Beruflich Dokumente
Kultur Dokumente
VCV Tower
(The highest cable production
line in Asia-Pacific)
International Standard
Introduction Cable Construction
Medium and high voltage power cable is one of the most important parts in power systems. They are exploited to Medium voltage underground power cable basically consists of the following parts.
distribute electrical energy between power plants, substations, factories and residential area. The premier quality and reliability
of the cables are necessary in order to prevent the outage of electricity supply occurring from the failure of the cable.
Phelps Dodge International (Thailand) Ltd. is the leader in medium and high voltage power cable, with the experiences
in manufacturing cables more than 40 years. We have state of the art facilities that can produce the high voltage underground
cable with the rated voltage up to 245 kV. The cables have been vigilantly designed to exceed international standards such as
IEC, ICEA, UL, DIN, VDE, AS/NZS, TIS, IS and other standards specified by customers. Materials used for manufacturing cables
have been thoroughly selected with stringent quality control system so as to ensure the high quality of the cable.
One important part of high voltage power cable is its insulation. In order to isolate the conductor from ground and other
conductors, materials with the best electrical and physical properties must be chosen. Cross-linked polyethylene (XLPE), since
its development in 1950s, became the material of choice for insulating power cable, because of its superior electrical property,
low dielectric loss angle and ease of installation and maintenance when comparing to conventional oil-filled cable and impregnated
paper insulated cable.
RatedThe rated
Voltage of Power Cable Components Detail Function
voltage of power cable is designated as follows.
U0/U (Um) Conductor Copper or Aluminium Carry the required current.
U0 = Phase-to-ground voltage Conductor shield or screen Semi-conducting compound Uniform electric field around
U = Phase-to-phase voltage (sometimes called “rated voltage”) the normally unsmooth
Um = Maximum value of the “highest system voltage” for which the equipment may be used. conductor and ensure close
Occasionally, the U0/U of the cable is different but the Um is the same. This indicates that these cables can be used on contact to the insulation.
the same system voltage which the rated voltage does not exceed Um. Insulation Cross-linked Withstand the operating voltage
Example: 12/20 (24) kV and 12.7/22 (24) kV can be used on the same system voltage that the rated voltage does not exceed 24 kV. polyethylene (XLPE) including impulse voltage from
Below is the recommendation of IEC 60502-2 for the selection of the rated voltage of cable.
lightning.
The rated voltage of the cable for a given application shall be suitble for the operating condition in system in which the cable is
used. To facilitate the selection of the cable, system are divided into three categories: Insulation shield or screen Semi-conducting compound Uniform electric field around
- category A : this category comprises those systems in which any phase conductor that comes in contact with earth or an the insulation and ensure close
earth conductor is disconnected form the system within 1 min: contact to the insulation and
- category B : this category comprises those systems which, under fault conditions, are operated for a short time with one prevent ionization in air space
phase earthed. This period, according to IEC 60183, should not exceed 1 h. For cables covered. This period, between insulation and metallic
a longer period, not exceeding 8 h. on any occasion, can be tolerated The total duration of earth faults in any shield which lead to the damage
year should not exceed 125 h; of the inslation.
- category C : this category comprises all systems which do not fall into category A or B. Metallic shield or screen Copper wire or Copper tape or Provide ground potential and
It should be realized that in a system where an earth fault is not automatically and promptly isolated, the extra stresses on the Lead sheath electrical path for the
insulation of cables during the earth fault reduce the life of the cables to a certain degree, if the system is expected to be capacitance discharge of the
operated fairly often with a permanent earth fault, it may be advisable to classify the system in category C.
insulation.
The values of U0 recommended for cables to be used in three-phasa systems are listed in Table 1.
Carry the single line to ground
fault current.
Recommended rated voltages U0 Binding tape Non-hygroscopic tape Provide smooth surface for the
Highest system voltage Rated voltage (U0) oversheath.
(Um) kV
Oversheath Polyethylene (PE) or Polyvinyl Provide environmental protection
kV Categories A and B Categories C
Chloride (PVC) i.e. mechanical, chemical, thermal
7.2 3.6 6.0
12.0 6.0 8.7 and moisture to the underlying
17.5 8.7 12.0 components.
24.0 12.0 18.0
36.0 18.0 - Besides the above basic construction, there are special components which added preferable property to the cables.
Special Function
In addition to the above cable construction, customer can request the special functions to provide superior protection and
ensure the long life of the cables.
We are capable of producing extra high voltage XLPE cables up to voltage of 245 kV. Furthermore, we are the To mitigate this shortcoming the Milliken conductor was developed. So today, all large conductors are constructed
only one in Thailand that can produce the highest size of cable going up to conductor size of 2,500 mm². Especially from 4 to 5 sector shaped conductors assembled together to form one round conductor. Each sector shaped conductor is
manufacturing cables of conductor size 1,000 mm² and higher is a case in point. These are commonly produced with lightly insulated so that this reduces the AC resistance by increasing the surface area at the edge which normally carries
Milliken construction with associated ability of higher current capacity as well as more flexibility as compared to traditional most of the current. As an example the Milliken conductor can carry at least 5% more current than a round compacted
round compacted conductor of the same size. Additionally the factory is fitted with specialized machinery capable of conductor of 1,000 mm². It is not economic to use this concept for smaller conductors, below 900 mm². Obviously higher
producing two types of special sheath such as Corrugated Metal Sheath and Seamless Lead Sheath. Both types of sheat the size of conductors more are the number of sectors.
have properties of near-perfect moisture barrier an important characteristic requirement for Power Cables as these guarantee
protection of cables in wet environment. Moreover the advantage of Lead sheath is that it can protect the cable insulation Such segmental conductors require critical manufacturing capability and PDITL is one of the few manufacturer to
from oil, chemicals and sulfides which makes it the preferred type for almost all petrochemical and refinery plants. possess such expertise. Another benefit from Milliken conductor is the greater flexibility of conductors compared to the round
compact conductor of the same size.
Milliken conductor, corrugated metal sheath and lead sheath need advance technology support, modern machinery
and expertise of production. Phelps Dodge International (Thailand) Limited is the one and only manufacturer in Thailand
who are capable of manufacturing Cables with these special construction, enabling us to support and provide nearly all
applications desired by the customers.
Milliken Conductor
Milliken Conductor Corrugated Metal Sheath Lead Sheath
• Higher Current carrying • Protection against physical / • Protection against physical /
capacity mechanical damage mechanical damage
• Increased flexibility • High Level of Moisture barrier • Near–perfect Moisture barrier
• Protection against Oil,
Chemicals and Sulfides
Corrugated Metal Sheath Lead Sheath
Aluminium, Copper and Stainless Steel can be used for corrugated metal sheath. The main function of all these types are to Lead is a very stable metal. Some lead water pipes have survived since Roman time. Extruded lead sheath is a perfect
create a perfect moisture barrier for power cables which imparts the protection of cables required for wet environment. moisture barrier. It also can prevent the cable insulation from oil, petrochemical and sulfides. Most petrochemical and refinery
The metal sheath is extruded over the insulation screen which is normally covered with semi-conductive water swellable tape. plant prefer cable with lead sheath. The cable with lead sheath has very long life. The advantage of lead sheath also includes
its flexibility and no mechanical stress exert on the cable insulation during production.
The metal sheath is seam welded by using TIG (Tungsten Inert Gas) welding technique and the integrity of the weld is ensured by
using eddy current detection equipment. Corrugation of course helps to reduce any rigidity of sheathing and will increase flexibility. Phelps Dodge International (Thailand) Ltd. has the capacity to manufacture cables with lead sheath starting from small
Corrugated Aluminium Sheath low voltage cable to extra high voltage cable.
Cables with corrugated aluminium sheath have high fault current carrying capability due to the high electrical conductivity of
Aluminium. This results in reduction of the external magnetic field and induced voltage. Good mechanical protection is also
achieved from Aluminium sheath due to its rigidity. The bitumen coating or bituminized tape over the Aluminium can be
requested to increase the corrosion resistance.
CABLE NAME REFERENCE STANDARD PAGE NO. 15 kV ALUMINIUM STRANDED CONDUCTOR CROSS-LINKED
POLYETHYLENE INSULATED AND SHEATHED SPACED AERIAL CABLE
Aluminium Aerial Cable
1) SPACED AERIAL CABLE
Cross-linked polyethylene insulation
15 kV Spaced aerial cable PDITL / MEA / PEA 1 APPLICATION :
25 kV Spaced aerial cable TIS 2341-2555 / MEA / PEA 2 For used in primary aerial cable
Cross-linked polyethylene sheath
35 kV Spaced aerial cable TIS 2341-2555 / MEA / PEA 3 on pole.
2) PARTIAL INSULATED CABLE
15 & 25 kV Partial insulated cable PDITL / MEA / PEA 4
35 kV Partial insulated cable PDITL / MEA / PEA 5 CLASSIFICATION :
Temperature :
Copper Underground Cable with XLPE Insulation Extruded semi-conducting Cross-linked
- Normal operation 90°C. polyethylene conductor shielding layer
1) SINGLE CORE - Emergency over load conditions Compact Aluminium conductor
130°C.
MXLP-CTS
- Short circuit conditions 250°C.
Copper conductor with copper tape shield IEC 60502-2 6-15
Voltage rating :
MXLP-CWS 15 kV phase to phase.
Copper conductor with copper wire shield IEC 60502-2 16-25
AC TESTING VOLTAGE : CONSTRUCTION :
MXLP-DATA
27 kV for 5 minutes Conductor : Compact stranded hard drawn Aluminium wire.
Copper conductor with double aluminium tape armour IEC 60502-2 26-35
Conductor shield : Semi-conducting cross-linked polyethylene.
MXLP-AWA REFERENCE STANDARD : Insulation : Cross-linked polyethylene (Natural)
Copper conductor with aluminium wire armour IEC 60502-2 36-45 PDITL / MEA / PEA Sheath : Track resistant cross-linked polyethylene (Black)
MXLP-LS-AWA
Copper conductor lead sheath cable with IEC 60502-2 46-53
aluminium wire armour Nominal Minimum Diameter Thickness Thickness Overall Maximum Minimum Allowable Cable Standard
cross - number of of of diameter DC. insulation ampacities weight packing
2) THREE CORES sectional of wire conductor insulation sheath (Approx.) conductor resistance in free (Approx.)
area (Approx.) resistance at 15.6°C air at 40°C
MXLP-CTS (3 cores)
Copper conductor three cores with copper tape shield IEC 60502-2 54-63 at 20°C ambient
MXLP-SWA (3 cores) 95 15 11.4 1.91 1.91 21.0 0.320 1,284 281 451 1,000/R
Copper conductor three cores with steel wire armour IEC 60502-2 74-83 120 15 12.9 1.91 1.91 22.5 0.253 1,152 324 552 1,000/R
150 15 14.1 1.91 1.91 24.0 0.206 1,070 375 639 1,000/R
MXLP-LS-SWA (3 cores) 185 30 15.8 1.91 1.91 25.5 0.164 980 433 763 1,000/R
Copper conductor three cores lead sheath cable with IEC 60502-2 84-93 240 30 18.3 1.91 1.91 28.0 0.125 874 525 953 1,000/R
steel wire armour R = Packing in reel
01
PHELPS DODGE CABLE TYPE SAC PHELPS DODGE CABLE TYPE SAC
on pole. on pole.
CLASSIFICATION : CLASSIFICATION :
Temperature : Temperature :
Extruded semi-conducting Cross-linked Extruded semi-conducting Cross-linked
- Normal operation 90°C. polyethylene conductor shielding layer - Normal operation 90°C. polyethylene conductor shielding layer
- Emergency over load conditions Compact Aluminium conductor - Emergency over load conditions Compact Aluminium conductor
130°C. 130°C.
- Short circuit conditions 250°C. - Short circuit conditions 250°C.
Voltage rating : Voltage rating :
25 kV phase to phase. 35 kV phase to phase.
Nominal Minimum Diameter Thickness Thickness Overall Maximum Minimum Allowable Cable Standard
Nominal Minimum Diameter Thickness Thickness Overall Maximum Minimum Allowable Cable Standard
cross - number of of of diameter DC. insulation ampacities weight packing
cross - number of of of diameter DC. insulation ampacities weight packing
sectional of wire conductor insulation sheath (Approx.) conductor resistance in free (Approx.)
sectional of wire conductor insulation sheath (Approx.) conductor resistance in free (Approx.)
area (Approx.) resistance at 15.6°C air at 40°C
area (Approx.) resistance at 15.6°C air at 40°C
at 20°C ambient
at 20°C ambient
mm² No. mm mm mm mm Ω / km MΩ-km A kg / km m
35 6 6.9 3.18 3.18 21.0 0.868 2,580 149 363 1,000/R mm² No. mm mm mm mm Ω / km MΩ-km A kg / km m
50 6 8.0 3.18 3.18 22.0 0.641 2,314 186 432 1,000/R 50 6 8.0 4.45 3.18 25.5 0.641 2,606 184 517 1,000/R
70 12 9.8 3.18 3.18 24.5 0.443 2,100 229 509 1,000/R 70 12 9.8 4.45 3.18 27.5 0.443 2,375 227 599 1,000/R
95 15 11.4 3.18 3.18 26.0 0.320 1,887 279 615 1,000/R 95 15 11.4 4.45 3.18 29.0 0.320 2,144 276 711 1,000/R
120 15 12.9 3.18 3.18 27.0 0.253 1,712 321 729 1,000/R 120 15 12.9 4.45 3.18 31.0 0.253 1,952 318 831 1,000/R
150 15 14.1 3.18 3.18 29.5 0.206 1,600 371 826 1,000/R 150 15 14.1 4.45 3.18 32.5 0.206 1,830 367 933 1,000/R
185 30 15.8 3.18 3.18 31.0 0.164 1,477 429 959 1,000/R 185 30 15.8 4.45 3.18 33.5 0.164 1,694 425 1,073 1,000/R
240 30 18.3 3.18 3.18 33.5 0.125 1,328 520 1,170 1,000/R 240 30 18.3 4.45 3.18 36.5 0.125 1,529 515 1,293 1,000/R
02 03
PHELPS DODGE CABLE TYPE PIC PHELPS DODGE CABLE TYPE PIC
CLASSIFICATION : CLASSIFICATION :
Temperature : Temperature :
- Normal operation 90°C. Cross-linked polyethylene insulation - Normal operation 90°C. Cross-linked polyethylene insulation
- Emergency over load conditions Extruded semi-conducting Cross-linked - Emergency over load conditions Extruded semi-conducting Cross-linked
polyethylene conductor shielding layer polyethylene conductor shielding layer
130°C. 130°C.
- Short circuit conditions 250°C. - Short circuit conditions 250°C.
Voltage rating : Voltage rating :
15 & 25 kV phase to phase. 35 kV phase to phase.
Nominal Minimum Diameter Thickness Overall Maximum Minimum Allowable Cable Standard Nominal Minimum Diameter Thickness Overall Maximum Minimum Allowable Cable Standard
cross - number of of diameter DC. insulation ampacities weight packing cross - number of of diameter DC. insulation ampacities weight packing
sectional of wire conductor conductor (Approx.) conductor resistance in free (Approx.) sectional of wire conductor conductor (Approx.) conductor resistance in free (Approx.)
area (Approx.) shield & resistance at 15.6°C air at 40°C area (Approx.) shield & resistance at 15.6°C air at 40°C
insulation at 20°C ambient insulation at 20°C ambient
04 05
PHELPS DODGE CABLE TYPE MXLP-CTS PHELPS DODGE CABLE TYPE MXLP-CTS
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
3.6 / 6 (7.2) kV COPPER CONDUCTOR WITH COPPER TAPE SHIELD Nominal Max Rdc Min Current Carrying Capacity* Current Carrying Capacity* Current Carrying Capacity*
cross- at 20 °C IR at (A) (A) (A)
sectional of Cdr. 20 In Air In Ground In PE Duct, In Ground
Insulation shield area
APPLICATION : Oversheath
mm /km km 0.5 x D e 0.5 x D e
Preferably used for urban networks.
35 0.524 778 167 209 167 244 147 187
Exposed in aerial, direct burial, 50 0.387 706 201 251 197 288 174 222
conduit, open tray and 70 0.268 611 252 315 241 356 212 273
underground duct installation. 95 0.193 544 309 386 288 428 255 328
120 0.153 493 358 448 327 489 290 375
Metallic shield 150 0.124 454 409 511 367 550 325 422
Insulation 185 0.0991 415 471 589 414 624 368 480
Max. Conductor Temperature : 240 0.0754 382 561 701 480 726 427 561
Conductor shield 300 0.0601 372 648 808 541 819 483 638
90 °C (Normal Operation)
Conductor 400 0.0470 353 755 942 613 934 551 733
500 0.0366 338 873 1,096 692 1,063 623 838
AC TEST VOLTAGE : 298 1,007 1,282 776 1,214 703 963
630 0.0283
12.5 kV for 5 minutes CONSTRUCTION : 800 0.0221 268 1,143 1,478 858 1,367 780 1,090
1,000 0.0176 231 1,292 1,701 937 1,524 855 1,224
Conductor : Compact round stranded copper.
REFERENCE STANDARD : 1,200 0.0151 216 1,383 1,841 987 1,625 904 1,311
Conductor shield : Semi-conducting cross-linked polyethylene.
IEC 60502-2
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene. *CONDITION :
Oversheath : Black PE (ST 7) (PVC is available upon request) 2. Ambient air temperature 40 °C
3. Ground temperature 30 °C
Nominal Minimum Diameter Nominal Diameter Nominal Overall Cable Standard
cross - number of thickness over thickness diameter weight packing
4. Depth of laying 0.8 m in ground
sectional of conductor of insulation of (Approx.) (Approx.)
area wire of (Approx.) insulation (Approx.) oversheath 5. Thermal resistivity of soil 1.2 K.m/W
conductor
mm2 mm mm mm mm mm kg/km m
6. Axial spacing between phase cables in flat formation
35 6 7.0 2.5 13.1 1.5 18 520 1,000/R
2xODcable or 2xODduct
50 6 8.0 2.5 14.1 1.6 19 655 1,000/R
70 12 9.7 2.5 15.8 1.6 21 875 1,000/R 7. Shields bonded at single point
95 15 11.3 2.5 17.4 1.7 23 1,140 1,000/R
120 18 12.8 2.5 18.9 1.7 24 1,395 1,000/R
150 18 14.2 2.5 20.3 1.8 26 1,670 1,000/R
185 30 15.8 2.5 21.9 1.8 27 2,025 1,000/R
240 34 18.2 2.6 24.5 1.9 30 2,610 500/R
300 34 20.3 2.8 27.0 2.0 33 3,245 500/R
400 53 23.0 3.0 30.2 2.1 36 4,095 500/R
500 53 25.9 3.2 33.7 2.2 40 5,160 250/R
630 53 29.9 3.2 37.7 2.3 44 6,555 250/R
800 53 33.8 3.2 41.6 2.4 48 8,280 250/R
1,000 53 39.8 3.2 47.6 2.6 55 10,380 250/R
1,200 - 42.9 3.2 50.7 2.7 58 12,005 250/R
R = Packing in reel
06 07
PHELPS DODGE CABLE TYPE MXLP-CTS PHELPS DODGE CABLE TYPE MXLP-CTS
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
6 / 10 (12) kV COPPER CONDUCTOR WITH COPPER TAPE SHIELD Nominal Max Rdc Min Current Carrying Current Carrying Current Carrying
cross- at 20 °C IR at Capacity* (A) Capacity* (A) Capacity* (A)
sectional of Cdr. 20 In Air In Ground In PE Duct, In Ground
Insulation shield area
APPLICATION : Oversheath
mm /km km 0.5 x D e 0.5 x D e
Preferably used for urban networks.
35 0.524 953 171 210 167 241 148 188
Exposed in aerial, direct burial, 50 0.387 869 204 252 197 285 174 222
conduit, open tray and 70 0.268 757 257 317 241 352 214 274
underground duct installation. 95 0.193 677 314 387 288 424 256 329
120 0.153 616 363 448 328 483 292 376
Metallic shield 150 0.124 569 414 511 367 545 327 423
Max. Conductor Temperature : 522 476 588 415 617 370 481
Insulation 185 0.0991
90 °C (Normal Operation) 240 0.0754 465 567 700 480 718 430 562
Conductor shield 300 0.0601 425 651 807 541 815 484 638
Conductor 400 0.0470 379 757 941 613 931 552 733
AC TEST VOLTAGE :
500 0.0366 343 873 1,095 692 1,062 624 839
21 kV for 5 minutes
630 0.0283 303 1,008 1,281 777 1,212 703 963
CONSTRUCTION : 800 0.0221 271 1,144 1,475 859 1,365 780 1,090
REFERENCE STANDARD : Conductor : Compact round stranded copper. 1,000 0.0176 235 1,293 1,699 938 1,522 857 1,225
IEC 60502-2 1,200 0.0151 219 1,385 1,839 988 1,623 905 1,311
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene. *CONDITION :
Oversheath : Black PE (ST 7) (PVC is available upon request) 2. Ambient air temperature 40 °C
3. Ground temperature 30 °C
Nominal Minimum Diameter Nominal Diameter Nominal Overall Cable Standard
cross - number of thickness over thickness diameter weight packing
4. Depth of laying 0.8 m in ground
sectional of conductor of insulation of (Approx.) (Approx.)
area wire of (Approx.) insulation (Approx.) oversheath 5. Thermal resistivity of soil 1.2 K.m/W
conductor
mm mm mm mm mm mm kg/km m
6. Axial spacing between phase cables in flat formation
35 6 7.0 3.4 14.9 1.6 20 575 1,000/R
2xODcable or 2xODduct
50 6 8.0 3.4 15.9 1.6 21 705 1,000/R
70 12 9.7 3.4 17.6 1.7 23 940 1,000/R 7. Shields bonded at single point
95 15 11.3 3.4 19.2 1.7 24 1,205 1,000/R
120 18 12.8 3.4 20.7 1.8 26 1,470 1,000/R
150 18 14.2 3.4 22.1 1.8 27 1,740 1,000/R
185 30 15.8 3.4 23.7 1.9 29 2,110 1,000/R
240 34 18.2 3.4 26.1 2.0 32 2,715 500/R
300 34 20.3 3.4 28.2 2.0 34 3,300 500/R
400 53 23.0 3.4 30.9 2.1 37 4,135 500/R
500 53 25.9 3.4 34.1 2.2 41 5,180 250/R
630 53 29.9 3.4 38.1 2.3 45 6,580 250/R
800 53 33.8 3.4 42.0 2.5 49 8,320 250/R
1,000 53 39.8 3.4 48.0 2.6 55 10,410 250/R
1,200 - 42.9 3.4 51.1 2.7 58 12,035 250/R
R = Packing in reel
08 09
PHELPS DODGE CABLE TYPE MXLP-CTS PHELPS DODGE CABLE TYPE MXLP-CTS
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
8.7 / 15 (17.5) kV COPPER CONDUCTOR WITH COPPER TAPE SHIELD Nominal Max Rdc Min Current Carrying Current Carrying Current Carrying
cross- at 20 °C IR at Capacity* (A) Capacity* (A) Capacity* (A)
sectional of Cdr. 20 In Air In Ground In PE Duct, In Ground
Insulation shield area
APPLICATION : Oversheath
mm /km km 0.5 x D e 0.5 x D e
Preferably used for urban networks.
35 0.524 1,158 174 211 167 238 149 189
Exposed in aerial, direct burial, 1,062 208 253 197 282 176 223
50 0.387
conduit, open tray and 70 0.268 931 261 317 241 348 215 274
underground duct installation. 95 0.193 837 318 387 289 419 257 330
120 0.153 765 368 449 328 478 293 377
Metallic shield 150 0.124 709 419 511 368 539 328 424
Max. Conductor Temperature :
Insulation 185 0.0991 653 481 587 415 611 371 481
90 °C (Normal Operation) 240 0.0754 584 572 698 481 712 432 563
Conductor shield 535 656 804 542 807 488 640
300 0.0601
AC TEST VOLTAGE : Conductor 400 0.0470 479 762 937 615 922 555 734
500 0.0366 434 878 1,088 693 1,052 628 840
30.5 kV for 5 minutes
630 0.0283 385 1,015 1,274 780 1,203 708 964
CONSTRUCTION : 800 0.0221 346 1,152 1,467 864 1,357 787 1,091
REFERENCE STANDARD : Conductor : Compact round stranded copper. 1,000 0.0176 300 1,302 1,687 944 1,513 865 1,227
IEC 60502-2 1,200 0.0151 281 1,394 1,826 995 1,614 913 1,313
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene. *CONDITION :
Oversheath : Black PE (ST 7) (PVC is available upon request) 2. Ambient air temperature 40 °C
3. Ground temperature 30 °C
Nominal Minimum Diameter Nominal Diameter Nominal Overall Cable Standard
cross - number of thickness over thickness diameter weight packing
4. Depth of laying 0.8 m in ground
sectional of conductor of insulation of (Approx.) (Approx.)
area wire of (Approx.) insulation (Approx.) oversheath 5. Thermal resistivity of soil 1.2 K.m/W
conductor
mm mm mm mm mm mm kg/km m
6. Axial spacing between phase cables in flat formation
35 6 7.0 4.5 16.9 1.7 22 645 1,000/R
2xODcable or 2xODduct
50 6 8.0 4.5 18.0 1.7 23 780 1,000/R
70 12 9.7 4.5 19.7 1.7 25 1,015 1,000/R 7. Shields bonded at single point
95 15 11.3 4.5 21.3 1.8 27 1,290 1,000/R
120 18 12.8 4.5 22.8 1.9 28 1,560 1,000/R
150 18 14.2 4.5 24.2 1.9 30 1,835 1,000/R
185 30 15.8 4.5 25.8 2.0 31 2,210 1,000/R
240 34 18.2 4.5 28.2 2.0 34 2,815 500/R
300 34 20.3 4.5 30.3 2.1 37 3,420 500/R
400 53 23.0 4.5 33.0 2.2 39 4,265 500/R
500 53 25.9 4.5 36.1 2.3 43 5,305 250/R
630 53 29.9 4.5 40.1 2.4 47 6,730 250/R
800 53 33.8 4.5 44.0 2.5 51 8,470 250/R
1,000 53 39.8 4.5 50.0 2.7 57 10,595 250/R
1,200 - 42.9 4.5 53.1 2.8 61 12,230 250/R
R = Packing in reel
10 11
PHELPS DODGE CABLE TYPE MXLP-CTS PHELPS DODGE CABLE TYPE MXLP-CTS
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
12 / 20 (24) kV COPPER CONDUCTOR WITH COPPER TAPE SHIELD Nominal Max Rdc Min Current Carrying Current Carrying Current Carrying
cross- at 20 °C IR at Capacity* (A) Capacity* (A) Capacity* (A)
sectional of Cdr. 20 In Air In Ground In PE Duct, In Ground
Insulation shield area
APPLICATION : Oversheath
mm /km km 0.5 x De 0.5 x De
Preferably used for urban networks.
35 0.524 1,336 177 212 168 235 150 189
Exposed in aerial, direct burial, 1,229 211 253 197 279 177 223
50 0.387
conduit, open tray and 70 0.268 1,085 264 318 242 344 217 275
underground duct installation. 95 0.193 979 322 387 289 414 259 331
120 0.153 897 372 448 328 474 294 377
Metallic shield 150 0.124 834 424 510 368 532 331 425
Max. Conductor Temperature :
Insulation 185 0.0991 770 486 586 415 604 374 482
90 °C (Normal Operation) 240 0.0754 692 576 696 481 705 433 563
Conductor shield 635 661 801 542 800 490 640
300 0.0601
AC TEST VOLTAGE : Conductor 400 0.0470 570 765 931 615 914 557 734
500 0.0366 519 883 1,082 695 1,044 631 840
42 kV for 5 minutes
630 0.0283 461 1,021 1,267 783 1,195 713 965
CONSTRUCTION : 800 0.0221 415 1,158 1,459 867 1,348 794 1,094
REFERENCE STANDARD : Conductor : Compact round stranded copper. 1,000 0.0176 361 1,308 1,677 949 1,506 871 1,229
IEC 60502-2 1,200 0.0151 338 1,401 1,813 1,001 1,606 922 1,316
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene. CONDITION :
Oversheath : Black PE (ST 7) (PVC is available upon request) 2. Ambient air temperature 40 °C
3. Ground temperature 30 °C
Nominal Minimum Diameter Nominal Diameter Nominal Overall Cable Standard
cross - number of thickness over thickness diameter weight packing
4. Depth of laying 0.8 m in ground
sectional of conductor of insulation of (Approx.) (Approx.)
area wire of (Approx.) insulation (Approx.) oversheath 5. Thermal resistivity of soil 1.2 K.m/W
conductor
mm mm mm mm mm mm kg/km m
6. Axial spacing between phase cables in flat formation
35 6 7.0 5.5 18.9 1.7 24 715 1,000/R
2xODcable or 2xODduct
50 6 8.0 5.5 20.0 1.8 25 860 1,000/R
70 12 9.7 5.5 21.7 1.8 27 1,100 1,000/R 7. Shields bonded at single point
95 15 11.3 5.5 23.3 1.9 29 1,380 1,000/R
120 18 12.8 5.5 24.8 1.9 30 1,645 1,000/R
150 18 14.2 5.5 26.2 2.0 32 1,960 1,000/R
185 30 15.8 5.5 27.8 2.0 34 2,330 1,000/R
240 34 18.2 5.5 30.2 2.1 36 2,930 500/R
300 34 20.3 5.5 32.3 2.2 39 3,540 500/R
400 53 23.0 5.5 35.0 2.3 41 4,385 500/R
500 53 25.9 5.5 38.1 2.4 45 5,445 250/R
630 53 29.9 5.5 42.1 2.5 49 6,885 250/R
800 53 33.8 5.5 46.0 2.6 53 8,635 250/R
1,000 53 39.8 5.5 52.0 2.7 59 10,765 250/R
1,200 - 42.9 5.5 55.1 2.9 63 12,425 250/R
R = Packing in reel
12 13
PHELPS DODGE CABLE TYPE MXLP-CTS PHELPS DODGE CABLE TYPE MXLP-CTS
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
18 / 30 (36) kV COPPER CONDUCTOR WITH COPPER TAPE SHIELD Nominal Max Rdc Min Current Carrying Current Carrying Current Carrying
cross- at 20 °C IR at Capacity* (A) Capacity* (A) Capacity* (A)
sectional of Cdr. 20 In Air In Ground In PE Duct, In Ground
Insulation shield area
APPLICATION : Oversheath
mm /km km 0.5 x D e 0.5 x D e
Preferably used for urban networks.
50 0.387 1,584 217 254 198 273 179 224
Exposed in aerial, direct burial, 70 0.268 1,413 271 317 242 336 219 276
conduit, open tray and 95 0.193 1,286 329 386 289 405 262 331
underground duct installation. 120 0.153 1,187 379 446 328 463 298 379
150 0.124 1,110 431 507 368 522 334 426
Metallic shield 185 0.0991 1,031 493 582 416 592 377 484
Max. Conductor Temperature : 933 582 689 482 691 438 565
Insulation 240 0.0754
90 °C (Normal Operation) 300 0.0601 861 667 792 543 785 495 641
Conductor shield 400 0.0470 779 773 921 617 898 563 735
AC TEST VOLTAGE : Conductor 500 0.0366 712 891 1,070 698 1,027 638 842
630 0.0283 636 1,030 1,250 788 1,176 723 968
63 kV for 5 minutes
800 0.0221 576 1,170 1,438 875 1,329 806 1,096
CONSTRUCTION : 1,000 0.0176 504 1,320 1,651 960 1,486 886 1,231
REFERENCE STANDARD : Conductor : Compact round stranded copper. 1,200 0.0151 473 1,414 1,785 1,013 1,587 938 1,319
IEC 60502-2
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene. *CONDITION :
Oversheath : Black PE (ST 7) (PVC is available upon request) 2. Ambient air temperature 40 °C
3. Ground temperature 30 °C
4. Depth of laying 0.8 m in ground
Nominal Minimum Diameter Nominal Diameter Nominal Overall Cable Standard
c ross - number of thickness over thickness diameter weight packing 5. Thermal resistivity of soil 1.2 K.m/W
sectional of conductor of insulation of (Approx.) (Approx.)
area wire of (Approx.) insulation (Approx.) oversheath 6. Axial spacing between phase cables in flat formation
conductor
mm mm mm mm mm mm kg/km m
2xODcable or 2xODduct
50 6 8.0 8.0 25.0 1.9 31 1,070 1,000/R
70 12 9.7 8.0 26.7 2.0 33 1,355 1,000/R 7. Shields bonded at single point
95 15 11.3 8.0 28.3 2.1 35 1,650 1,000/R
120 18 12.8 8.0 29.8 2.1 36 1,930 1,000/R
150 18 14.2 8.0 31.2 2.1 38 2,225 1,000/R
185 30 15.8 8.0 32.8 2.2 39 2,620 500/R
240 34 18.2 8.0 35.2 2.3 42 3,225 500/R
300 34 20.3 8.0 37.3 2.3 44 3,840 500/R
400 53 23.0 8.0 40.0 2.5 47 4,735 250/R
500 53 25.9 8.0 43.2 2.5 50 5,805 250/R
630 53 29.9 8.0 47.2 2.7 54 7,290 250/R
800 53 33.8 8.0 51.1 2.8 59 9,075 250/R
1,000 53 39.8 8.0 57.1 2.9 65 11,250 250/R
1,200 - 42.9 8.0 60.2 3.0 68 12,920 250/R
R = Packing in reel
14 15
PHELPS DODGE CABLE TYPE MXLP-CWS PHELPS DODGE CABLE TYPE MXLP-CWS
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
3.6 / 6 (7.2) kV COPPER CONDUCTOR WITH COPPER WIRE SHIELD Nominal Max Rdc Min Current Carrying Capacity* Current Carrying Capacity* Current Carrying Capacity*
cross- at 20 °C IR at (A) (A) (A)
Conductor shield sectional of Cdr. 20 In Air In Ground In PE Duct, In Ground
area
Insulation shield
APPLICATION :
Binding Tape mm /km km 0.5 x D e 0.5 x D e
Preferably used for urban networks.
Oversheath 35 0.524 782 174 216 168 176 149 155
Exposed in aerial, direct burial, 50 0.387 681 208 259 198 207 176 182
conduit, open tray and 70 0.268 588 261 325 242 254 216 224
underground duct installation. 95 0.193 523 319 397 289 303 258 268
120 0.153 474 370 460 328 345 294 306
150 0.124 436 422 526 368 387 330 343
Max. Conductor Temperature : Metallic shield
185 0.0991 399 486 605 415 438 373 389
90 °C (Normal Operation) Insulation 240 0.0754 367 578 721 480 509 435 454
300 0.0601 359 665 828 539 575 492 516
Conductor
AC TEST VOLTAGE : 400 0.0470 344 773 964 611 655 564 593
500 0.0366 339 893 1,117 689 746 645 679
12.5 kV for 5 minutes
630 0.0283 299 1,032 1,307 774 850 737 780
CONSTRUCTION : 800 0.0221 268 1,170 1,504 855 955 834 886
REFERENCE STANDARD : Conductor : Compact round stranded copper. 1,000 0.0176 232 1,321 1,728 932 1,063 933 997
IEC 60502-2 Conductor shield : Semi-conducting cross-linked polyethylene. 1,200 0.0151 216 1,413 1,869 982 1,133 1,000 1,071
16 17
PHELPS DODGE CABLE TYPE MXLP-CWS PHELPS DODGE CABLE TYPE MXLP-CWS
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
6 / 10 (12) kV COPPER CONDUCTOR WITH COPPER WIRE SHIELD Nominal Max Rdc Min Current Carrying Capacity* Current Carrying Capacity* Current Carrying Capacity*
cross- at 20 °C IR at (A) (A) (A)
Conductor shield sectional of Cdr. 20 In Air In Ground In PE Duct, In Ground
area
Insulation shield
APPLICATION :
Binding Tape mm /km km 0.5 x D e 0.5 x D e
Preferably used for urban networks.
Oversheath 35 0.524 991 176 216 168 176 150 156
Exposed in aerial, direct burial,
50 0.387 869 211 259 198 207 177 183
conduit, open tray and 70 0.268 757 265 325 242 254 217 225
underground duct installation. 95 0.193 677 323 397 289 303 259 269
120 0.153 616 373 459 328 345 295 307
150 0.124 569 426 524 368 387 331 345
Max. Conductor Temperature : Metallic shield
185 0.0991 522 489 603 414 438 375 391
90 °C (Normal Operation) Insulation 240 0.0754 465 582 717 480 508 436 456
Conductor 300 0.0601 425 668 825 540 574 494 518
AC TEST VOLTAGE : 400 0.0470 382 774 961 611 655 565 594
500 0.0366 354 894 1,116 689 745 644 679
21 kV for 5 minutes
630 0.0283 313 1,033 1,305 774 849 738 781
CONSTRUCTION : 800 0.0221 281 1,171 1,502 855 955 833 886
REFERENCE STANDARD : Conductor : Compact round stranded copper. 1,000 0.0176 243 1,321 1,726 933 1,063 933 996
IEC 60502-2 Conductor shield : Semi-conducting cross-linked polyethylene. 1,200 0.0151 227 1,415 1,865 983 1,133 999 1,070
18 19
PHELPS DODGE CABLE TYPE MXLP-CWS PHELPS DODGE CABLE TYPE MXLP-CWS
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
8.7 / 15 (17.5) kV COPPER CONDUCTOR WITH COPPER WIRE SHIELD Nominal Max Rdc Min Current Carrying Capacity* Current Carrying Capacity* Current Carrying Capacity*
cross- at 20 °C IR at (A) (A) (A)
Conductor shield sectional of Cdr. 20 In Air In Ground In PE Duct, In Ground
area
Insulation shield
APPLICATION :
Binding Tape mm /km km 0.5 x D e 0.5 x D e
Preferably used for urban networks.
Oversheath 35 0.524 1,213 179 216 168 176 151 156
Exposed in aerial, direct burial, 50 0.387 1,062 214 259 198 207 178 184
conduit, open tray and 70 0.268 931 268 325 242 253 218 226
underground duct installation. 95 0.193 837 326 396 289 303 260 271
120 0.153 765 377 458 328 345 296 309
150 0.124 709 430 522 367 387 332 346
Max. Conductor Temperature : Metallic shield
185 0.0991 653 494 600 414 437 377 393
90 °C (Normal Operation) Insulation 240 0.0754 584 586 713 480 508 439 459
300 0.0601 535 672 820 540 574 496 520
Conductor
AC TEST VOLTAGE : 400 0.0470 483 778 955 612 655 567 595
500 0.0366 445 898 1,108 690 745 648 683
30.5 kV for 5 minutes
630 0.0283 394 1,037 1,296 776 850 740 783
CONSTRUCTION : 800 0.0221 355 1,176 1,491 859 956 835 888
REFERENCE STANDARD : Conductor : Compact round stranded copper. 1,000 0.0176 308 1,327 1,712 938 1,064 937 1,001
IEC 60502-2 Conductor shield : Semi-conducting cross-linked polyethylene. 1,200 0.0151 288 1,420 1,851 988 1,134 1,001 1,073
20 21
PHELPS DODGE CABLE TYPE MXLP-CWS PHELPS DODGE CABLE TYPE MXLP-CWS
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
12 / 20 (24) kV COPPER CONDUCTOR WITH COPPER WIRE SHIELD Nominal Max Rdc Min Current Carrying Capacity* Current Carrying Capacity* Current Carrying Capacity*
cross- at 20 °C IR at (A) (A) (A)
Conductor shield sectional of Cdr. 20 In Air In Ground In PE Duct, In Ground
area
Insulation shield
APPLICATION :
Binding Tape mm /km km 0.5 x D e 0.5 x D e
Preferably used for urban networks.
Oversheath 35 0.524 1,391 181 216 168 175 152 157
Exposed in aerial, direct burial, 50 0.387 1,229 217 259 198 207 179 186
conduit, open tray and 70 0.268 1,085 271 324 242 253 219 227
underground duct installation. 95 0.193 979 329 395 289 303 261 272
120 0.153 897 380 457 328 344 298 310
150 0.124 834 433 520 367 387 334 348
Max. Conductor Temperature : Metallic shield
185 0.0991 770 497 597 414 437 378 395
90 °C (Normal Operation) Insulation 240 0.0754 692 589 710 479 508 440 460
300 0.0601 635 674 816 540 574 497 521
Conductor
AC TEST VOLTAGE : 400 0.0470 575 781 950 612 655 568 597
500 0.0366 529 900 1,101 691 745 649 684
42 kV for 5 minutes
630 0.0283 470 1,040 1,287 778 850 742 785
CONSTRUCTION : 800 0.0221 424 1,180 1,480 862 956 839 892
REFERENCE STANDARD : Conductor : Compact round stranded copper. 1,000 0.0176 368 1,332 1,699 942 1,065 939 1,003
IEC 60502-2 Conductor shield : Semi-conducting cross-linked polyethylene. 1,200 0.0151 345 1,425 1,837 993 1,135 1,003 1,074
R = Packing in reel
22 23
PHELPS DODGE CABLE TYPE MXLP-CWS PHELPS DODGE CABLE TYPE MXLP-CWS
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
18 / 30 (36) kV COPPER CONDUCTOR WITH COPPER WIRE SHIELD Nominal Max Rdc Min Current Carrying Capacity* Current Carrying Capacity* Current Carrying Capacity*
cross- at 20 °C IR at (A) (A) (A)
Conductor shield sectional of Cdr. 20 In Air In Ground In PE Duct, In Ground
area
Insulation shield
APPLICATION :
Binding Tape mm /km km 0.5 x D e 0.5 x D e
Preferably used for urban networks.
Oversheath 50 0.387 1,584 221 258 198 207 181 187
Exposed in aerial, direct burial, 70 0.268 1,413 276 323 241 253 221 230
conduit, open tray and 95 0.193 1,286 335 393 288 303 264 275
underground duct installation. 120 0.153 1,187 386 453 327 344 301 313
150 0.124 1,110 439 516 367 386 338 352
185 0.0991 1,031 502 592 414 437 381 398
Max. Conductor Temperature : Metallic shield
240 0.0754 933 594 702 480 508 443 464
90 °C (Normal Operation) Insulation 300 0.0601 861 680 806 540 574 502 527
400 0.0470 785 787 937 613 655 573 603
Conductor
AC TEST VOLTAGE : 500 0.0366 721 907 1,085 693 746 653 689
630 0.0283 645 1,047 1,267 782 851 748 792
63 kV for 5 minutes
800 0.0221 584 1,189 1,457 868 957 844 897
CONSTRUCTION : 1,000 0.0176 511 1,341 1,670 951 1,067 945 1,010
REFERENCE STANDARD : Conductor : Compact round stranded copper. 1,200 0.0151 480 1,436 1,806 1,004 1,138 1,010 1,082
IEC 60502-2 Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
*CONDITION :
Insulation shield : Semi-conducting cross-linked polyethylene.
Metallic shield : Annealed copper wire with copper contact tape 1. Conductor temperature 90 °C
24 25
PHELPS DODGE CABLE TYPE MXLP-DATA PHELPS DODGE CABLE TYPE MXLP-DATA
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
3.6 / 6 (7.2) kV COPPER CONDUCTOR WITH DOUBLE ALUMINIUM TAPE ARMOUR
Nominal Max Rdc Min Current Carrying Current Carrying Current Carrying
cross- at 20 °C IR at Capacity* Capacity* Capacity*
Conductor shield sectional of Cdr. 20 (A) (A) (A)
area In Air In Ground In PE Duct, In Ground
Insulation shield
APPLICATION :
Preferably used for urban networks.
Separation sheath
Oversheath
Exposed in aerial, direct burial,
mm /km km 0.5 x D e 0.5 x D e
conduit, open tray and
35 0.524 802 179 217 170 184 151 157
underground duct installation.
50 0.387 722 214 260 200 217 178 185
70 0.268 625 268 326 244 266 218 226
Max. Conductor Temperature : Armour
95 0.193 552 326 398 292 319 260 271
90 °C (Normal Operation) Copper tape 120 0.153 491 377 460 331 363 296 308
150 0.124 455 429 524 371 408 332 346
Insulation
185 0.0991 412 492 602 419 461 376 392
AC TEST VOLTAGE : Conductor 240 0.0754 379 584 715 485 536 437 457
12.5 kV for 5 minutes 300 0.0601 366 670 822 546 606 495 519
CONSTRUCTION : 400 0.0470 346 778 956 620 691 566 596
REFERENCE STANDARD : Conductor : Compact round stranded copper. 500 0.0366 328 898 1,109 700 786 643 681
IEC 60502-2 630 0.0283 293 1,038 1,296 788 896 734 783
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene. 800 0.0221 263 1,176 1,491 872 1,008 823 886
Insulation shield : Semi-conducting cross-linked polyethylene. 1,000 0.0176 228 1,328 1,709 953 1,122 916 996
Metallic shield : Copper tape shield 1,200 0.0151 214 1,420 1,847 1,005 1,196 978 1,069
Separation sheath : Black PE (PVC is available upon request)
Armour : Double Aluminium tape
Oversheath : Black PE (ST 7) (PVC is available upon request) *CONDITION :
Nominal Minimum Diameter Nominal Diameter Nominal Nominal Diameter Nominal Overall Cable Standard 1. Conductor temperature 90 °C
cross- number of thickness over thickness thickness over thickness diameter weight packing
sectional of conductor of insulation of of armour of (Approx.) (Approx.) 2. Ambient air temperature 40 °C
area wire of (Approx.) insulation (Approx.) separation sheath Aluminium tape (Approx.) oversheath
conductor
armour 3. Ground temperature 30 °C
mm mm mm mm mm mm mm mm mm kg/km m
35 6 7.0 2.5 13.5 1.2 0.5 19.0 1.7 23 645 1,000/R 4. Depth of laying 0.8 m in ground
50 6 8.0 2.5 14.5 1.2 0.5 20.5 1.7 24 780 1,000/R 5. Thermal resistivity of soil 1.2 K.m/W
70 12 9.7 2.5 16.0 1.2 0.5 22.0 1.8 26 1,020 1,000/R
95 15 11.3 2.5 18.0 1.2 0.5 23.5 1.8 28 1,290 1,000/R 6. Axial spacing between phase cables in flat formation
120 18 12.8 2.5 19.5 1.2 0.5 25.0 1.9 29 1,555 1,000/R 2xODcable or 2xODduct
150 18 14.2 2.5 20.5 1.2 0.5 26.5 1.9 31 1,830 1,000/R
185 30 15.8 2.5 22.5 1.2 0.5 28.0 2.0 33 2,205 1,000/R 7. Shield and armour bonded at single point
240 34 18.2 2.6 25.0 1.2 0.5 30.5 2.1 35 2,800 500/R
300 34 20.3 2.8 27.5 1.2 0.5 33.0 2.1 38 3,415 500/R
400 53 23.0 3.0 30.5 1.2 0.5 36.5 2.3 41 4,290 500/R
500 53 25.9 3.2 34.0 1.3 0.5 40.0 2.4 45 5,380 250/R
630 53 29.9 3.2 38.0 1.4 0.5 44.5 2.5 50 6,815 250/R
800 53 33.8 3.2 42.0 1.4 0.5 48.0 2.6 54 8,550 250/R
1,000 53 39.8 3.2 48.0 1.5 0.5 54.5 2.8 61 10,695 250/R
1,200 - 42.9 3.2 51.0 1.6 0.5 57.5 2.9 64 12,345 250/R
R = Packing in reel
26 27
PHELPS DODGE CABLE TYPE MXLP-DATA PHELPS DODGE CABLE TYPE MXLP-DATA
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
6 / 10 (12) kV COPPER CONDUCTOR WITH DOUBLE ALUMINIUM TAPE ARMOUR
Nominal Max Rdc Min Current Carrying Current Carrying Current Carrying
cross- at 20 °C IR at Capacity* Capacity* Capacity*
Conductor shield sectional of Cdr. 20 (A) (A) (A)
area In Air In Ground In PE Duct, In Ground
Insulation shield
APPLICATION :
Preferably used for urban networks.
Separation sheath
Oversheath
Exposed in aerial, direct burial,
mm /km km 0.5 x D e 0.5 x D e
conduit, open tray and
35 0.524 985 181 217 170 183 151 157
underground duct installation.
50 0.387 899 216 260 200 216 179 185
70 0.268 784 270 326 244 265 218 227
Max. Conductor Temperature : Armour
95 0.193 701 329 397 292 318 261 272
90 °C (Normal Operation) Copper tape 120 0.153 639 380 459 331 362 297 310
150 0.124 590 432 522 371 406 333 347
Insulation
185 0.0991 542 495 600 419 460 377 394
AC TEST VOLTAGE : Conductor 240 0.0754 483 586 713 485 534 439 459
21 kV for 5 minutes
300 0.0601 442 672 819 546 604 496 520
CONSTRUCTION : 400 0.0470 394 779 954 620 690 565 595
REFERENCE STANDARD : Conductor : Compact round stranded copper. 500 0.0366 357 899 1,107 700 785 644 682
IEC 60502-2 Conductor shield : Semi-conducting cross-linked polyethylene. 630 0.0283 315 1,038 1,294 788 896 733 782
Insulation : Cross-linked polyethylene. 800 0.0221 283 1,177 1,488 873 1,008 824 887
Insulation shield : Semi-conducting cross-linked polyethylene. 1,000 0.0176 244 1,328 1,707 954 1,121 915 996
Metallic shield : Copper tape shield 1,200 0.0151 228 1,421 1,844 1,006 1,195 977 1,068
Separation sheath : Black PE (PVC is available upon request)
Armour : Double Aluminium tape
Oversheath : Black PE (ST 7) (PVC is available upon request)
*CONDITION :
Nominal Minimum Diameter Nominal Diameter Nominal Nominal Diameter Nominal Overall Cable Standard
1. Conductor temperature 90 °C
cross-sectional number of thickness over thickness thickness over thickness diameter weight packing
area of conductor of insulation of of armour of (Approx.) (Approx.)
wire of (Approx.) insulation (Approx.) separation sheath Aluminium tape (Approx.) oversheath
2. Ambient air temperature 40 °C
conductor
armour
mm mm mm mm mm mm mm mm mm kg/km m
3. Ground temperature 30 °C
35 6 7.0 3.4 15.5 1.2 0.5 21.0 1.7 25 710 1,000/R 4. Depth of laying 0.8 m in ground
50 6 8.0 3.4 16.5 1.2 0.5 22.0 1.8 26 855 1,000/R
70 12 9.7 3.4 18.0 1.2 0.5 24.0 1.8 28 1,095 1,000/R 5. Thermal resistivity of soil 1.2 K.m/W
95 15 11.3 3.4 19.5 1.2 0.5 25.5 1.9 30 1,375 1,000/R 6. Axial spacing between phase cables in flat formation
120 18 12.8 3.4 21.0 1.2 0.5 27.0 1.9 31 1,635 1,000/R
150 18 14.2 3.4 22.5 1.2 0.5 28.5 2.0 33 1,925 1,000/R 2xODcable or 2xODduct
185 30 15.8 3.4 24.0 1.2 0.5 30.0 2.0 34 2,295 1,000/R
7. Shield and armours bonded at single point
240 34 18.2 3.4 26.5 1.2 0.5 32.5 2.1 37 2,885 500/R
300 34 20.3 3.4 28.5 1.2 0.5 34.5 2.2 39 3,490 500/R
400 53 23.0 3.4 31.5 1.2 0.5 37.0 2.3 42 4,330 500/R
500 53 25.9 3.4 34.5 1.3 0.5 40.5 2.4 46 5,395 250/R
630 53 29.9 3.4 38.5 1.4 0.5 44.5 2.5 50 6,835 250/R
800 53 33.8 3.4 42.5 1.4 0.5 48.5 2.6 54 8,575 250/R
1,000 53 39.8 3.4 48.5 1.5 0.5 55.0 2.8 61 10,720 250/R
1,200 - 42.9 3.4 51.5 1.6 0.5 58.0 2.9 65 12,370 250/R
R = Packing in reel
28 29
PHELPS DODGE CABLE TYPE MXLP-DATA PHELPS DODGE CABLE TYPE MXLP-DATA
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
8.7 / 15 (17.5) kV COPPER CONDUCTOR WITH DOUBLE ALUMINIUM TAPE ARMOUR
Nominal Max Rdc Min Current Carrying Current Carrying Current Carrying
cross- at 20 °C IR at Capacity* Capacity* Capacity*
Conductor shield sectional of Cdr. 20 (A) (A) (A)
area In Air In Ground In PE Duct, In Ground
Insulation shield
APPLICATION :
Preferably used for urban networks.
Separation sheath
Oversheath
Exposed in aerial, direct burial,
conduit, open tray and mm /km km 0.5 x De 0.5 x De
underground duct installation. 35 0.524 1,207 183 217 169 182 152 158
50 0.387 1,107 219 259 199 215 179 186
Max. Conductor Temperature : Armour 70 0.268 973 273 325 244 264 220 228
Copper tape 95 0.193 875 332 396 291 316 263 273
90 °C (Normal Operation)
120 0.153 800 383 457 331 360 298 311
Insulation 150 0.124 742 435 520 371 404 335 350
AC TEST VOLTAGE : Conductor 185 0.0991 684 498 597 419 458 379 396
30.5 kV for 5 minutes 240 0.0754 613 589 708 485 532 440 461
CONSTRUCTION : 300 0.0601 562 675 814 547 602 498 523
400 0.0470 504 782 946 621 687 568 598
REFERENCE STANDARD : Conductor : Compact round stranded copper. 500 0.0366 457 902 1,099 701 783 646 684
IEC 60502-2 Conductor shield : Semi-conducting cross-linked polyethylene. 630 0.0283 405 1,042 1,284 790 893 737 786
Insulation : Cross-linked polyethylene. 800 0.0221 365 1,182 1,475 876 1,005 827 889
Insulation shield : Semi-conducting cross-linked polyethylene. 1,000 0.0176 316 1,333 1,691 959 1,119 921 1,000
Metallic shield : Copper tape shield 1,200 0.0151 296 1,426 1,827 1,011 1,193 980 1,070
Separation sheath : Black PE (PVC is available upon request)
Armour : Double Aluminium tape
Oversheath : Black PE (ST 7) (PVC is available upon request)
*CONDITION :
Nominal
Nominal Minimum Diameter Nominal Diameter Nominal Nominal Diameter Nominal Overall Cable Standard
1. Conductor temperature 90 °C
cross-sectional number of thickness over thickness thickness over thickness diameter weight packing
area of conductor of insulation of of armour of (Approx.) (Approx.)
wire of (Approx.) insulation (Approx.) separation sheath Aluminium tape (Approx.) oversheath
2. Ambient air temperature 40 °C
conductor
armour
mm mm mm mm mm mm mm mm mm kg/km m
3. Ground temperature 30 °C
35 6 7.0 4.5 17.5 1.2 0.5 23.5 1.8 27 805 1,000/R 4. Depth of laying 0.8 m in ground
50 6 8.0 4.5 18.5 1.2 0.5 24.5 1.9 29 955 1,000/R
70 12 9.7 4.5 20.5 1.2 0.5 26.0 1.9 30 1,195 1,000/R 5. Thermal resistivity of soil 1.2 K.m/W
95 15 11.3 4.5 22.0 1.2 0.5 27.5 2.0 32 1,480 1,000/R 6. Axial spacing between phase cables in flat formation
120 18 12.8 4.5 23.5 1.2 0.5 29.0 2.0 34 1,750 1,000/R
150 18 14.2 4.5 25.0 1.2 0.5 30.5 2.1 35 2,045 1,000/R 2xODcable or 2xODduct
185 30 15.8 4.5 26.5 1.2 0.5 32.0 2.1 37 2,420 1,000/R
7. Shield and armours bonded at single point
240 34 18.2 4.5 29.0 1.2 0.5 34.5 2.2 40 3,020 500/R
300 34 20.3 4.5 31.0 1.2 0.5 36.5 2.3 42 3,635 500/R
400 53 23.0 4.5 33.5 1.3 0.5 39.5 2.4 45 4,505 500/R
500 53 25.9 4.5 37.0 1.3 0.5 42.5 2.5 48 5,570 250/R
630 53 29.9 4.5 41.0 1.4 0.5 47.0 2.6 53 7,025 250/R
800 53 33.8 4.5 44.5 1.5 0.5 51.0 2.7 57 8,795 250/R
1,000 53 39.8 4.5 50.5 1.6 0.5 57.5 2.9 64 10,970 250/R
1,200 - 42.9 4.5 54.0 1.6 0.5 60.5 3.0 67 12,615 250/R
R = Packing in reel
30 31
PHELPS DODGE CABLE TYPE MXLP-DATA PHELPS DODGE CABLE TYPE MXLP-DATA
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
12 / 20 (24) kV COPPER CONDUCTOR WITH DOUBLE ALUMINIUM TAPE ARMOUR
Nominal Max Rdc Min Current Carrying Current Carrying Current Carrying
cross- at 20 °C IR at Capacity* Capacity* Capacity*
Conductor shield sectional of Cdr. 20 (A) (A) (A)
area In Air In Ground In PE Duct, In Ground
Insulation shield
APPLICATION :
Preferably used for urban networks.
Separation sheath
Oversheath
Exposed in aerial, direct burial,
mm /km km 0.5 x D e 0.5 x D e
conduit, open tray and
35 0.524 1,384 185 217 169 181 153 159
underground duct installation.
50 0.387 1,276 220 259 199 214 180 187
70 0.268 1,127 275 324 244 263 220 229
Max. Conductor Temperature : Armour 95 0.193 1,018 334 395 291 315 264 274
90 °C (Normal Operation) Copper tape 120 0.153 934 385 456 331 359 300 313
150 0.124 869 437 518 371 403 336 351
Insulation
185 0.0991 803 500 594 419 456 380 397
AC TEST VOLTAGE : Conductor 240 0.0754 722 591 705 485 530 442 463
42 kV for 5 minutes 300 0.0601 664 677 809 547 600 499 524
CONSTRUCTION : 400 0.0470 597 784 941 621 685 570 600
REFERENCE STANDARD : 500 0.0366 543 904 1,092 702 780 649 687
Conductor : Compact round stranded copper.
IEC 60502-2 630 0.0283 483 1,044 1,275 792 891 739 788
Conductor shield : Semi-conducting cross-linked polyethylene.
800 0.0221 435 1,185 1,465 879 1,003 831 893
Insulation : Cross-linked polyethylene.
1,000 0.0176 379 1,336 1,679 962 1,117 923 1,002
Insulation shield : Semi-conducting cross-linked polyethylene.
1,200 0.0151 355 1,429 1,813 1,015 1,191 985 1,074
Metallic shield : Copper tape shield
Separation sheath : Black PE (PVC is available upon request)
Armour : Double Aluminium tape
Oversheath : Black PE (ST 7) (PVC is available upon request)
*CONDITION :
1. Conductor temperature 90 °C
Nominal Minimum Diameter Nominal Diameter Nominal Nominal Diameter Nominal Overall Cable Standard
cross-sectional number of thickness over thickness thickness over thickness diameter weight packing 2. Ambient air temperature 40 °C
area of conductor insulation armour (Approx.) (Approx.)
of of of of
wire of
conductor
(Approx.) insulation (Approx.) separation sheath Aluminium tape (Approx.) oversheath 3. Ground temperature 30 °C
armour
mm mm mm mm mm mm mm mm mm kg/km m 4. Depth of laying 0.8 m in ground
35 6 7.0 5.5 19.5 1.2 0.5 25.5 1.9 30 895 1,000/R
50 6 8.0 5.5 20.5 1.2 0.5 26.5 1.9 31 1,040 1,000/R 5. Thermal resistivity of soil 1.2 K.m/W
70 12 9.7 5.5 22.5 1.2 0.5 28.0 2.0 33 1,300 1,000/R 6. Axial spacing between phase cables in flat formation
95 15 11.3 5.5 24.0 1.2 0.5 30.0 2.0 34 1,580 1,000/R
120 18 12.8 5.5 25.5 1.2 0.5 31.5 2.1 36 1,865 1,000/R 2xODcable or 2xODduct
150 18 14.2 5.5 27.0 1.2 0.5 32.5 2.1 37 2,155 1,000/R 7. Shield and armours bonded at single point
185 30 15.8 5.5 28.5 1.2 0.5 34.5 2.2 39 2,540 500/R
240 34 18.2 5.5 31.0 1.2 0.5 36.5 2.3 42 3,155 500/R
300 34 20.3 5.5 33.0 1.3 0.5 39.0 2.3 44 3,775 500/R
400 53 23.0 5.5 35.5 1.3 0.5 41.5 2.4 47 4,640 500/R
500 53 25.9 5.5 39.0 1.4 0.5 45.0 2.5 51 5,730 250/R
630 53 29.9 5.5 43.0 1.4 0.5 49.0 2.6 55 7,185 250/R
800 53 33.8 5.5 46.5 1.5 0.5 53.0 2.8 59 8,985 250/R
1,000 53 39.8 5.5 52.5 1.6 0.5 59.5 2.9 66 11,160 250/R
1,200 - 42.9 5.5 56.0 1.7 0.5 62.5 3.0 69 12,835 250/R
R = Packing in reel
32 33
PHELPS DODGE CABLE TYPE MXLP-DATA PHELPS DODGE CABLE TYPE MXLP-DATA
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
18 / 30 (36) kV COPPER CONDUCTOR WITH DOUBLE ALUMINIUM TAPE ARMOUR
Nominal Max Rdc Min Current Carrying Current Carrying Current Carrying
cross- at 20 °C IR at Capacity* Capacity* Capacity*
Conductor shield sectional of Cdr. 20 (A) (A) (A)
area In Air In Ground In PE Duct, In Ground
Insulation shield
APPLICATION :
Preferably used for urban networks.
Separation sheath
Oversheath
Exposed in aerial, direct burial,
mm /km km 0.5 x D e 0.5 x D e
conduit, open tray and
50 0.387 1,632 224 257 198 212 176 182
underground duct installation.
70 0.268 1,457 278 322 241 260 216 224
95 0.193 1,328 338 391 288 312 258 268
Max. Conductor Temperature : Armour
120 0.153 1,227 389 451 327 355 294 305
90 °C (Normal Operation) Copper tape 150 0.124 1,148 441 513 367 399 330 344
185 0.0991 1,067 504 587 414 452 373 390
Insulation
240 0.0754 966 595 696 480 526 434 454
AC TEST VOLTAGE : Conductor 300 0.0601 893 681 798 541 595 492 515
63 kV for 5 minutes 400 0.0470 808 788 927 614 680 562 590
CONSTRUCTION : 500 0.0366 740 907 1,074 695 775 640 676
REFERENCE STANDARD : 630 0.0283 662 1,048 1,254 784 885 731 777
Conductor : Compact round stranded copper.
IEC 60502-2 800 0.0221 600 1,189 1,439 872 997 822 880
Conductor shield : Semi-conducting cross-linked polyethylene.
1,000 0.0176 525 1,341 1,648 955 1,112 917 991
Insulation : Cross-linked polyethylene.
1,200 0.0151 493 1,435 1,779 1,009 1,186 977 1,062
Insulation shield : Semi-conducting cross-linked polyethylene.
Metallic shield : Copper tape shield
Separation sheath : Black PE (PVC is available upon request)
Armour : Double Aluminium tape
*CONDITION :
Oversheath : Black PE (ST 7) (PVC is available upon request)
1. Conductor temperature 90 °C
2. Ambient air temperature 40 °C
Nominal Minimum Diameter Nominal Diameter Nominal Nominal Diameter Nominal Overall Cable Standard
cross-sectional number of thickness over thickness thickness over thickness diameter weight packing 3. Ground temperature 30 °C
area of wire conductor of insulation of of armour of (Approx.) (Approx.)
of (Approx.) insulation (Approx.) separation sheath Aluminium tape (Approx.) oversheath
4. Depth of laying 0.8 m in ground
conductor armour
mm mm mm mm mm mm mm mm mm kg/km m
5. Thermal resistivity of soil 1.2 K.m/W
50 6 8.0 8.0 26.0 1.2 0.5 31.5 2.1 36 1,305 1,000/R
70 12 9.7 8.0 27.5 1.2 0.5 33.5 2.1 38 1,565 1,000/R 6. Axial spacing between phase cables in flat formation
95 15 11.3 8.0 29.0 1.2 0.5 35.0 2.2 40 1,875 1,000/R 2xODcable or 2xODduct
120 18 12.8 8.0 30.5 1.2 0.5 36.5 2.3 42 2,170 1,000/R
7. Shield and armours bonded at single point
150 18 14.2 8.0 32.0 1.3 0.5 38.0 2.3 43 2,480 1,000/R
185 30 15.8 8.0 33.5 1.3 0.5 39.5 2.4 45 2,885 500/R
240 34 18.2 8.0 36.0 1.3 0.5 42.0 2.4 47 3,505 500/R
300 34 20.3 8.0 38.0 1.4 0.5 44.5 2.5 50 4,160 500/R
400 53 23.0 8.0 41.0 1.4 0.5 47.0 2.6 53 5,050 250/R
500 53 25.9 8.0 44.0 1.5 0.5 50.5 2.7 56 6,165 250/R
630 53 29.9 8.0 48.0 1.5 0.5 54.5 2.8 61 7,655 250/R
800 53 33.8 8.0 52.0 1.6 0.5 58.5 3.0 65 9,495 250/R
1,000 53 39.8 8.0 58.0 1.7 0.5 64.5 3.1 72 11,720 250/R
1,200 - 42.9 8.0 61.0 1.8 0.5 68.0 3.2 75 13,425 250/R
R = Packing in reel
34 35
PHELPS DODGE CABLE TYPE MXLP-AWA PHELPS DODGE CABLE TYPE MXLP-AWA
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
3.6 / 6 (7.2) kV COPPER CONDUCTOR WITH ALUMINIUM WIRE ARMOUR Nominal Max Rdc Min Current Carrying Capacity* Current Carrying Capacity* Current Carrying Capacity*
Conductor shield cross- at 20 °C IR at (A) (A) (A)
sectional of Cdr. 20 In Air In Ground In PE Duct, In Ground
Insulation shield area
36 37
PHELPS DODGE CABLE TYPE MXLP-AWA PHELPS DODGE CABLE TYPE MXLP-AWA
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
6 / 10 (12) kV COPPER CONDUCTOR WITH ALUMINIUM WIRE ARMOUR Nominal Max Rdc Min Current Carrying Capacity* Current Carrying Capacity* Current Carrying Capacity*
Conductor shield cross- at 20 °C IR at (A) (A) (A)
sectional of Cdr. 20 In Air In Ground In PE Duct, In Ground
Insulation shield area
38 39
PHELPS DODGE CABLE TYPE MXLP-AWA PHELPS DODGE CABLE TYPE MXLP-AWA
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
8.7 / 15 (17.5) kV COPPER CONDUCTOR WITH ALUMINIUM WIRE ARMOUR Nominal Max Rdc Min Current Carrying Capacity* Current Carrying Capacity* Current Carrying Capacity*
cross- at 20 °C IR at (A) (A) (A)
Conductor shield In Air In Ground In PE Duct, In Ground
sectional of Cdr. 20
Insulation shield area
40 41
PHELPS DODGE CABLE TYPE MXLP-AWA PHELPS DODGE CABLE TYPE MXLP-AWA
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
12 / 20 (24) kV COPPER CONDUCTOR WITH ALUMINIUM WIRE ARMOUR Nominal Max Rdc Min Current Carrying Capacity* Current Carrying Capacity* Current Carrying Capacity*
cross- at 20 °C IR at (A) (A) (A)
Conductor shield sectional of Cdr. 20 In Air In Ground In PE Duct, In Ground
Insulation shield area
mm mm mm mm mm mm mm mm mm kg/km m
6. Axial spacing between phase cables in flat formation
35 6 7.0 5.5 18.9 1.2 1.60 25.6 1.9 29 1,165 1,000/R 2xODcable or 2xODduct
50 6 8.0 5.5 19.9 1.2 1.60 26.7 2.0 31 1,340 1,000/R
7. Shield and armour bonded at single point
70 12 9.7 5.5 21.6 1.2 2.00 29.2 2.0 33 1,690 1,000/R
95 15 11.3 5.5 23.2 1.2 2.00 30.8 2.1 35 2,015 1,000/R
120 18 12.8 5.5 24.7 1.2 2.00 32.3 2.1 36 2,325 1,000/R
150 18 14.2 5.5 26.1 1.2 2.00 33.7 2.2 38 2,655 500/R
185 30 15.8 5.5 27.7 1.2 2.00 35.3 2.2 40 3,060 500/R
240 34 18.2 5.5 30.1 1.2 2.00 37.7 2.3 42 3,725 500/R
300 34 20.3 5.5 32.2 1.3 2.50 41.0 2.4 46 4,555 500/R
400 53 23.0 5.5 34.9 1.3 2.50 43.7 2.5 49 5,490 250/R
500 53 25.9 5.5 38.1 1.4 2.50 46.8 2.6 52 6,780 250/R
630 53 29.9 5.5 42.1 1.4 2.50 50.8 2.8 56 8,400 250/R
800 53 33.8 5.5 46.0 1.5 2.50 54.9 2.9 61 10,325 250/R
1,000 53 39.8 5.5 52.0 1.6 2.50 61.2 3.0 67 12,705 250/R
1,200 - 42.9 5.5 55.1 1.7 2.50 64.5 3.2 71 14,525 250/R
R = Packing in reel
42 43
PHELPS DODGE CABLE TYPE MXLP-AWA PHELPS DODGE CABLE TYPE MXLP-AWA
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
18 / 30 (36) kV COPPER CONDUCTOR WITH ALUMINIUM WIRE ARMOUR Nominal Max Rdc Min Current Carrying Capacity* Current Carrying Capacity* Current Carrying Capacity*
cross- at 20 °C IR at (A) (A) (A)
Conductor shield sectional of Cdr. 20 In Air In Ground In PE Duct, In Ground
Insulation shield area
44 45
PHELPS DODGE CABLE TYPE MXLP-LS-AWA PHELPS DODGE CABLE TYPE MXLP-LS-AWA
46 47
PHELPS DODGE CABLE TYPE MXLP-LS-AWA PHELPS DODGE CABLE TYPE MXLP-LS-AWA
48 49
PHELPS DODGE CABLE TYPE MXLP-LS-AWA PHELPS DODGE CABLE TYPE MXLP-LS-AWA
50 51
PHELPS DODGE CABLE TYPE MXLP-LS-AWA PHELPS DODGE CABLE TYPE MXLP-LS-AWA
Nominal Minimum Diameter Nominal Diameter Nominal Nominal Nominal Nominal Diameter Nominal Overall Cable Standard 5. Thermal resistivity of soil 1.2 K.m/W
cross- number of thickness over thickness thickness thickness diameter over thickness diameter weight packing
sectional of conductor of insulation of of of of armour of (Approx.) (Approx.)
insulation inner lead sheath separation Aluminium (Approx.) oversheath
6. Axial spacing between phase cables in flat formation
area wire of (Approx.) (Approx.)
conductor covering sheath wire
armour
2xODcable or 2xODduct
7. Shield and armour bonded at single point
mm mm mm mm mm mm mm mm mm mm mm kg/km m
50 6 8.0 8.0 25.6 1.2 1.6 1.5 2.50 40.9 2.4 46 3,965 500/R
70 12 9.7 8.0 27.3 1.2 1.6 1.5 2.50 42.6 2.5 48 4,385 500/R
95 15 11.3 8.0 28.9 1.2 1.7 1.5 2.50 44.4 2.5 50 4,945 500/R
120 18 12.8 8.0 30.4 1.2 1.7 1.5 2.50 45.9 2.6 52 5,380 250/R
150 18 14.2 8.0 31.8 1.3 1.8 1.5 2.50 47.7 2.6 53 5,975 250/R
185 30 15.8 8.0 33.4 1.3 1.8 1.5 2.50 49.3 2.7 55 6,525 250/R
240 34 18.2 8.0 35.8 1.3 1.9 1.5 2.50 51.9 2.8 58 7,540 250/R
300 34 20.3 8.0 37.9 1.4 1.9 1.5 2.50 54.2 2.9 61 8,400 250/R
400 53 23.0 8.0 40.6 1.4 2.0 1.6 2.50 57.4 3.0 64 9,785 250/R
500 53 25.9 8.0 43.5 1.5 2.1 1.6 2.50 60.7 3.1 67 11,405 250/R
630 53 29.9 8.0 47.7 1.5 2.2 1.7 2.50 65.3 3.2 72 13,535 250/R
800 53 33.8 8.0 51.7 1.6 2.3 1.8 3.15 71.2 3.4 79 16,375 250/R
1,000 53 39.8 8.0 57.7 1.7 2.4 1.9 3.15 77.8 3.6 86 19,620 250/R
1,200 - 42.9 8.0 60.8 1.8 2.6 1.9 3.15 81.5 3.7 90 22,250 250/R
R = Packing in reel
52 53
PHELPS DODGE CABLE TYPE MXLP-CTS (3 CORES) PHELPS DODGE CABLE TYPE MXLP-CTS (3 CORES)
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
3.6/6 (7.2) kV COPPER CONDUCTOR THREE CORES WITH COPPER TAPE SHIELD Nominal Max Rdc Min Current Carrying Capacity* Current Carrying Capacity* Current Carrying Capacity*
cross- at 20 °C IR at (A) (A) (A)
Conductor shield sectional of Cdr. 20 In Air In Ground In PE Duct, In Ground
area
Insulation shield
APPLICATION :
Filler
Preferably used for urban networks. mm /km km 0.3 x D e
Oversheath
Exposed in aerial, direct burial,
35 0.524 778 169 168 131
conduit, open tray and 50 0.387 706 203 197 154
underground duct installation. 70 0.268 611 255 242 190
95 0.193 544 312 289 229
Max. Conductor Temperature : Binding tape 120 0.153 493 362 328 262
Metallic shield 150 0.124 454 412 368 295
90 °C (Normal Operation)
185 0.0991 415 474 415 334
Insulation
240 0.0754 382 563 480 390
AC TEST VOLTAGE : Conductor 300 0.0601 372 647 540 443
12.5 kV for 5 minutes 400 0.0470 353 750 611 506
CONSTRUCTION :
REFERENCE STANDARD : Conductor : Compact round stranded copper.
IEC 60502-2 Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
*CONDITION :
Insulation shield : Semi-conducting cross-linked polyethylene.
Metallic shield : Copper tape shield 1. Conductor temperature 90 °C
Filler : Nonhygroscopic material 2. Ambient air temperature 40 °C
Binding tape : Polyester and/or Spunbond tape
3. Ground temperature 30 °C
Oversheath : Black PE (ST 7) (PVC is available upon request)
4. Depth of laying 0.8 m in ground
5. Thermal resistivity of soil 1.2 K.m/W
Nominal Minimum Diameter Nominal Diameter Nominal Overall Cable Standard
cross- number of thickness over thickness diameter weight packing
of of
6. Shields bonded at single point or both ends
sectional of conductor insulation (Approx.) (Approx.)
area wire of (Approx.) insulation (Approx.) oversheath
conductor
mm mm mm mm mm mm kg/km m
54 55
PHELPS DODGE CABLE TYPE MXLP-CTS (3 CORES) PHELPS DODGE CABLE TYPE MXLP-CTS (3 CORES)
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
6/10 (12) kV COPPER CONDUCTOR THREE CORES WITH COPPER TAPE SHIELD Nominal Max Rdc Min Current Carrying Capacity* Current Carrying Capacity* Current Carrying Capacity*
cross- at 20 °C IR at (A) (A) (A)
Conductor shield sectional of Cdr. 20 In Air In Ground In PE Duct, In Ground
area
Insulation shield
APPLICATION :
Filler
Preferably used for urban networks. 0.3 x D e
Oversheath mm /km km
Exposed in aerial, direct burial,
35 0.524 985 173 168 133
conduit, open tray and
50 0.387 899 207 198 157
underground duct installation. 70 0.268 784 259 242 193
95 0.193 701 317 289 232
Binding tape
Max. Conductor Temperature : 120 0.153 639 366 328 265
90 °C (Normal Operation) Metallic shield 150 0.124 590 417 368 298
Insulation 185 0.0991 542 479 415 338
AC TEST VOLTAGE : 240 0.0754 483 567 481 394
Conductor
300 0.0601 442 650 541 446
21 kV for 5 minutes
400 0.0470 394 752 612 509
CONSTRUCTION :
REFERENCE STANDARD : Conductor : Compact round stranded copper.
IEC 60502-2 Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene. *CONDITION :
Metallic shield : Copper tape shield 1. Conductor temperature 90 °C
Filler : Nonhygroscopic material
2. Ambient air temperature 40 °C
Binding tape : Polyester and/or Spunbond tape
Oversheath : Black PE (ST 7) (PVC is available upon request) 3. Ground temperature 30 °C
4. Depth of laying 0.8 m in ground
Nominal Minimum Diameter Nominal Diameter Nominal Overall Cable Standard 5. Thermal resistivity of soil 1.2 K.m/W
cross - number of thickness over thickness diameter weight packing
sectional of conductor of insulation of (Approx.) (Approx.) 6. Shields bonded at single point or both ends
area wire of (Approx.) insulation (Approx.) ove rsheath
conductor
mm mm mm mm mm mm kg/km m
56 57
PHELPS DODGE CABLE TYPE MXLP-CTS (3 CORES) PHELPS DODGE CABLE TYPE MXLP-CTS (3 CORES)
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
8.7/15 (17.5) kV COPPER CONDUCTOR THREE CORES WITH COPPER TAPE SHIELD Nominal Max Rdc Min Current Carrying Capacity* Current Carrying Capacity* Current Carrying Capacity*
cross- at 20 °C IR at (A) (A) (A)
Conductor shield sectional of Cdr. 20 In Air In Ground In PE Duct, In Ground
area
Insulation shield
APPLICATION :
Filler
Preferably used for urban networks.
Oversheath mm /km km 0.3 x D e
Exposed in aerial, direct burial,
35 0.524 1,207 176 168 135
conduit, open tray and
50 0.387 1,107 211 198 159
underground duct installation. 70 0.268 973 264 242 196
95 0.193 875 321 289 235
Max. Conductor Temperature : Binding tape 120 0.153 800 371 329 268
90 °C (Normal Operation) Metallic shield 150 0.124 742 422 369 302
185 0.0991 684 483 416 342
Insulation
240 0.0754 613 572 482 399
AC TEST VOLTAGE : Conductor
300 0.0601 562 655 542 451
30.5 kV for 5 minutes
400 0.0470 503 758 614 514
CONSTRUCTION :
REFERENCE STANDARD : Conductor : Compact round stranded copper.
IEC 60502-2 Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene. *CONDITION :
Metallic shield : Copper tape shield
1. Conductor temperature 90 °C
Filler : Nonhygroscopic material
Binding tape : Polyester and/or Spunbond tape 2. Ambient air temperature 40 °C
Oversheath : Black PE (ST 7) (PVC is available upon request) 3. Ground temperature 30 °C
4. Depth of laying 0.8 m in ground
Nominal Minimum Diameter Nominal Diameter Nominal Overall Cable Standard 5. Thermal resistivity of soil 1.2 K.m/W
cross- number of thickness over thickness diameter weight packing
sectional of conductor of insulation of (Approx.) (Approx.)
insulation oversheath
6. Shields bonded at single point or both ends
area wire of (Approx.) (Approx.)
conductor
mm mm mm mm mm mm kg/km m
58 59
PHELPS DODGE CABLE TYPE MXLP-CTS (3 CORES) PHELPS DODGE CABLE TYPE MXLP-CTS (3 CORES)
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
12/20 (24) kV COPPER CONDUCTOR THREE CORES WITH COPPER TAPE SHIELD Nominal Max Rdc Min Current Carrying Capacity* Current Carrying Capacity* Current Carrying Capacity*
cross- at 20 °C IR at (A) (A) (A)
Conductor shield sectional of Cdr. 20 In Air In Ground In PE Duct, In Ground
area
Insulation shield
APPLICATION :
Filler
Preferably used for urban networks. mm /km km 0.3 x D e
Oversheath
Exposed in aerial, direct burial, 35 0.524 1,384 179 168 137
conduit, open tray and 50 0.387 1,276 213 198 161
underground duct installation. 70 0.268 1,127 267 242 198
95 0.193 1,018 324 290 238
Binding tape 120 0.153 934 374 329 271
Max. Conductor Temperature :
150 0.124 869 425 369 305
90 °C (Normal Operation) Metallic shield
185 0.0991 803 487 416 345
Insulation 240 0.0754 722 576 482 402
AC TEST VOLTAGE : Conductor 300 0.0601 664 659 543 455
42 kV for 5 minutes 400 0.0470 596 762 615 519
CONSTRUCTION :
REFERENCE STANDARD : Conductor : Compact round stranded copper.
IEC 60502-2 Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene. *CONDITION :
Insulation shield : Semi-conducting cross-linked polyethylene.
1. Conductor temperature 90 °C
Metallic shield : Copper tape shield
Filler : Nonhygroscopic material 2. Ambient air temperature 40 °C
Binding tape : Polyester and/or Spunbond tape 3. Ground temperature 30 °C
Oversheath : Black PE (ST 7) (PVC is available upon request)
4. Depth of laying 0.8 m in ground
5. Thermal resistivity of soil 1.2 K.m/W
Nominal Minimum Diameter Nominal Diameter Nominal Overall Cable Standard
cross- number of thickness over thickness diameter weight packing 6. Shields bonded at single point or both ends
sectional of conductor of insulation of (Approx.) (Approx.)
area wire of (Approx.) insulation (Approx.) oversheath
conductor
mm mm mm mm mm mm kg/km m
60 61
PHELPS DODGE CABLE TYPE MXLP-CTS (3 CORES) PHELPS DODGE CABLE TYPE MXLP-CTS (3 CORES)
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
18/30 (36) kV COPPER CONDUCTOR THREE CORES WITH COPPER TAPE SHIELD Nominal Max Rdc Min Current Carrying Capacity* Current Carrying Capacity* Current Carrying Capacity*
cross- at 20 °C IR at (A) (A) (A)
Conductor shield sectional of Cdr. 20 In Air In Ground In PE Duct, In Ground
area
Insulation shield
APPLICATION :
Filler
Preferably used for urban networks. mm /km km 0.3 x D e
Oversheath
Exposed in aerial, direct burial, 50 0.387 1,632 218 198 166
conduit, open tray and 70 0.268 1,457 272 243 203
underground duct installation. 95 0.193 1,328 330 290 243
120 0.153 1,227 380 329 277
150 0.124 1,148 431 369 312
Max. Conductor Temperature : Binding tape
185 0.0991 1,067 493 417 353
90 °C (Normal Operation) Metallic shield
240 0.0754 966 582 483 411
Insulation 300 0.0601 893 666 544 465
AC TEST VOLTAGE : Conductor 400 0.0470 808 769 617 530
63 kV for 5 minutes
CONSTRUCTION :
REFERENCE STANDARD : Conductor : Compact round stranded copper.
IEC 60502-2 Conductor shield : Semi-conducting cross-linked polyethylene. *CONDITION :
Insulation : Cross-linked polyethylene. 1. Conductor temperature 90 °C
Insulation shield : Semi-conducting cross-linked polyethylene.
Metallic shield : Copper tape shield 2. Ambient air temperature 40 °C
Filler : Nonhygroscopic material 3. Ground temperature 30 °C
Binding tape : Polyester and/or Spunbond tape
4. Depth of laying 0.8 m in ground
Oversheath : Black PE (ST 7) (PVC is available upon request)
5. Thermal resistivity of soil 1.2 K.m/W
6. Shields bonded at single point or both ends
Nominal Minimum Diameter Nominal Diameter Nominal Overall Cable Standard
cross- number of thickness over thickness diameter weight packing
sectional of conductor of insulation of (Approx.) (Approx.)
area wire of (Approx.) insulation (Approx.) ov ersheath
conductor
mm mm mm mm mm mm kg/km m
62 63
PHELPS DODGE CABLE TYPE MXLP-DSTA (3 CORES) PHELPS DODGE CABLE TYPE MXLP-DSTA (3 CORES)
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
3.6/6 (7.2) kV COPPER CONDUCTOR THREE CORES WITH DOUBLE STEEL TAPE ARMOUR Nominal Max Rdc Min Current Carrying Current Carrying Current Carrying
Conductor shield cross- at 20 °C IR at Capacity* Capacity* Capacity*
sectional of Cdr. 20 (A) (A) (A)
Insulation shield area In Air In Ground In PE Duct, In Ground
Binding tape
APPLICATION : Armour
Preferably used for urban networks. Oversheath mm /km km 0.3 x D e
Exposed in aerial, direct burial,
35 0.524 778 173 167 133
conduit, open tray and
50 0.387 706 207 197 157
underground duct installation.
70 0.268 611 259 240 193
Inner covering 95 0.193 544 315 287 232
Max. Conductor Temperature : Filler 120 0.153 493 364 326 264
90 °C (Normal Operation) Metallic shield 150 0.124 454 413 364 297
Insulation 185 0.0991 415 473 411 337
Conductor 240 0.0754 382 559 475 392
AC TEST VOLTAGE :
12.5 kV for 5 minutes 300 0.0601 372 640 532 443
CONSTRUCTION :
400 0.0470 353 738 601 505
Conductor : Compact round stranded copper.
REFERENCE STANDARD : Conductor shield : Semi-conducting cross-linked polyethylene.
IEC 60502-2 Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Shield : Copper tape shield
Filler : Nonhygroscopic material *CONDITION :
Binding tape : Polyester and/or Spunbond tape 1. Conductor temperature 90 °C
Inner covering : Black PE (PVC is available upon request)
Armour : Double steel tape 2. Ambient air temperature 40 °C
Oversheath : Black PE (ST 7) (PVC is available upon request) 3. Ground temperature 30 °C
4. Depth of laying 0.8 m in ground
Nominal Minimum Diameter Nominal Diameter Nominal Nominal Diameter Nominal Overall Cable Standard 5. Thermal resistivity of soil 1.2 K.m/W
cross- number of thickness over thickness thickness over thickness diameter weight packing
sectional of conductor of insulation of of armour of (Approx.) (Approx.)
area wire of (Approx.) insulation (Approx.) inner steel tape (Approx.) oversheath
6. Shields bonded at single point or both ends
conductor covering armour
mm mm mm mm mm mm mm mm mm kg/km m
64 65
PHELPS DODGE CABLE TYPE MXLP-DSTA (3 CORES) PHELPS DODGE CABLE TYPE MXLP-DSTA (3 CORES)
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
6/10 (12) kV COPPER CONDUCTOR THREE CORES WITH DOUBLE STEEL TAPE ARMOUR Nominal Max Rdc Min Current Carrying Current Carrying Current Carrying
Conductor shield cross- at 20 °C IR at Capacity* Capacity* Capacity*
sectional of Cdr. 20 (A) (A) (A)
Insulation shield area In Air In Ground In PE Duct, In Ground
Binding tape
APPLICATION : Armour
Preferably used for urban networks. Oversheath mm /km km 0.3 x D e
Exposed in aerial, direct burial,
35 0.524 985 175 167 135
conduit, open tray and
50 0.387 899 210 197 159
underground duct installation. 70 0.268 784 262 241 195
Inner covering 95 0.193 701 319 287 235
Max. Conductor Temperature : Filler 120 0.153 639 367 326 267
90 °C (Normal Operation) Metallic shield 150 0.124 590 417 365 300
Insulation 185 0.0991 542 477 411 340
Conductor 240 0.0754 483 563 475 395
AC TEST VOLTAGE :
21 kV for 5 minutes 300 0.0601 442 642 533 446
CONSTRUCTION :
400 0.0470 394 742 601 507
Conductor : Compact round stranded copper.
REFERENCE STANDARD : Conductor shield : Semi-conducting cross-linked polyethylene.
IEC 60502-2 Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Shield : Copper tape shield
Filler : Nonhygroscopic material *CONDITION :
Binding tape : Polyester and/or Spunbond tape 1. Conductor temperature 90 °C
Inner covering : Black PE (PVC is available upon request)
Armour : Double steel tape 2. Ambient air temperature 40 °C
Oversheath : Black PE (ST 7) (PVC is available upon request) 3. Ground temperature 30 °C
4. Depth of laying 0.8 m in ground
Nominal Minimum Diameter Nominal Diameter Nominal Nominal Diameter Nominal Overall Cable Standard 5. Thermal resistivity of soil 1.2 K.m/W
cross - number of thickness over thickness thickness over thickness diameter weight packing
sectional of conductor of insulation of of armour of (Approx.) (Approx.)
6. Shields bonded at single point or both ends
area wire of (Approx.) insulation (Approx.) inner steel tape (Approx.) oversheath
conductor covering armour
mm mm mm mm mm mm mm mm mm kg/km m
66 67
PHELPS DODGE CABLE TYPE MXLP-DSTA (3 CORES) PHELPS DODGE CABLE TYPE MXLP-DSTA (3 CORES)
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
8.7/15 (17.5) kV COPPER CONDUCTOR THREE CORES WITH DOUBLE STEEL TAPE ARMOUR Nominal Max Rdc Min Current Carrying Current Carrying Current Carrying
Conductor shield cross- at 20 °C IR at Capacity* Capacity* Capacity*
sectional of Cdr. 20 (A) (A) (A)
Insulation shield area In Air In Ground In PE Duct, In Ground
Binding tape
APPLICATION : Armour
Preferably used for urban networks. Oversheath mm /km km 0.3 x D e
Exposed in aerial, direct burial,
35 0.524 1,207 178 167 137
conduit, open tray and
50 0.387 1,107 212 197 161
underground duct installation. 70 0.268 973 265 241 198
Inner covering 95 0.193 875 322 287 237
Max. Conductor Temperature : Filler 120 0.153 800 371 326 270
90 °C (Normal Operation) Metallic shield 150 0.124 742 421 365 304
Insulation 185 0.0991 684 481 412 344
Conductor 240 0.0754 613 567 476 399
AC TEST VOLTAGE :
30.5 kV for 5 minutes 300 0.0601 562 647 534 450
CONSTRUCTION :
400 0.0470 503 746 603 512
Conductor : Compact round stranded copper.
REFERENCE STANDARD : Conductor shield : Semi-conducting cross-linked polyethylene.
IEC 60502-2 Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Shield : Copper tape shield
Filler : Nonhygroscopic material *CONDITION :
Binding tape : Polyester and/or Spunbond tape 1. Conductor temperature 90 °C
Inner covering : Black PE (PVC is available upon request)
Armour : Double steel tape 2. Ambient air temperature 40 °C
Oversheath : Black PE (ST 7) (PVC is available upon request) 3. Ground temperature 30 °C
4. Depth of laying 0.8 m in ground
Nominal Minimum Diameter Nominal Diameter Nominal Nominal Diameter Nominal Overall Cable Standard 5. Thermal resistivity of soil 1.2 K.m/W
cross - number of thickness over thickness thickness over thickness diameter weight packing
sectional of conductor of insulation of of armour of (Approx.) (Approx.)
area wire of (Approx.) insulation (Approx.) inner steel tape (Approx.) oversheath
6. Shields bonded at single point or both ends
conductor covering armour
mm mm mm mm mm mm mm mm mm kg/km m
68 69
PHELPS DODGE CABLE TYPE MXLP-DSTA (3 CORES) PHELPS DODGE CABLE TYPE MXLP-DSTA (3 CORES)
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
12/20 (24) kV COPPER CONDUCTOR THREE CORES WITH DOUBLE STEEL TAPE ARMOUR Nominal Max Rdc Min Current Carrying Current Carrying Current Carrying
Conductor shield cross- at 20 °C IR at Capacity* Capacity* Capacity*
sectional of Cdr. 20 (A) (A) (A)
Insulation shield area In Air In Ground In PE Duct, In Ground
Binding tape
APPLICATION : Armour
Preferably used for urban networks. Oversheath mm /km km 0.3 x D e
Exposed in aerial, direct burial,
35 0.524 1,384 180 167 138
conduit, open tray and
50 0.387 1,276 214 197 163
underground duct installation. 70 0.268 1,127 267 241 200
Inner covering 95 0.193 1,018 324 288 240
Max. Conductor Temperature : Filler 120 0.153 934 374 326 273
90 °C (Normal Operation) Metallic shield 150 0.124 869 424 366 306
Insulation 185 0.0991 803 483 412 346
Conductor 240 0.0754 722 570 476 402
AC TEST VOLTAGE :
42 kV for 5 minutes 300 0.0601 664 652 535 455
CONSTRUCTION :
400 0.0470 596 750 604 516
Conductor : Compact round stranded copper.
REFERENCE STANDARD : Conductor shield : Semi-conducting cross-linked polyethylene.
IEC 60502-2 Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Shield : Copper tape shield
Filler : Nonhygroscopic material *CONDITION :
Binding tape : Polyester and/or Spunbond tape 1. Conductor temperature 90 °C
Inner covering : Black PE (PVC is available upon request)
Armour : Double steel tape 2. Ambient air temperature 40 °C
Oversheath : Black PE (ST 7) (PVC is available upon request) 3. Ground temperature 30 °C
4. Depth of laying 0.8 m in ground
Nominal Minimum Diameter Nominal Diameter Nominal Nominal Diameter Nominal Overall Cable Standard 5. Thermal resistivity of soil 1.2 K.m/W
cross- number of thickness over thickness thickness over thickness diameter weight packing
sectional of conductor of insulation of of armour of (Approx.) (Approx.)
area wire of (Approx.) insulation (Approx.) (App rox.) over sheath
6. Shields bonded at single point or both ends
inner steel tape
conductor covering armour
mm mm mm mm mm mm mm mm mm kg/km m
70 71
PHELPS DODGE CABLE TYPE MXLP-DSTA (3 CORES) PHELPS DODGE CABLE TYPE MXLP-DSTA (3 CORES)
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
18/30 (36) kV COPPER CONDUCTOR THREE CORES WITH DOUBLE STEEL TAPE ARMOUR Nominal Max Rdc Min Current Carrying Current Carrying Current Carrying
Conductor shield cross- at 20 °C IR at Capacity* Capacity* Capacity*
sectional of Cdr. 20 (A) (A) (A)
Insulation shield area In Air In Ground In PE Duct, In Ground
Binding tape
APPLICATION : Armour
Preferably used for urban networks. Oversheath mm /km km 0.3 x D e
Exposed in aerial, direct burial,
50 0.387 1,632 218 197 167
conduit, open tray and
70 0.268 1,457 271 241 205
underground duct installation. 95 0.193 1,328 329 288 245
Inner covering 120 0.153 1,227 378 327 279
Max. Conductor Temperature : Filler 150 0.124 1,148 430 366 313
90 °C (Normal Operation) Metallic shield 185 0.0991 1,067 490 413 354
Insulation 240 0.0754 966 577 477 410
Conductor 300 0.0601 893 656 535 463
AC TEST VOLTAGE :
63 kV for 5 minutes 400 0.0470 808 754 605 525
CONSTRUCTION :
Conductor : Compact round stranded copper.
REFERENCE STANDARD : Conductor shield : Semi-conducting cross-linked polyethylene.
IEC 60502-2 Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene. *CONDITION :
Shield : Copper tape shield
Filler : Nonhygroscopic material 1. Conductor temperature 90 °C
Binding tape : Polyester and/or Spunbond tape 2. Ambient air temperature 40 °C
Inner covering : Black PE (PVC is available upon request)
Armour : Double steel tape 3. Ground temperature 30 °C
Oversheath : Black PE (ST 7) (PVC is available upon request) 4. Depth of laying 0.8 m in ground
5. Thermal resistivity of soil 1.2 K.m/W
Nominal Minimum Diameter Nominal Diameter Nominal Nominal Diameter Nominal Overall Cable Standard
cross- number of thickness over thickness thickness over thickness diameter weight packing
6. Shields bonded at single point or both ends
sectional of conductor of insulation of of armour of (Approx.) (Approx.)
area wire of (Approx.) insulation (Approx.) inner steel tape (Approx.) oversheath
conductor covering armour
mm mm mm mm mm mm mm mm mm kg/km m
72 73
PHELPS DODGE CABLE TYPE MXLP-SWA (3 CORES) PHELPS DODGE CABLE TYPE MXLP-SWA (3 CORES)
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
3.6/6 (7.2) kV COPPER CONDUCTOR THREE CORES WITH STEEL WIRE ARMOUR Nominal Max Rdc Min Current Carrying Current Carrying Current Carrying
Conductor shield cross- at 20 °C IR at Capacity* Capacity* Capacity*
Insulation shield sectional of Cdr. 20 (A) (A) (A)
area In Air In Ground In PE Duct, In Ground
Binding tape
APPLICATION : Armour
Preferably used for urban networks. Oversheath
mm /km km 0.3 x D e
Exposed in aerial, direct burial,
35 0.524 778 172 166 133
conduit, open tray and 50 0.387 706 207 196 157
underground duct installation. 70 0.268 611 258 239 193
Binding tape 95 0.193 544 313 285 231
Inner Covering
Max. Conductor Temperature : 120 0.153 493 361 322 263
Filler
90 °C (Normal Operation) Metallic shield 150 0.124 454 408 358 297
Insulation 185 0.0991 415 466 404 332
AC TEST VOLTAGE : Conductor 240 0.0754 382 548 463 384
300 0.0601 372 620 513 429
12.5 kV for 5 minutes CONSTRUCTION :
400 0.0470 353 707 571 482
Conductor : Compact round stranded copper.
REFERENCE STANDARD : Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
IEC 60502-2 Insulation shield : Semi-conducting cross-linked polyethylene.
Metallic shield : Copper tape shield
Filler : Nonhygroscopic material *CONDITION :
Binding tape : Polyester and/or Spunbond tape
1. Conductor temperature 90 °C
Inner Covering : Black PE (PVC is available upon request)
Armour : Galvanized steel wire 2. Ambient air temperature 40 °C
Binding tape : Polyester and/or Spunbond tape
Oversheath : Black PE (ST 7) (PVC is available upon request) 3. Ground temperature 30 °C
4. Depth of laying 0.8 m in ground
Nominal Minimum Diameter Nominal Diameter Nominal Nominal Diameter Nominal Overall Cable Standard 5. Thermal resistivity of soil 1.2 K.m/W
cross- number of thickness over thickness diameter over thickness diameter weight packing
sectional of conductor of insulation of of armour of (Approx.) (Approx.) 6. Shields and armours bonded at both ends
area wire of (Approx.) insulation (Approx.) separation steel wire (Approx.) oversheath
conductor sheath armour
mm mm mm mm mm mm mm mm mm kg/km m
74 75
PHELPS DODGE CABLE TYPE MXLP-SWA (3 CORES) PHELPS DODGE CABLE TYPE MXLP-SWA (3 CORES)
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
6/10 (12) kV COPPER CONDUCTOR THREE CORES WITH STEEL WIRE ARMOUR Nominal Max Rdc Min Current Carrying Current Carrying Current Carrying
Conductor shield cross- at 20 °C IR at Capacity* Capacity* Capacity*
Insulation shield sectional of Cdr. 20 (A) (A) (A)
area In Air In Ground In PE Duct, In Ground
Binding tape
APPLICATION : Armour
Preferably used for urban networks. Oversheath
mm /km km 0.3 x D e
Nominal Minimum Diameter Nominal Diameter Nominal Nominal Diameter Nominal Overall Cable Standard 5. Thermal resistivity of soil 1.2 K.m/W
cross- number of thickness over thickness diameter over thickness diameter weight packing
sectional of conductor of insulation of of armour of (Approx.) (Approx.) 6. Shields and armours bonded at both ends
area wire of (Approx.) insulation (Approx.) separation steel wire (Approx.) oversheath
conductor sheath armour
mm mm mm mm mm mm mm mm mm kg/km m
76 77
PHELPS DODGE CABLE TYPE MXLP-SWA (3 CORES) PHELPS DODGE CABLE TYPE MXLP-SWA (3 CORES)
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
8.7/15 (17.5) kV COPPER CONDUCTOR THREE CORES WITH STEEL WIRE ARMOUR Nominal Max Rdc Min Current Carrying Current Carrying Current Carrying
Conductor shield cross- at 20 °C IR at Capacity* Capacity* Capacity*
Insulation shield sectional of Cdr. 20 (A) (A) (A)
area In Air In Ground In PE Duct, In Ground
Binding tape
APPLICATION : Armour
Preferably used for urban networks. Oversheath
mm /km km 0.3 x D e
Exposed in aerial, direct burial,
35 0.524 1,207 178 166 137
conduit, open tray and
PHELPS DODGE 50 0.387 1,107 212 196 161
underground duct installation. 70 0.268 973 264 239 198
Binding tape 95 0.193 875 319 285 236
Inner Covering
Max. Conductor Temperature : 120 0.153 800 367 322 268
Filler
90 °C (Normal Operation) Metallic shield 150 0.124 742 415 359 302
Insulation 185 0.0991 684 474 403 338
AC TEST VOLTAGE : Conductor 240 0.0754 613 553 461 389
300 0.0601 562 626 513 434
30.5 kV for 5 minutes CONSTRUCTION :
400 0.0470 503 712 571 486
Conductor : Compact round stranded copper.
REFERENCE STANDARD : Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
IEC 60502-2 Insulation shield : Semi-conducting cross-linked polyethylene.
Metallic shield : Copper tape shield
Filler : Nonhygroscopic material *CONDITION :
Binding tape : Polyester and/or Spunbond tape
Inner Covering : Black PE (PVC is available upon request) 1. Conductor temperature 90 °C
Armour : Galvanized steel wire 2. Ambient air temperature 40 °C
Binding tape : Polyester and/or Spunbond tape
Oversheath : Black PE (ST 7) (PVC is available upon request) 3. Ground temperature 30 °C
4. Depth of laying 0.8 m in ground
Nominal Minimum Diameter Nominal Diameter Nominal Nominal Diameter Nominal Overall Cable Standard 5. Thermal resistivity of soil 1.2 K.m/W
cross- number of thickness over thickness diameter over thickness diameter weight packing
sectional of conductor of insulation of of armour of (Approx.) (Approx.) 6. Shields and armours bonded at both ends
area wire of (Approx.) insulation (Approx.) separation steel wire (Approx.) oversheath
conductor sheath armour
mm mm mm mm mm mm mm mm mm kg/km m
78 79
PHELPS DODGE CABLE TYPE MXLP-SWA (3 CORES) PHELPS DODGE CABLE TYPE MXLP-SWA (3 CORES)
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
12/20 (24) kV COPPER CONDUCTOR THREE CORES WITH STEEL WIRE ARMOUR Nominal Max Rdc Min Current Carrying Current Carrying Current Carrying
Conductor shield cross- at 20 °C IR at Capacity* Capacity* Capacity*
Insulation shield sectional of Cdr. 20 (A) (A) (A)
area In Air In Ground In PE Duct, In Ground
Binding tape
APPLICATION : Armour
Preferably used for urban networks. Oversheath
mm /km km 0.3 x D e
Exposed in aerial, direct burial,
35 0.524 1,384 180 167 139
conduit, open tray and
50 0.387 1,276 214 196 163
underground duct installation. 70 0.268 1,127 266 239 200
Binding tape 95 0.193 1,018 322 285 238
Inner Covering
Max. Conductor Temperature :
Filler 120 0.153 934 370 323 271
90 °C (Normal Operation) Metallic shield 150 0.124 869 417 358 304
Insulation 185 0.0991 803 475 402 340
AC TEST VOLTAGE : Conductor 240 0.0754 722 556 461 391
300 0.0601 664 628 512 437
42 kV for 5 minutes CONSTRUCTION :
400 0.0470 596 710 565 485
Conductor : Compact round stranded copper.
REFERENCE STANDARD : Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
IEC 60502-2 Insulation shield : Semi-conducting cross-linked polyethylene.
Metallic shield : Copper tape shield
Filler : Nonhygroscopic material *CONDITION :
Binding tape : Polyester and/or Spunbond tape
Inner Covering : Black PE (PVC is available upon request) 1. Conductor temperature 90 °C
Armour : Galvanized steel wire 2. Ambient air temperature 40 °C
Binding tape : Polyester and/or Spunbond tape
Oversheath : Black PE (ST 7) (PVC is available upon request) 3. Ground temperature 30 °C
4. Depth of laying 0.8 m in ground
Nominal Minimum Diameter Nominal Diameter Nominal Diameter Diameter Nominal Overall Cable Standard 5. Thermal resistivity of soil 1.2 K.m/W
cross- number of thickness over thickness of over thickness diameter weight packing
sectional of conductor of insulation of steel wire armour of (Approx.) (Approx.) 6. Shields and armours bonded at both ends
area wire of (A pprox.) insulation (Approx.) separation armour (Approx.) oversheath
conductor sheath
mm mm mm mm mm mm mm mm mm kg/km m
80 81
PHELPS DODGE CABLE TYPE MXLP-SWA (3 CORES) PHELPS DODGE CABLE TYPE MXLP-SWA (3 CORES)
MEDIUM VOLTAGE CROSS-LINKED POLYETHYLENE CABLE Electrical Characteristics and Current Carrying Capacity
18/30 (36) kV COPPER CONDUCTOR THREE CORES WITH STEEL WIRE ARMOUR Nominal Max Rdc Min Current Carrying Current Carrying Current Carrying
Conductor shield cross- at 20 °C IR at Capacity* Capacity* Capacity*
Insulation shield sectional of Cdr. 20 (A) (A) (A)
area In Air In Ground In PE Duct, In Ground
Binding tape
APPLICATION : Armour
Preferably used for urban networks. Oversheath
Exposed in aerial, direct burial, mm /km km 0.3 x D e
mm mm mm mm mm mm mm mm mm kg/km m
82 83
PHELPS DODGE CABLE TYPE MXLP-LS-SWA (3 CORES) PHELPS DODGE CABLE TYPE MXLP-LS-SWA (3 CORES)
mm mm mm mm mm mm mm mm mm mm mm kg/km m
35 6 7.0 2.5 13.2 1.2 1.7 1.5 2.50 45.5 2.5 51 6,425 250/R
50 6 8.0 2.5 14.3 1.2 1.8 1.5 2.50 48.0 2.6 54 7,250 250/R
70 12 9.7 2.5 16.0 1.4 1.9 1.5 2.50 52.3 2.8 58 8,715 250/R
95 15 11.3 2.5 17.6 1.4 2.0 1.5 2.50 56.0 2.9 62 10,180 250/R
120 18 12.8 2.5 19.1 1.4 2.1 1.6 2.50 59.6 3.0 66 11,700 250/R
150 18 14.2 2.5 20.5 1.6 2.1 1.7 2.50 63.3 3.1 70 13,090 250/R
185 30 15.8 2.5 22.1 1.6 2.2 1.7 2.50 66.9 3.3 74 14,960 250/R
240 34 18.2 2.6 24.7 1.6 2.4 1.8 3.15 74.5 3.5 82 19,055 250/R
300 34 20.3 2.8 27.2 1.8 2.6 1.9 3.15 80.9 3.7 89 22,600 250/R
400 53 23.0 3.0 30.3 1.8 2.8 2.1 3.15 88.5 4.0 97 27,260 250/R
R = Packing in reel
84 85
PHELPS DODGE CABLE TYPE MXLP-LS-SWA (3 CORES) PHELPS DODGE CABLE TYPE MXLP-LS-SWA (3 CORES)
mm mm mm mm mm mm mm mm mm mm mm kg/km m
35 6 7.0 3.4 15.1 1.4 1.8 1.5 2.50 50.2 2.7 56 7,365 250/R
50 6 8.0 3.4 16.2 1.4 1.9 1.5 2.50 52.7 2.8 59 8,270 250/R
70 12 9.7 3.4 17.9 1.4 2.0 1.5 2.50 56.6 2.9 63 9,675 250/R
95 15 11.3 3.4 19.5 1.4 2.1 1.6 2.50 60.4 3.0 67 11,250 250/R
120 18 12.8 3.4 21.0 1.6 2.2 1.7 2.50 64.5 3.2 71 12,865 250/R
150 18 14.2 3.4 22.4 1.6 2.3 1.7 3.15 69.0 3.3 76 15,235 250/R
185 30 15.8 3.4 24.0 1.6 2.4 1.8 3.15 72.9 3.5 81 17,285 250/R
240 34 18.2 3.4 26.4 1.6 2.5 1.9 3.15 78.5 3.6 86 20,275 250/R
300 34 20.3 3.4 28.5 1.8 2.6 2.0 3.15 83.9 3.8 92 23,380 250/R
400 53 23.0 3.4 31.2 1.8 2.8 2.1 3.15 90.3 4.1 99 27,740 250/R
R = Packing in reel
86 87
PHELPS DODGE CABLE TYPE MXLP-LS-SWA (3 CORES) PHELPS DODGE CABLE TYPE MXLP-LS-SWA (3 CORES)
mm mm mm mm mm mm mm mm mm mm mm kg/km m
35 6 7.0 4.5 17.4 1.4 1.9 1.5 2.50 55.3 2.9 62 8,475 250/R
50 6 8.0 4.5 18.4 1.4 2.0 1.6 2.50 58.0 3.0 65 9,440 250/R
70 12 9.7 4.5 20.1 1.6 2.1 1.6 2.50 62.3 3.1 69 11,015 250/R
95 15 11.3 4.5 21.7 1.6 2.2 1.7 2.50 66.1 3.2 73 12,610 250/R
120 18 12.8 4.5 23.2 1.6 2.3 1.8 3.15 71.1 3.4 78 15,080 250/R
150 18 14.2 4.5 24.6 1.6 2.4 1.8 3.15 74.3 3.5 82 16,720 250/R
185 30 15.8 4.5 26.2 1.6 2.5 1.9 3.15 78.2 3.6 86 18,740 250/R
240 34 18.2 4.5 28.6 1.8 2.6 2.0 3.15 84.2 3.8 92 21,985 250/R
300 34 20.3 4.5 30.7 1.8 2.8 2.1 3.15 89.3 4.0 98 25,310 250/R
400 53 23.0 4.5 33.4 1.8 3.0 2.2 4.00 97.5 4.3 107 31,405 250/R
R = Packing in reel
88 89
PHELPS DODGE CABLE TYPE MXLP-LS-SWA (3 CORES) PHELPS DODGE CABLE TYPE MXLP-LS-SWA (3 CORES)
mm mm mm mm mm mm mm mm mm mm mm kg/km m
35 6 7.0 5.5 19.4 1.4 2.1 1.6 2.50 60.4 3.0 67 9,735 250/R
50 6 8.0 5.5 20.5 1.6 2.2 1.7 2.50 63.5 3.2 70 10,885 250/R
70 12 9.7 5.5 22.2 1.6 2.3 1.7 2.50 67.3 3.3 75 12,425 250/R
95 15 11.3 5.5 23.8 1.6 2.4 1.8 3.15 72.5 3.4 80 14,975 250/R
120 18 12.8 5.5 25.3 1.6 2.4 1.9 3.15 76.0 3.6 84 16,440 250/R
150 18 14.2 5.5 26.7 1.6 2.5 1.9 3.15 79.2 3.7 87 18,130 250/R
185 30 15.8 5.5 28.3 1.8 2.6 2.0 3.15 83.5 3.8 92 20,360 250/R
240 34 18.2 5.5 30.7 1.8 2.8 2.1 3.15 89.3 4.0 98 23,825 250/R
300 34 20.3 5.5 32.8 1.8 2.9 2.2 4.00 95.9 4.2 105 28,495 250/R
400 53 23.0 5.5 35.5 1.8 3.1 2.3 4.00 102.4 4.5 112 33,300 250/R
R = Packing in reel
90 91
PHELPS DODGE CABLE TYPE MXLP-LS-SWA (3 CORES) PHELPS DODGE CABLE TYPE MXLP-LS-SWA (3 CORES)
Nominal Minimum Diameter Nominal Diameter Nominal Nominal Nominal Nominal Diameter Nominal Overall Cable Standard 6. Shields and armours bonded at both ends or single point
cross - number of thickness over thickness thickness thickness diameter over thickness diameter weight packing
sectional of conductor of insulation of of of of armour of (Approx.) (Approx.)
area wire of (Approx.) insulation (Approx.) inner lead sheath separation steel wire (Approx.) oversheath
conductor covering sheath armour
mm mm mm mm mm mm mm mm mm mm mm kg/km m
50 6 8.0 8.0 25.6 1.6 2.5 1.9 3.15 76.9 3.6 85 15,105 250/R
70 12 9.7 8.0 27.3 1.8 2.6 2.0 3.15 81.4 3.7 89 17,005 250/R
95 15 11.3 8.0 28.9 1.8 2.7 2.0 3.15 85.1 3.9 94 18,920 250/R
120 18 12.8 8.0 30.4 1.8 2.8 2.1 3.15 88.7 4.0 97 20,745 250/R
150 18 14.2 8.0 31.8 1.8 2.9 2.2 3.15 92.2 4.1 101 22,605 250/R
185 30 15.8 8.0 33.4 1.8 3.0 2.2 4.00 97.5 4.3 107 26,380 250/R
240 34 18.2 8.0 35.8 1.8 3.1 2.3 4.00 103.1 4.5 113 29,865 250/R
300 34 20.3 8.0 37.9 2.0 3.2 2.4 4.00 108.5 4.6 118 33,395 250/R
400 53 23.0 8.0 40.6 2.0 3.4 2.6 4.00 115.1 4.9 126 38,520 250/R
R = Packing in reel
92 93
CURRENT CARRYING CAPACITY
The current carrying capacity of underground XLPE cable largely affected from the installation condition. The current
Three-core Cable Directly Buried in Ground
CORRECTION FACTOR FOR DEPTH OF LAYING Single-core Cable Laid in Duct in Ground
Single-core Cable Directly Buried in Ground
Nominal Depth of Laying
Nominal Depth of Laying cross- (m)
cross- sectional
(m)
sectional area
area mm² 0.50 0.60 0.80 1.00 1.25 1.50 1.75 2.00 2.50 3.00
mm² 0.50 0.60 0.80 1.00 1.25 1.50 1.75 2.00 2.50 3.00 35 1.03 1.02 1.00 0.98 0.97 0.96 0.95 0.94 0.93 0.92
35 1.05 1.03 1.00 0.98 0.96 0.95 0.93 0.92 0.91 0.89 50 1.04 1.02 1.00 0.98 0.97 0.96 0.95 0.94 0.93 0.92
50 1.05 1.03 1.00 0.98 0.96 0.94 0.93 0.92 0.91 0.89 70 1.04 1.02 1.00 0.98 0.97 0.96 0.95 0.94 0.92 0.91
70 1.05 1.03 1.00 0.98 0.96 0.94 0.93 0.92 0.90 0.89 95 1.04 1.02 1.00 0.98 0.97 0.95 0.94 0.94 0.92 0.91
95 1.05 1.03 1.00 0.98 0.96 0.94 0.93 0.92 0.90 0.89 120 1.04 1.02 1.00 0.98 0.97 0.95 0.94 0.93 0.92 0.91
120 1.05 1.03 1.00 0.98 0.96 0.94 0.93 0.91 0.90 0.88 150 1.04 1.02 1.00 0.98 0.96 0.95 0.94 0.93 0.92 0.90
150 1.06 1.03 1.00 0.98 0.95 0.94 0.92 0.91 0.90 0.88 185 1.04 1.03 1.00 0.98 0.96 0.95 0.94 0.93 0.91 0.90
185 1.06 1.03 1.00 0.98 0.95 0.94 0.92 0.91 0.89 0.88 240 1.05 1.03 1.00 0.98 0.96 0.95 0.94 0.93 0.91 0.90
240 1.06 1.04 1.00 0.98 0.95 0.93 0.92 0.91 0.89 0.87 300 1.05 1.03 1.00 0.98 0.96 0.95 0.93 0.92 0.91 0.89
300 1.06 1.04 1.00 0.97 0.95 0.93 0.92 0.91 0.89 0.87 400 1.05 1.03 1.00 0.98 0.96 0.94 0.93 0.92 0.90 0.89
400 1.06 1.04 1.00 0.97 0.95 0.93 0.92 0.90 0.88 0.87 500 1.05 1.03 1.00 0.98 0.96 0.94 0.93 0.92 0.90 0.89
500 1.07 1.04 1.00 0.97 0.95 0.93 0.91 0.90 0.88 0.87 630 1.05 1.03 1.00 0.98 0.96 0.94 0.92 0.91 0.90 0.88
630 1.07 1.04 1.00 0.97 0.95 0.93 0.91 0.90 0.88 0.86 800 1.06 1.03 1.00 0.98 0.95 0.94 0.92 0.91 0.89 0.88
800 1.07 1.04 1.00 0.97 0.94 0.92 0.91 0.90 0.87 0.86 1000 1.06 1.04 1.00 0.97 0.95 0.93 0.92 0.91 0.89 0.87
1000 1.07 1.04 1.00 0.97 0.94 0.92 0.91 0.89 0.87 0.85 1200 1.06 1.04 1.00 0.97 0.95 0.93 0.92 0.90 0.88 0.87
1200 1.08 1.04 1.00 0.97 0.94 0.92 0.90 0.89 0.87 0.85
Three-core Cable Laid in Duct in Ground CORRECTION FACTOR FOR GROUPS OF THREE-CORE CABLE IN HORIZONTAL
FORMATION DIRECTLY BURIED IN GROUND
Nominal Depth of Laying
cross- (m) Number of Spacing between duct group centers (mm)
sectional
area Circuits Touching 200 400 600 800
mm² 0.50 0.60 0.80 1.00 1.25 1.50 1.75 2.00 2.50 3.00 2 0.80 0.86 0.90 0.92 0.94
35 1.03 1.02 1.00 0.99 0.98 0.97 0.96 0.95 0.94 0.93 3 0.69 0.77 0.82 0.86 0.89
50 1.03 1.02 1.00 0.99 0.97 0.96 0.96 0.95 0.94 0.93 4 0.62 0.72 0.79 0.83 0.87
70 1.03 1.02 1.00 0.99 0.97 0.96 0.95 0.95 0.94 0.93 5 0.57 0.68 0.76 0.81 0.85
95 1.03 1.02 1.00 0.99 0.97 0.96 0.95 0.95 0.93 0.92 6 0.54 0.65 0.74 0.80 0.84
120 1.03 1.02 1.00 0.99 0.97 0.96 0.95 0.94 0.93 0.92
150 1.04 1.02 1.00 0.98 0.97 0.96 0.95 0.94 0.93 0.92
CORRECTION FACTOR FOR GROUPS OF THREE-CORE CABLE IN HORIZONTAL
185 1.04 1.02 1.00 0.98 0.97 0.96 0.95 0.94 0.93 0.92
FORMATION IN SINGLE-WAY DUCTS
240 1.04 1.02 1.00 0.98 0.97 0.96 0.94 0.94 0.92 0.91
300 1.04 1.02 1.00 0.98 0.97 0.95 0.94 0.93 0.92 0.91 Number of Spacing between duct group centers (mm)
400 1.04 1.03 1.00 0.98 0.96 0.95 0.94 0.93 0.92 0.90 Circuits Touching 200 400 600 800
2 0.85 0.88 0.92 0.94 0.95
3 0.75 0.80 0.85 0.88 0.91
CORRECTION FACTOR FOR GROUPS OF THREE-PHASE CIRCUITS OF SINGLE-CORE
4 0.69 0.75 0.82 0.86 0.89
CABLES DIRECTLY BURIED IN GROUND
5 0.65 0.72 0.79 0.84 0.87
Number of Spacing between group centers (mm) 6 0.62 0.69 0.77 0.83 0.87
Circuits Touching 200 400 600 800
2 0.73 0.83 0.88 0.90 0.92
3 0.60 0.73 0.79 0.83 0.86
4 0.54 0.68 0.75 0.80 0.84
5 0.49 0.63 0.72 0.78 0.82
6 0.46 0.61 0.70 0.76 0.81
floor should be concrete or firm enough to prevent the drum from sinking. Chocks must be used to prevent the movement of Maximum Allowable Conductor Stress (S)
the drum. The cable drum should be kept in a place where security and fire damage are protected during storage. Cable Type Material Temper N/mm²
All Copper Soft 70
Power Aluminum Hard 50
Safe Handling and Unloading of Cable Drum Maximum Allowable Pulling Tension = S x n x A
1. As received at stores or site, check the cable drums for any physical damages to the drum and outer wooden
laggings. Also check that the cable end cover are proper and in position. S = Maximum allowable conductor stress , kg/mm²
2. Loading/unloading of the drum to or from truck should be done by crane or use of a ramp. Do not drop the drum n = Number of conductors
or throw from the truck since this is not only damage the drum, the cable may also be damaged. Follows the below picture. A = Nominal cross-sectional area of conductor , mm²
Cable Grip over Outer Sheath - The maximum pulling tension is 4400 N but in no case shall not be more than pulling at
FOR WOODEN REEL FOR STEEL REEL conductor
CAUTION CAUTION 3. If the pulling tension is likely to be close to the maximum pulling tension (in rage of 10%), the tension metering
device is recommended.
4. Do not start and stop pull, pull and constant low speed.
5. Do not lay the cable with sharp bend, twisting or kinking. Care must be taken since this will harm the cable.
3. Flanges shall be kept always in up-right position during storage and handling and paying off or during transportation
of drum. Use pair of jacks with stand and shaft for mounting cable drums before paying off. Spindles of adequate size will be 6. The bending radius (R) during pulling of the cable should not exceed the following value.
selected depending on the weight and size of the cable drum.
4. After removal of the drum lagging, a thorough physical inspection of the cable shall be carried out.
5. Roll the drum only in the direction of painted arrow on the drum flanges and only for short distances.
Correct Method Correct Method R
Correct Method Correct Method Medium Voltage Cable ( ≤ 33kV) with and without Armour
Type of Cable Installation Bending Radius as a Multiple of Cable Diameter
Cable placed into position adjacent to
joint or termination with former
Single-core Unarmoured 15
6. Keep a man stationed near the drum with a plank wedged against the flange so that overrunning of the drum could Single-core Armoured 12
be prevented if rolling stops.
Three-core Unarmoured 12
Three-core Armoured 10
7. Cable end shall be taken out from the top side of the mounted drum of cable, and never from the bottom side.
8. Do not lay the damaged cables before repair and testing.
CERTIFICATE PHELPS DODGE CABLE TYPE MXLP-LS-SWA (3 CORES)
93