MULTI STOREY COMMERCIAL BUILDING (G+4) PLAN
ALL DIMENSIONS ARE IN FEET’S AND INCHES
Column positioning
SLAB NUMBERING
BEAM NUMBERING
COLUMN NUMBERING
PRELIMINARY DESIGN
i.e., Ly /Lx>2
Thickness of slab:
Effective span:
Ly/Lx =3.17/3.17 =1
Loads:
=(6.37×106/0.138×20×1000)1/2
Span of beam=3.05+2×0.3/2=3.35m
Grade of concrete=M20
Grade of steel=Fe415
=(1/2×3.35×1.675)×2
=5.611m2
Load calculations
= (1.525+1.525) × (1.525+0.762)
=6.97 m 2
= (4×3.5×0.3×0.35×25)+(1×0.3×0.35×25)
=39.375 KN
=563.00KN ~ 565 KN
= (4×(28+13.95)) × (1-0.3)
=117.46 KN
=117.5 KN
Pu =0.4fckAc+0.67fyAsc
1142.67×1000=7.84Ag+5.561Ag
= (4×3.5×0.23×0.35×25)+(1×0.23×0.35×25)
=30.187 KN
=563.08KN = 565 KN
= (4×(28+13.95)) × (1-0.4)
=100.68 KN
=101 KN
Pu =0.4fckAc+0.67fyAsc
1105×1000=7.52Ag+16.683Ag
Kani’s method
.
Procedure for Analysis a frame by Kani’s method
1.Calculation of loads that are imposed on to the respective beams and
convert them into U.D.L. The different loads effective on to the beams are
slab load ,floor finish ,wall load ,load of the beam and live load.
5.Place the R.F, Fixed end moments in the exact pattern for iterating moment
contributions also, displacement contributions if sway exists.
CALCULATIONS:
Loads:
Dead load on slab = 0.12×1×25 = 3KN/m
Live load =4×1 =4 KN/m
Floor finishes = 1×1 = 1KN/m
Partition load = 1×1 = 1KN/m
Total load W = 3+2+1+1 = 9 KN/m
Factored load W = 1.5×7 = 13.5KN/m
u
As per IS: 456-2000(Clause D.2.1),
The bending moment coefficients are αx αy
-Ve moment at continuous edge 0.047 0.047
+Ve moment at mid-span 0.035 0.035
Negative B.M at continuous edge in shorter span = αxWl x2
= 0.047×13.5×3.17 = 6.37KNm
2
=0.035×13.5×3.17 = 4.74KNm 2
= 0.035×13.5×3.17 = 6.37KNm 2
= (6.37×10 /0.138×20×1000)
6 1/2
A = 150.96 mm
st 2
Consider least of it
1. 300 mm
2. 3d =3 x 120 =360mm
3. 333.002 mm
A = 111.6 mm
st 2
Consider least of it
1. 300 mm
2. 3d =360mm
3. 300 mm
A = 150.96 mm
st 2
Consider least of it
1. 300 mm
2. 3d = 360mm
3. 333 mm
A = 111.6 mm
st 2
Consider least of it
1. 300 mm
2. 3d = 360mm
3. 300 mm
V = W L / 2 =(13.5 × 3.17)/2=21.4 KN
u
From IS 456-2000
τC=0.28 N/mm 2
τC > τv
P = A × 100/ bd = 0.1258
t st
Effective cover = 20 mm
M = 153.05 KN-m
u lim
M >M
u lim u
M=0.87×fy×A ×d(1-A ×fy/fck×b×d) st st
A = 612.63 mm
st 2
REINFORCEMENT AT END A:
Where, ( Xu max/d)=0.48
Where,( Xu max/d)=0.48
M = 153.05 KN-m
u lim
M >M
u lim u
A = 131.74 mm
st 2
Acts as T beam
b = (4800/6)+(300)+(6 x 120)
f
b = 1820 mm
f
( Xu max/d)=0.48
( X /480)=0.48
u max
M = 0.36 x f x b x X (d – 0.42 X )
u ck f u u
X = 20.46 mm
u
X >X
u max u
REINFORCEMENT:
A = 848.57 mm
st 2
SHEAR REINFORCEMENT :
V = W L / 2 =(57.895 × 4.8)/2=138.948 KN
u
From IS 456-2000
τC=0.566 N/mm 2
τC < τv
shear reinforcement is required
A = 2 x π/4 x 8 = 100.5 mm
sv 2 2
Sv = 236.74 ~ 230mm
(i) 230mm
(iii) 300mm
P = A × 100/ bd = 0.779
t st
CALCULATION:
Dimensions = 300mm x 350mm
Design load = 927.789 KN
Moment in X X = 14.68 KNm
Moment in Y Y = 4.86 KNm
In YY direction
In XX direction ,
e = L/300 + D/30
min both ends are fixed
Therefore , e = 20mm
min
In YY direction ,
Therefore , e = 19.33mm
min
ECCENTRICITIES AS PER CODE
Actual eccentricities are less than minimum eccentricity and eccentricities as per code
P = 0.4×f ×A +0.67 f A
u ck c y sc
A = 2042.88mm
sc 2
Using 20 mm diameter bars,
a = /4x 20 = 314.5 mm
st 2 2
CHECK :
LATERAL TIES :
(ii) 6 mm
2)16 times bar dia =16×20 =320mm [16 x diameter of the bar]
3)300mm
= 92.77 KN
Total load = W + W c f
= 927. 78 + 92.77
=1020.55KN
=1020.55/230
= 4.43m 2
=662.699(0.9-d)
= 596.42 - 662.699d
= 605.073(0.975-d) -(1)
= 672d -(2)
672d=589.94-605.07d
d=0.461m
ii) Two-way shear:
= q × (XY-(0.23+d) x (0.5+d))
u
= c. A
=perimeter x d
=((0.3+d) +(0.35+d)) d
=(0.65+2d) d
d = 0.575 m
iii) Depth of footing by bending moment
= 287.598KN-m
=268.39 KN-m
M =0.138 x f x b x d
u ck 2
d=222.75mm~0.225 m
d=0.575mm
=638 ~650 mm
A =1377.19 mm
st 2
A =1280.66 mm
st 2
=2484 mm >1280mm 2 2
Total reinforcement in shorter direction = 2/B+1 where,B=y/x = 2.3/2.1 =1.0952 Reinforcement in central band/2484 = 2/1.095+1
= 2371.13mm 2
Spacing S =
v 201.06/2371.13 x 2100 = 178.00 ~170mm c/c
(ii) 300
(iii) d=592
= 2100-300/2
=900mm >752.2mm
Hence Ok
DESIGN OF STAIR CASE
Thread = 250 mm
=9 - 1= 8
=8 x 250 =2000mm
d =(M
req u lim /0.138 fck b) 1/2
= 11.22 mm ~ 105mm
d >d
prov req
=167.5 mm ~170mm
= 5.44KN/m
= ½ x 0.2x 0.25 x 25
=0.625 KN/m
= 2.5KN/m
=8.44 KN/m
= 5 x 1 = 5 KN/m
= 28.28 KN- m
MAIN REINFORCEMENT
Ast = 594.94mm 2
Spacing Sv =( ( (π /4 ) x 12 ) /A ) x 1000
2 st
Sv =( ( (π /4 ) x 12 ) /594.94) x 1000
2
= 190.08mm ~ 190 mm
(i) 190mm
(ii) 450mm
DISTRIBUTION REINFORCEMENT
Spacing Sv =( ( (π /4 ) x 10 ) /A ) x 1000
2 st
Sv =( ( (π /4 ) x 10 ) /594.94) x 1000
2
=384.95mm ~ 380 mm
Consider lesser of the following
(i) 380mm
(ii) 450mm
Provide 10mm diameter bars at a distance of 380 mm center to center spacing for distribution reinforcement