Moment
would be redistributed / transfered from the slab. If simple supported the load from the slab will
act at 1/3 the bearing length giving a small eccentricity from the centre line.
Well, per ACI section 14.3.6 you can count on vertical reinforcement as compression
reinforcement without ties as long as the steel area is less than 0.01 x Ag.
Local axis definition in Etabs, V13 in plane shear in vertical plane, V23 out plan shear in
horizontal plane( plane 2)
Normal or 3rd Blue
1st Red
2nd White
in CSI Analysis Reference manual at p.144 is specified that F11&F22 are axial forces along axis
1&2, F12 is shear within plane 1-2, M11&M22 are bending moments out of plane, and M12 is
torsional moment, and V13&V23 are transverse shear out of plane
CALCULATION
Calculate the ultimate resistance of soil ( R ) using the formula given below.
R = (w * h) / d
Where,
NOTES TO REMEMBER
1. F.O.S varies from 2 to 3 depending upon the type of structure and site condition.
2. In order to get reliable test result, perform this test on different types of soil and then use your
judgment to reach at any conclusion.
3. Instead of using solid steel ball or square cube, we can also use CBR test plunger, or Cone
(used for cone penetration test)
NOTES TO REMEMBER
1. For non-cohesive soils the values should be reduced by 50% if the water table is above or near
base of footing.
2. These values should be used only for preliminary design. The actual bearing capacity of soil
should be calculated as per the standard codes.
The Mackintosh Probe development was based on the principles stated by Hvorslev
(1948) for drive rods for sounding and sampling and recommended methods for static
and dynamic sounding by European Group Subcommittee (1968). The probe consists
of a cased screwed onto the lower end of the rod. The rods are of 16mm diameter HY
steel each of length 120 cm. The rods are connected to each other by 25 mm outer
diameter couplings. These couplings provide the lateral support to the rods so as to
prevent buckling during driving. Driving is performed with a small hammer of 5 kg in
weight and falling vertically through a fixed height of 30 cm along a guide rod. The
total number of blows required for the pointer to penetrate a distance of 30 cm is
recorded and used as a measure of the consistency of cohesive soil and the packing of
granular soil.
Where,
P = safe pressure (kN/m2)
R = Mackintosh Probe Penetration resistance in blows/0.3m
Plain Wall Check
In the following, the concrete area is the gross area of the general wall, or the gross area of the mid
zone if one exists.
For the end zone the design criteria for a reinforced concrete column element applies.
Before placing vertical reinforcement in the wall, the following checks are performed to determine if the
given section of wall can act potentially as a plain wall or not.
a) Check for stresses at the corner of a wall
If there are no tensile stresses developed in the wall it is in compression throughout and check
passes.
b) Check for bending utilization
Check the bending utilization is less than 10%
i.e Asc, required = 0.1*0.0025* Ac = 0.00025* Ac (For fy=500 N/mm2)
Asc, required = 0.1*0.003* Ac = 0.0003* Ac (For fy=250 N/mm2)
The figure 10% stated above is not code dependent value, it is a matter of engineering judgment.
Limiting minimum ratio of vertical reinforcement area to gross concrete area, v,lim,min
Limiting maximum ratio of vertical reinforcement area to gross concrete area, v,lim,max
The recommended values are:7
IF nw ≥ 0 (i.e compression)
Total minimum area of vertical reinforcement, Asc,min = v, lim,min*Ac = 0.004*Ac
Total maximum area of vertical reinforcement, Asc,max = v,lim,max*Ac = 0.04*Ac
Where
Ac = Gross area of the concrete wall
nw = The total design axial load on the wall due to design ultimate loads
Where 2 layers are specified distributed equally to each face, this is a minimum of 0.002*Ac placed at
each face.
ELSE
Total minimum area of vertical reinforcement, Asc,min = v, lim,min*Ac
= 0.008* Ac (For fy=250 N/mm2)
= 0.0045* Ac (For fy=500 N/mm2)
In this case reinforcement should be placed in 2 layers.
BS 8110-1:1997 equation 43
BS 8110-1:1997 equation 44
BS 8110-1:1997 equation 45
BS 8110-1:1997 equation 46
BS 8110-1:1997 cl 3.9.4.18
BS 8110-1:1997 cl 3.9.4.19
BS 8110-1:1997 cl 3.12.7.5
BS 8110-1:1997 cl 3.9.3.5
Horizontal reinforcement
For some of the horizontal bar parameters, additional user defined limits can be applied - where this is
the case values are specified in Design Options > Wall > Reinforcement Layout.
Limiting minimum ratio of horizontal reinforcement area to gross concrete area, h,lim,min
Limiting maximum ratio of horizontal reinforcement area to gross concrete area, h,lim,max
Where the main vertical reinforcement is used to resist compression and does not exceed 2% of the
concrete area, at least the following percentage of horizontal reinforcement should be provided,
depending upon the characteristic strength of reinforcement.1
Minimum area of horizontal reinforcement, Ash,min = h, lim,min*Ac
= 0.003*Ac (For fy = 250 N/mm2)
= 0.0025*Ac (For fy = 500 N/mm2)
Where
Ac= Gross area of the concrete wall
fy = Characteristics strength of reinforcement.
IF
Asc > 0.02*Ac
THEN
Links are provided as per section Link/Containment Reinforcement in addition to the above
requirement.2
Although not a BS code requirement, an additional check is performed for the maximum area of
horizontal reinforcement:
Asc,maxsh,max = h,lim,max*Ac = 0.04*Ac
BS 8110-1:1997 cl 3.12.7.4
BS 8110-1:1997 cl 3.12.7.5
BS 8110-1:1997 cl 3.12.7.4
BS 8110-1:1997 cl 3.12.11.1
Link/Containment Reinforcement
The containment steel reinforcement provided in the form of link contributes to the shear resistance.
It must be provided when the vertical area of reinforcement in the 2 faces exceeds 0.02*Ac1
Reinforcement area
There is no code requirement to satisfy.
It is expected that the maximum diameter of link, w,max will not be greater than the vertical bar
diameter.
v,max ≤ v
BS 8100-1:1997 cl 3.12.7.5
BS 8100-1:1997 cl 3.12.7.5