RELAY CO-ORDINATION
AND
RELAY SETTING REPORT
PROJECT : BSVI
CLIENT : IOCL.
LOCATION : BONGAIGAON
HOLD:
1. HV, MV MOTOR, VFD.
Format No. EIL 1641-1924 Rev. 1 Copyright EIL – All rights reserved
DOCUMENT No.
RELAY CO-ORDINATION & RELAY
SETTING REPORT A888-999-16-50-49410 Rev. 0
Page 2 of 4
INDEX
S. NO. DESCRIPTION
1.0 GENERAL
Format No. EIL 1641-1924 Rev. 1 Copyright EIL – All rights reserved
DOCUMENT No.
RELAY CO-ORDINATION & RELAY
SETTING REPORT A888-999-16-50-49410 Rev. 0
Page 3 of 4
1.0 GENERAL
1.1 Introduction
The intent of this document is to cover the relay co-ordination aspect for various
switchboards in the refinery complex and provide relay settings for all relays being
used in the switchboards across the BSVI Project located at Bongaigaon.
2.0 Brief Description of the Electrical System
The BSVI Project includes, but is not limited to, the following:
Process Units
These units form part of overall BSVI Project, which includes Process units such as
NHT, SRU/SWS/SRU, and revamp of existing DHDT and HGU units and offsites
facilities.
Power Supply/ Distribution System
Power for BSVI facilities shall be made available from S/S-31 at 6.6kV level. It shall be
further stepped down to 415V using 6.6/0.433kV distribution transformers.
Power for revamp loads shall be obtained from the existing switchboards in existing
substations by addition of extension panels/ addition of feeders in vacant modules.
All HV motors above 110 KW shall be fed from 6.6kV switchboards. 6.6kV power shall be
stepped down to 415V using 6.6kV/0.433kV distribution transformers for feeding 415V loads
through power control centres (PCC), motor control centres (MCC), auxiliary service board
(ASB) and lighting distribution boards (LDB) in Substations.
MV motors up to 55 kW shall be fed through PMCCs/MCCs, whereas motors rated from 55
kW to 110 kW should be fed from PMCCs/PCCs. A separate auxiliary service board shall be
provided in each substation to feed miscellaneous loads like Power Panels, welding
receptacles etc.
Lighting system shall consist of Normal/Emergency lighting distribution boards (LDB/ELDB),
energy saving lighting system panels complete with transformer, Lighting and power panels
etc. Substations shall have adequately rated 415V/415V lighting transformer(s). Separate
lighting transformers shall be provided for ‘normal’ and ‘emergency’ lighting. Critical lighting
at 220V DC shall be catered by DCDB.
220V DC system located at substation shall cater to control supply for switchgear control &
critical lighting. 110V AC UPS system provided in SRR shall be used for all the Un-
interrupted power supply requirements of DCS, Instrumentation/Electrical loads .
Format No. EIL 1641-1924 Rev. 1 Copyright EIL – All rights reserved
DOCUMENT No.
RELAY CO-ORDINATION & RELAY
SETTING REPORT A888-999-16-50-49410 Rev. 0
Page 4 of 4
3.4 The through fault current for various distribution transformers are as tabulated below:
Format No. EIL 1641-1924 Rev. 1 Copyright EIL – All rights reserved
Document no.: A888-999-16-50-1740
500 500
300 300
R-I/C-1 HV 35211 - N
OC1
R-B/C HV 35211 - N
100 OC1 100
30
R-B/C PCC-35301 - N 30
OC1
R-I/C-2 PCC-35031 - G - 51
OC1
10 10
R-O/G PCC-35031 - N
OC1
5 R-B/C MCC-35311 - N 5
Seconds
Seconds
OC1
3 3
R-I/C-2 PCC-35031 - N - 51
OC1
1 R-I/C MCC-35311 - N 1
OC1
.5 .5
.3 .3
.1 .1
.05 .05
.03 .03
R-B/C HV
R-I/C-1 H
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Star5
500 500
CB1 R-PANEL NO. 5(31-HV-214) - P
300 OC1 300
R-B/C HV 35211 - P
R-B/C MCC-35311
OC1- P
100 100
OC1 R-I/C-1 HV 35211 - P
OC1
50 50
30 30
10 10
Seconds
OC1
3 3
R-I/C-2 PCC-35031 - P - 51
OC1
1 1
R-B/C PCC-35301 - P
OC1
.5 .5
R-O/G PCC-35031 - P
.3 OC1 .3
.1 .1
R-I/C MCC-35311 - P
.05 OC1 .05
.03 .03
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Star5
Notes:
1) All relays are to be set as nondirectional.
2) t Reset for IDMT all relays shall be set as 0 sec.
3) NA : Not applicable
4) 27 U setting is indicative and same shall not be connected to 86
(OUTGOING FEEDERS)
NEMA NO. Relay Elements 1000A ACB 800A ACB
Notes:
1) All CTUM 15 Relays in MCCB and MCCB+CONTCATOR feeders shall be set at 10% & 1Sec.
(BUS PT FEEDERS)
NEMA NO. Feeder Type Bus PT Bus PT
Switchboard no. (Substation No.)
PCC MCC
Panel nos.
Relay Model/ Make REF-615H
Main VT Ratio 415 / 110 V
27 VT Connection 3 Vpn
Function OR
Voltage Setting 40%
27 R
Delay Type DMT
Time Setting 0 Sec.
Function OR
Voltage Setting 80%
27C27 H
Delay Type DMT
Ie> Function DT DT
Note:
1) t Reset for all IDMT relays shall be set as 0 sec.
2) NA : Not applicable
Panel nos.
Relay Model/ Make REU615
Main VT Ratio 6600 / 110 V
27 VT Connection 3 Vpn
Function OR
Voltage Setting 0.40
27 R
Delay Type DMT
Time Setting 0 Sec.
Function OR
Voltage Setting 0.80
27C
Delay Type DMT
Time Setting 3 Sec.
(TRANSFORMER FEEDERS)
NEMA NO. Feeder Type 2500 KVA Trafo. Feeders
Switchboard No. (Substation No.) HV-61211 HV-61212
Panel Nos.
Receiving end Trafo. No. TR-35031, TR-35033 TR-35032, TR-35034
Rating 2500 KVA
Relay Model/ Make REF620
Main CT Ratio 250/1A 250/1A
I>> Function
Ie> Function
Ie> Function
Note:
1) t Reset for all IDMT relays shall be set as 0 sec.
2) NA : Not applicable
2. Relay settings