Project Title: Structural Assessment and Detailed Engineering Design for the Repair and Retrofitting of Government Buildings

ent Buildings in Preparation for "The Big One" Contract Package 2


Location: Havana Building - Juan Sumulong Elementary School (Manila City)
Client : Department of Public Works and Highways - National Capital Region
Subject : FOOTING CAPACITY INVESTIGATION

Footing Mark : F2
I. INPUT DATA

421.2 Strength reduction factor


Table 421.2.2 (e/f) φ tension 0.90
Table 421.2.1 (b) φ shear 0.75
420.6.1.3 Concrete cover 0.075 m

Given Footing Dimension:


Along b 2.4 m
Along h 2.4 m
depth of footing, e 1.5 m
thickness of footing , g 0.38 m
Effective depth, dact = t - cover - 1.5db 0.275 m
arm 1.12 m

Given Footing Reinforcement:


Rebar diameter
Along b 0.02 m
Along h 0.02 m
c-c Spacing
ALong b 0.2 m
Along h 0.2 m

Given Column Dimension


Column, j 1 m
Column, k 0.2 m
L 1.1 m
m 0.7 m

Unit wt of soil, gsoil 18 kN/m3

Unit wt of concrete, gc 23.6 kN/m3


Concrete compressive strength, fc' 10.349 MPa
Steel yield strength, fy 231 MPa
Allowable bearing pressure (1.5 m below the ground) 100 kPa

II. SOLVING FOR BEARING PRESSURES


Determine max and min bearing pressure on soil :
- Use unfactored loads
- Include weight of pedestal
- Include weight of footing
- Include weight of soil on top of footing
- Resolve shear forces into equivalent moment forces on footing
- Moment forces are in two directions Mx and Mz
- Add Moment due to DL and LL

Pedestal Load/ Column Load = 0.00 kN


Weight of Footing = 51.66 kN
Weight of Soil = 112.09 kN

Fx Fy Fz Mx My Mz
Node No. Footing No. Load Case
kN. kN. kN. kNm. kNm. kNm.
297 1 DL -2.18 497.64 8.54 13.99 0.03 5.54
F2
2 LL -0.19 66.32 1.89 3.03 0.00 0.27

Demand Forces FY (add


Node No. Footing No. Load Case MX MZ pedestal)

Mx1+Mx2 My1+My2 Fz1+Fz2


1 DL 13.99 5.54 497.64
297 F2