Beruflich Dokumente
Kultur Dokumente
Note: The company keeps the right to perfect the instruction. If equipments do not agree with the
instruction at anywhere, please contact our company in time. We will provide you with corresponding
service.
®
is registered trademark of Beijing Sifang Automation Co., Ltd.
We reserve all rights to this document, even in the event that a patent is issued and a different
commercial proprietary right is registered. Improper use, in particular reproduction and dissemination
to third parties, is not permitted.
This document has been carefully checked. If the user nevertheless detects any errors, he is asked to
notify us as soon as possible.
The data contained in this manual is intended solely for the IED description and is not to be deemed
to be a statement of guaranteed properties. In the interests of our customers, we constantly seek to
ensure that our products are developed to the latest technological standards as a result; it is possible
that there may be some differences between the hardware/software product and this information
product.
Manufacturer:
Beijing Sifang Automation Co., Ltd.
Overview
CSC-326 is selective, reliable and high speed u Communication with station automation system
IED (Intelligent Electronic Device) for transformer
The IED is able to provide all main protection
protection with powerful capabilities to cover
functions and backup protection functions in one
following applications:
case, including differential protection, restricted
u For large and medium two- or three-winding earth fault (REF), overexcitation, thermal
transformers, and autotransformer overload, overcurrent, earth fault protection, etc.
u Used in a wide range of voltage levels, up to The integrated flexible logic make the IED
1000kV suitable to be applied to (auto)transformers
with all the possible vector groups, with/without
u For single or multi-breaker arrangement
earthing connection inside the protected zone.
u Up to 7 three-phase sets of CTs input (special
The wide application flexibility makes the IED an
ordering)
excellent choice for both new installations and
u Work as main protection unit only or full retrofitting of the existing stations.
functions unit for the complicated application
1
Features
u Protection and monitoring IED with extensive v Overload protection (50OL)
functional library, user configuration possibility
v Delta winding overload protection (50OL)
and expandable hardware design to meet with
user’s special requirements v Overexcitation protection (24)
v Overvoltage protection (59)
u Inter-lock between two CPU modules, avoiding
maloperation due to internal severe fault of v Circuit breaker failure protection (50BF)
one module
v Poles discordance protection (50PD)
u Transformer differential protection (87T) v Dead zone protection (50SH-Z)
v Treble slope percent differential protection v Voltage transformer secondary circuit
v Automatic CT ratio matching supervision (97FF)
v Automatic vector group and zero sequence v Current transformer secondary circuit
current compensation supervision
nd
v Settable 2 harmonic restraint function for u 2 sets external trip commands (BIs → BOs)
transformer inrush
u Self-supervision to all modules in the IED
v Fuzzy waveform recognition restraint function
for transformer inrush u Complete information recording: tripping reports,
rd th
alarm reports, startup reports and general
v 3 or 5 harmonic restraint for overexcitation
operation reports. Any kinds of reports can be
v CT saturation detection stored up to 2000 and be memorized even in
case of power disconnection
v CT secondary circuit supervison
v Differential current alarm u Up to three electric /optical Ethernet ports can
be selected to communicate with substation
u Restricted earth fault protection (87N) automation system by IEC61850 or IEC60870-
v Two slope percent REF protection 5-103 protocols
2
Functions
Protection functions
IEC 61850 IEC 60617
Description ANSI Code Logical Node graphical
Name symbol
Differential protection
Transformer differential protection 87T PDIF
Restricted earth fault protection 87N PDIF
Current protection
3IINV>
Overcurrent protection 50, 51, 67 PTOC 3I >>
3I >>>
I0INV>
Earth fault protection 50N, 51N, 67N PEFM I0>>
I0>>>
Neutral earth fault protection 50G, 51G, 67G
Thermal overload protection 49 PTTR Ith
Overload protection 50OL PTOC 3I >OL
Delta Winding Overload Protection 50OL
Voltage protection
Overexcitation protection 24 PVPH U/f>
3
Functions
Monitoring functions
Description
Auxiliary contacts of circuit breaker supervision
Self-supervision
Fault recorder
Station communication
Description
Front communication port
Isolated RS232 port
Rear communication port
0-2 isolated electrical RS485 communication ports
0-3 Ethernet electrical/optical communication ports
Time synchronization port
Communication protocols
IEC 61850 protocol
IEC 60870-5-103 protocol
4
Functions
Application for two-winding transformer
5
Functions
Application for three-winding transformer
6
Functions
Application for autotransformer
7
Protection function
Slope 2 takes into consideration current-
Transformer differential
proportional errors which may result from
protection (87T) transformation errors of the main CTs, the input
The transformer differential protection function CTs of the IED, or from erroneous current caused
is provided to protect two-winding transformer, by the position of the tap changer in power
three-winding transformer and auto-transformer transformer.
in various configurations up to 1000 kV voltage
In the range of high current which may give
level, with internal CT ratio matching, vector
rise to high differential current as a result of CT
group and zero sequence current compensation.
saturation, slope 3 is applicable to provide more
The following features would be applied:
stabilization.
Operating characteristic The differential and restraining currents are
The Figure 4 illustrates operating characteristic calculated separately in each phase of the
of treble slope percent differential protection and protected object. Automatic identification of
instantaneous differential protection. fault location is fulfilled with recognition of
differential and restraint current trace around the
characteristic.
8
Protection function
a result, matching to various power transformer which can be used to set the protection in a way
and CT ratios is performed purely mathematically that when the 2nd harmonic recognition is fulfilled
inside the IED and no external matching CT is only in one phase, not only the phase with the
required. inrush current, but also the remaining phases of
percent differential protection are blocked for a
Automatic vector group and zero certain duration as well.
sequence current compensation
Overexcitation restraint
Transformers have different vector groups, which
cause a shift of the phase angles between the Stabilization of percent differential protection
currents flowing through their high medium and function is provided against unwanted differential
low voltage sides. Without adequate correction, currents caused by transformer overexcitation.
this phase shift would cause a false differential Since steady state overexcitation is characterized
current. Furthermore, the existence of the neutral by odd harmonics, the 3rd or the 5th harmonic
point(s) of the power transformer has a great can be selected in the IED to recognize for
impact on the differential current during through overexcitation condition.
fault currents.
Current transformer saturation supervision
The IED is capable to automatically compensate
This integrated function is capable to recognize
for the adverse effect of various vector groups of
CT saturation. CT saturation can be detected
power transformers as well as the zero sequence
when both the 2nd and 3rd harmonic contents of
current which may flow into the protected zone,
phase currents amongst all phase currents are
depending on the condition of the neutral point(s).
more than a threshold. If the CT saturation occurs
This is achieved just by informing the IED about
simultaneously with external fault recognition,
the vector group of the power transformer, and
differential protection will be blocked.
then, all necessary compensations would be
performed automatically by using coefficient Differential current supervision
matrices programmed inside the IED. This
simplifies application of the IED in various In normal operation condition, zero differential
configurations. current is expected in each phase. The differential
current supervision monitors the differential
Inrush restraint current of each phase. An alarm report will be
given, if the differential current exceeds the
This feature is provided in the IED to prevent
threshold value for a delay time.
percent differential protection from false tripping
caused by high short-time magnetizing currents
which may be present during transformer Restricted earth fault protection
energizing (inrush currents). (87N)
Two algorithms are available in the IED to detect The REF protection provides higher sensitivity
inrush conditions. The first one operates based on and higher speed when they measure individually
2nd harmonic stabilization, whereas the second on each winding. They are capable to detect
algorithm utilizes fuzzy wave recognition of inrush earth faults in (auto) transformer earthed. A
conditions based on the current waveform. precondition for using these functions is that a
neutral CT should be provided.
Furthermore, a cross blocking feature is provided
9
Protection function
Operating characteristic Difference of transient characteristic of
CTs detection
The Figure 5 illustrates the dual slope operating
characteristics of the REF. Difference of transient characteristic of phase or
neutral CTs may result in zero-sequence current
in REF protection during an external three-phase
fault. To remove this problem, the situation is
detected by using the calculated positive and
zero-sequence currents. The condition is checked
for each side of transformer separately.
10
Protection function
current, Inrush current comprises large second where:
harmonic current which doesn’t appear in short ФPh_Char: The settable the characteristic angle
circuit current. Therefore, the inrush current may
affect the protection functions which operate The assignment of the applied measuring values
based on the fundamental component of the used in direction determination has been shown
measured current. Accordingly, inrush restraint in Table 1 for different types of faults.
logic is provided to prevent overcurrent protection
from maloperation. Table 1 Assignment of applied current and reference
voltage for directional element
Furthermore, by recognition of the inrush current
in one phase, it is possible to set the protection Phase Current Voltage
in a way that not only the phase with the A Ia Ubc
considerable inrush current, but also the other B Ib Uca
phases of the overcurrent protection are blocked C Ic Uab
for a certain time. This is achieved by cross-
For three-phase short-circuit fault, without any
blocking feature integrated in the IED.
healthy phase, memory voltage values are used
The inrush restraint function has a maximum to determine direction clearly if the measured
inrush current setting. Once the measuring voltage values are not sufficient. The detected
current exceeds the setting, the overcurrent direction is based on the voltage of previously
protection will not be blocked any longer. saved cycles.
11
Protection function
u Each stage can be set individually for inrush Two operation areas are provided for direction
restraint determination, the forward area toward the
protected object and the reverse area toward the
u Settable maximum inrush current
system, which are shown in Figure 7.
u Inrush restraint function adopting 2nd harmonic
Furthermore, under the VT failure situation, it can
measured phase or earth current settable
be set to block directional earth fault protection or
u VT secondary circuit supervision for directional to apply non-directional earth fault protection.
protection function. Once VT failure happens,
Inrush restraint function
the directional stage can be set to be blocked
or to be non-directional The protection relay may detect large magnetizing
inrush currents during transformer energizing. In
u Zero-sequence current is calculated by
addition to considerably unbalanced fundamental
summation of 3 phase currents
current, Inrush current comprises large second
Directional element harmonic current which doesn’t appear in short
circuit current. Therefore, the inrush current may
The earth fault protection adopts zero sequence affect the protection functions which operate
directional element which compares the zero based on the fundamental component of the
sequence system quantities: measured current. Accordingly, inrush restraint
logic is provided to prevent earth fault protection
u 3I0, current is calculated from the sum of the
from mis-tripping.
three phase currents.
Since inrush current cannot be more than a
u 3U0, the voltage is used as reference voltage.
specified value, the inrush restraint provides an
It is calculated from the sum of the three phase
upper current limit in which blocking does not
voltages.
occur.
Figure 7 Direction detection characteristic of zero u 11 kinds of the IEC and ANSI inverse time
sequence directional element characteristic curves as well as optional user
where: defined characteristic
Ф0_Char: The settable characteristic angle
12
Protection function
u Each stage can be set to be directional/non- The insulating material surrounding the windings
directional independently ages rapidly if the temperature exceeds the
design limit value. Thus, a thermal protection
u Zero sequence directional element. Its
function is required to supplement the existing
characteristic is same as earth fault protection
winding temperature device. The thermal overload
illustrated in Figure 7
protection estimates winding temperature and
u Directional element can be set to be forward thus prevents it from thermal damaging.
toward the protected object or reverse toward
The thermal overload protection operates based
system for all stages
on an approximate replica of the temperature rise
u Setable directional element characteristic in the protected object caused by overload.
angle to satisfy the different network conditions
The thermal replica can be implemented based
and applications
on thermal models (Cold or Hot Curve) of
u Inrush restraint function can be set for each IEC60255-8 standard.
stage separately
The thermal overload in the IED is provided
u Settable maximum inrush current with one trip stage as well as one alarm stage.
It is possible to set the alarm stage at a certain
u VT secondary circuit supervision for directional percentage of the setting value applied at the trip
protection function stage.
u Neutral current is measured from dedicated The calculation is performed separately for each
neutral CT phase, based on fundamental component and
harmonic components.
Inrush restraint feature
The neutral earth fault protection may detect Overload protection (50OL)
large magnetizing inrush currents flowing when
transformer is energized. The IED supervises load flow in real time. If
each phase current is greater than the dedicated
Directional element setting for a set delay time, the protection will
issue alarm.
Directional determination of neutral earth fault
element adopts the zero sequence directional
element as same as the one applied by earth Transformer delta winding
fault protection. The only difference is that the overload protection (50OL)
measured current is measured from the neutral
When there is a dedicated CT for each phase of
point CT instead of being calculated from three
the transformer delta winding, the protection is
phase currents.
provided to monitor the load flow in real time. If
all three phase current are always greater than
Thermal overload protection (49) the setting of power swing for a setting time, the
alarm will be reported.
13
Protection function
Overexcitation protection (24) u First stage can be set to alarm or trip
One voltage rise occur possibly in the power The protection can be three-phase started to
system during abnormal conditions such as allow use with three phase tripping applications.
no-load, lightly load, or open line end on long
Once a circuit breaker operating failure occurs
line. The protection can be used as open line
on a feeder/transformer, the bus section which
end detector or as system voltage supervision
the feeder/transformer is connected with can be
normally.
selectively isolated by the protection. In addition
The protection provides following features: the CBs of the other windings of the transformer
are tripped at the same time.
u Two definite time stages
14
Protection function
In the event of a circuit breaker failure with a
busbar fault, a trip signal is issued to trip the CBs
of the other windings of the transformer.
15
Protection function
currents of all sides of transformer. If only one
Poles discordance protection
or two phase currents drop down less than a
(50PD) threshold and the differential current is larger
than a preset threshold, CT secondary circuit
The phase segregated operating circuit breakers
open is determined and alarm will be issued. The
can be in different positions (close-open) due
CT open alarm can be set to block differential
to electrical or mechanical failures during the
protection or not.
system normal operation.
Voltage transformer secondary circuit
The protection operates based on information
from auxiliary contacts of the circuit breaker with
supervision
additional criteria. A measured voltage failure, due to a broken
conductor or a short circuit fault in the secondary
The protection performs following functions:
circuit of voltage transformer, may result in
u 3 phase CB Aux contacts supervision unwanted operation of the protection functions
which work based on voltage criteria. VT failure
u Current criteria checking (including phase supervision function is provided to block these
current, zero and negative sequence current) protection functions and enable the backup
protection functions. The features of the function
Secondary system supervision are as follows:
Open or short circuited CT cores can cause u 1-phase AC voltage MCB monitoring
unwanted operation of some protection functions
such as earth fault current and negative u Zero and negative sequence current monitoring
sequence current functions. u Applicable in solid grounded, compensated or
During the normal operation without any isolated networks
disturbance, the IED monitors the three phase
16
Monitoring function
Self-supervision u CPU module and communication module
perform real time inter-supervision. Therefore
u All modules can perform self-supervision to its
communication interruption between them is
key hardware components and program, as
detected and related alarm will be given
soon as energizing. Parts of the modules are
self-supervised in real time. All internal faults u CRC code checks for the setting, program and
or abnormal conditions will initiate an alarm. configuration, etc.
The fatal faults among them will result in the
whole IED blocked
17
Station communication
Overview Ethernet communication ports
The IED is able to connect to one or more substation Up to 3 electrical or optical Ethernet communication
level systems or equipments simultaneously, through ports are provided to connect with substation
the communication ports with communication automation system. These two out of three ports
protocols supported. (Shown in Figure 11) can work in parallel for one protocol, IEC61850 or
IEC60870-5-103.
Front communication port
There is a serial RS232 port on the front plate of
Communication protocol
all the IEDs. Through this port, the IED can be The IED supports station communication with IEC
connected to the personal computer for setting, 61850-8 and IED60870-5-103 protocols.
testing and configuration using the dedicated
By means of IEC61850, GOOSE peer- to peer
Sifang software tool.
communication make it possible that bay IEDs
RS485 communication ports can exchange information with each other
directly, and a simple master-less system can be
Up to 2 isolated electrical RS485 communication
set up for bay and system interlocking and other
ports are provided to connect with substation
interactive function.
automation system. These two ports can work in
parallel for IEC60870-5-103.
18
Station communication
Time synchronization port via time synchronization receivers. The IED can
adapt the second or minute pulse in the pulse
All IEDs feature a permanently integrated
mode automatically.
electrical time synchronization port (shown
in Figure 12). It can be used to feed timing Meanwhile, SNTP network time synchronization
telegrams in IRIG-B or pulse format into the IEDs can be applied.
19
Software tools
CSmart protection manager is a user-friendly time, circle diagrams, vector diagrams, bar
software tool for engineering, parameter setting, charts and data sheet
disturbance handling and monitoring. It provides
versatile functionalities required throughout the
life cycle of protection IEDs. Its features are as
follows:
u Modification, import and export of parameter u Password-protected access for different jobs
sets sorted by protection functions, with setting such as parameter setting, commissioning and
logicality check controlling (authorized staff only)
u Precise fault analysis by Fisewave software: u Testing and diagnostic functions –decisive
visualization of fault records in curves over support in the commissioning phase
20
Hardware
Human-machine Interface (HMI)
The human-machine interface is simple and easy into zones, each of them with a well-defined
to understand – the whole front plate is divided functionality:
21
Hardware
Analogue Input Module (AIM) The time synchronization port is equipped, which
can work in pulse mode or IRIG-B mode. SNTP
The analogue input module is used to galvanically
mode can be applied through communication
separate and transform the secondary currents
port.
and voltages generated by the measuring
transformers. In addition, a series printer port is also reserved.
22
Dimension
C E
Legend A B C D E
Dimension 177 482.6 265 320 437.2
Unit: mm
E
C
A
B
Figure 15 Cut-out on the panel
Legend A B C D E
Dimension 450 465 101.6 178 6.5
Unit: mm
23
Typical connection
A. For 2 windings transformer with 2 breakers on high and low voltage
windings respectively
Figure 16 Typical connection diagram for 2 windings transformer with 2 breakers on high and low voltage windings
respectively
24
Typical connection
B. For 2 windings transformer with 1 breaker on high and low voltage
windings respectively
Figure 17 Typical connection diagram for 2 windings transformer with 1 breaker on high and low voltage windings
respectively
25
Typical connection
C. For 3 windings transformer with 1 breaker on high, medium and
low voltage windings respectively
Figure 18 Typical connection diagram for 3 windings transformer with 1 breaker on high, medium and low voltage
windings respectively
26
Typical connection
D. For 3 windings transformer with 2 breakers on high and medium
voltage winding and 1 breaker on low voltage windings respectively
Figure 19 Typical connection diagram for 3 windings transformer with 2 breakers on high and medium voltage
winding and 1 breaker on low voltage windings respectively
27
Typical connection
E. For 3 windings transformer with 3 breaker on high and low voltage
windings respectively, and 1 breaker on medium voltage winding
Figure 20 Typical connection diagram for 3 windings transformer with 3 breaker on high and low voltage windings
respectively, and 1 breaker on medium voltage winding
28
Typical connection
F. For autotransformer with 2 breaker on high voltage winding, and 1
breaker on medium and low voltage windings respectively
Figure 21 Typical connection diagram for autotransformer with 2 breaker on high voltage winding, and 1 breaker
on medium and low voltage windings respectively
29
Rear terminals
The rear view of the protection IED
30
Rear terminals
Terminals of Analogue Input Module (AIM)
31
Rear terminals
The Analogue Input Module ' Table 5 Description of terminals of AIM D
32
Rear terminals
The Analogue Input Module G Table 6 Description of terminals of AIM G
a10 Null
b10 Null
a11 Null
b11 Null
33
Rear terminals
Terminals of Binary Input Module (BIM)
34
Rear terminals
Terminals of Binary Output Module (BOM)
R R R R R R R R
1 3 5 7 9 11 13 15
c a
c 02 a02
c 04 a04
c06 a06
c08 a08
c10 a10
c12 a12
c14 a14
c16 a16
c18 a18
c 20 a20
c 22 a22
c 24 a24
c 26 a26
c 28 a28
c 30 a30
c 32 a32
R R R R R R R R
2 4 6 8 10 12 14 16
35
Rear terminals
Table 8 Definition of terminals of BOM A
36
Rear terminals
Binary Output Module C
The module provides 16 output relays for signal, with total 19 contacts.
R R R R R R R
4 5 1 2 3 6 7
c a
c 02 a02
c 04 a04
c06 a06
c08 a08
c10 a10
c12 a12
c14 a14
c16 a16
c18 a18
c 20 a20
c 22 a22
c 24 a24
c 26 a26
c 28 a28
c 30 a30
c 32 a32
R R R R R R R R R
8 9 10 11 12 13 14 15 16
37
Rear terminals
Table 9 Definition of terminals of BOM C
38
Rear terminals
Terminals of Power Supply Module (PSM)
Table 10 Definition of terminals of PSM
c a Terminal Definition
39
Rear terminals
Terminals of Communication Module (COM)
01 Terminal Definition
02 Ethernet port A 01 Null
03
02 Null
04
03 Null
05
06 04 Null
07 Ethernet port B 05 Optional RS485 port - 2B
08 06 Optional RS485 port - 2A
09 07 Optional RS485 port - 1B
10
08 Optional RS485 port - 1A
11
Ethernet port C 09 Time synchronization
12
13
10 Time synchronization GND
14 11 Null
15 12 Null
16 13 Null
14 Null
Figure 30 Terminals arrangement of COM
15 Null
16 Null
Optional optical fiber or RJ45
Ethernet Port A port for station automation
system
Optional optical fiber or RJ45
Ethernet Port B port for station automation
system
Optional optical fiber or RJ45
Ethernet Port C port for station automation
system
40
Technical data
Basic data
Frequency
Item Data
System rated frequency 50 or 60 Hz
41
Technical data
Auxiliary voltage
Item Data
100 ~ 125 V DC
Rated auxiliary voltage Vaux
195 ~ 250 V DC
Permissible tolerance ±%20 Uaux
Power consumption
Normal operation ≤ 30 W
Tripping condition ≤ 50 W
Binary inputs
Item Data
24 V DC
Input voltage range 110/125 V DC
220/250 V DC
Response time/dropout time Software provides de-bounce time
Power consumption, energized 2 mA
Binary outputs
Item Data
Max. system voltage 250 V DC/AC
5 A continuous
Current carrying capacity 30 A for 0.5 s making current
2000 switching cycles
150 W (DC)
Making capacity at inductive load with L/R>10 ms
1250 VA (AC)
250 mA, 100 W resistive, for AC, cos φ > 0.4
Breaking capacity
50 W, for DC at L/R < 40 ms
42
Technical data
Type tests
Insulation test
Item Data
IEC 60255-5:2000
Standards GB/T 15145-2001
DL/T 478-2001
3.5 kV DC
Insulation resistance
43
Technical data
Electromagnetic compatibility tests
Item Data
GB/T 14598.9-2002
Identify IEC 60255-22-3:2000, for radiated electromagnetic field
disturbance test
GB/T 14598.10-2007
Identify IEC 60255-22-4:2002, for electrical fast transient/burst
immunity test
GB/T 14598.13-2008
Modify from IEC 60255-22-1:2007, for 1MHz burst immunity test
GB/T 14598.14-1998
Identify IEC 60255-22-2:1996, for electrostatic discharge test
GB/T 14598.18-2007
Identify with IEC 60255-22-5:2002, for surge immunity test
GB/T 14598.19-2007
Identify with IEC 60255-22-7:2003, for power frequency
immunity test
GB/T 14598.20-2007
Identify with IEC 60255-26:2004, for electromagnetic compatibility
requirements
8 kV contact discharge
15 kV air gap discharge
Electrostatic discharge both polarities; 150 pF; Ri = 330 Ω
IEC 60255-22-2; class IV
and EN 61000-4-2; class IV
44
Technical data
Radio-frequency electromagnetic 10 V/m, 900 MHz; repetition rate 200 Hz, on duration 50 %
field disturbance pulse-modulated IEC 61000-4-3/ENV 50204, class III
4 kV
Fast transient disturbance
IEC 60255-22-4 and IEC 61000-4-4, class IV
4 kV
Fast transient surge withstand
capability test 5 kHz
ANSI/IEEE C37.90.1
0.15 to 80 MHz
Conducted emission CISPR11, class A
EN61000-6-4:2005
45
Technical data
Mechanical tests
Item Data
During operation
IEC 60255-21-1:1988
Standards
IEC 60255-21-2
Sinusoidal
10 to 50 Hz; ± 0.035 mm amplitude
Vibration 50 to 150 Hz
IEC 60255-21-1, class 2
IEC 60068-2-6
Semi-sinusoidal
Acceleration 5 g, duration 11 ms; 6 shocks in both directions of 3 axes
Shock
IEC 60255-21-2, class 1
IEC 60068-2-27
During transportation
Sinusoidal
5 to 8 Hz: ±7.5 mm amplitude
8 to 150 Hz; 2 g acceleration
Vibration frequency sweep 1 octave/min
20 cycles in 3 perpendicular axes
IEC 60255-21-1, class 2
IEC 60068-2-6
Semi-sinusoidal
Acceleration 15 g, duration 11 ms
Shock 6 shocks in both directions of 3 axes
IEC 60255-21-2, Class 1
IEC 60068-2-27
Semi-sinusoidal
Acceleration 10 g, duration 16 ms
46
Technical data
Environmental tests
Item Data
Temperatures
-25 to +70 °C
Type-tested , test Bd, for 16 h IEC 60068-2-1
IEC 60068-2-2
-10 to +55 °C
IEC 60255-6
Recommended permanent operating temperature
(Legibility of display may be impaired above
+55 °C /+131 °F)
Humidity
IED design
Item Data
Case size 4 U × 19 inch
Weight ≤ 8 kg
IP20 class I
Protection level EN 60529
IEC 60529
CE certificate
Item Data
EMC Directive EN 61000-6-2 and EN61000-6-4 (EMC Council Directive 2004/108/EC)
47
Technical data
Station communication ports
Front communication port
Item Data
Number 1
Isolated, RS232; front panel
Connection
9-pin subminiature connector, for CSmart
Communication speed 9600 baud
Time synchronization
Item Data
Mode Pulse mode
IRIG-B signal format IRIG-B000
2-wire connector
Connection
Rear port in communication module
Voltage levels differential input
48
Technical data
Ethernet communication port
Item Data
Electrical communication port
Number 0~3
RJ45 connector
Connection
Rear port in communication module
Max. length of communication cable 100 m
IEC 61850 protocol
Communication speed 100 Mbit/s
Connection SC connector
Rear port in communication module
Optical cable type Multi-mode
49
Technical data
Functions
NOTE:
Ir: CT rated secondary current, 1A or 5A
In: nominal current of the reference side of transformer
50
Technical data
Tolerance
Pickup characteristic ±3% of setting value or ±0.02Ir
User-defined characteristic ( i
(I_SET )
A
P
1 )
+B k
51
Technical data
Tolerance of definite time stage
Current pickup ≤ ±3% of setting value or ±0.02Ir
Angle ≤ ±3°D
Delay time ≤ ±1% setting value or 40 ms
Tolerance of inverse time stage
Current pickup Remote communication
≤ ±3% of setting value or ±0.02I r
Angle ≤ ±3°
Delay time ≤ ±5% setting value + 40 ms
User-defined characteristic
( i
(I_SET )
A
P
1 )
+B k
52
Technical data
Time of inverse time stage
Dropout time approx. 40 ms
Minimum operating time 20 ms
Maximum operating time 100 s
Dropout ratio of definite time stage
Current element Approx. 0.95 when I/In ≥ 0.5
Tolerance of definite time stage
Current pickup ≤ ±3% of setting value or ±0.02Ir
Angle ≤ ±3°
Delay time ≤ ±1% setting value or 40 ms
Tolerance of inverse time stage
Current pickup ≤ ±3% of setting value or ±0.02Ir
Angle ≤ ±3°
Delay time ≤ ±5% setting value + 40 ms
53
Technical data
User-defined characteristic ( i
(I_SET )
A
P
1 )
+B k
54
Technical data
Thermal overload protection (ANSI-49)
Setting range
Current 0.1 to 10 A , when Ir = 1 A
0.5 to 50 A , when Ir = 5 A
Thermal heating/cooling time const 6 ~ 9999
Cool down time 1 ~ 9999
Thermal time characteristic
t = t ln{
I I}
I I
2 2
eq q
Tolerance
Current pickup ≤ ±3% of setting value or ±0.02Ir
Thermal trip time ≤ ±1% or 0.1 s
55
Technical data
Pole discordance protection (ANSI 50PD)
Setting range
0.05 to 20 A , when Ir = 1 A
Current
0.25 to 100 A when Ir = 5 A
Delay time 0.1 to 60 s, step 0.01 s
Tolerances
Pickup ≤ ±3% of setting value or ±0.02Ir
Delay time ≤ ±1% or +40 ms
56
Technical data
Time
Pickup time ≤ 30 ms
Dropout time ≤ 50 ms
Tolerances
Pickup thresholds ≤ ±3 % of setting value or 1 V
Time ≤ ±1 % or 40 ms
57
Ordering
Configuration of the pre-configure versions
Table 12 Functions list of the pre-configure versions
Description Selection
Pre-configure version M1 M3 M5 M7 M2 M4 M6 M8 N1
58
Ordering
NOTE:
H2 – Two breakers on High voltage side; Two CT
■ : Standard function inject in IED
□ : Optional function M1 – One breaker on Medium voltage side; One
Number: the quantity of the function provided CT inject in IED
L1 – One breaker on Low voltage side; One CT
N1: Transformer type:
inject in IED
2W – Two winding transformer
3W—Three winding transformer N3: Application:
AT – Autotransformer M – work as main protection only
F – Full functions version, work as main and
N2: Breaker arrangement: backup protection in one IED
Ordering Number
Product type
No. 1 2 3 4 5 6 7
Code C S □ □ □ □ □
59
Ordering
Terminals of Analogue Input Module
A: Plug in type
16 □
B: Screw type with ring lug
Analogue Input Module (AIM)
17,18 □□ AIM1
BA: Analogue input module BA [3I (1 A) + 9 U]
19 □ Quantity
BB: Analogue input module BB [3I (5 A) + 9 U]
20,21 □□ AIM2
FA: Analogue input module FA [8I (1 A) + 4 U]
22 □ Quantity FB: Analogue input module FB [8I (5 A) + 4 U]
23,24 □□ AIM3 GA: Analogue input module GA [9I (1 A)]
35 □ BOM4 X: Null
36 □ Quantity
Communication protocol
A: IEC61850-8 protocol and IEC60870-5-103 protocol
46 □
B: IEC60870-5-103 protocol
60
Ordering
Communication ports
A: Two optical Ethernet ports and two RS485 ports
B: Two electric Ethernet ports and two RS485 ports
47 □
C: Three optical Ethernet ports and one RS485 port
D: Three electric Ethernet ports and one RS485 port
Time synchronization port
A: IRIG-B mode
48 □
B: Pulse mode
Example:
The following ordering number means:
16 B The terminal type of analogue input module is screw type for ring lug
61
Ordering
Analogue Input Module (AIM)
17,18 FA AIM1
Three AIMs FA (8I (1 A)+4 U) are selected.
19 3 Quantity
20,21 XX AIM2
Null
22 X Quantity
23,24 XX AIM3
Null
25 X Quantity
26,27 XX AIM4
Null
28 X Quantity
Binary Input Module (BIM)
29,30 AA BIM1
One BIM AA (30BI, 220 V) is selected.
31 1 Quantity
32,33 XX BIM2
Null
34 X Quantity
35,36 XX BIM3
Null
37 X Quantity
Binary Output Module (BOM)
29 A BOM1
Three BOM A (16 output relays for tripping) are selected
30 3 Quantity
31 C BOM2
One BOM C (16 output relays for signal, 19 contacts) is selected.
32 1 Quantity
33 X BOM3
Null
34 X Quantity
35 X BOM4
Null
36 X Quantity
Communication protocol
The communication protocols, IEC61850-8 protocol and IEC60870-5-103
46 A
protocol, are applied.
Communication ports
47 A Two optical Ethernet ports and two RS485 ports are selected.
Time synchronization port
48 A The time synchronization mode is IRIG-B mode.
62
Address: No.9 Shangdi 4th Street, Haidian District,
Beijing, P.R.C. 100085
Tel: +86 10 62962554, +86 10 62961515 ext.8998
Fax: +86 10 82783625
Email:sf_sales@sf-auto.com
Website: http://www.sf-auto.com