabinet
Distribution of
2525
2225
2065
shock absorber
A B C D E F
230
150
12130
12430
UAA400ST3-FBAE
Installation foundation
A B C D E F
Base of the unit
Electric control cabinet
Distribution of
2525
2225
2065
shock absorber
A B C D E F
150
12130
12430
UAA450ST3-FBAE
Installation foundation
A B C D E F H I
Base of the unit
Distribution of
2225
2065
shock absorber
A B C D E F H I
150 1200 1800 1500 1700 1600 1600 1600 1600
230
150
13930
14230
55
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Foundation drawing
UAY105SR3-FBAE
Installation
foundation A B
Base of
the unit
Electric
control cabinet
Distribution of
shock absorber
A B
UAY125SR3-FBAE
Installation
foundation
A B C
Base of
the unit
Electric
control cabinet
Distribution of
shock absorber
A B C
56
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Foundation drawing
UAY150SR3-FBAE
Installation
foundation
A B C
Base of
the unit
Electric
control cabinet
Distribution of
shock absorber
A B C
UAY175(204)SR3-FBAE
Installation
foundation
Base of
the unit A B C
Electric
control cabinet
Distribution of
shock absorber
A B C
57
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Foundation drawing
UAY220SR3-FBAE
Installation
foundation
Base of
the unit A B C D
Electric
control cabinet
Distribution of
shock absorber
A B C D
58
DAIKIN Air-Cooled Screw Chiller/Heat Pump
1500
1500
1500
1500
Notes: ■
During the installation of the unit: (1) If the wall height H > 2.5 m, the distance between the unit and the wall L ≥ H + 0.5 m;
(2) If 1.1 m ≤ wall height H ≤ 2.5 m, L ≥ 2.5 m;
(3) If wall height H < 1.1 m, L ≥ 1.5 m.
■ If multiple units are installed, each unit must have sufficient space for maintenance.
59
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Operation limits
Heat Pump
Heat
Cooling Heating Water
Recovery
Model Heater
ST LC SC ST SR -
Note:
If special application requirement is needed, please contact DAIKIN.
7 UAY245ST3-FBAE/UAA245ST3-FBAE 8 UAY291ST3-FBAE/UAA291ST3-FBAE
9 UAY348ST3-FBAE/UAA348ST3-FBAE 10 UAY380ST3-FBAE/UAA380ST3-FBAE
11 UAA400ST3-FBAE 12 UAA450ST3-FBAE
60
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Electrical specifications
Super-high-efficiency series
High-efficiency series
■ T he maximum operating current in the above table refers to the maximum operating current during cooling or heating within
Notes:
the operation range.
■ W orking conditions for the nominal operating current: During cooling, the ambient temperature for dry bulb is 35°C, and
the temperature of inlet/outlet chilled water is 12°C/7°C. During heating, the ambient temperature for dry bulb is 7°C,
the temperature for wet bulb is 6°C, and the temperature of inlet/outlet hot water is 40°C/45°C.
■ Inter-phase unbalance range: ≤ 2%
■ Power supply voltage: 380 V±10%
61
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Electrical specifications
Nominal
Compressor Fan
operating current Maximum
Startup
Model Nominal operating
Fuse Cooling (A) current (A)
Quantity Quantity current (A) current (A)
specification (A) Heating (A)
per pcs
UAA105ST3-FBAE 1 315 6 4 190 321 473
UAA125ST3-FBAE 1 355 8 4 238 349 480
UAA150ST3-FBAE 1 400 10 4 312 431 708
UAA175ST3-FBAE 1 500 12 4 342 505 715
UAA204ST3-FBAE 1 500 12 4 374 540 715
UAA220ST3-FBAE 1 630 14 4 415 637 740
UAA245ST3-FBAE 2 355*2 16 4 477 698 829
UAA291ST3-FBAE 2 355/400 18 4 549 780 1057
UAA348ST3-FBAE 2 400*2 20 4 624 861 1139
UAA380ST3-FBAE 2 500*2 24 4 683 1011 1221
UAA400ST3-FBAE 2 500*2 24 4 749 1080 1255
UAA450ST3-FBAE 2 630*2 28 4 830 1275 1377
Nominal operating
Compressor Fan
current Maximum Startup
Model Nominal operating current
Fuse Cooling Heating
Quantity Quantity current (A) current (A) (A)
specification (A) (A) (A)
per pcs
UAY105SR3 1 315 6 4 190 200 321 473
UAY125SR3 1 355 8 4 238 233 349 480
UAY150SR3 1 400 10 4 312 290 431 708
UAY175SR3 1 500 12 4 342 332 505 715
UAY204SR3 1 500 12 4 374 355 540 715
UAY220SR3 1 630 14 4 415 400 637 740
Notes: ■ T he maximum operating current in the above table refers to the maximum operating current during cooling or heating within
the operation range.
■ W orking conditions for the nominal operating current: During cooling, the ambient temperature for dry bulb is 35°C, and
the temperature of inlet/outlet chilled water is 12°C/7°C. During heating, the ambient temperature for dry bulb is 7°C,
the temperature for wet bulb is 6°C, and the temperature of inlet/outlet hot water is 40°C/45°C.
■ Inter-phase unbalance range: ≤ 2%
■ Power supply voltage: 380 V±10%
62
block
of the unit
M3 terminal
Control cabinet
8
Water switch on the air conditioner side
On-site wiring diagram
23 25 26
Heat recovery auxiliary electric heating signal
28A 28E
Dry-steam auxiliary electric heating signal
53 54
breaker
of the unit
Control cabinet
Incoming circuit
R
I>
Remote power-on/power-off
S
I>
Remote mode selection
power supply
This function is disabled for cooling-only units.
58 59 60 61
T
I>
Isolation switch
60+ 50 73
Fault signal of system 2
To earth line
Incoming lines of main power supply
90 91
Heat recovery water switch
197 198
63
DAIKIN Air-Cooled Screw Chiller/Heat Pump
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Notes:
Main unit's control cabinet Auxiliary unit's control cabinet 1. Wirings for main unit's and auxiliary unit's
control cabinets showed in the left figure
are applicable only to the following unit
models:
UAY266ST3-FBBE
UAY300ST3-FBBE
UAY355ST3-FBBE
UAY390ST3-FBBE
UAY400ST3-FBBE
Outlet water Outlet water UAY415ST3-FBBE
temperature temperature sensor UAY424ST3-FBBE
sensor of of auxiliary unit UAY450ST3-FBBE
main unit
2. The preceding models adopt twin power
supply wiring.
Shielded twisted pair
All exposed wires must be
protected with conduits.
Notes: ■ The wiring of the dashed part must be completed by the customer.
■ The customer is advised to configure an outdoor incoming circuit breaker.
■ The selected external wires and circuit breakers for all units must be larger than the maximum operating current of the units,
and furthermore, they will not cause malfunction conditions due to start current.
■ Due to the impact of layout and length, supplies cannot provide details about the main power wiring. Please refer to relevant
materials.
1 Unit failure Passive dry contact output For failure signal output of the unit (Figure 1)
2 Water pump control output Passive dry contact output For water pump control output (Figures 2 and 3)
3 Water flow switch Passive dry contact input For detecting water flow of the unit (Figure 4)
4 Remote startup/shutdown Passive dry contact input For remote startup/shutdown of the unit (Figure 5)
5 Remote mode selection Passive dry contact input For remote mode selection of the unit (Figure 6)
6 System failure signal 1 Passive dry contact output For failure signal output of the unit (Figure 7)
7 System failure signal 2 Passive dry contact output For failure signal output of the unit (Figure 8)
Heat recovery auxiliary electric Used to output the auxiliary electric heating signal
8 Passive dry contact output
heating signal for units. For details, see Figures 9 and 10.
Dry-steam auxiliary electric heater Used to output the auxiliary electric heating signal
9 Passive dry contact output
signal for units. For details, see Figures 9 and 10.
64
DAIKIN Air-Cooled Screw Chiller/Heat Pump
M3(25)
M3(60)
Control Control Remote mode selection switch
cabinet cabinet
M3(26)
~ M3(61)
220 V AC power
Terminal block alarm indicator 220V~/50Hz Terminal block
Figure 1 Figure 6
M3(401)
M3(50)
M3(401) M3(50)
Figure 8
~ M3(53)
AC power
380V~/50Hz Control Constantly closed point for
electric heating protection
Water pump contactor cabinet
(with a coil voltage of 380 V) M3(54)
Figure 3 ~
AC power supply
Terminal block Electric heating contactor 220V~/50Hz
The voltage of the coil on
M3(8) the contactor is 220 V. Figure 9
Control F116
Water flow switch
cabinet M3(53)
M3(23)
Control Constantly closed point for
electric heating protection
cabinet
Terminal block M3(54)
Figure 4 ~
AC power supply
Terminal block Intermediate 220V~/50Hz
relay
M3(58)
Control Remote switch of the unit
cabinet ~
AC power supply
M3(59)
380V~/50Hz
M3(197)
Control F116
Notes:
■ * This function is not available for cooling-only and total heat recovery units.
■ For the terminal blocks in figures 2 and 3, M3(401) and M3(402) indicate the output contacts for pump control on the
air conditioning side; M3(90) and M3(91) indicate the output contacts for pump control on the heat recovery side.
■ For the terminal blocks in figures 9 and 10, M3(53) and M3(54) indicate the signal contacts for auxiliary electric heating
on the air conditioning side; M3(28A) and M3(28E) indicate the signal contacts for auxiliary electric heating on the heat
recovery side.
■ Operating signals of the unit come from the operating signals of the water pump. If M3 (401) and M3 (402) are externally
connected to a water pump contactor, the operating signals of unit come from the normally-open contact of the contactor.
■ When the unit is in the remote mode control, switch Q8 must be set to “Heating". It can be controlled by connecting a remote
switch to M3 (60) and M3 (61). The short contact tag between M3 (60) and M3 (61) must be removed.
■ The failure, water pump output and electric heater contact can bear an AC voltage of only 230 V. If the water pump contactor
uses a 380 V coil, conversion is required. See Figure 3/10.
■ Since the units are under constant improvement, use the drawing delivered with the related unit for reference.
65
DAIKIN Air-Cooled Screw Chiller/Heat Pump
2-way valve
Fan coil
2-way valve
Fan coil
2-way valve
Fan coil
2-way valve
Fan coil
S oft connector
Water replenishing valve
Expansion tank
Heater
Filter
valve
Sewage discharge
S oft connector
Relief valve
Gate valve
Gate valve
Thermometer
Pressure gauge
Water pump
bypass valve
Differential pressure
Gate valve
S oft connector
Gate valve
Gate valve
Thermometer
Pressure gauge
1 All pipes must be as level and simple as possible to reduce water resistance.
2 It is recommended to install manual stop valve for a component that requires manual maintenance.
5 Install hoses at the water inlets and outlets of a unit to prevent vibration from being transmitted to buildings.
66
DAIKIN Air-Cooled Screw Chiller/Heat Pump
1 A heat insulation layer with a thickness of at least 10 millimeter must be wrapped around the chilled water pipe.
2 A water filter with at least 25 meshes per square inch must be installed at the inlet of the water-side heat exchanger.
The chilled water pipe must be cleaned by using a bypass pipe. It’s prohibited to clean the water pipes through the water-
3
side heat exchanger.
A water flow switch must be installed at the water outlet of the water-side heat exchanger. The distance of the level straight
4 pipe between both ends of the flow swith must be five times more than the diameter at least.The water flow direction in the
water flow switch must be the same as that in the water system.
5 A relief valve with a opening pressure less than 1.0 MPa must be installed.
6 An automatic water replenishment device must be installed to ensure sufficient water in the water system.
A pump with a proper water flow and lift must be installed at the water inlet of the water-side heat exchanger to ensure that
7
the actual water flow is between 70% - 130% of the rated water flow for the unit when the unit is working.
9 Stop valves must be installed at the water inlet and outlet of the unit.
An automatic relief valve must be installed at the top of water pipes to ensure that air in the water system can be discharged
10
when the unit is working.
An auxiliary heater or other heating devices must be installed to ensure that water in the water system does not freeze when
11 the environment temperature drops below zero (this requirement only applies to areas where the environment temperature
may drop below 0°C).
12 The chilled water pipe must comply with the local piping engineering regulations and rules.
13 The water used in the water system must comply with related industry standards.
Water Flow
The design water flow of water system should be the same as rated water flow of unit. Of course, the unit is able to operate
at condition of 70%~130% rated water flow. However, water flow out of this range may cause unit alarm, or even reduce
the unit life expectancy.
Water Volume
It is very important to design the water system with suitable water volume. With too much low water volume, air conditioning
terminal device will not be able to operate at stable condition, then the user may feel uncomfortable. Moreover, the chiller
with lower water volume may be frequently on/off, then may cause the chiller alarm, or even damage evaporator and
system.
Minimum water volume: To avoid the above happened, water volume of water system must be at least more than the
minimum water volume
Minimum water volume (m3) = Rated cooling capacity of chiller (kW) × 0.0068
67
DAIKIN Air-Cooled Screw Chiller/Heat Pump
The workload of a DAIKIN water chiller is controlled by the outlet water temperature which can be set by using the unit
controller.
By default, the outlet water temperature is set to 7°C. It can be set from 4~15°C. Out of this range, some other parameters
are needed to be changed as well. Please contact local DAIKIN office or distributor to have professional technician to do
the setting accordingly.
While installing the water system, it may create a lot of welding slag, dirt or other impurity. It may damage the evaporator if
the chiller is connected directly to the water system without cleaning. Please do not run the water into chiller until the water
is clean and qualified.
Water quality directly affects the performance and life expectancy of the unit. Therefore, the water quality must be tested
and properly managed for the unit to work properly.
68
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Main controller
2
1
3 5
MT3006 4
5
1 2 3 4 Turn
Turn Clockwise Press
Anticlockwise
Screen Alarm Query Shortcut key Return Up Down Enter
69
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Operation Panel
4
1 2 3
CM1 CM2
I1 I1
I2 A I2 A
I3 I3
5 6
1 2 3 4 5 6
EMERGENCY Programmable Programmable
UNIT SWITCH 1#SYS SW. 2#SYS SW.
STOP ammeter of 1# ammeter of 2#
70
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Control functions
Enter Password ►
Main Menu 1/12
Unit Status=
Off:Password
Enter Unit Sw ►
Active Setpt=
Unit Status= 7.0°C
Off: Unit Sw
Active Setpt= 7.0°C
Step 4: Turn “UNIT SWITCH” Q0 to “ON”, the screen displays the following:
Main Menu 1/12
Enter Password ►
Main Menu
Unit Status= 1/12
Auto:
Enter Evap Recirc
Password ►
Active
Unit Setpt =
Status= 7.0°C
Auto: Evap Recirc
Active Setpt = 7.0°C
6 Temperatures 1/8
Evap LWT= 15.0°C 71
6
Evap Temperatures
EWT= 1/8
20.0°C
DAIKIN Air-Cooled Screw Chiller/Heat Pump
After the unit and water circulation started, confirm whether the water system works properly. If the controller does not
display “Auto: Evap Recirc”, see 10.1.
Step 5: Turn the “1#SYS SW.” Q1 and “2#SYS SW.” Q2 to “ON”, then unit will start and adjust load automatically.
If it need circuit 1 or circuit 2 run alone, just turn the respective switch to “ON”.
Enter Password ►
(1) Shutdown the Circuit Unit Status=
To shutdown circuit 1# or circuit 2#, turnOff:theMain Menu
switch 1/12 circuit to “OFF”. After these operations,
of the corresponding
Unit Sw
the circuit will shutdown automatically.Enter Password ►
Active Setpt= 7.0°C
(2) Shutdown the Unit
Unit Status=
Step 1: Turn “1#SYS SW.” and “2#SYS SW.” to “OFF”;
Off: Unit Sw
Step 2: Turn “UNIT SWITCH” to “OFF”.
Active
After these operations, the unit will shutdown Setpt=
automatically. 7.0°C
Main Menu 1/12
Enter Password
Main Menu ►
1/12
Setting Temperature Unit Status=
Enter Main
Password
Menu ►
1/12
Auto: Evap Recirc
Unit Status=
Enter the user password and choose “View/Set Unit” ► “Temperatures”. The following screen
Enter Setpt in
= main menu
ActivePassword then choose
7.0°C
displays: Off:
Unit Unit Sw
Status=
Active
Auto:Setpt=
Evap Recirc 7.0°C
Active
6 Setpt =
Temperatures 7.0°C 1/8
Evap LWT= 15.0°C
Main Menu 1/12
Evap EWT= 20.0°C
Enter
6 Password
Temperatures
Evap Delta T=
►1/8
0.0dK
Unit
Evap Status=
ActiveLWT=
Setpt= 15.0°C
7.0°C
Auto:
Evap EWT=Evap Recirc 20.0°C
ActiveDelta
Evap SetptT=
= 7.0°C 0.0dK
6 Temperatures 6/8
Turn the knob clockwise. The following menus
Activedisplay
Setpt= in turn: 7.0°C
Active Setpt= 45.0°C
Outside Air= 45.0°C
6 Temperatures
6 Temperatures 1/8
6/8
Cool LWT 1= 7.0°C
Evap LWT=
Active Setpt= 15.0°C
45.0°C
Cool LWT 2= 7.0°C
Evap EWT=
Outside Air= 20.0°C
45.0°C
EvapLWT
Cool Delta1=T= 0.0dK
7.0°C
Active
6 LWT
Cool Setpt=
Temperatures
2= 7.0°C
1/1
7.0°C
Cool Temperatures
6 LWT 1= 6/8
7.0°C
“Cool LWT 1” indicates the setpoint of evaporator
6 leaving water temperature1/1
Temperatures in cooling mode. The value range is
Active Setpt= 45.0°C
(4.0°C, 15.0°C).
“Cool LWT 2” indicates the double setpointOutside Air= of leaving water in 45.0°C
temperature cooling mode. The value range is
Cool
Cool LWT
LWT 1=
1= 7.0°C
7.0°C
(4.0°C, 15.0°C).
Cool
For example, to set "Cool LWT 1", select the LWT
item 2=
and press
Main Menu the knob. The 7.0°C
following
1/12 interface displays:
Enter Password ►
Unit
6 Status=
Temperatures 1/1
Main Menu 1/12
Off: Unit Sw
Enter Password ►
Active Setpt=
Cool LWT 1= 7.0°C
Unit Status=
Off: Unit Sw
ActiveEnter
Setpt=Password 2/2
7.0°C
Turn the knob clockwise to increase the value and turn it anticlockwise to decrease the value, and press the knob to
Main Menu 1/12
confirm the setting. Then the previous menu displays and the parameter setting takes effect. Other parameters can be set
Enter PW
Enter Password ****
►2/2
in the same way. Enter Password
Unit Status=
Off: Unit Sw
Enter PW ****
Active
6 Setpt=
Main Menu 7.0°C
1/15
Enter Password ►
72
Quick
6 Enter Password
menuMenu
Main ►
2/2
1/15
View/Set
Enter Unit
Password ►
►
Active Setpt =
Setpt=
Unit Status= 7.0°C 7.0°C
Auto: Evap Recirc
Active Setpt = 7.0°C
6 Temperatures
Main Menu 1/8 DAIKIN Air-Cooled Screw Chiller/Heat Pump
1/12
Evap
Enter LWT=
Password 15.0°C
►
Evap
Unit Temperatures
6 Status=
EWT= 1/8
20.0°C
Evap
Evap Delta
LWT=
Auto: T= Recirc
Evap 0.0dK
15.0°C
Active
Evap Setpt=
EWT=
Active Setpt = 7.0°C 7.0°C
20.0°C
Parameter Viewing and Setting Evap Delta T= 0.0dK
Active
6 Setpt=
Temperatures 7.0°C
6/8
6
ActiveTemperatures
Setpt= 1/8
45.0°C
6
Outside
Cool
! Air=
Evap LWT=
ActiveLWT
Evap EWT=
WARNING20.0°C
Temperatures
1=
Setpt= 7.0°C
45.0°C
6/8
45.0°C
15.0°C
Cool
Evap LWT
Delta
Outside 2=
Air=T= 7.0°C
0.0dK
45.0°C
Parameter
Parameter setting
setting mustmust be in
be in accord accord
with
Active
Cool this with this operation
1= operation manual.
Setpt=
LWT
manual.
Improper
7.0°C
7.0°C
Improper
setting can causesetting
erratic
chiller operation and damage to the
can cause erratic chiller operation chiller.
Cool LWT 2=and damage to the 7.0°Cchiller.
6 Temperatures 1/1
6 Temperatures 6/8
View/Set Circuit
Step 2: Press the knob to enter the quick menu: ►
▼
6 Quick Menu 1/13
Unit
6 Status =
Main Menu 3/15
▼Enter
6 Off:
Quick Unit
Menu
Password Sw ►
1/13
Active
Unit Setpt=
Status
Shortcut =
menu 7.0°C
►
Evap
Off: LWT=
Unit 20.0°C
View/Set UnitSw ►
Active Setpt=
View/Set Circuit 7.0°C
►
Evap LWT= 20.0°C
6 Main Menu 3/15
Enter Password ►
6 View/Set Unit 1/8
Mainmenu
6Shortcut Menu 3/15►
Status/Settings
View/Set
Enter Unit
Password
►
►►
Set-Up ►
View/Set
Shortcut Circuit
menu ►►
Temperatures ►
View/Set Unit ►
Date/Time/Schedules ►
View/Set Circuit ►
6 View/Set Unit 1/8
Status/Settings ►
View/Set Unit
6Set-Up ►
1/8
Temperatures
Status/Settings ►►
Date/Time/Schedules
Set-Up ►►
Temperatures ►
Date/Time/Schedules ►
74
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Turn the knob clockwise or anticlockwise to view other parameters in the quick menu.
Note: In the “Property” column, “R” indicates that the item can be read by user. R/W indicates that the item can be read and written
(changed) by user. The same below.
75
Enter Password
6 Main Menu ►
2/15
Quick Menu ►
Enter Password ►
View/Set Unit ►
Quick Menu
DAIKIN Air-Cooled Screw Chiller/Heat Pump View/Set Circuit
►
►
View/Set Unit ►
View/Set Circuit ►
▼6 Quick Menu 1/13
Unit Status =
View/Set Unit ▼6Off:Quick Menu
Unit Sw
1/13
Unit Status =
Active Setpt= 7.0°C
Choose the View/Set Unit menu in the main menu;
Off: press
Unit Swthe knob to view or set operation parameters for the unit.
Evap LWT= 20.0°C
Step 1: The View/Set Unit menu is as follows:
Active Setpt= 7.0°C
Evap LWT= 20.0°C
6 Main Menu 3/15
Enter Password ►
6 Main Menu 3/15
Shortcut menu ►
Enter Password ►
View/Set Unit ►
Shortcut menu ►
View/Set Circuit ►
View/Set Unit ►
View/Set Circuit ►
Step 2: Press the knob to enter the View/Set Unit menu:
6 View/Set Unit 1/8
Status/Settings
6 View/Set Unit
►1/8
Set-Up ►
Status/Settings
Temperatures
►
►
Set-Up
Date/Time/Schedules ►
►
Temperatures ►
Date/Time/Schedules ►
Status/Settings
After entering the Status/Settings menu, you can view and set the following parameters:
76
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Set-Up
Temperatures
77
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Date/Time/ Schedules
78
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Power Conservation
Ctrlr IP Setup
Design Conditions
Menu Password
79
DAIKIN Air-Cooled Screw Chiller/Heat Pump
View/Set Circuit
Choose the View/Set Circuit menu in the main menu, press the knob to view and set operation parameters for the circuit.
Step 1: The View/Set Circuit menu is as follows:
Circuit #1
6 View/Set Circuit
►
1/2
Circuit #2 ►
Circuit #1 ►
Circuit #2 ►
Status/Settings
Comp 1/2
Circuit #1 ►
Choose the Time Until Restart menu in the main#2menu, press the knob to view
Circuit ► the remaining time to restart for the
system.
Step 1: The Remaining time to restart is as follows:
81
Enter Password ►
6
Quick Main Menu
menu ►
4/15
View/Set
Enter Unit
Password ►
View/Set
Quick
6 Circuit
menu
Main Menu ►11/15
DAIKIN Air-Cooled Screw Chiller/Heat Pump
View/Set Unit
Evap LWT=
►
20.0°C
View/Set Circuit
Unit Capacity =
►
00.0%
Unit View/Set
6 Mode = Circuit Cool
1/2
Time Until Restart
Circuit #1 ►►
Step 2: Press the knob to enter the Time
6 Until Restart
View/Set menu:
Circuit 1/2
Circuit #2 ►
Circuit
6 #1 Main Menu ►
4/15
6
Circuit
Enter Time Until Restart
#2
Password ►►1/2
Quick
C1 menu
Cycle Tm Left ►0s
MainUnit
6 View/Set Menu ►
11/15
C2 Cycle Tm Left 0s
View/Set
Evap LWT=Circuit ►
20.0°C
6 Main Menu
Unit Capacity = 11/15
00.0%
Unit
EvapMode
LWT== Cool
20.0°C
No. Menu Property Unit Description
1 C1 Cycle Tm Left
Time
R Unit
Until Restart
Capacity
s =Menu
View
►
the remaining00.0%
time
1/2before
6
6 View/Set
Main Circuit 13/15 compressor 1 can be restarted
2 C2 Cycle Tm Left R Unit Mode s= Coolbefore compressor 2 can be restarted
View the remaining time
Unit Mode
Circuit
Time
=
#1Restart
Until ►►cool
Time Until Restart
Circuit #2 ►►
6AlarmsTime Until Restart 1/2►
Scheduled Maintenance
Scheduled Maintenance
C1 Cycle Tm Left 0s►
6 Time Until Restart 1/2
Choose the Scheduled Maintenance in the main Tm
C2 Cycle menu,
Left press the knob to check
0s the information about scheduled
maintenance. C16 CycleMain Menu
Tm Left 11/15
0s
Step 1: The Scheduled Maintenance
C2 isCycle
EvapasLWT=
follows:
Tm Left 20.0°C
0s
6 Scheduled Maintenance 1/3
Unit Capacity = 00.0%
Next Maint= Nov 2010
Unit Mode
6 Main=Menu Cool
13/15
Support
Time Reference=
Until Restart ►
Unit Mode = cool
999+555-5555
Time
6 Until
Main Restart
Menu ►
13/15
Alarms
Unit Mode = ►
cool
Scheduled
Time
6 Until Maintenance
Restart
Time Until Restart
►
►1/2
Alarms
6 Main Menu ►
14/15
C1 Cycle Tm Left 0s
Scheduled Maintenance ►
Time Until
C2 Cycle Tm Restart
Left ►0s
Step 2: Press the knob to enter the Scheduled Maintenance menu:
6
AlarmsScheduled Maintenance ► 1/3
Next Maint= Maintenance
Scheduled ►
Nov 2010
6 Scheduled Maintenance 1/3
Support Reference=
About Chiller ►
Next
6 Maint=
Main Menu
999+555-5555 Nov 2010 13/15
Unit Mode
Support =
Reference= cool
Time Until Restart
999+555-5555 ►
Alarms ►
Main Menu
6Scheduled Maintenance 14/15►
No. Menu Property Unit
Time Until Restart ► Description
1 Next Maint R/W 6 -- Main View the next maintance time
Menu 14/15
2 Support Reference R Alarms
-- View the telephone number ►of technical support personnel
Time Until Restart ►
6 Scheduled
Scheduled Maintenance Maintenance ► 1/3
Alarms
About
Next Chiller
Maint=
►
►
Nov 2010
About Chiller Scheduled Maintenance ►
Support Reference=
About Chiller
999+555-5555 ►
Choose the About Chiller in the main menu, press the knob to check the relevant data of the unit.
Step 1: The About Chiller is as follows:
82
DAIKIN Air-Cooled Screw Chiller/Heat Pump
Press the knob to confirm the setting. Then return to previous level menu.
83
Warning ● Daikin Industries, Ltd.’s products are manufactured for export to numerous countries throughout
the world. Daikin Industries, Ltd. does not have control over which products are exported to and
used in a particular country. Prior to purchase, please therefore confirm with your local authorized
importer, distributor and/or retailer whether this product conforms to the applicable standards, and
is suitable for use, in the region where the product will be used. This statement does not purport to
exclude, restrict or modify the application of any local legislation.
● Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
● Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorized parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
● Read the User’s Manual carefully before using this product. The User’s Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.