Beruflich Dokumente
Kultur Dokumente
1
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
Preface
This manual is edited on the basis of provisions and relevant drawings from
manufacturer and design institute, only for gas turbine generator system maintenance
of Pakistan Nandipur 425MW Gas Turbine Combined Cycle Power Plant. With the
progress of the project, the manual will be supplemented and improved.
2
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
Content
1General ........................................................................................................ 1
1.1Safety First ....................................................................................................... 1
1.2Risk Assessment............................................................................................... 1
1.3Purge the Engine .............................................................................................. 2
1.4 Keep Complete Records.................................................................................. 2
1.5Maintenance Tasks ........................................................................................... 2
1.6 Maintenance Checks ....................................................................................... 2
1.7Anti-seize Compound....................................................................................... 3
1.8 Sealing Compound .......................................................................................... 4
1.9 Joint Compound .............................................................................................. 4
1.10Piping Flanges ................................................................................................ 4
1.11Bolt and Stud Torquing .................................................................................. 5
1.11.1Before Torquing ...................................................................................... 5
1.11.2Classification of Joints ............................................................................ 5
1.12 Recommend Solvents, Sealants, Cleaners, ETC........................................... 7
1.12.1 Listing..................................................................................................... 7
1.12.2 Note On Anti-seize Compound, High Temperature: ............................. 9
1.13 Ordering Renewal Parts ................................................................................ 9
1.14 Repair and Replacement Parts .................................................................... 10
2 Maintenance Consideration ................................................................... 11
2.1 Introduce........................................................................................................ 11
2.2 Maintenance Planning ................................................................................... 11
3 Gas Turbine Maintenance Devices Inspection..................................... 14
3.1Borescope Inspection ..................................................................................... 14
3.2 Standby Inspections ...................................................................................... 18
3.3 Running Inspections ...................................................................................... 18
3.4Load and Exhaust Temperature ..................................................................... 19
3.5 Vibration Level ............................................................................................. 19
3.6 Fuel Flow and Pressure ................................................................................. 20
3.7 Exhaust Temperature and Spread Variation ................................................. 20
3.8 Startup Time .................................................................................................. 20
1
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
2
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
4.14.1Definition .............................................................................................. 58
4.14.2 Maintenance Schedule ......................................................................... 58
4.15Water Injection System ................................................................................ 59
4.15.1Definition .............................................................................................. 59
4.15.2 Maintenance Schedule ......................................................................... 60
4.16Compressor Inlet Guide Vanes System ....................................................... 61
4.16.1Definition .............................................................................................. 61
4.16.2 Maintenance Schedule ......................................................................... 61
4.17 Inlet and Exhaust System ............................................................................ 62
4.17.1Definition .............................................................................................. 62
4.17.2 Maintenance Schedule ......................................................................... 62
4.18 Fuel Purge System....................................................................................... 65
4.18.1 Definition ............................................................................................. 65
4.18.2Maintenance Schedule .......................................................................... 66
4.19Accessoryand Load Gear and Couplings ..................................................... 66
4.20Acoustical Enclosure .................................................................................... 67
4.21Electrical Auxiliary ...................................................................................... 68
4.22 System ......................................................................................................... 69
4.23Instrument Air System ................................................................................. 70
4.23.1General .................................................................................................. 72
4.23.2Screw compressor RAFALE 37 kW CMP301 ..................................... 72
4.23.3Compressed air tank 500L TK601 ........................................................ 73
4.23.4Air cooler ARO203HT CLR201 ........................................................... 74
4.23.5Water separator filter SEP201 & SEP302 ............................................ 75
4.23.6 Adsorption air dryer SAD255 DRY401 .............................................. 75
4.23.7 Maintenance Schedule ......................................................................... 77
4.24Steam Injection System ................................................................................ 80
5 Generator ................................................................................................. 81
5.1Specification of Generator ............................................................................. 81
5.2 An Effective Maintenance Program of Generator ........................................ 82
5.3 Bearing .......................................................................................................... 85
5.4 Generator Coolers ......................................................................................... 86
5.5 Shaft Grounding Brushes .............................................................................. 88
5.6 Brushless exciter ........................................................................................... 89
5.6.1Periodic Maintenance .............................................................................. 89
5.6.2Replacementof Diodes ............................................................................ 89
5.6.3 Insulation Resistance.............................................................................. 90
3
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
4
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
5
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
1General
At all times when performing maintenance work on gas turbines the
following general practices should be observed:
1.1Safety First
Establish a risk assessment, secure access, always follow site safety
procedure, use permit to work and access permit supported by the relevant
lock out/tag out procedure disable unit’s fire protection system and provide an
alternate means of fire protection while the gas turbine’s system is disabled.
Warning
Fire suppressants, in a concentration sufficient to extinguish fire
create an atmosphere that will not support life. It is extremely hazardous
to enter the compartment after the fire protection system has discharged.
Anyone rendered unconscious by fire suppressant should be rescued as
quickly as possible and revived immediately with artificial respiration or
by mouth-to-mouth resuscitation. The extent and type or safeguards and
personnel warnings that may be necessary must be designed to meet the
particular requirements of each situation. It is recommended that
personnel be adequately trained to cope with such an emergency.
1.2Risk Assessment
Risk assessment is an important step in protecting the workers and the
business. It helps to focus on the risks that really matters in the workplace.
Risk assessment is the determination of quantitative or qualitative value of
risk related to a concrete situation and a recognized threat.
Risk assessment includes identifying hazard and risk. Hazard is anything
that may cause harm. Risk is the probability of harmful effect to human or to
ecological systems resulting from exposure to an environmental stressor.
Risk assessment shall be established prior to carry any work on the gas
turbine. It can be driven by specific procedure from the End User or from any
sources of good practice. Hazard and risk can be classified according to ISO
14121.
The main steps for risk assessment are:
Identify the activity, the hazards
Decide who might be harmed and how
Evaluate the risks and decide on precaution
Record your findings and implement them
1
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
Review your assessment and update if necessary
1.5Maintenance Tasks
Use penetrating oil prior to bolt removal. Recommended Solvents, sealers,
cleaners, etc... in this chapter for listing of acceptable penetrating oils).
Clean all removed parts and fasteners and store in separate containers,
tagged to simplify reassembly.
Protect all casing flanges from rust and mechanical damage after removal.
Grease, layout dye or commercial rust inhibitors will retard flange rusting, and
plywood, masonite or equal will prevent mechanical damage.
Debar mating surfaces and eliminate flange face high spots before
assembling any casings. Carborundum stones and flat mill files are effective
for these tasks.
Cover all open pipe and tubing. Do not stuff rags in pipes. Sheet metal or
plywood is effective covers for large pipes, and duct tape will protect tubing.
Never use pipe wrenches or pliers on tube fittings.
Do not reuse gaskets - unless specifically instructed to do so in the
procedures.
Do not reuse lock plates internal to the unit.
Match mark piping, fuel nozzles, couplings and casings to assist in proper
orientation during reassembly.
Don not mark on any combustion system or turbine components with any
compounds containing lead. Nickel base alloys are subject to attack when
heated in the presence of sulfur, lead, copper and other metals. These
materials can cause embritlement and cracking at elevated temperatures. Some
common sources of these compounds are copper hammers, paint, markers and
machining oil. Use of tags wired to the parts (avoid aluminum or other low
melting point alloys), and markers certified free of injurious materials can
eliminate this source of contamination.
2
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
inspection, maintenance checks and taking clearance readings.
Axial readings must be taken with the rotor positioned downstream (toward
the exhaust end) in contact with the active face of the thrust bearing. Any
pressure applied in moving the rotor aft should be released prior to taking rotor
position or clearance measurements.
Parallel bars and feeler stock, when used with proper attention to detail,
provide good measurements. In order to obtain proper measurement accuracy,
the total thickness of the parallel bar and feeler stock must be measured with a
micrometer.
Snap gages may be used to obtain measurements when proper attention is
applied to the gage orientation. Snap gages used on bevel surfaces will result in
inaccurate readings. taper gages is not recommended because the pointed end of
the gage often “bottoms” on an internal curved surface before an accurate
reading can be obtained. This gage should not be used to take radial clearances.
Never rotate the unit rotor when the unit is undergoing inspection and
maintenance checks without adhering to the following precautions.
Check that the thrust bearing is fully assembled in unit.
Check close clearance areas for potential interference and foreign object
damage.
Warn personnel working on unit to stand clear.
Do not turn the rotor against direction of rotation
To properly tighten new Swagelok stop-collar fittings, snug the nut by hand
after cleaning threads. Then tighten the nut until the stop-collar just stops
turning
1.7Anti-seize Compound
Anti-seize compound shall be applied on all rotor and stator bolting
threads, dowels, rabbets and sliding fits (internal and external), external
bolting threads for mounting associated equipment, pipe flanges, ductwork
etc... Also apply on vertical flange faces of the top halves of outer casings that
may be subject to removal for maintenance.
NOTE
This usage must be restricted to a thin film such that the compound is
not forced into the inner gas path. Should this occur, it must, where
possible, be carefully removed.
Do not apply anti-seize compound to pipe threads or bolting threads internal
to oil or water tanks.
Anti-seize shall not contain sulfur
3
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
1.10Piping Flanges
Use anti-seize compound on the bolts.
Re-install flanges with clean flange surfaces, new gaskets, check gasket
positioning and check flanges concentricity and parallelism. Pipe flanges must
not be forced into alignment. Do not pry on the flanges. If flanges cannot be
brought to within 1/8” (3.18 mm) of parallel by hand, the piping should be
reformed or replaced.
When the flanges are parallel with a new gasket in place, insert the bolts by
hand, proceed to sequence tightening at the relevant tightening torque, secure
bolts with locknut or locking plate for nuts as per drawing.
4
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
1.11.1Before Torquing
Remove foreign matter from bolt, nut and bolting surfaces
Apply anti-seize compound to bolt and nut threads and bearing surfaces.
Tighten bolt/or nut to be sure threads are free, then back off until free from
surface. Snug against surface and torque to values shown in Table 1.11.1.
When using impact wrenches, torque to values in Table1.11.1
1.11.2Classification of Joints
All classes of joints (oil tight, air tight and for frame rigidity) with metal to
metal contact shall have their bolt or stud elongation determined by micrometer
measurements, torque wrench or by head rotation. See Tables1.11.1and1.11.2.
All gasket joints shall have their bolt and stud elongation determined by
micrometer measurements or torque wrench. See Tables1.11.1and1.11.2.
To ensure air tight joints there must be a 50 % contact over the critical area.
Burrs and high spots must be removed before assembly.
To ensure an oil tight joint, a line of continuous contact, with 0.25 inch (6.35
mm) minimum width, must be maintained, in addition to 50 % contact over the
critical area. The 50 % contact must be equally distributed over the critical area.
6
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
1.12.1 Listing
DESCRIPTION
NAME REFERENCE
ORAPPLICATION
Non-hardening adhesive
Dux seal plastic 158A2557PT-1
compound.
DGY 1
Used on compartment door
Petrolatum Atlantic Richfield, Gulf Oil.
gaskets to prevent sticking.
Humble oil or equivalent
Silicone rubber sealant white
RTV-102 Adhesive General Electric Co.
paste.
Silicone rubber sealant. Good
RTV-106 Adhesive for high temperature areas red General Electric Co.
paste.
Locktite Pipe
Used on all pipe thread joints. 118D5700
Sealant with Teflon
Locktite Plastic
Oil to air sealing joints. 226A1482P1
Gasket #47
Bolting anti-seize compound,
Fel-Pro C-102 287A1397
high temperature.
Bolting anti-seize compound,
Never Seeze 248A5801
low temperature.
Perfect Seal Gasket sealing compound. K9692676
Contact Cement Exhaust system. 226A2449
Rubber Cement Heat exchanger head gaskets. 248A5557P1
High temperature aluminum
Paint 262A3194P1
silicone.
Rust inhibitive beige primer.
Paint 262A3195P1
Water reducible.
Thinner 1500
High temperature aluminum
Alkyd Resin General Electric Co.
paint.
05B7A
Thinner Carboline Exhaust system paint thinner Carboline Co.
7
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
33 for Carboline 11 Grey. 32 Hanley Ct.
St. Louis, Mo. 63122
Carboline Co.
Primer Carbo Zinc
Exhaust system paint. 32 Hanley Ct.
Grey
St. Louis, Mo. 63122
Galvanizing paint Unit walkways. 211A8426
Uniroyal Industrial
Apply on heat exchanger head
Adhesive Rubber 248A5557P1
gaskets.
Cement # 6128
Sealing Fiber Sealing fiber for use in
256A1201P4
Adaco electrical conduits.
Adaco # 1 Sealing Sealing compound for use in
256A1200P4
Compound electrical conduits.
Quick setting type suitable for
Adhesives 158A7228P1
outdoor environments.
3M2121 Strip Unit lagging, soft,
156A1563P2 or P1
Caulk non-hardening sealer.
MorelandChemical
Co. Sodiumilicote Heavy grade adhesive paste. 239A5612P19
Adhesive
Vimasco 136 Canvas lagging adhesive. 248A5660P1
Fluorescent penetrant, for From Magnaflux
Zyglo ZL22
crack checks. Corporation (Chicago, Ill.)
Plus Gas Formula From Dockrell Agencies
"A" Penetrating oil. (Scarborough, Ontario,
Dismantling Fluid Canada)
From KANO laboratories,
Kano "Kroil" Penetrating oil.
Inc. (Nashville, Tenn.)
WD-40 Company 1061
WD-40 Penetrating oil. Cudahy Place,
San Diego, Calif. 92116
Cleaning solvent (petroleum Standard Oil of Ohio,
Stoddard Solvent
spirits). Cleveland, Ohio 44115
Cleaning solvent (petroleum Exxon Company Pelham,
Exxon Varsol 1
spirits). N.Y. 10803
Cleaning solvent (petroleum Exxon Company Pelham,
Exxon Varsol 18
spirits). N.Y. 10803
Boron Fast Dry Cleaning solvent (petroleum Standard Oil of Ohio,
3137 spirits). Cleveland, Ohio 44115
Cleaning solvent (petroleum Eastern Chemicals Co.,
Multicleaner N°18
spirits). Albany, N.Y.
Turco Products Co.,
Turco Cold Spray Rust inhibitor.
Patterson, N.J.
Used to lubricate Dresser type Victaulic Co. of America,
Victaulic Lubricant
coupling pipe ends and rubber 3100 Hamilton Blvd., South
(SoapBase)
seal lips inside and outside Plainfield .N.J.07080
8
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
diameters.
Heat Transfer
Used in VTR temperature
Compound Grade 235A6987
regulating valve wells
Z-80
Lead 25 ppm
9
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
Description or function of the part being ordered and location of the part
on the unit.
Part number (drawing number) stamped on the part or from a reference
drawing.
If a modification type drawing applies against the assembly from which
replacement parts are being ordered, note both the assembly and modification
drawing numbers and titles Quantity of items needed.
Parts which form one complete working unit must be ordered together; for
example, shafts and bushings, both halves of a bearing, etc...If no drawing,
parts list, or reference publication is available which shows the replacement
part required, a sketch or sample of the item, together with all necessary
dimensions and description of the part’s function, should accompany the order.
Attention to these directions will greatly expedite the shipment of spare and
renewal parts.
10
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
to paint or stencil (lead and sulfur free) the Purchaser’s name and the turbine
serial number on the part. This is particularly true on parts such as wheels,
diaphragms, nozzles and heavy castings. This practice will facilitate rapid
identification when the part reaches the repair facility.
Gas turbine division should be notified at once of the shipment. Returned
apparatus must be properly packaged and the parts protected to prevent
damage from rust, corrosion and handling. Adherence to the above
suggestions will facilitate checking and inspection of the returned material and
assure more expeditious repair of the material at the factory.
2 Maintenance Consideration
2.1 Introduce
Maintenance costs and availability are two of the most important concerns to
a heavy-duty gas turbine equipment owner. Therefore, a well thought out
maintenance program that optimizes the owner’s costs and maximizes
equipment availability should be instituted. For this maintenance program to be
effective, owners should develop a general understanding of the relationship
between the operating plans and priorities for the plant, the skill level of
operating and maintenance personnel, and all equipment manufacturer’s
recommendations regarding the number and types of inspections, spare parts
planning, and other major factors affecting component life and proper operation
of the equipment.
In this document, operating and maintenance practices for heavy-duty gas
turbines will be reviewed, with emphasis placed on types of inspections plus
operating factors that influence maintenance schedules. A well-planned
maintenance program will result in maximum equipment availability and
optimization of maintenance costs.
Note:
• The operation and maintenance practices outlined in this document are
based on full utilization of GE-approved parts, repairs, and services.
• The operating and maintenance discussions presented are generally
applicable to all GE heavy-duty gas turbines; i.e.,MS3000, 5000, 6000, 7000
and 9000. For purposes of illustration, the MS7001EA was chosen for most
components except exhaust systems, which are illustrated using different gas
turbine models as indicated. Consult the GE Operation and Maintenance
(O&M)Manual for specific questions on a given machine, or contact the local
GE Energy representative.
11
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
reliability and availability. The correct implementation of planned
maintenance and inspection provides direct benefits in reduced forced outages
and increased starting reliability, which in turn can reduce unscheduled repairs
and downtime. The primary factors that affect the maintenance planning
process are shown in Figure 1. The owners’ operating mode and practices will
determine how each factor is weighted. Parts unique to a gas turbine requiring
the most careful attention are those associated with the combustion process,
together with those exposed to the hot gases discharged from the combustion
system.
These are called the combustion section and hot gas path parts, and they
include combustion liners, end caps, fuel nozzle assemblies, crossfire tubes,
transition pieces, turbine nozzles, turbine stationary shrouds and turbine
buckets. Additional areas for consideration and planning, though longer-term
concerns, are the lives of the compressor rotor, turbine rotor, casings and
exhaust diffuser. The basic design and recommended maintenance of GE
heavy-duty gas turbines are oriented toward:
• Maximum periods of operation between inspections and overhauls.
• In-place, on-site inspection and maintenance.
• Use of local trade skills to disassemble, inspect and re-assemble gas
turbine components.
In addition to maintenance of the basic gas turbine, the control devices,
fuel-metering equipment, gas turbine auxiliaries, load package, and other
station auxiliaries also require periodic servicing.
The primary maintenance effort involves five basic systems: controls and
accessories, combustion, turbine, generator and balance-of-plant. Controls and
accessories are typically serviced in outages of short duration, whereas the
other four systems are maintained through less frequent outages of longer
duration. Gas turbine maintenance starts with a clear understanding of the
plant operation and the environment in which the plant operates. These two
factors should be the basis for developing a maintenance plan for gas turbines.
The inspection and repair requirements, outlined in the O&M Manual
provided to each owner, lend themselves to establishing a pattern of
inspections. These inspection patterns will vary from site to site and owner
operators should understand how factors such as air and fuel quality will be
used to develop an inspection and maintenance program. In addition,
supplementary information is provided through a system of Technical
Information Letters (TILs) associated with specific gas turbines after shipment.
This updated information, in addition to the O&M Manual, assures optimum
installation, operation and maintenance of the turbine. (See Figure 2.) Many
of the TILs contain advisory technical recommendations to help resolve
issues(as they become known) and to help improve the operation,
maintenance, safety, reliability or availability of the turbine. There
commendations contained in TILs should be reviewed and factored into the
12
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
overall maintenance planning program. For a maintenance program to be
effective, from both cost and turbine availability standpoints, owners must
develop a general understanding of the relationship between their operating
plans and priorities for the plant and the manufacturer’s recommendations
regarding the number and types of inspections, spare parts planning, and other
major factors affecting the life and proper operation of the equipment. Each of
these issues will be discussed in greater detail in the sections that follow.
Figure-1 Key factors affecting maintenance planning
13
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
3.1Borescope Inspection
An effective borescope inspection (BI) program can monitor the condition
of internal components without the need for casing removal. Borescope
inspections should be scheduled with consideration given to the operation and
environment of the gas turbine and information from the O&M manual and
TILs.
GE heavy-duty gas turbine designs incorporate provisions in both
compressor casings and turbine shells for gas path visual inspection of
intermediate compressor rotor stages, first, second and third-stage turbine
buckets and turbine nozzle partitions by means of the optical borescope. These
provisions, consisting of radially aligned holes through the compressor
casings, turbine shell and internal stationary turbine shrouds, are designed to
allow the penetration of an optical borescope into the compressor or turbine
flow path area, as shown in Figure 3. Borescope inspection access locations
for F Class gas turbines can be found in Appendix E.
Figure 4 provides a recommended interval for a planned borescope
inspection program following initial base line inspections. It should be
recognized that these borescope inspection intervals are based on average unit
operating modes. Adjustment of these borescope intervals may be made based
on operating experience and the individual unit mode of operation, the fuels
used and the results of previous borescope inspections.
In general, an annual or semiannual borescope inspection should use all
the available access points to verify the safe and uncompromised condition of
the static and rotating hard ware. This should include, but is not limited to,
signs of excessive gas path fouling, symptoms of surface degradation (such as
erosion, corrosion, or spalling), displaced components, deformation or impact
damage, material loss, nicks, dents, cracking, indications of contact or rubbing,
or other anomalous conditions.
Figure 3. MS7001E gas turbine borescope inspection access locations
14
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
15
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
Table -2 lists the access holes location, casing holes thread size, dimension
from forward or aft face of compressor discharge case and number of holes in
each location.
Table -2 MS-9001E Inspection Access Hole Location
Number
No. Identification Location
of holes
557.35 mm (21.943”) from aft
1 2nd stage compressor stator flange forward compressor 1
casing
2 3rd stage compressor stator 290.45 mm (11.435”) from aft 1
16
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
flange forward compressor
casing
683.69 mm (26.917”) from aft
3 6th stage compressor stator 1
flange aft compressor casing
518.69 mm (20.421”) from aft
4 7th stage compressor stator 1
flange aft compressor casing
356.57 mm (14.038”) from aft
5 8th stage compressor stator 1
flange aft compressor casing
155.60 mm (6.126”) from
6 11th stage compressor stator forward flange compressor 2
discharge casing
814.48 mm (32.066”) from
7 16th stage compressor stator forward flange compressor 2
discharge casing
1548.66 mm (60.971”) aft of
Aft compressor discharge
8 compressor discharge casing 1
casing
forward flange
1st stage nozzle trailing edge
292.51 mm (11.516”) from
9 and 1st stage bucket leading 8
forward turbine flange
edge
2nd stage nozzle leading edge 391.59 & 405.05 mm (15.417”
10 and 1st stage bucket trailing & 15.947”) from forward 8
edge turbine flange
2nd stage nozzle trailing edge
567.56 mm (22.345”) from aft
11 and 2nd stage bucket leading 5
turbine flange
edge
456.59 mm (17.976”) from aft
3rd stage nozzle leading edge
turbine flange & 832.87 mm
12 and 2nd-stage bucket trailing 5
(32.790”) from forward
edge
turbine flange
456.59 mm (17.976”) from aft
3rd stage nozzle trailing edge
turbine flange & 832.87 mm
13 and 3rd stage bucket leading 5
(32.790”) from forward
edge
turbine flange
3rd stage nozzle trailing edge
130.35 mm (5.132”) from aft
14 and 3rd stage bucket leading 5
turbine flange
edge
1st stage nozzle probes 336.55 mm (13.25”) from
15 4
(position check) forward turbine flange
1st stage turbine clearance 336.55 mm (13.25”) from
16 4
meter forward turbine flange
2st stage turbine clearance 491.74 mm (19.36”) from aft
17 4
meter turbine flange
3st stage turbine clearance 42.93 mm (1.69”) from aft
18 4
meter turbine flange
19 1st stage compressor 396.19 mm (15.598”) from 4
17
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
(clearance meter) forward flange of forward
compressor casing
384.81 mm (15.150”) from
6st stage compressor
20 forward flange of aft 4
(clearance meter)
compressor casing
457.61 mm (18.016”) aft of
13st stage compressor
21 compressor discharge casing 4
(clearance meter)
forward flange
991.99 mm (39.055”) aft of
16st stage compressor
22 compressor discharge casing 4
(clearance meter)
forward flange
18
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
regular intervals and should be recorded to permit an evaluation of the turbine
performance and maintenance requirements as a function of operating time.
This operating inspection data, summarized inFigure6, includes: load versus
exhaust temperature, vibration, fuel flow and pressure, bearing metal
temperature, lube oil pressure, exhaust gas temperatures, exhaust temperature
spread variation and startup time. This list is only a minimum and other
parameters should be used as necessary. A graph of these parameters will help
provide a basis for judging the conditions of the system.
Deviations from the norm help pinpoint impending trouble, changes in
calibration or damaged components.
Figure 6. Operating inspection data parameters
19
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
20
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
21
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
• Visually inspect the compressor inlet, checking the condition of the
IGVs, IGV bushings, and first stage rotating blades.
• Check the condition of IGV actuators and rack-and-pinion gearing.
• Visually inspect compressor discharge case struts for signs of cracking.
• Visually inspect compressor discharge case inner barrel if accessible.
• Visually inspect the last-stage buckets and shrouds.
• Visually inspect the exhaust diffuser for any cracks inflow path surfaces.
Inspect insulated surfaces for loose or missing insulation and/or attachment
hardware in internal and external locations. In E-class machines, inspect the
insulation on the radial diffuser and inside the exhaust plenum as well.
• Inspect exhaust frame flex seals, L-seals, and horizontal joint gaskets for
any signs of wear or damage.
• Verify proper operation of purge and check valves. Confirm proper
setting and calibration of the combustion controls.
After the combustion inspection is complete and the unit is returned to
service, the removed combustion hardware can be inspected by a qualified GE
field service representative and, if necessary, sent to a qualified GE Service
Center for repairs. There moved fuel nozzles can be cleaned on-site and flow
tested on-site, if suitable test facilities are available. For F Class gas turbines it
is recommended that repairs and fuel nozzle flow testing be performed at
qualified GE Service Centers.
Figure 7. Combustion inspection – key elements
22
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
23
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
For inspection of the hot gas path (Figure 5), all combustion transition
pieces and the first-stage turbine nozzle assemblies must be removed.
Removal of the second- and third-stage turbine nozzle segment assemblies is
optional, depending upon the results of visual observations, clearance
measurements, and other required inspections. The buckets can usually be
inspected in place.
Fluorescent penetrant inspection (FPI) of the bucket vane sections may be
required to detect any cracks. In addition, a complete set of internal turbine
radial and axial clearances(opening and closing) must be taken during any hot
gas path inspection. Re-assembly must meet clearance diagram requirements
to ensure against rubs and to maintain unit performance. Typical hot gas path
inspection requirements for all machines are:
• Inspect and record condition of first, second and third-stage buckets. If it
is determined that the turbine buckets should be removed, follow bucket
removal and condition recording instructions. Buckets with protective coating
should be evaluated for remaining coating life.
• Inspect and record condition of first-, second- and third-stage nozzles.
• Inspect and record condition of later-stage nozzle diaphragm packings.
• Check seals for rubs and deterioration of clearance.
• Record the bucket tip clearances.
• Inspect bucket shank seals for clearance, rubs and deterioration.
• Perform inspections on cutter teeth of tip-shrouded buckets. Consider
refurbishment of buckets with worn cutter teeth, particularly if concurrently
refurbishing the honeycomb of the corresponding stationary shrouds. Consult
your GE Energy representative to confirm that the bucket under consideration
is repairable.
• Check the turbine stationary shrouds for clearance, cracking, erosion,
oxidation, rubbing and build-up.
• Check and replace any faulty wheel space thermocouples.
• Enter compressor inlet plenum and observe the condition of the forward
24
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
section of the compressor.
• Visually inspect the compressor inlet, checking the condition of the
IGVs, IGV bushings, and first stage rotating blades.
• Check the condition of IGV actuators and rack-and-pinion gearing.
• Enter the combustion wrapper and, with a borescope, observe the
condition of the blading in the aft end of the axial flow compressor.
• Visually inspect compressor discharge case struts for signs of cracking.
• Visually inspect compressor discharge case inner barrel if accessible.
• Visually inspect the turbine shell shroud hooks for sign of cracking.
• Visually inspect the exhaust diffuser for any cracks in flow path surfaces.
Inspect insulated surfaces for loose or missing insulation and/or attachment
hardware in internal and external locations. In E-class machines, inspect the
insulation on the radial diffuser and inside the exhaust plenum as well.
• Inspect exhaust frame flex seals, L-seals, and horizontal joint gaskets for any
signs of wear or damage
The first-stage turbine nozzle assembly is exposed to the direct hot gas
discharge from the combustion process and is subjected to the highest gas
temperatures in the turbine section. Such conditions frequently cause nozzle
cracking and oxidation and, in fact, this is expected. The second- and third-stage
nozzles are exposed to high gas bending loads, which in combination with the
operating temperatures, can lead to downstream deflection and closure of critical
axial clearances. To a degree, nozzle distress can be tolerated and criteria have
been established for determining when repair is required. These limits are
contained in the Operations and Maintenance Manuals previously described.
However, as a general rule, first stage nozzles will require repair at the hot gas
path inspection. The second- and third-stage nozzles may require refurbishment
to re-establish the proper axial clearances. Normally, turbine nozzles can be
repaired several times and it is generally repair cost versus replacement cost that
dictates there placement decision.
Coatings play a critical role in protecting the buckets operating at high metal
temperatures to ensure that the full capability of the high strength super alloy is
maintained and that the bucket rupture life meets design expectations. This is
particularly true of cooled bucket designs that operate above 1985°F (1085°C)
firing temperature. Significant exposure of the base metal to the environment will
accelerate the creep rate and can lead to premature replacement through a
combination of increased temperature and stress and a reduction in material
strength, as described in Figure 10. This degradation process is driven by
oxidation of the unprotected base alloy. In the past, on early generation uncooled
designs, surface degradation due to corrosion or oxidation was considered to be a
performance issue and not factor in bucket life. This is no longer the case at the
higher firing temperatures of current generation designs. Given the importance of
25
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
coatings, it must be recognized that even the best coatings available will have a
finite life and the condition of the coating will play a major role in determining
bucket life. Refurbishment through stripping and recoating is an option for
achieving bucket’s expected/design life, but if recoating is selected, it should be
done before the coating is breached to expose base metal. Normally, for turbines
in the MS7001EA class, this means that recoating will be required at the hot gas
path inspection. If recoating is not performed at the hot gas path inspection, the
life of the buckets would generally extend to the major inspection, at which point
the buckets would be replaced. For F class gas turbines, recoating of the first
stage buckets is recommended at each hot gas path inspection. Visual and
borescope examination of the hot gas path parts during the combustion
inspections as well as nozzle-deflection measurements will allow the operator to
monitor distress patterns and progression. This makes part-life predictions more
accurate and allows adequate time to plan for replacement or refurbishment at the
time of the hot gas path inspection. It is important to recognize that to avoid
extending the hot gas path inspection, the necessary spare parts should be on site
prior to taking the unit out of service.
Figure 10. Stage 1 bucket oxidation and bucket life
27
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
• Visually inspect the exhaust diffuser for any cracks in flow path surfaces.
Inspect insulated surfaces for loose or missing insulation and/or attachment
hardware in internal and external locations. In E-class machines, inspect the
28
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
insulation on the radial diffuser and inside the exhaust plenum as well.
• Inspect exhaust frame flex seals, L-seals, and horizontal joint gaskets for
any signs of wear or damage. Inspect steam gland seals for wear and oxidation.
• Check torque values for steam gland bolts and re-torque to full values.
• Check alignment – gas turbine to generator/gas turbine to accessory gear
4.1 Introduction
The present document related to the maintenance of the accessories of gas
turbines is a guide for the End User’s maintenance Engineers.
The aim of this document is to give maintenance interval and
recommendation for the gas turbine accessories systems and their components.
The maintenance activities recommended in this guide are typical and do
not pertain to any particular plant equipment model.
Maintenance activities are mainly driven by periodical checkup and routine
inspections.
● Periodical checkup are jobs to be carried out at predetermined frequencies
like monthly, annually, or during gas turbine inspections as combustion, hot gas
path, major.
● Routine inspections are checkup carried out more often like daily, weekly,
in relation with gas turbine operation. They are related to parameters read out
and analysis, visual inspection, abnormal noise, as explained in the Operation
volume.
● Routine inspections may impact periodical maintenance activities and
may shorten the frequencies defined in the tables here below.
The present document applies for accessories of gas turbines frame 6B, 6C,
6FA, 9E.
4.2Safety
The End User shall take appropriate steps to ensure that only workers who
have received adequate instruction shall have access to equipment. The End
User shall ensure site safe work practices are implemented and enforced (e.g.
proper operator response action to control system alarms, energy isolation
procedures (lockout/tag out), personal protective equipment, permit space entry
procedures, posting of warning signs, training, Material Safety Data Sheets
(MSDS), etc.).
The End User shall ensure that site safe work practices integrate access
permit, work permit and relevant permits and procedures to cover all aspect of
29
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
safety.
Content of Tables
Maintenance schedule and maintenance activities of each device of a single
system are listed, system by system, in the different tables below. Some devices
like pressure transducers, check valves, orifices, installed in different systems
have identical maintenance schedule and maintenance activities whatever the
system they belong to. These devices are grouped in the first table called
“Standard devices”. The tables are divided into several columns. The two first
are:
Device: designation of the device,
NOTE
Underlined device names are only for a specific gas turbine frame
Check / inspect: list the maintenance activities
The other columns tell how often a device or an equipment should be
inspected and whether or not the turbine can be operating at the time of the
inspection. The meaning of the letters used is:
D: Daily Inspection
W: Weekly Inspection
M: Monthly Inspection
Q: Quarterly Inspection
SA: Semi-annual Inspection
CI: Combustion Inspection
HGPI: Hot Gas Path Inspection
MI: Major Overhaul Inspection
O: Turbine Operating
S: Turbine Shutdown
The recommended maintenance activities, frequencies and turbine status
are representative of an average power plant installation and include both
peaking and continuous operating stations. They are not intended to cover all
variations of equipment supplied and may depend upon station environment. In
some cases, a shutdown may be recommended solely as a precaution against
possible injury to maintenance personnel, because the location of the
component or device is in a hazardous area.
As per GER 3620 maintenance activities are influenced by many factors
like the type and quality of fuel, the starting cycle, the power setting and duty
application, the steam/water injection. Maintenance interval requirement for
below listed devices may also be impacted by those factors. Due to enormous
30
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
variety of operating conditions from a power plant to another, maintenance
adjustment has to be based on experience and observations made by the End
User.
Lubrication frequency will vary, depending on turbine operating hours and
ambient temperature. It is therefore suggested to keep records of lubrication
intervals to determine variances between periods listed on the chart and those
scheduled for a specific installation.
For all the devices listed here below, always refer to the Original
Equipment Manufacturer (OEM)technical literature / equipment publication
for accurate information regarding maintenance schedule and maintenance
activities for each device.
31
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
37
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
4.4.1Definition
38
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
39
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
40
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
The lubricating oil intended for this service is a rust and oxidation inhibiting
petroleum lubricating oil or synthetic hydrocarbon with greater high temperature
oxidation stability than conventional lubricating oils. Operating experience has
shown the antioxidant of the di-tertiary butyl-para-cresol (DBPC) type is not
adequate for this service. The inhibitors must be of the non-volatile type.
A listing of recommended properties of new oil is shown in Table 1. Included
with this listing is the ASTM test method and the recommended value. The reader
should refer to these methods for details of the tests. The oil is an International
Standards Organization Viscosity Grade 32 (ISO VG 32) oil. The properties
listed are rather typical of turbine lubricating oils except for the oxidation test
requirements. Note that the values in Table 1 are only recommended values. An
oil that has been shown to perform successfully in the field may still be used even
if all values in Table 1 have not been satisfied.
For several years there have been investigations to decide on appropriate
laboratory tests which could distinguish between fluids which gave satisfactory
service in a turbine and those which did not. To date, there has not been complete
correlation between laboratory testing and field experience.
There are three methods recognized by the ASTM for determining carbon
residue. They are D-524,“Ramsbottom Carbon Residue of Petroleum Products”,
D-4530, “Determination of Carbon Residue(Micro Method)” and D-189,
“Conradson Carbon Residue of Petroleum Products”. Although these methods are
similar in concept, they do not provide identical results. Each method contains a
graph that can be used to convert the results for comparison to the other methods.
Although Table 1 only contains acceptance criteria for D-524, either of the other
two methods can be used instead provided the results obtained are equivalent to
the value contained in Table 1 for D-524.
Two oxidation tests are listed in Table 1. The ASTM D-943 (Oxidation
41
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
Characteristics of Inhibited Steam-Turbine Oils) minimum value must be
satisfied for this service. In addition, both of the Oxidation Stability by Rotating
Bomb tests described below must be satisfied.
ASTM D-2272, Standard Test Method for Oxidation Stability of Steam
Turbine Oils by Rotating Bomb, presently shows the best correlation with service
experience but it is not absolute. It has been found that the volatility of the
inhibitor can have a significant effect on the results of this test. As stated above,
these inhibitors need to be non-volatile.
The ASTM D-2272 test should be run in the normal way and a second test run
on oil which has been treated to remove volatiles. This pretreatment is done by
putting the oil to be tested in a test tube 38 mm ID× 300 mm L. (This is the same
tube used for the International Harvester BT-10 oxidation test.) This tube is
immersed in a bath maintained at 250_F (l21_C). Clean, dry nitrogen is then
bubbled through the heated oil for 48 hours at the rate of 3 liters per hour. The
treated oil is then tested per ASTM D-2272.
4.4.3.2 Corrosion-Preventative Materials
Manufacturing procedures provide for corrosion protection by cleaning and
treating all metal surfaces which will be in contact with the lubricating oil in the
lubrication system.
The inside walls of the lubricating oil tank are processed at the factory using an
oil-resistant paint.
The inner surfaces of all lubricating oil piping, bearings, hydraulic control
devices, and other apparatus whose surfaces will be in contact with the turbine
lubricating oil are coated with a vapor space rust-inhibited(VSI) lubricating oil
which is used as a combination test and shipping oil.
In addition, 50 gallons of this oil is put in the reservoir at shipment and the
system openings are closed. The oil and its vapors provide corrosion protection
during shipment and installation.
At installation this oil should be removed and the reservoir manually cleaned.
The remaining VSI oil should be removed with a displacement flush.
4.5Trip Oil System
42
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
4.6.1Definition
The cooling water system is designed for insuring cooling down of:
• The lubricating oil
• The turbine supports
• The flame detectors
• The atomizing air system
The above equipment is part of the installation’s cooling water closed loop.
Cooling water characteristics:
Cooling water characteristics must comply with this manual.
Lubricating oil temperature:
During gas turbine operation the lubricating oil temperature is between 49°C
and 70°C (120°F – 158°F) according to the water flow through the heat exchanger
and the site ambient air temperature.
43
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
44
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
� Tube and shell inspection if loss of performance :
pressure droop increase or reduction of thermal S
efficiency
� Erosion of blades, deposit on blades, rust,
corrosion, peeling
� External visual check for excessive noise or O
vibration
S
Fan � Cleanliness of ducts, housing, screens, blades
S
� Erosion of blades, deposit on blades, rust,
corrosion, peeling
Air trap � External visual check for fluid leak, device O
automatic damage
vent valve � Cleanliness of internal parts S
4.7Starting Means System
4.7.1Definition
The starting means system is designed for insuring the following functions:
• To break away and crank the shaft line up to nominal speed
• To allow the shaft line cooling down
• To crank the unit for Off line washing
The starting means includes:
• A main electrical cranking motor loaded at 130% of nominal power at maximum torque
• An electrical turning gear motor
• A torque converter including an auxiliary two ways electrical motor to drive the variable inlet guide vanes to adjust the
output torque during starting sequences.
45
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
Lube oil from auxiliary lube oil pump feeds the torque converter during cranking sequences
4.7.2 Maintenance Schedule
4.8.1Definition
The liquid fuel system providing liquid fuel for the combustion chambers is designed for insuring the following
functions:
• Fire, warm up and accelerate the unit up to nominal speed
• Power the unit up to base load
• Shut down and trip the unit
The liquid fuel system is an open loop including:
• A safety valve to stop the fuel flow
• A shaft driven main fuel pump
46
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
• A control valve to adjust the fuel flow by bypassing the main fuel pump
• An electrical clutch to drive the main fuel pump
• Dual high pressure filter
• A flow divider to distribute equal flow in each combustion chamber
• Turbine casing and exhaust casing drain valves to drain the unburned liquid fuel at false starts
Nozzle pressure:
A manual selector is provided to measure individual nozzle pressure. The maximum allowed pressure spread between
the nozzles couldn’t exceed 10 bars. High spread configuration must be analyzed and rectified urgently.
4.8.2 Maintenance Schedule
48
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
4.9.1Definition
Atomization is the process whereby a volume of liquid is converted into a multiplicity of very small droplet by air
stream. The atomizing air system is designed for insuring the following functions:
• To atomize the liquid fuel
• To purge the water injection lines when water is not used
49
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
The atomizing air system is an open loop where the air from the axial compressor is cooled down and then pressurized
by the shaft driven main compressor. An electrical motor driven booster built up the atomizing air pressure during starting
sequence.
Additional information
Permanent purging:
Permanent atomizing air purging is provided through small orifices and silencers at compressor upstream.
Air ejector:
An air ejector installed on the top of the accessory gear box receives air flow from the atomizing air system to create a
gear box vacuum pressure.
Compressor washing:
Manual valves are provided to isolate atomizing air lines during compressor Off line washing sequence.
4.9.2 Maintenance Schedule
50
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
4.10.1 Definition
The fire protection system is designed for insuring the following functions:
• To detect fire automatically
• To trip the unit and extinguish fire quickly
• To keep low concentration of combustive agent after fire
• To inform the operator
• To allow manual firefighting release in the enclosures listed here below :
• Auxiliaries
• Gas turbine
• Load
Firefighting is achieved using carbon dioxide (CO2)
Additional information
51
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
Compartments access:
Access inside the compartments at any time must be under strict control using access permit or work permit to
guaranty operator safety regarding potential risk including carbon dioxide emission.
Fire alarm:
Fire alarm appears before fire trip. Any alarm must be investigated and rectified quickly
Carbon dioxide emission:
After carbon dioxide emission and confirmation that fire risk do not exist anymore, the compartment ventilation must
be activated the clear the inside atmosphere. Concentration measurement must be carried out to confirm safe access.
4.10.2 Maintenance Schedule
53
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
4.12.1Definition
The hydraulic supply system is designed to provide high pressure oil at constant pressure to control:
• The liquid fuel bypass regulating valve and stop valve
• The compressor inlet guide vanes
The hydraulic supply system is a closed loop where the oil pressure is built up from lubricating oil header by:
• A shaft driven main pump
• An electrical motor driven auxiliary pump for starting and shut down sequences
Hydraulic oil supply conditioning includes:
• Automatic purging
• Dual filtering
• Accumulator
Hydraulic oil flows back to the lubricating oil tank by gravity.
4.12.2Maintenance Schedule
Hydraulic Supply System
54
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection Major
Inspection – X other period O : turbine Operating – S : turbine Shut down
4.13.1 Definition
The heating and ventilation system is designed for insuring the following functions:
• To evacuate the hot air from inside the compartment to outside
• To dilute gas leak to avoid hazardous area in the enclosures listed here below:
•Auxiliaries
•Gas turbine
•Exhaust
•Load
•Water injection skid
Enclosure purpose is:
• To protect personnel from high temperature and fire risks.
• To provide proper cooling and ventilation for the equipment.
• To provide attenuation of the noise generated by the equipment
55
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
• To contain fire fighting medium
• To provide weather protection for the equipment.
Redundant electrically driven fans provide airflow. Ventilation airflow direction is according to the need of each
enclosure.
Flap at ventilation air intake are use to restrict airflow while the ventilation is not in operation and to participate to fire
fighting effectiveness.
Electrical heaters are provided in enclosures for heating the ambient air except in exhaust and load compartments.
Additional information
Compartments access:
Access inside the compartments at any time must be under strict control using access permit or work permit to
guaranty operator safety regarding potential risk including carbon dioxide emission.
Carbon dioxide emission:
After carbon dioxide emission and confirmation that fire risk do not exist any more, the compartment ventilation must
be activated to clear the inside atmosphere. Concentration measurement must be carried out to confirm safe access.
Unit cooling down sequence:
During cooling down period using turning gear, all the turbine compartment doors must remain closed to avoid cool air
excess flow distribution near the gas turbine casing.
4.13.2 Maintenance Schedule
57
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
4.14Compressor Washing System
4.14.1Definition
The compressor and turbine washing system is designed for insuring the following functions:
• To clean the compressor at stand still (Off line)
• To clean the compressor at nominal speed (On line)
• To clean the gas turbine
A module not included in this chapter provides the clean washing water flow. OFF line washing and ON line washing
use specific spray manifold. Turbine washing uses atomizing air manifold.
4.14.2 Maintenance Schedule
58
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
4.15.1Definition
The water injection system is designed to reduce the NOx level when the gas turbine is burning liquid fuel.
The water injection system is an open loop where water flow is built up by an electrically driven water pump. The
system includes
• Temporary and permanent filters
• An electrically driven water pump
• A water pump re-circulating line to allow pump cooling down
• A water flow regulating valve to adjust the water flow according to the fuel flow
• A flow meter
• Two stop valve to cut off the water flow in each manifold
Injection water flow is injected in the combustion chambers by two manifolds and evacuated in the atmosphere
through the exhaust duct. The regulating valve controls the total injected water flow.
Flow regulating valve and stop valve are piloted using instrument air.
59
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
4.15.2 Maintenance Schedule
4.16.1Definition
The inlet guide vanes system is designed to adjust the compressor airflow according to compressor and combustion
needs.
The compressor inlet guide vanes system is actuated with hydraulic supply. The oil returns to the lubricating oil tank
by gravity.
4.16.2 Maintenance Schedule
� Clean if necessary S
� Check for Corrosion, abrasion, pitting, leading/trailing S
Inlet Guide Vanes
edge damage
� Check backlash and bushing clearance S
4.17 Inlet and Exhaust System
4.17.1Definition
The flow inlet & exhaust is designed for insuring the following functions:
• To supply the gas turbine with filtered air flow
• To reduce the compressor air inlet acoustical level
• To protect the air inlet duct against high pressure drop
4.17.2 Maintenance Schedule
62
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
4.18.1 Definition
The turbine solid compound cleaning system is designed to inject solid compound at the gas turbine inlet to remove
part of the undesirable deposit and ashes due to the use of low grade liquid fuels.
The turbine cleaning system includes a cleaning skid and a set of manual valves with injection nozzles, one for each
combustion chamber. The cleaning skid consist of :
• A low pressure hopper to store the solid compound for one combustion chamber
• A motorized valve to fill up the high pressure hopper
• A high pressure hopper to store the solid compound for one combustion chamber
• An air ejector
• A set of manual valves
Air from the atomizing air system is used to inject the cleaning compound into one combustion chamber at a time
through dilution holes at the end of the liner.
The cleaning cycle is performed at full speed no load.
The cycle of the turbine cleaning system is as follow:
• Fill up manually the low pressure hopper with 25 kg of solid compound for combustion chamber # 1
• Transfer the 25 kg solid compound from low pressure hopper to the high pressure hopper
65
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
• Inject the solid compound in chamber # 1 during 3 to 5 minutes
• Fill up manually the low pressure hopper with 25 kg of solid compound for combustion chamber # 8
• Transfer the 25 kg solid compound from low pressure hopper to the high pressure hopper
• Inject the solid compound in chamber # 8
• Continue the cleaning sequence for other combustion chambers, one by one in the following
order # 2, # 9, # 3, # 10, # 4, # 11, # 5, # 12, # 6, # 13, # 7, # 14 to balance first nozzle cleaning and to avoid
unbalance in turbine's performance or temperature.
4.18.2Maintenance Schedule
66
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection Major
Inspection – X other period O : turbine Operating – S : turbine Shut down
Device Check/inspect D W M Q S CI HGPI MI X
9E Accessory � Visual check according to OEM technical S
coupling literature
� Visual check according to OEM technical
Load coupling
literature S
� Visual check for leak, damage, loose bolts, S
Accessory gear anchor bolts, cleanliness, maintenance as per OEM
box literature
S
� Gear box inspection through inspection door
� Visual check for leak, damage, loose bolts, S
anchor bolts, cleanliness, maintenance as per OEM
Load gear box literature
S
� Gear box inspection through inspection door
4.20Acoustical Enclosure
Acoustical Enclosure
Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection Major
Inspection – X other period O : turbine Operating – S : turbine Shut down
Device Check/inspect D W M Q S CI HGPI MI X
� External visual check damage, loose mounting S
Structure
bolts, corrosion
67
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
68
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
System
Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection Major
Inspection – X other period O : turbine Operating – S : turbine Shut down
69
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
Component function
TK601 Compressed air tank
CAB001 Electrical cubicle
NV201 Air cooler outlet check valve
NV301 Air compressor outlet check valve
NV601 Self cleaning air outlet check valve
NV611 Instrument air outlet check valve
HV201 Air cooler inlet manual isolation valve HT
HV202 Air cooler outlet isolation valve
HV203 Separator air cooler automatic drain valve
HV204 Separator air cooler manual drain valve
HV254 Air cooler regulation pressure switch instrumentation valve
HV301 Compressor air outlet isolation valve
HV303 Separator air cooler automatic drain valve
HV304 Separator air cooler manual drain valve
HV401 Air dryer inlet isolating valve
HV402 Air dryer outlet isolating valve
HV403 Pre filter automatic drain valve
HV404 Pre dryer outlet isolation valve
HV405 Air dryer bypass valve
HV413 Oil filter automatic drain valve
HV414 Oil filter manual drain valve
HV433 Final filter manual drain valve
HV601 Self cleaning air outlet isolating valve
HV603 Air tank automatic drain valve
HV604 Air tank manually drain valve
HV611 Instrument air outlet isolating valve
HV652 Air tank regulation pressure switch instrumentation valve
HV651 Air tank pressure indicator instrumentation valve
HV661 Air tank low pressure switch instrumentation valve
PCV252 Air cooler pneumatic valve air pilot pressure control valve
PCV254 Air cooler outlet pressure control valve
PCV661 Air outlet pneumatic valve air pilot pressure control valve
PCV665 Instrument air outlet pressure control valve
TSV252 Air cooler outlet pneumatic isolation valve
FSV661 Air outlet pneumatic isolation valve
PSV255 Air cooler outlet pressure safety valve
PSV651 Air tank pressure safety valve
PSV666 Instrument air outlet pressure safety valve
PDI451 Pre filter pressure differential manometer
PDI461 Oil filter pressure differential manometer
PDI481 Final filter pressure differential manometer
70
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
PI651 Air tank pressure indicator
TI251 Air cooler inlet temperature indicator
TI253 Air cooler outlet temperature indicator
TSH252 Air cooler outlet temperature switch high
FY252 Air cooler pneumatic valve pilot air solenoid valve
FY253 Separator air cooler solenoid drain valve
FY351 Separator compressor solenoid drain valve
FY453 Pre filter solenoid drain valve
FY463 Oil filter solenoid drain valve
FY653 Air tank solenoid drain valve
FY661 Air outlet pneumatic valve pilot air solenoid valve
FLT201 Separator air cooler Y filter drain
FLT301 Separator compressor Y filter drain
FLT431 Pre filter Y filter drain
FLT441 Oil filter Y filter drain
FLT601 Air tank Y filter drain
SEP201 Air cooler outlet separator
SEP302 Compressor outlet separator
FLT401 Pre filter
FLT402 Oil filter
FLT403 Final filter
PSLH254 Air cooler regulation pressure switch
PLSH652 Air tank regulation pressure switch
PSL661 Air tank low pressure switch
CLR201 Air cooler
FAN201 Air cooler fan
MO201 Air cooler motor
DRY401 Adsorption air dryer vessel 1
DRY402 Adsorption air dryer vessel 2
FY471 Adsorption air dryer solenoid valve
FY472 Adsorption air dryer solenoid valve
FY473 Adsorption air dryer solenoid valve
FY474 Adsorption air dryer solenoid valve
NV421 Adsorption air dryer check valve
NV422 Adsorption air dryer check valve
MI491 Adsorption air dryer moist indicator
CMP301 Auxiliary screw compressor
MO301 Auxiliary screw compressor motor
SEP301 Auxiliary screw compressor separator
CLR301 Auxiliary screw compressor air/oil exchanger
FAN301 Auxiliary screw compressor exchanger fan
MO302 Auxiliary screw compressor exchanger fan motor
PSH301 Auxiliary screw compressor high pressure switch
PSV301 Auxiliary screw compressor mini pressure switch
71
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
PSV302 Auxiliary screw compressor pressure safety valve
TSH301 Auxiliary screw compressor temperature switch
TSV351 Auxiliary screw compressor thermostatic valve
PCV301 Auxiliary screw compressor pressure control valve
PI301 Auxiliary screw compressor oil pressure indicator
PI302 Auxiliary screw compressor air pressure indicator
FY301 Auxiliary screw compressor regulation solenoid valve
4.23.1General
The role of the self-cleaning air filter GDX system, designed for GT frame
9Eev, is to remove the contaminants of the ambient air sucked by the G.T.
compressor, in order to protect the mechanical components such as compressor and
turbine blades against erosion, corrosion and fouling.
Self cleaning is accomplished by intermittently injecting compressed through
the blowpipes. Each pulse of air from the blowpipe into the filter cartridge provides
a shock wave inside the filter cartridge and a momentary reverse flow.
The power plant includes 3 Gas Turbine of 9EeV type. Each gas turbine is
supplied by an outdoor
Air processing unit, located close the GT and is designed to supply compressed
air to the GT’s self-cleaning air filter and for instrument air.
The equipment are designed for neutral air compressed free of aggressive
elements.
It’s installed in a tempered container to protect production air compressed skid
components against freezing and sun, direct rain, dust or sand wind.
The Air Processing Unit includes:
- One auxiliary screw compressor CMP301, 37 kW to supply compressed air to
self-cleaning air filter and instrument air for the plant.
- One motorized air cooler CLR201 for the purpose of cooling the compressed
air coming from GT to +5°C above ambient.
- One compressed air tank TK601 500 liters with adsorption air dryer DRY401
for self-cleaning air filter and for instrument air.
- Necessary filters, drain and instrumentation
4.23.2Screw compressor RAFALE 37 kW CMP301
72
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
The compressor outlet working pressure is from 8 to 10 bar.
- Type ................................................................................ RAF50-3 SP
- Working pressure ........................................................... 8 / 10 bar
- Max. working pressure: .................................................. 12 bar
- Nominal flow ................................................................... 230 Nm3/h
- Compressor revolution speed ......................................... 4000 rpm.
- Coupling ......................................................................... 5 Belts XPA 1180
- Installed power ............................................................... 37 kW
- Revolution speed ............................................................ 2960 rpm.
- Protection class .............................................................. IP55
- Isolation class ................................................................. F
- Temperature class .......................................................... B
- Supply voltage / frequency ............................................. 400 V / 50 Hz
- Heating element ............................................................. yes
- Wiring ............................................................................. Star/Delta start-up
- Working temperature ...................................................... 0°C to +55°C
- Air outlet connection ....................................................... 1”1/2
4.23.3Compressed air tank 500L TK601
The 500 litres air tank will store air coming from the GT for self cleaning air
filter and instrument air.
It's designed following PED CE / ASME VIII, hot dip galvanised.
- Capacity .......................................................... 500 L
- Fluid ................................................................ Compressed air
- Type ................................................................ vertical
- Design pressure ............................................... 10.6 bar
- Maximum allowable temperature .................... +100 °C
- Minimum design metal temperature ................ -15°C
- Hydrostatic test pressure ................................... 15.9 bar
- Joint Efficiency .......................................0.7 (longitudinal) / 0.65 (circular)
- Construction ..................................................... Directive 97/23 CE
- Design .............................................................. ASME VIII div 1
- Protection ........................................................ Int./Ext. galvanized
- Weight of vessel ................................................ 150 kg approx.
73
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
The air receiver is equipped with:
- One pressure safety valve 10.5 bar PSV651
- One pressure indicator PI651 with instrumentation valve HV651
- One regulation pressure switch PSLH652 with instrumentation valve HV652
- An automatic drain system composed by:
- A solenoid drain valve FY653 with Y filter FLT601
- An isolating valve 1/2" HV603
- A by-passed valve 1/2" HV604
Self cleaning air filter outlet S1:
- One isolating self cleaning outlet valve HV601
- One outlet check valve NV601
- One automatic valve FSV661 controlled by:
- One pressure switch low PSL661 with instrumentation valve HV661
- A solenoid valve FY661
- Pressure regulator PCV661
Instrument and service air outlet S2:
- One instrument air outlet valve HV611
- One instrument air outlet check valve NV611
- One pressure control valve PCV665 to reduce to 7 bar instrument and service
air
- One pressure safety valve PSV666 for instrument and service air 8 bar
In case of compressed air low pressure PSL661 in the tank TK601, the priority
is maintaining instrument and service air pressure to 7 bar and FSV661 is closing
the self cleaning compressed air flow. When the pressure is going up 8 bar,
FSV661 will be opened automatically
4.23.4Air cooler ARO203HT CLR201
An air forced air cooler cool air coming from gas turbine to be used by
compressed air network.
This air cooler is designed to decrease temperature for air coming from gas
turbines compressors
from 390°C to 55°C.
- Air flow capacity .............................................................. 203 Nm3/h
- Air inlet temperature ....................................................... 390 °C
- Air outlet temperature ..................................................... +5°C above
ambient
74
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
- Maximum working pressure ............................................ 16 bar
- Connections .................................................................... 1” 1/2 G M
- Motor fan power .............................................................. 0.55 kW
- Voltage ........................................................................... 400V/3ph/50Hz
The air cooler is equipped with:
- Manual isolating inlet valve HV201
- Pneumatic isolation valve TSV252 controlled by:
- An solenoid valve FY252
- Pressure regulator PCV252
- Temperature switch high TSH252
- Pressure switch regulation PSLH254 with instrumentation valve HV254
- An inlet temperature indicator TI251
- An outlet temperature indicator TI253
- An outlet pressure control valve PCV254 (setting: 10 bar)
- A pressure safety valve PSV255 (setting: 10.5 bar)
- An outlet isolating valve HV202 with check valve NV201
4.23.5Water separator filter SEP201 & SEP302
Located downstream air cooler and air compressor, the water separator is
designed to separate water due to temperature decrease in the air forced cooler.
- Type ................................................................................ Centrifugal
condensate separator
- Air flow capacity .............................................................. 330 Nm3/h
- Maximum working pressure ............................................ 16 bar
- Nominal pressure drop ................................................... 0.07 bar
- Connections .................................................................... 1” G F
The water separator filter is equipped with:
- An automatic drain system composed by:
- A solenoid drain valve FY253 &FY351 with Y filter FLT201 &FLT301
- An isolating valve 1/2" HV203 &HV303
- A by-passed valve 1/2" HV204 &HV304
4.23.6 Adsorption air dryer SAD255 DRY401
The adsorption air dryer is located upstream air tank and is able to dry 180
Nm3/h flow rate necessary for self cleaning filter and instrument air. It removes
humidity of the compressed air for abusing with negative ambient temperature.
75
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
- Air flow capacity at outlet (*) ........................................... 180Nm3/h
(*) working pressure 8 bar - air inlet temperature 50°C
- Type ................................................................................ SAD255
- Maximum working pressure ............................................ 16 bar
- Working temperature ...................................................... -10°C to 55°C
- Dew point ........................................................................ -25 °C
- Connections .................................................................... 1” G
- Supply voltage ................................................................ 230V – 50/60Hz
- Weight ............................................................................ 196 kg
The air dryer is composed of:
- Two desiccant element receivers DRY401 &DRY402
- Four solenoid valves FY471, FY472, FY473, FY474
- Two check valves NV421, NV422
- One restricted dry air line
- Two isolating valves HV401, HV402
- One bypass by isolating valve HV405
- One moist indicator MI491
- One cyclone pre-filter FLT401 to remove liquid particles. The efficiency is
99.5% for particles above 1Micron.
- Air flow capacity .............................................................. 300 Nm3/h
- Type ................................................................................ G11Z
- Maximum working pressure ............................................ 16 bar
- Maximum cartridge pressure drop .................................. 0.5 bar
- Working temperature ...................................................... 1.5°C to 55°C
- Connections .................................................................... 1”G
- Filtration .......................................................................... 1 μ
The pre filter is equipped with
- An automatic drain system composed of:
- A solenoid drain valve FY453 with Y filter FLT431
- An isolating valve HV403
- A by-passed valve HV404
- A local clogging indicator PDI451
- One micro oil filter FLT402 to remove oil particles. The efficiency is 99.5%
for particles above0.01Micron.
76
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
- Air flow capacity .............................................................. 300 Nm3/h
- Type ................................................................................ G11X
- Maximum working pressure ............................................ 16 bar
- Maximum cartridge pressure drop .................................. 0.5 bar
- Working temperature ...................................................... 1.5°C to 55°C
- Connections .................................................................... 1”G
- Filtration .......................................................................... 0.01 μ
The micro oil filter is equipped with
- An automatic drain system composed of:
- A solenoid drain valve FY463 with Y filter FLT441
- An isolating valve HV413
- A by-passed valve HV414
- A local clogging indicator PDI461
- One final filter FLT403 to remove dust particles of the desiccant. The
efficiency is 99.5% for particles above 1Micron.
- Air flow capacity .............................................................. 300 Nm3/h
- Type ................................................................................ G11Z
- Maximum working pressure ............................................ 16 bar
- Maximum cartridge pressure drop .................................. 0.5 bar
- Working temperature ...................................................... 1.5°C to 55°C
- Connections .................................................................... 1”G
- Filtration .......................................................................... 1 μ
The final filter is equipped with
- A manual drain valve HV433
- A local clogging indicator PDI481
4.23.7 Maintenance Schedule
PREVENTIVE MAINTENANCE SCHEDULEAIR COMPRESSED SYSTEM
SEQUENC
DESCRIPTIO PERIO
UNIT E ACTION
N D
NUMBER
Carry out a general visual
Air
GT1-GT check and watch out for
SAP compressed D
2-GT3 possible disturbances during
skid
operation
GT1-GT Air Check the ventilation system
SAP D
2-GT3 compressed and the temperature inside the
77
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
skid container which should be
between +5°C and +45°C
GT1-GT Screw Check and Top up if necessary
CMP301 D
2-GT3 compressor the compressor oil level
Check the loading and off
GT1-GT Screw
CMP301 D loading pressure on the
2-GT3 compressor
compressor pressure gauge
FY253,
Check function by manually
GT1-GT FY351 Solenoid
D operating the bypass
2-GT3 FY453, drain valve
condensate drain
FY463
Do an optical color test on the
blue gel indicator
GT1-GT Adsorption air
DRY401 D (Orange=-25°C / Pink=0°C /
2-GT3 dryer
Transparent
=+15°C)
Check the good ventilation of
GT1-GT Air cooler
CLR201 D the air cooler, reading
2-GT3 ARO203 HT
temperature indicator
GT1-GT Electrical
CAB001 W Check lamp using lamp test
2-GT3 cubicle
Check the differential
GT1-GT
FLT401 Pre filter W pressure of filter; it should not
2-GT3
exceed 0,5 bar.
Check the differential
GT1-GT
FLT402 Oil filter W pressure of filter; it should not
2-GT3
exceed 0.5 bar.
Check the differential
GT1-GT
FLT403 Final filter W pressure of filter; it should not
2-GT3
exceed 0.5 bar.
Check the back pressure at the
silencer placed behind the
4-port directional valve
GT1-GT Adsorption air combination; it should not
DRY401 W
2-GT3 dryer exceed 0.5 bar. Use
manometer of the vessel
which is to be
regenerated.
Check the internal condition
GT1-GT Screw
CMP301 W of compressor for eventual
2-GT3 compressor
leakages
FLT201,
GT1-GT FLT301
Y filter M Clean the screen
2-GT3 FLT431,
FLT441
78
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
FLT601
GT1-GT Screw
CMP301 M Check belts tension
2-GT3 compressor
GT1-GT Screw Check and clean if necessary
CMP301 M
2-GT3 compressor the intake air filter
GT1-GT Screw
CMP301 M Clean air/oil exchanger
2-GT3 compressor
GT1-GT Screw Change the air/oil separator
CMP301 6M
2-GT3 compressor cartridge
GT1-GT Screw
CMP301 6M Change the intake air filter
2-GT3 compressor
GT1-GT Screw
CMP301 6M Change oil filter cartridge
2-GT3 compressor
GT1-GT Screw
CMP301 6M Drain the compressor oil
2-GT3 compressor
GT1-GT compressed
SAP 6M Clean the unit
2-GT3 skid
GT1-GT Screw Check the flexibility of the
CMP301 Y
2-GT3 compressor hoses.
FY253
Completely disassemble the
FY351 Solenoid
GT1-GT drain and clean all
FY453 drain valve Y
2-GT3 components. Replace if
FY463
necessary
FY653
GT1-GT
FLT401 Pre filter Y Replace filter cartridge
2-GT3
GT1-GT
FLT402 Oil filter Y Replace filter cartridge
2-GT3
GT1-GT
FLT403 Final filter Y Replace filter cartridge
2-GT3
Check the desiccant for
impurities and change it if
necessary. A
brownish/yellowish tone
GT1-GT Adsorption air
DRY401 Y indicates that it has been
2-GT3 dryer
soiled with oil. The desiccant
has a normal lifetime of about
8000
operating hours.
Check the wedge wire screen
GT1-GT Adsorption air and the dust screen installed in
DRY401 Y
2-GT3 dryer the vessel for impurities and if
necessary, clean them.
GT1-GT Adsorption air Check the function of the
DRY401 Y
2-GT3 dryer 4-port directional valve
79
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
combination by sending
electrical control
signals.
Air
GT1-GT Change the air intake
SAP compressed Y
2-GT3 ventilation filter
skid
Check the correct operation of
GT1-GT Screw various protection device such
CMP301 2Y
2-GT3 compressor as safety valve, temperature
switch and thermal overload.
GT1-GT Screw Inspect the motor and
CMP301 2Y
2-GT3 compressor compressor bearings
GT1-GT Compressed Check the acceptable minimal
TK601 *
2-GT3 air tank residual thickness
GT1-GT Pressure Check the good functioning
PSV255 *
2-GT3 safety valve and test of maneuverability
GT1-GT Pressure Check the good functioning
PSV651 *
2-GT3 safety valve and test of maneuverability
Check the good
GT1-GT Pressure
PSV666 * functioning and test of
2-GT3 safety valve
maneuverability
MAINTENANCE PERIOD
D=Daily 6M=Every 6 months
W=Weekly Y=Yearly
M=Monthly 2Y=Every 2 years
*=as much as required by the regulation current in the country of exploitation
4.24Steam Injection System
Steam Injection System
Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection –
Hot Gas Path Inspection Major Inspection – X other period O : turbine Operating –
S : turbine Shut down
Device Check/inspect D W M Q S CI HGPI MI X
Check steam properties still in O
accordance with GEK
Steam
101944 and Control
specification
External visual check for steam O
Steam
or water leak, loose support,
system
damage insulation
� Check for leaks at the valve O
Flow sealing system (packing, gland,
control stem).
valve � Check for wear S
� Check the valve stroke S
80
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
according to control signal
� Check for leaks at the valve O
sealing system (packing, gland,
stem).
Stop � Check the good operation of
valve the valve according to
command signal S
� Proceed to valve seat leak
test to confirm valve operation S
� Check level of condensate
Pressure
pot, fill up with water if
transducer
necessary S
5 Generator
5.1Specification of Generator
ESTIMATED GENERATOR DATA
Generator Type: 9A5
Generator Number: 954X116-118
Station/Project: Nandipur 3x 9E Dongfang Offer
Customer: DONGFANG ELECTRIC CORP
GENERATOR RATING
150000 kVA 3000 RPM 15000 Volts 0.85 PF 0 psig 40 °C Gas 127500 kW 5774
Amps
375 Field Volts 698.817 Ft Alt 0.58 SCR 50 Hz 3 Phase WYE Connection
Exciter Rating
Type : Brushless
360 kW 375 Volts 960 D.CAmps Field Amps @ Generator rated Load 880
Total temperatures are guaranteed
Insulation Class Temperature Rise
not to exceed:
Stator coils: 122 °C by embedded
Armature F B
detector
Field coils 120 °C by Resistance Armature F B
Collector Gas Rise 20 °C by RTD
Cooling water Requirements @ Generator Rating
Generator Output: 150000kVA
Loss to Coolers: 1634KW
Inlet Water Temperature: 36°C
Outlet Cold Gas
40°C
Temperature
Coolant 100%WATER
Maximum Fouling Factor: 0.0005 1/(btu /
81
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
(hours*footsquared*F) )
700 GPM (total for all
Total Water Flow Required:
coolers)
Coolant temperature Max 60 °C
Head Loss Per Cooler: 14 Feet of Water
Maximum Operating 125 psig
Pressure: 8.6184 bar
Dielectric tests (Between coils and ground, 50/60 hertz AC for 1 min)
Stator 31000V
Rotor 3071V
Maintenance Frequency
There are a number of components, which require routine maintenance or
inspections between scheduled outages. The operator will find these
recommendations in various equipment sections, and should also include
additional maintenance tasks as operating experience indicates. Results of this
routine maintenance should be retained in well-organized files readily available
for reference. These routine maintenance records coupled with the information
from the monitored operating data are a good indicator of pending service or
operating problems that should be addressed at the next scheduled outage. The
monitored information alone is usually not sufficient for tracking or highlighting
trends.
During the first several months of operation, the stator winding support
system and some of the other generator components experience a break-in
period with more severe duty/wear than normal. Therefore, the first major
maintenance inspection is recommended for one year after it is placed in service.
For the purposes of the first major inspection, one year is defined as 8760
operating hours; or 300 starts. Regardless of the generator’s duty, the first
inspection should not be deferred beyond two (2) calendar years from COD. If
the unit’s operating experience has been unusual because of mis operation or
very limited in-service hours, etc. You may wish to discuss your particular
circumstances you’re your local GEField Service Office for recommendations
specific to your circumstances.
Subsequent planned outages must also be performed in a timely fashion.
Experience has shown that regularly scheduled maintenance outages are one of
the most important steps in retaining unit reliability and reducing major
repair/failure expenses. A minor maintenance outage is recommended every
30months. During these outages the end shields or end plates are removed to
permit inspection of the end winding area, but the field remains in place. A
82
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
major outage is recommended every 60 months. This includes removing the
field from the stator or using MAGIC (Miniature Air Gap Inspection Crawler) to
permit a thorough inspection of the core section of the stator and field. To
inspect the field and stator using MAGIC requires the removal of a few entrance
gap baffles to allow access to the air gap with the field in place. The inspection
must include a comprehensive series of electrical tests and a thorough visual
inspection. Each has their particular advantage and neither alone is sufficient.
See Section V for a brief description of the capabilities of MAGIC and MAGIC
Jr.
Older generators with asphalt insulated stator windings and core lengths
greater than 150 inches are subject to girth crack failures in the stator bars, and
therefore, these generators should be re inspected twice as often (Minor Outage
- 18 months; Major Outage - 36 months).
These recommended outage intervals have proven themselves over many
years of use. However, high equipment reliability and outage costs, have lead to
increasing interest in extending the time between major inspections. Condition
Based Maintenance (CBM) is one method in development to do this, and is the
focus of considerable attention in the industry. CBM relies on availability of
reliable on-line instrumentation and evaluation techniques. As these evaluation
methods become proven and practical, they will be incorporated into
recommended operation and maintenance packages such that maintenance
outages can be scheduled based on the condition of the unit.
Table 1 Recommended Stator Tests
STATOR
MA
Inspection AI HY LC Mino
Compon GIC/ Major
Test Objectives & R D SW r
ent RAC
Assessment
Checks for
RTD Gas &
calibration &
Element Winding X X X X X
poor
Res. RTD’s
connections.
RTD
Stator Insulation
Ground
Winding condition of X X X X X
Insulatio
RTD’s RTD.
n
Winding Checks for poor
Stator
Copper connections & X X X X X
Winding
Res. breaks.
Insulatio Contamination
n CE and/or
X X X X X
Resistan Bearing deterioration of
ce(aka insulation.
83
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
Megger) Contamination
Hydroge
and/or
n Seal X X X X
deterioration of
Casing
insulation.
Contamination
Polariza
Stator and/or
tion X X X X X
Winding deterioration of
Index
insulation.
Contamination
DC
Stator and/or
Leakage X X X X X
Winding deterioration of
Current
insulation.
Over Ground wall
Stator
Potentia insulation X X X X X
Winding
l/Hipot integrity
Wedge Detect wedge
Stator
Tightnes tightness X X X X X
Wedges
s Map deterioration
Magneti
c Scalar Stator
Weak or
Potentia Core
damaged core X X X X X
l Insulatio
enamel.
(EL n
CID)
Visual Core
Foreign Object
Inspecti Laminati X X X X X
Damage
ons ons
Migration,
Space
cooling passage X X X X X
Blocks
blockage
Gas Gap Cracked welds,
X X X X X
Baffles looseness
Evidence of
Stator
abrasion or X X X X X
Wedges
looseness
Evidence of
Stator
abrasion or X X X X X
Bars
looseness
Evidence of
End
relative motion,
Winding
dusting and/or
s and
greasing, X X X X X X
connecti
loose/broken
on
ties, loose
rings
hardware, corona
84
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
activity
Copper Overheating,
Flux hardware X X X X X
Shield looseness
Overall
Oil or other
cleanline X X X X X
contamination
ss
OPTIONAL TESTS
Partial Stator
Dischar Winding Localized
X X X R R
ge Insulatio deterioration
Analysis n
Water Water
Flow Cooled Restrictions in
X O
Verifica Stator hydraulic circuit
tion Winding
Stator
Core Weak or
Core
Ring damaged core X X X O
Insulatio
Test enamel
n
Dynami
Stator Potentially
c Freq.
End damaging X X X O
Respons
Winding resonance.
e
Slot
Bar Check slot
Support X X X O
Jacking clearance
System
Air – Air Cooled Generator HYD – Hydrogen Cooled Generator LCSW –
Hydrogen Cooled Generator with Liquid Cooled Winding
O - Optional Test X - Pertains only to type of unit selected R - These test are
performed while the unit is running.
Note: Gas cooled bars use the hydrogen column. During high voltage testing the
hollow conductors should be shorted to copper strand
5.3 Bearing
85
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
scraper to remove any material upset due to scratching.
E. Check the pivoting surfaces of the shoes and retainer for scratches,
scoring, or other evidence of wear. Polish with fine scotchbrite pad if necessary.
F. Check seal ring bore and faces for nicked edges, deep scratches, or scoring.
Polish with fine scotchbrite pad as necessary. Stone or lap the joint surfaces if
burrs or raised edges exist. Replace seal ring if the diametral clearance between
the journal and the ring bore exceeds 0.020″ at any point.
G. Check flexible hose element of the high pressure lift assembly for signs of
damage. If damage is found, replace entire high pressure lift assembly.
H. Tilting Pad Journal Bearing Clearance Check
Disassemble bearing and prepare parts for clearance check per disassembly
and maintenance instructions. Blue journal shoe pivot surface and check for
contact area and position.
Check for shaft or running clearance on 5 pad bearing as follows:
a. Turn or select a stub mandrel whose diameter is within 0.001 inch of
shaft size. One end of the mandrel must be square with the turned diameter.
Bolt mandrel to a heavy plate with a clean flat, preferable ground surface.
Clamp assembly to table or surface plate.
b. Assemble bearing around mandrel.
c. Tap bearing lightly in back of each shoe to insure that shoes are properly
seated in place.
d. Set dial indicator directly in back of a shoe and move bearing back and
forth in a direct line with the indicator and record reading. Several movements
should be made until the same indicator reading is repeated.
e. Repeat this procedure for each shoe. Set indicator to zero setting for
every new position. Be sure only bearing movement is recorded and not a
possible shift or mandrel or indicator stand.
5.4 Generator Coolers
Except for the rolled joints between the tubes and the tube sheets, all of the joints
on the coolant side of the cooler are outside the circulating hydrogen/air space. This
means that any normal servicing or repairs, such as plugging leaking tubes,
re-rolling tubes, tightening or replacing gaskets, and cleaning tubes can be done
without removing the cooler from the generator.
WARNING
SERVICING OR REPAIRING THE COOLER WHILE THE
GENERATOR IS OPERATING WITH HYDROGEN IN THE CASING IS
EXTREMELY HAZARDOUS AND SHOULD NOT BE ATTEMPTED.
If a hydrogen-cooled generator cooler section fails, the coolant flow to that
86
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
cooler section should be shutoff and the cooler drained. The generator should then
be operated at the levels specified for one section shut down per the original
design data sheet (for example 80% load) until such a time when it is practical to
purge the generator of hydrogen. Only after the generator is purged of hydrogen
should the cooler be repaired.
CAUTION
Eye bolts must be used when lifting the coolers.
A. Repair of Leaky Tube
If it is necessary to repair a leaky tube, the coolant flow to that cooler section
should be shut off and the cooler drained. When the generator has been purged of
hydrogen, if required, the water box covers on each end should be removed. The
faulty tube may be found by pressure testing each tube.
The tube can then be plugged by driving tapered phenolic plugs or equivalent
into both ends of the tube. A few ineffective tubes in each section should not
seriously jeopardize performance. It may be possible to operate satisfactorily with
as many as 10% of the tubes plugged if other conditions such as coolant
temperature and cleanliness of tubes are favorable, and if the plugged tubes are
not concentrated in a small area. The cooler should be replaced if the number of
plugged tubes is suspected to inhibit performance.
B. Cleaning the Tubes
Periodic cleaning improves the heat transfer efficiency of a hydrogen or
air-cooled generator cooler and increases cooler service life by removing deposits
and other obstructions that may cause corrosion. The frequency of cleaning will
depend on local conditions and specific customer maintenance programs.
If it should become necessary to clean the cooler sections while operating, the
coolers may be taken out of service one at a time for cleaning without completely
shutting down the unit. The maximum heat load that may be removed with one
cooler section out of service must be limited to the values given on the Generator
Performance Data drawing C902. For a hydrogen-cooled generator it is not
necessary to remove hydrogen from the machine to clean the cooler sections if the
hydrogen seals around the tube sheets are not broken.
CAUTION
Metal plugs, wire brushes, and similar tools that will disturb or scratch the metal
surface of the tubes are not recommended.
Cleaning cooler tubes with high-pressure water, or water and high-pressure air
is effective in many instances. Specially designed rubber plugs, fiber brushes, or
nylon brushes forced through the tubes with compressed air or high-pressure
water may be required for a more effective cleaning job. Power-driven rotating
brushes, with nylon bristles, have also been shown to be effective.
While the coolers are particularly suited for mechanical cleaning, there may be
a preference for chemical cleaning. There are hazards involved in selecting and
87
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
using the proper cleaning solution as well as ensuring the proper neutralizing and
flushing. Cleaning of this type should be done under the close supervision of
specialists in this type of work. Normally, the outside or plate surface should not
become dirty. If this happens and performance is affected, the cooler should be
removed and cleaned with a stream of water or low-pressure steam followed by
drying with an air blast. If there is an oily deposit, it may be necessary to remove it
by applying an air blast saturated with a solvent suitable for removing the film.
For reasons of safety, reference should be made to the separate instructions listed
in the Table of Contents of the Composite Book for proper choice of a solvent and
its use.
C. Inspection
The best time for the annual inspection and cleaning of the cooler is prior to the
warm season. The need for additional cleaning may be indicated by a gradual
increase in the generator temperatures not attributable to some other cause.
D. Correspondence
For identification purposes, all correspondence should reference the catalog
number, serial number and cooler manufacturer stamped on the cooler nameplate.
The generator and turbine number should also be included.
5.5 Shaft Grounding Brushes
5.6.1Periodic Maintenance
The exciter rotor, stator, and diode wheel should be cleaned with the same
regularity and in the same manner as the main generator. Make certain that the
rectifier diodes and heat sinks are kept free of dust, grease, and similar material (see
paragraph 3.1.1) because such coatings restrict dissipation of heat and cause low
egger readings. All electrical connections should be in good condition and be
tightly fastened. The corrosion resistant coating on the wheel should not be
damaged. Any connections removed and replaced should be coated with a good
quality, air- drying insulating varnish.
Diode Wheel Cleaning Procedure:
NOTE
Take insulation measurement before and after cleaning (see paragraph 3.3).
WARNING
Adequate diode wheel cleaning requires solvent use. Provide adequate
ventilation and avoid contact with skin. Use extreme caution with petroleum
solvents, as their fumes are highly flammable.
For best results, apply solvents under pressure using an aspirator or similar
device with a clean, dry, compressed air supply. Less efficient, but acceptable
means of applying solvent include self-contained (garden-type)sprayers, vacuum
cleaner with spray attachment, portable sprayers and so forth.
Initial cleaning should be done with a slow drying solvent having good oil and
dirt cutting properties. This should wash out most of the dirt, oil, and soot. Use
“Stoddard” solvent, mineral spirits, or alcohol. This should be followed by a quick
drying solvent such as Freon-TF which finish-cleans and leaves the wheel dry.
5.6.2Replacementof Diodes
89
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
To properly install diodes and minimize stress on the assembly, follow these
steps:
a. Install the diode modules on diode wheel per
Drawings 1002195 and 1002171.
b. Check to make sure the modules are seated against the wheel rim and that
the diode leads are not under strain.
5.6.3 Insulation Resistance
Initial checks
All electrical installations, however complex, must be meticulously checked
before being powered up. This check is of particular importance for installations
which may, when they have been powered up, be in an explosion risk zone. To be
totally effective, this check must be performed in the presence of a qualified
representative of the organization which has carried out the work and the user's
service manager or maintenance supervisor, and possibly a representative of the
firm which designed the installation. These checks result in the issuing of an
acceptance report. It is vitally important that this evaluation be carried out in a
rigorous and detailed way, as many important checking operations are possible
without any risk, as long as the installations are not powered up. They will no
longer be able to be carried out without extremely rigorous precautions, once the
plant is working, if the plant operates continuously.
Frequent monitoring
90
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
This monitoring, generally performed by the operation personnel, includes:
- preventive monitoring of the state of the equipment (cables, cable glands, etc.)
taking into account the environment (heat, humidity),
- detecting abnormalities which may be dangerous, as early as possible, such as
damage to a cable sheath caused by abrasion,
- providing regular effective personnel training on the risks involved and how to
minimize them.
Regulatory periodic checks
They can be performed by a technician (who may or may not work for the
company) with an in depth knowledge of the field of prevention of risks caused by
electricity and of the associated regulations. But usually to ensure objectivity and
because of a lack of resources (both personnel and equipment), the company will
use an approved checking body.
5.8 Low Voltage Motors88BT-1/2 Maintenance
General inspection
– Inspect the machine at regular intervals.
– Keep the machine clean and ensure free ventilation airflow.
– Check the condition of shaft seals (e.g. V-ring) and replace if necessary.
– Check the condition of connections and mounting and assembly bolts.
– Check the bearing condition by listening for unusual noise, vibration
measurement, bearing temperature, inspection of spent grease or SPM bearing
monitoring.
* When changes of condition occur, dismantle the machine, check the parts and
replace if necessary.
Machines with permanently greased bearings
Bearings are usually permanently greased bearings of either Z or 2Z types.
Bearing types are specified in the respective product catalogues and on the
rating plate of all our motors except smaller frame sizes.
As a guide, adequate lubrication for sizes up to 200 can be achieved for the
following duration, according to L1
(i.e. that 99 % of the motors are sure to make the interval time) at ambient
temperature of 25°C. For duties with ambient temperatures higher than 25°C,see
the respective product catalogue.
91
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
92
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
B. Automatic lubrication
The grease outlet plug must be removed permanently with automatic
lubrication or open closing valve if fitted. Some motors may be equipped with a
collector for old grease. Follow the special instructions given for the equipment.
We recommend only the use of electro mechanical systems. Contact your
local ABB Sales Office.
The amount of grease per each lubrication interval stated in the tables 4-5
should be doubled if an automatic regreasing system is used.
If 2-pole motors are being automatically regreased, the note (NOTE!)
concerning lubricant recommendations given for 2-pole motors in the chapter
Lubricants shall be followed.
Lubricants
When regreasing, use only special ball bearing grease with the following
properties:
– good quality grease with lithium complex soap and with mineral- or
PAO-oil
– base oil viscosity 100-160 cST at 40°C
– consistency NLGI grade 1.5 - 3 *)
– temperature range -30°C - +120°C, continuously.
*) For vertical mounted motors or in hot conditions a stiffer end of scale is
recommended.
Grease with the correct properties is available from all major lubricant
manufacturers.
Admixtures are recommended, but a written guarantee must be obtained from
the lubricant manufacturer specially concerning EP admixtures, that admixtures
do not damage bearings or the properties of lubricants at the operating
temperature range.
If the ambient temperature is below -25 ° C or above+55 ° C, or bearing
temperature is above 110°C, consult ABB Sales Office regarding suitable grease.
The following high performance grease can be used
– Esso Unirex N2, N3 or S2 (lithium complex base)
– Mobil Mobilith SHC 100 (lithium complex base)
–Shell Albida EMS 2 (lithium complex base)
– SKF LGHQ 3 (lithium complex base)
– Kluber Kluberplex BEM 41-132(special lithium base)
–FAG Arcanol TEMP110 (lithium complex base)Lubrication intervals for
other grease full-filling there quired properties, contact your local ABB Sales
93
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
Office.
The following grease can be used:
–FAG L69 (polyurea base)
–Kluber Kluber quiet BH 72-102 (polyurea base)
–Lubcon Turmogrease PU703 (polyurea base)
If other lubricants are used, check with the manufacturer that the qualities
correspond to those of the above mentioned lubricants, or if the compatibility of
the lubricant is uncertain, contact your local ABB Sales Office.
5.9 Exhaust Chamber Cooling Air Fan 88EF1/2
Depending on the use the ventilator is put to, maintenance work may be
curative, preventive or conditional.
It is the responsibility of the user, depending on operational requirements and
accessibility, to define maintenance policies.
The recommendations given below are for information only – for standard,
industrial use. The periods between maintenance may be adjusted to cope with the
precise conditions of use of the ventilator. Our Support Department can provide
further assistance in the choice of maintenance policies to be implemented.
Preventive maintenance:
Conditional maintenance
It is possible, by monitoring certain parameters, to delay having to carry out
certain motor bearing lubrication and replacement operations until the condition
of the components themselves actually justify their replacement.
We thus list, for information, certain possible monitoring methods and
thresholds to be applied to a ventilator being used for standard industrial use.
These measures may be modified with regard to the type of use and system
surrounding the ventilator.
Monitoring the temperature of the motor bearings:
The bearings can, on request, be fitted with a temperature sensor to provide
constant monitoring of their internal temperatures.
——If this internal temperature increased by more than 10°C in less than one
hour at a constant ambient temperature, the equipment must be shut down and
94
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
locked-out. Change the bearing in question.
——The internal temperature tends to increase slowly over time. When it rises
to a level of greater than 10°C higher than the temperature recorded for the
machine when new (after running-in), top up the lubricant. If, after restarting, the
temperature does not drop to a level close to that of a new machine, the bearings
should be replaced.
Monitoring motor bearing vibration speed:
The bearings can, on request, be fitted with accelerometers used to provide
continual monitoring of vibration levels.
——If the level of vibration suddenly varies through an amplitude of more
than 15% of the level recorded when new, shutdown the ventilator and check:
——The condition of the transmission belts,
——The condition of the drive shaft and motor bearings,
——The presence of balance weights on the turbine wheel.
Replace any damaged component.
——Due to wear on rotating components, the vibration levels will tend to rise
over time. When the level reaches that defined by ISO 14694 as an alarm
threshold, schedule a SERVICE 2 as soon as possible. The alarm thresholds are:
——7.1 mm/s for a rigid installation
——11.8 mm/s for flexible mountings
All work described below is based upon a securely locked-out ventilator with
its electrical connections disconnected to eliminate any risk to the personnel
involved.
The exhaust and inlet holes are presumed to be accessible.
Cleaning and Inspecting the Turbine Wheel – Access via an inspection
hatch fitted to the casing
——Remove the inspection hatch on the spiral casing.
——Clean the turbine, one blade at a time – turning it by hand. Never use
solvent cleaners this risks damaging the coating. Never spray liquid into the space
this will buildup in the base of the casing.
——Then carry out a visual inspection of each blade checking that there are
no cracks or splits.
——Check the appearance of the turbine disk and cone. Check that the
balance weights are present.
——Refit the inspection hatch.
95
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
Cleaning and inspecting the turbine wheel – access via the inlet casing
This operation concerns narrow ventilators where the width of the casing is
insufficient for an inspection hatch.
——Remove the inlet housing
——Carry out the cleaning and verification operations described in the above
paragraph.
——Refit and adjust the housing (See Para. ‘Adjusting the housing’)
96
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
5.10 Oil Mist Eliminator 88QV-1A
The totally enclosed and fan cooled three phase squirrel cage induction motors
require very little maintenance nevertheless it is recommended to check the
motor regularly in order to prevent a breakdown caused by dust, moisture,
vibrations, too much or too little greasing.
Dust:
The outer parts of the totally enclosed motors, especially the cooling ribs or
cooling channels, have to be kept as clean as possible in order not to obstruct the
cooling air from the fan extracting the heat from the motor frame.
Moisture:
Motors, which are not often run, should be started from time to time to
prevent moisture affecting the windings in the long time.
Wear &vibration
To prevent abnormal wear &vibration, one should:
_take care that the tension of the belt or the chain is not too high
_check whether the mounting of directly coupled machines is correct
_check whether the foundation bolts the bolts to fasten the motor and the
slide rails are tight.
Greasing
Before they leave the factory, the bearings of the DUTCHI Motors are filled
with a high quality Lithium base grease.
The sizes 56 up to and including 250 are provided with shielded/sealed
bearing (ZZ-C3), which have been filled with life-time grease by the
manufacture of the bearings.
Motor with sealed bearing and no re-lubrication system require no
maintenance other than checking for noise &temperature during their lifetime.
Sizes 280 up to and including 400, has been provided with a permanent
lubrication system containing a grease valve.
The lubrication must take place when the machine is running.
The old grease is ejected from the grease valve thus maintaining the correct
level and avoiding overfilling which would be harmful.
Bearing type and bearing inside diameter
97
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
98
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
4000 hours of exploitation or twice a year.
2nd degree of maintenance
The second degree consists to realize a complementary inspection of the
ignored points from the previous operations and to set the critical points reliable,
as noticed on the components status by repairing or exchanging parts. Objective
of an examination is to realize a complete revision, opening sub-ensembles of the
motor: cooling systems, bearings, junction boxes, stator and rotor status through
trap doors. This degree of maintenance imply the use of measure instruments for
electrical characteristics of the machine.
A spectral analyses of the motor could be realized to detect any anomalies of
the components:
- Wear detection of the rollers,
- Mechanical break,
- Unbalance, alignment
- Default of sealing or resonance
- Electrical defaults,
- Etc.
This allow to anticipate curative or palliative actions of maintenance.
They have to be controlled every 8000 hours of exploitation, means once a
year.
3rd degree of maintenance
The third degree consist to realize a complete inspection of the machine
components and important works of maintenance necessary to repair completely
consequences of defaults and failures reported.
If necessary, those operations can include the complete dismantling of major
parts as the rotor, using adapted tools. Those operations imply a specialized
knowledge, including corrective or preventive maintenance works done by
specialized teams, using general or particular instructions of maintenance. It is
imperative to previously determine spare parts needed for this operations, based
on the previous inspection and to reduce repairing time. Plan to realize this degree
of maintenance every 40 000 hours of exploitation, corresponding to 5 years of
exploitation.
99
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
100
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
101
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
102
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
company) with an in depth knowledge of the field of prevention of risks caused
by electricity and of the associated regulations. But usually to ensure objectivity
and because of a lack of resources (both personnel and equipment), the company
will use an approved checking body.
5.12.3 Bearing Check
The machine must be stored in a sheltered place well protected from moisture
(i.e. a warehouse).Actually, if the relative humidity degree rises above 90 %,
then the insulation level drops very rapidly to become almost non existent when
reaching 100 %.
5.12.5 Electrical checks
103
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
voltage during 12 hours with the rotor blocked (rotor short-circuited for slipring
motors),
- or supply it with D.C. voltage, the three phases being series connected (by a
D.C. generator with separate excitation or a storage battery for motors of less
than 30 HP) adjusted to about 1 to 2 %of the rated voltage.
The A.C. or D.C. current should not exceed:
- 40 % of the rated current for drip-proof motors,
- 60 % of the rated current for totally-enclosed motors.
It is advisable to check the current with a clip-on ammeter (A.C.) or with a
shunted ammeter (D.C.)and to put a thermometer on the frame: if the
temperature overcomes 70°C, reduce the above values of voltages or currents by
5 % for a 10°C shift.
5.12.6 Mechanical checks.
Obviously similar conditions arise, if the machine has not been running for a
long time, though remaining installed at its operational site.
So as to avoid the difficulties mentioned above, the use of heaters (space
heaters) is recommended, as well as periodical maintenance runs.
6 .Acoustic Enclosures Maintenance
6.1Gas Turbine Enclosure Maintenance Diagram
104
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
Component
Identification Maintenance
Designation Frequency Action Quantity
Component Sequence
(see note)
Code Number
1xxx 33DT Doors 6M Visual control of seals status 10m
1xxx Doors Hinges 6M Hinges lubrications
1xxx Panic bar M Manual good working checking N.A.
4xxx Frame Assy 6M Visual control of frame N.A.
2xxx Panels and Accessories 6M Visual control of panels N.A.
3xxx Panels and Accessories 6M Visual control of seals status 10m
3xxx Panels and Accessories 6M Visual control of seals status 10m
5xxx Roof panel 6M Visual control seals status 10m
3xxx Lighting (Spot) 3M Control status of lighting 1
3xxx Lighting (Spot) 3M Control status of lighting (bulb) 1
8xxx 88BT Duct blowing Outlet 3M Visual control of flexible sleeve 2
8xxx 88BT Duct blowing Outlet 3M Visual control of flexible sleeve 2
8xxx 88VG Duct blowing Inlet 3M Visual control of flexible sleeve 2
8xxx 88VG Duct blowing Inlet 3M Visual control of flexible sleeve 2
8xxx 88VG Duct blowing Outlet 3M Visual control of flexible sleeve 2
8xxx 88EF Duct blowing Inlet 3M Visual control of flexible sleeve 2
8xxx 88EF Duct blowing Outlet 3M Visual control of flexible sleeve 2
8xxx Duct blowing 3M Visual control of seal status 7m
8xxx 63VL 88VL inlet 3M Visual control of dumper 1
8xxx 88VG Inlet 3M Visual control of seal status 10m
8xxx 88BT Damper 3M Control status of Damper 2
8xxx 88VG Damper 3M Control status of Damper 2
8xxx 88VG Damper 3M Control status of Damper 1
8xxx 88EF Damper 3M Control status of Damper 2
105
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
Filter 1M Control status and cleanness filter 1
Filter 1M Control status and cleanness filter 1
Filter 1M Control status and cleanness filter 1
6.2WI Module Enclosure Maintenance Diagram
COMPONENT
maintenance
identification
DESIGNATION frequency ACTION Quantity
Component Sequence
(see note)
Code Number
1xxx Doors 6M Visual control of seals status 10m
3xxx Panels and Accessories 6M Visual control of seals status 10m
Visual control of
8xxx 88JS DAMPER 3M 2
dumper
8xxx 88JS MOTOR 3M Control of motor 1
Control of filter
8xxx FILTER 1M 1
(cleanness)
Control of electrical
8xxx 20JS SOLENOIDE 3M solenoid (cleanness, mechanical 2
adjustment…)
Control status of
8xxx 66JS DPSL 3M 1
pressure switch
6.3Genertor Acoustic Enclosure Maintenance Diagram
Component
Identification Maintenance
Designation Frequency Action Quantity
component Sequence
(see note)
Code Number
1xxx 33DT Doors 6M Visual control of seals status 10m
106
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
1xxx Doors Hinges 6M Hinges lubrications
1xxx Panic bar M Manual good working checking .A.
4xxx Frame Assy 6M Visual control of frame A.
2xxx Panels and Accessories 6M Visual control of panels A.
3xxx Panels and Accessories 6M Visual control of seals status 10m
3xxx Panels and Accessories 6M Visual control of seals status 10m
5xxx Roof panels 6M Visual control seals status 10m
8xxx 88GV Duct blowing Outlet 3M Visual control of flexible sleeve 2
8xxx 88GV Duct blowing Outlet 3M Visual control of flexible sleeve 2
8xxx Duct blowing 3M Visual control of seal status 7m
8xxx 88VG Inlet 3M Visual control of seal status 10m
8xxx 88GV Damper 3M Control status of Damper 2
6.4 Maintenance of PEECC
107
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
season for cleanliness. Clean when necessary.
2. Inspect blower motor and wheel for cleanliness and check lubrication
each cooling season. Clean when necessary.
3. Check that electrical connections are tight and check controls for
proper operation each cooling system
1M Inspect air filters each month. Clean or replace when necessary.
Includes visual and acoustic inspection of different parts of the center as
well as verification of their correct operations:
1. Open doors and rear covers of the equipment.
2. In case of contactors and circuit breaker with pottery blow chamber,
check there is no either verification or metallization.
3. If service operation allows, open the circuit breakers carry out
connection operation, trip relays and verify disconnecting contacts.
MOTOR CONTROL
1 4. Verify mechanism, contacts, micro switches or limit switches, and
CENTRE
check actions every certain no of operations.
5. Verify signaling lamps.
6. Check that terminal blocks and terminals have the suitable clamping
pressure and clamp them stronger if necessary.
7. Introduce with draw able modules.
8. Close doors and covers and restore the equipment to the primitive
connection status.
The whole installation shall be reviewed and cleaned once a year or
twice a year at latest. For that purpose a schedule that allows part of the
main busbar keep working could be followed with the corresponding
MOTOR CONTROL surveillance and safety standards. In this case cleaning intervals for the
1
CENTRE different equipment shall be controlled.
1. Disconnect busbars and ensure they will not be re-connected.
2. Open doors, rear and front covers and verify that is not powered.
Connect phases to the earth.
108
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
3. Screw-off rear and top covers.
4. Clean supports of the bus bars, etc.
5. Examine and tighten bolted joints.
6. Verify the status of the bus bar supports and flexible bridges.
7. Withdraw with draw able modules and clean them.
8. Control, clean and lubricate plug contacts.
9. Control socket contacts (spring pressure, contact surface) and clean
them.
10. Clean grounding contact of with draw able panel and also the
grounding flat bar of the panel.
11. Clean carefully the panel interior.
12. Verify the rubber or neoprene joints.
13. Clean the warning lamps and auxiliary contacts and verify them
(only when not powered).
14. Put all covers of the connections and re-assemble parts that were
removed.
GENERATOR
PROTECTION
1 Refer to Manual dedicated to this panel
AND EXCITATION
PANEL
GAS TURBINE
1 Refer to Manual dedicated to this panel
CONTROL PANEL
OPERATOR
1 Refer to Manual dedicated to this panel
INTERFACE PANEL
1 AUXILIARY PANEL Refer to Manual dedicated to this panel
FIRE FIGHTING
1 Refer to Manual dedicated to this panel
PANEL
109
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
110
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
country-specific standards.
As regards the required manual dexterity, the maintenance shall be carried
out correctly by qualified staff, using the appropriate equipment and tools.
Battery Chargers
ANY INTERVENTION SHALL BE CARRIED OUT BY QUALIFIED
STAFF HAVING BEEN
INFORMED OF THE SPECIFIC ELECTRICITY HAZARDS AND OF
THE PRECAUTIONS TO
BE TAKEN.
DANGEROUS VOLTAGES ARE AT ALL TIMES PRESENT AT THE
TERMINALS OF THE
BATTERY, THE CHARGER AND THE LOW-VOLTAGE PANEL.
NEVER PRESUME THAT A VOLTAGE IS PRESENT OR ABSENT :
ALWAYS CHECK BY MEANS OF A VOLTMETER.
Note :
The purpose of the maintenance is to prove that the assembly conforms to the
applicable rules and regulations at the time of manufacture or at the time of
modifications. Special attention shall be given to the monitoring and inspection
of the conditions and materials linked to the safety of the staff, energized
components and cleanliness.
For protective measures, reference shall, as a rule, be made to the
country-specific standards.
As regards the required manual dexterity, the maintenance shall be carried
out correctly by qualified staff, using the appropriate equipment and tools.
6.4.1.3 Preventive Maintenance Instructions
Motor Control Centre
The tightening torque of the connection screws varies according to their
respective diameters:
M5 screws: torque of 5.5 Nm to 6.5 Nm max.
M6 screws: torque of 8 Nm to 10 Nm max.
M8 screws: torque of 15 Nm to 17 Nm max.
Battery Chargers
Rectifier maintenance:
Dedust the complete rectifier once per year. Perform, at regular intervals, an
inspection comprising the following operations:
1 - Disconnect the mains input and the battery.
111
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
2 - Inspect the components and the cabling. Especially look for signs of
overheating and melting of insulating material. Check all connections. Check
that none of the wires is disconnected.
3 - Check that the ventilation is not obstructed.
4 - For rectifiers equipped with air inlet filters (on the door), check that the
filters are clean.
5 - Check the operation of the rectifier and the voltage levels.
Fan maintenance:
The three-phase equipment (TPR) of more than 100 A are equipped with a
fan.
1 - A thermo contact (optional) mounted on the heat sink of the power
converter activates the fan when a temperature of 64°C is exceeded. The fan has
a life cycle of approx. 5 years.
2 - It is recommended to replace the fan every three years. This operation
shall be carried out by specialized staff.
6.4.2 Corrective Maintenance Instructions
6.4.2.1General
Remote alarms in the control room are not sufficient for troubleshooting.
They allow locating the faulty equipment.
Local alarms provide more information about the kind of fault and allow
troubleshooting.
Before starting troubleshooting, it is required to check if the fault is not
caused by external equipment. The wiring and protection circuits must conform
to the original diagrams and setting specifications.
Before replacing a faulty component (in particular electronic one) it is
needed to check if the configuration and the settings of the new component are
correct.
The safety rules must be respected during troubleshooting: the system must
be stopped and the power switched off.
6.4.2.2 Fault processing
General:
Troubleshooting:
The purpose of the procedures is to provide a guide for locating the faulty
component by using the displayed messages as the procedure entry.
The paragraph deals with the faults which are caused by the equipment
discussed in the present document.
6.4.2.3 Troubleshooting procedures
112
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
Control/monitoring 125 VDC. Fault (30DC-1)
Fault description:
A 125 VDC distribution fault is detected in the low voltage distribution
panel.
Possible fault origin:
Faulty circuit controlled by one of the following circuit breakers.
Fault result:
Generation of a fault in the gas turbine control panel.
Troubleshooting:
When the system is stopped, check the following:
State of the circuit breakers and identify the breaker which detected the fault.
Circuit protected by the opened circuit breaker.
AC power supply faults (30AC-1, 30AC-2 and 30AC-3)
Faults description:
A 400, 230 or 230UPS VAC power supply fault is detected in the low
voltage distribution panel.
Possible faults origin:
Faulty 400, 230 or 230UPS VAC circuit.
Fault result:
Generation of a fault in the gas turbine control panel.
Troubleshooting:
When the system is stopped, check the following:
State of the circuit breakers and identify the breaker which detected the fault.
Circuit protected by the opened circuit breaker.
6.4.3 Storage Instructions
113
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
The electronic cards are packed separately using a thermo welded pocket and
dehydrating bags. The pocket is provided with hygrometry indicators.
The hygrometry indicators need to be checked regularly in order to guarantee
correct storage conditions.
Storage of spare parts
The spare parts must be stored in a dry location and kept away from heat,
dust and destructive chemical agents.
The spare parts must also be protected against possible mechanical damage.
Battery Chargers
Temperature:
Storage: -25°C to +70°C
Relative humidity:
Storage: 15% to 90% in original package
Low-voltage panel:
If the unpacked unit or a unit in an inappropriate package has remained in a
very humid environment, it is recommended to heat the room or to energize the
heating resistors, if present.
Unless otherwise agreed between the user and the manufacturer, the relevant
transport, storage and on-site assembly conditions shall be met.
Admissible temperatures between -25°C and +55°C and up to +40°C for
short periods not exceeding 24 hours.
114
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
115
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
D09000913-04A Rev.
LIST OF SPARE PARTS DURING START-UP OF THE INSTALLATION AIR COMPRESSED SYSTEM
A Date : 13/10/09
DESIGNATION SPARE PARTS Quantity
SYST ITEM Installed for
UNIT DESCRIPTION DESCRIPTION TYPE start-up
EM No.
GT1-GT2-GT3 SAP CMP301 Screw compressor RAFALE 37 kW Screw air end 7 103 004 (1) 1 0
Desiccat : molecular
GT1-GT2-GT3 SAP DRY401 Adsorption air dryer SAD255 7 213 000 (2) 50 kg 0 kg
sieve
port directional valve 63330002530
GT1-GT2-GT3 SAP DRY401 Adsorption air dryer SAD255 1 0
combination V1-V4 0 (2)
Check valve block 63331002530
GT1-GT2-GT3 SAP DRY401 Adsorption air dryer SAD255 1 0
V5-V6 0 (2)
GT1-GT2-GT3 SAP DRY401 Adsorption air dryer SAD255 Dew point indicator gel 7 770 025 (2) 1 0
79903000250
GT1-GT2-GT3 SAP DRY401 Adsorption air dryer SAD255 Silencer 1 0
1 (2)
GT1-GT2-GT3 SAP DRY401 Adsorption air dryer SAD255 Solenoid valve 7 314 011 (2) 4 0
FLT401 Pre fiter / Final filter
GT1-GT2-GT3 SAP Pre filter / Final filter G11Z 7 214 405 (3) 2 0
FLT403 cartridge
GT1-GT2-GT3 SAP FLT402 Oil filter G11X Oil filter cartridge 7 214 205 (4) 1 0
D09000913-04B Rev.
LIST OF SPARE PARTS FOR 2 YEARS OF EXPLOITATION AIR COMPRESSED SYSTEM
A Date 13/10/09
DESIGNATION SPARE PARTS Quantity
Installed for 2
SYSTE ITEM
UNIT DESCRIPTION DESCRIPTION TYPE years
M No.
GT1-GT2-
SAP CMP301 Screw compressor RAFALE 37 kW Oil filter cartridge 7 216 101 (1) 1 1
GT3
GT1-GT2- Primary air intake filter
SAP CMP 301 Screw compressor RAFALE 37 kW 7 210 032 (1) 1 1
GT3 cartridge
GT1-GT2- Security air intake filter
SAP CMP 301 Screw compressor RAFALE 37 kW 7 210 035 (1) 1 1
GT3 cartridge
116
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
D09000913-04B Rev.
LIST OF SPARE PARTS FOR 2 YEARS OF EXPLOITATION AIR COMPRESSED SYSTEM
A Date 13/10/09
DESIGNATION SPARE PARTS Quantity
Installed for 2
SYSTE ITEM
UNIT DESCRIPTION DESCRIPTION TYPE years
M No.
GT1-GT2-
SAP CMP301 Screw compressor RAFALE 37 kW Separator cartridge 7 211 003 (1) 1 1
GT3
GT1-GT2- Separator cartridge
SAP CMP301 Screw compressor RAFALE 37 kW 7 501 030 (1) 1 1
GT3 O-ring
GT1-GT2-
SAP CMP301 Screw compressor RAFALE 37 kW Belts XPA 1180 7 081 056 (1) 5 5
GT3
GT1-GT2-
SAP CMP301 Screw compressor RAFALE 37 kW Oil P46 (can 25l) 7 550 040 (1) 30 l 30 L
GT3
GT1-GT2-
SAP CMP301 Screw compressor RAFALE 37 kW Regulation valve 7 375 067 (1) 1 0
GT3
GT1-GT2-
SAP CMP301 Screw compressor RAFALE 37 kW Oil return hose 7 355 032 (1) 1 1
GT3
GT1-GT2- Air/oil outlet screw air
SAP CMP301 Screw compressor RAFALE 37 kW 7 357 039 (1) 1 1
GT3 end hose
GT1-GT2- Air outlet separator /
SAP CMP301 Screw compressor RAFALE 37 kW 7 357 038 (1) 1 1
GT3 exchanger
GT1-GT2-
SAP CMP301 Screw compressor RAFALE 37 kW Pressure safety valve 7 720 051 (1) 1 0
GT3
GT1-GT2-
SAP CMP301 Screw compressor RAFALE 37 kW Thermostatic valve 7 230 009 (1) 1 0
GT3
GT1-GT2-
SAP CMP301 Screw compressor RAFALE 37 kW Pressure switch 7 700 019 (1) 1 0
GT3
GT1-GT2-
SAP CMP301 Screw compressor RAFALE 37 kW Pressure gauge 7 741 310 (1) 2 0
GT3
GT1-GT2- Regulation solenoid
SAP CMP301 Screw compressor RAFALE 37 kW 7 375 067 (1) 1 0
GT3 valve
GT1-GT2-
SAP CMP301 Screw compressor RAFALE 37 kW Oil thermostat 7 710 007 (1) 1 0
GT3
117
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
D09000913-04B Rev.
LIST OF SPARE PARTS FOR 2 YEARS OF EXPLOITATION AIR COMPRESSED SYSTEM
A Date 13/10/09
DESIGNATION SPARE PARTS Quantity
Installed for 2
SYSTE ITEM
UNIT DESCRIPTION DESCRIPTION TYPE years
M No.
GT1-GT2-
SAP CMP301 Screw compressor RAFALE 37 kW Oil drain valve 7 370 009 (1) 1 0
GT3
GT1-GT2-
SAP CMP301 Screw compressor RAFALE 37 kW Oil drain plug + gasket 7 603 032 (1) 1 0
GT3
GT1-GT2-
SAP CMP301 Screw compressor RAFALE 37 kW Screw air end 7 103 004 (1) 1 0
GT3
GT1-GT2- Desicca : molecular
SAP DRY401 Adsorption air dryer SAD255 7 213 000 (2) 50 kg 50 kg
GT3 sieve
GT1-GT2- 4-port directional valve 63330002530
SAP DRY401 Adsorption air dryer SAD255 1 0
GT3 combination V1-V4 0 (2)
GT1-GT2- Check valve block 63331002530
SAP DRY401 Adsorption air dryer SAD255 1 0
GT3 V5-V6 0 (2)
GT1-GT2-
SAP DRY401 Adsorption air dryer SAD255 Dew point indicator gel 7 770 025 (2) 1 0
GT3
GT1-GT2- 79903000250
SAP DRY401 Adsorption air dryer SAD255 Silencer 1 0
GT3 1 (2)
GT1-GT2-
SAP DRY401 Adsorption air dryer SAD255 Solenoid valve 7 314 011 (2) 4 0
GT3
GT1-GT2- FLT401 / Pre fiter / Final filter
SAP Pre filter / Final filter G11Z 7 214 405 (3) 2 2
GT3 FLT403 cartridge
GT1-GT2-
SAP FLT402 Oil filter G11X Oil filter cartridge 7 214 205 (4) 1 1
GT3
D09000913-04C Rev.
LIST OF SPARE PARTS FOR 5 YEARS OF EXPLOITATION AIR COMPRESSED SYSTEM
A Date 13/10/09
DESIGNATION SPARE PARTS Quantity
SYSTE ITEM Installed for 5
UNIT DESCRIPTION DESCRIPTION TYPE years
M No.
118
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
D09000913-04C Rev.
LIST OF SPARE PARTS FOR 5 YEARS OF EXPLOITATION AIR COMPRESSED SYSTEM
A Date 13/10/09
DESIGNATION SPARE PARTS Quantity
SYSTE ITEM Installed for 5
UNIT DESCRIPTION DESCRIPTION TYPE years
M No.
GT1-GT2-
SAP CMP301 Screw compressor RAFALE 37 kW Oil filter cartridge 7 216 101 (1) 1 2
GT3
GT1-GT2- Primary air intake filter
SAP CMP 301 Screw compressor RAFALE 37 kW 7 210 032 (1) 1 1
GT3 cartridge
GT1-GT2- Security air intake filter
SAP CMP 301 Screw compressor RAFALE 37 kW 7 210 035 (1) 1 2
GT3 cartridge
GT1-GT2-
SAP CMP301 Screw compressor RAFALE 37 kW Separator cartridge 7 211 003 (1) 1 2
GT3
GT1-GT2- Separator cartridge
SAP CMP301 Screw compressor RAFALE 37 kW 7 501 030 (1) 1 2
GT3 O-ring
GT1-GT2-
SAP CMP301 Screw compressor RAFALE 37 kW Belts XPA 1180 7 081 056 (1) 5 10
GT3
GT1-GT2-
SAP CMP301 Screw compressor RAFALE 37 kW Oil P46 (can 25l) 7 550 040 (1) 30 l 60 L
GT3
GT1-GT2-
SAP CMP301 Screw compressor RAFALE 37 kW Regulation valve 7 375 067 (1) 1 0
GT3
GT1-GT2-
SAP CMP301 Screw compressor RAFALE 37 kW Oil return hose 7 355 032 (1) 1 2
GT3
GT1-GT2- Air/oil outlet screw air
SAP CMP301 Screw compressor RAFALE 37 kW 7 357 039 (1) 1 2
GT3 end hose
GT1-GT2- Air outlet separator /
SAP CMP301 Screw compressor RAFALE 37 kW 7 357 038 (1) 1 2
GT3 exchanger
GT1-GT2-
SAP CMP301 Screw compressor RAFALE 37 kW Pressure safety valve 7 720 051 (1) 1 1
GT3
GT1-GT2-
SAP CMP301 Screw compressor RAFALE 37 kW Thermostatic valve 7 230 009 (1) 1 0
GT3
GT1-GT2-
SAP CMP301 Screw compressor RAFALE 37 kW Pressure switch 7 700 019 (1) 1 0
GT3
GT1-GT2- SAP CMP301 Screw compressor RAFALE 37 kW Pressure gauge 7 741 310 (1) 2 0
119
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
D09000913-04C Rev.
LIST OF SPARE PARTS FOR 5 YEARS OF EXPLOITATION AIR COMPRESSED SYSTEM
A Date 13/10/09
DESIGNATION SPARE PARTS Quantity
SYSTE ITEM Installed for 5
UNIT DESCRIPTION DESCRIPTION TYPE years
M No.
GT3
GT1-GT2- Regulation solenoid
SAP CMP301 Screw compressor RAFALE 37 kW 7 375 067 (1) 1 1
GT3 valve
GT1-GT2-
SAP CMP301 Screw compressor RAFALE 37 kW Oil thermostat 7 710 007 (1) 1 0
GT3
GT1-GT2-
SAP CMP301 Screw compressor RAFALE 37 kW Oil drain valve 7 370 009 (1) 1 0
GT3
GT1-GT2-
SAP CMP301 Screw compressor RAFALE 37 kW Oil drain plug + gasket 7 603 032 (1) 1 0
GT3
GT1-GT2-
SAP CMP301 Screw compressor RAFALE 37 kW Screw air end 7 103 004 (1) 1 0
GT3
GT1-GT2- Desiccate: molecular
SAP DRY401 Adsorption air dryer SAD255 7 213 000 (2) 50 kg 80 kg
GT3 sieve
GT1-GT2- 4-port directional valve 63330002530
SAP DRY401 Adsorption air dryer SAD255 1 0
GT3 combination V1-V4 0 (2)
GT1-GT2- Check valve block 63331002530
SAP DRY401 Adsorption air dryer SAD255 1 0
GT3 V5-V6 0 (2)
GT1-GT2-
SAP DRY401 Adsorption air dryer SAD255 Dew point indicator gel 7 770 025 (2) 1 0
GT3
GT1-GT2- 79903000250
SAP DRY401 Adsorption air dryer SAD255 Silencer 1 1
GT3 1 (2)
GT1-GT2-
SAP DRY401 Adsorption air dryer SAD255 Solenoid valve 7 314 011 (2) 4 0
GT3
GT1-GT2- FLT401 / Profited / Final filter
SAP Pre filter / Final filter G11Z 7 214 405 (3) 2 4
GT3 FLT403 cartridge
GT1-GT2-
SAP FLT402 Oil filter G11X Oil filter cartridge 7 214 205 (4) 1 2
GT3
120
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
121
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
Appendix – 2- SPARE PARTS OF MCC
START-UP SPARE PARTS MCC
No. Catalogue Code Manufacturer Description Quantity
1 F5.1A CABUR FUSE 5X20,250V,IF=1A 3
2 F5.2A CABUR FUSE 5X20,250V,IF=2A 6
3 F5.4A CABUR FUSE 5X20,250V,IF=4A 3
4 F5.6,3A CABUR FUSE 5X20,250V,IF=6,3A 3
5 17419 FERRAZ FUSIBLE 14X51,4A,GI-GG 3
6 17933 FERRAZ FUSIBLE 14X51,12A, AM 3
7 18951 FERRAZ FUSIBLE 22X58,50A,AM 3
8 18955 FERRAZ FUSIBLE 22X58,63A,AM 6
9 18959 FERRAZ FUSIBLE 22X58,80A,AM 3
10 18965 FERRAZ FUSIBLE 22X58,125A,AM 6
11 1591250 ITALWEBER FUSIBLE NH1 250A/AM WITH STRIKER 3
12 DCB CABLE LUG 6mm2 d=10mm 20
13 DCB CABLE LUG 10mm2 d=10mm 20
14 DCB CABLE LUG 16mm2 d=10mm 20
15 DCB CABLE LUG 25mm2 d=10mm 10
16 DCB CABLE LUG 35mm2 d=10mm 10
17 DCB CABLE LUG 50mm2 d=10mm 10
18 DCB CABLE LUG 95mm2 d=10mm 10
19 DCB CABLE LUG 120mm2 d=10mm 10
20 DCB CABLE LUG 185mm2 d=10mm 5
21 2009-1040S CUBIC M10x40 screw, class 8,8 150
22 2018-1000 CUBIC Disc washer M10 150
23 0070-0000 CUBIC SPACER 150
24 0062-0000 CUBIC SPECIAL NUT 150
25 31900 DCB HEAT SHRINK TUBING 1" 6m
122
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
2 YEARS MCC SPARE PARTS LIST
No. Catalogue Code Manufacturer Description Qty
1 1SDA 038291 R1 ABB SHUNT OPENING RELEASE 120-127VAC/DC 0
2 1SDA 038301 R1 ABB SHUNT CLOSING RELEASE 120-127VAC/DC 0
3 1SDA 038323 R1 ABB MOTOR OPERATOR 100-130VAC/DC 0
4 1SDA 038329 R1 ABB INTERLOCK CABLES FOR FIXED PARTS OF 2 CB'S 0
5 1SDA 038351 R1 ABB PADLOCKS FOR EMAX 0
6 1SDA 038361 R1 ABB 5 AUX. CONTACTS SIGNAL RACKED-IN/TEST/RACKED-OUT 0
7 1SDA 038364 R1 ABB INTERLOCK FOR FIXED PART WITHDRAWABLE CB 0
8 1SDA 038366 R1 ABB INTERLOCK FOR MOVING PART OF WITHDRAWABLE CB 0
9 1SDA 055781 R1 ABB 3P BREAKER EMAX W-MP E1N 1600A; 50KA; PR122P-LSIG 0
10 1SDA 058260 R1 ABB ELECTRICAL SIGNALLING OF OVERCURRENT RELEASES TRIP 0
11 1SDA 058267 R1 ABB 10 AUX. CONTACTS SIGNAL CB OPEN/CLOSED 5NO 0
12 1SDA 058278 R1 ABB LOCK IN RACKED-IN/TEST/RACKED-OUT POSITION 0
13 1SDA 059672 R1 ABB 3 POLES FIXED PARTS VR FOR EMAX SIZE E1 0
14 1SFA616921R2141 ABB INTEGRATED LED 130VAC/DC RED 10
15 1SFA616921R2142 ABB INTEGRATED LED 130VAC/DC GREEN 10
16 1SFA616921R2143 ABB INTEGRATED LED 130VAC/DC YELLOW 10
17 1SFA616921R2144 ABB INTEGRATED LED 130VAC/DC BLUE 1
18 FPL7449115R0005 ABB NORE125-01G;1NC;125A;125VDC 1
19 FPL7519115R0005 ABB I〇RE170-10G;1N〇;170A;125VDC 1
20 FPTN410013R0001 ABB AUXILIARY CONTACTS CA12-11 1
21 FPTN410056R0001 ABB SUPPORT 巳 RACKET FOR CA12 1
22 HB0200 ABB AC/DC CURRENT TRANSDUCER 200A,15V DC 1
23 08-50-0013 ABB MOLEX CRIMP TERMINAL - 2759 1
24 22-01-1042 ABB MOLEX CRIMP TERMINAL HOUSING - 5051-N 1
25 ACB.120/BB CABUR Terminal block 120mmp,I=269A 1
26 ACB.185/BB CABUR Terminal block 185mmp,I=353A 1
27 BTU CABUR End bracket BTU 39
123
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
28 CB16/PT CABUR End section 2
124
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
5 YEARS MCC SPARE PARTS LIST
No. Catalogue Code Manufacturer Description Quantity
29 CB2/PT CABUR End section 12
30 CB4/6/PT CABUR End section 2
31 CBD.16 CABUR Terminal block 16mmp,In=76A 18
32 CBD.2 CABUR Terminal block 2,5mmp,In=24A 210
33 CBD.35 CABUR Terminal block 35mmp,In=125A 2
34 CBD.6 CABUR Terminal block 6mmp,In=41A 66
35 CPM/21 CABUR Screws and sleeve 2
36 CPM/83 CABUR Screws and sleeve 4
37 CSC/00 CABUR Marking tags "0" 4
38 CSC/09 CABUR Marking tags from 0 up to 9 92
39 CSC/11 CABUR Marking tags "1" 30
40 CSC/22 CABUR Marking tags "2" 24
41 CSC/33 CABUR Marking tags "3" 8
42 CSC/44 CABUR Marking tags "4" 4
43 CSC/55 CABUR Marking tags "5" 4
44 CSC/66 CABUR Marking tags "6" 4
45 CSC/77 CABUR Marking tags "7" 4
46 CSC/88 CABUR Marking tags "8" 4
47 CSC/99 CABUR Marking tags "9" 4
48 DFM/600 CABUR Partition for CBD.2 34
49 F5.1A CABUR FUSE 5X20,250V,IF=1A 2
50 F5.2A CABUR FUSE 5X20,250V,IF=2A 6
51 F5.4A CABUR FUSE 5X20,250V,IF=4A 2
52 F5.6,3A CABUR FUSE 5X20,250V,IF=6,3A 2
53 GPM.240/B B CABUR Terminal block 240mmp,I=415A 2
54 PM/20/2 CABUR 2P cross-connections for CBD.2 6
55 PM/20/3 CABUR 3P cross-connections for CBD.2 2
56 PM/20/5 CABUR 5P cross-connections for CBD.2 6
57 PMP/01 CABUR Multiple communing bar 2
58 PMP/13 CABUR Multiple communing bar 4
59 PRT/P CABUR TERMINAL BLOCK COVER 2
60 SFR.4 CABUR TERMINAL BLOCK WITH FUSE 8
125
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
5 YEARS MCC SPARE PARTS LIST
No. Catalogue Code Manufacturer Description Quantity
61 SFR.4/D3A CABUR DIODE-HOLDER BY255/3A, 1300V 2
62 SFR/PT CABUR END SECTION 10
63 SPS/1 CABUR COVER SUPPORT 2
64 SPS/3 CABUR COVER SUPPORT 2
65 TE.4/0 CABUR Earth Terminal block 4mmp 2
66 TIM CABUR TIM MARKING PLATE 14
67 XCSF3 CABUR POWER SUPPLIES CSF3/90-264;24VDC;3A 2
68 FRS2 CARLO GAVAZZI FRONT MOUNTING BEZEL 2
69 MI 100 CARLO GAVAZZI CURRENT METERING TRANSFORMER 10-100AAC 2
70 S 411 CARLO GAVAZZI 11-PINS SOCKET 2
71 SM 115 230 CARLO GAVAZZI 1-PHASE AC CURRENT CONTROL 0,5-500AAC,230VAC 2
72 RMPU3000 ENERDIS 3 PHASE UNDER VOLTAGE RELAY 500V,45-65HZ 2
73 0115168.23 ENTRELEC TERMINAL BLOCK WITH 1N4007 2
74 17419 FERRAZ FUS LE 14X51,4A,GI-GG 6
75 17933 FERRAZ FUS LE 14X51,12A,AM 6
76 18951 FERRAZ FUS LE 22X58,50A,AM 6
77 18955 FERRAZ FUS LE 22X58,63A,AM 12
78 18959 FERRAZ FUS LE 22X58,80A,AM 6
79 18965 FERRAZ FUS LE 22X58,125A,AM 6
80 D211580 FERRAZ FUSED DISCONNECTOR CMS14/MICR〇“,3P,50A 2
81 Q222470 FERRAZ FUSED DISCONNECTOR CMS22/MICRO,3P,125A 4
82 T215665 FERRAZ FUSED DISCONNECTOR CMS14/MICRO,3P,50A 2
83 1F72-EV-600 FRER VOLTMETER EQ72;0-600V,50HZ;DIRECT 2
84 430088 G.E. FA1BR1 RONIS KEYLOCK 1104B 2
85 430818 G.E. FABAT10 BELL ALARM CONTACT BLOCK NO 2
86 430837 G.E. FAS10R AUX CONTACT NO RIGHT MOUNTED 2
87 430879 G.E. PADLOCKING REMOVABLE FD1PR 2
88 431751 G.E. 3P CIRCUIT BREAKER 80A FEN36TA080JF 2
89 432979 G.E. 3P CIRCUIT BREAKER 200A FEN36TD200KF 2
90 432982 G.E. 3P CIRCUIT BREAKER 250A FEN36TD250KF 2
91 435073 G.E. 3P MAG-BREAKER 7A FEN36MC007JF 2
92 435085 G.E. 3P MAG-BREAKER 50A FEN36MC050JF 2
126
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
5 YEARS MCC SPARE PARTS LIST
No. Catalogue Code Manufacturer Description Quantity
93 435088 G.E. 3P MAG-BREAKER 100A FEN36MC100JF 2
94 435094 G.E. 3P MAG-BREAKER 160A FEN36MC160JF 50KA 2
95 436495 G.E. FENRF/5 ROTARY HANDLE DIRECT ON DEVICE 2
96 607500 G.E. 2P RESIDUAL CURRENT DEVICE 32A/0,03A-D〇CA232/030 2
97 607502 G.E. 2P RESIDUAL CURRENT DEVICE 32A/0,3A-D〇CA232/300 2
98 624929 G.E. PADLOCKING RACKET KS 18
99 672568 G.E. CHANGEABLE AUX./SIGNAL CONTACT CA S/H 18
100 673322 G.E. 2P CIRCUIT BREAKER ;6A/C;10KA-EP102UCC06 2
101 673324 G.E. 2P CIRCUIT BREAKER ;10A/C;10KA-EP102UCC10 2
102 673326 G.E. 2P CIRCUIT BREAKER ;16A/C;10KA-EP102UCC16 4
103 673328 G.E. 2P CIRCUIT BREAKER ;25A/C;10KA-EP102UCC25 2
104 674888 G.E. 2P CIRCUIT BREAKER G100;2A/C;10KA-G102C02 2
105 674890 G.E. 2P CIRCUIT BREAKER G100;4A/C;10KA-G102C04 2
106 674891 G.E. 2P CIRCUIT BREAKER G100;6A/C;10KA-G102C06 12
107 674893 G.E. 2P CIRCUIT BREAKER G100;10A/C;10KA-G102C10 2
108 674895 G.E. 2P CIRCUIT BREAKER G100;16A/C;10KA-G102C16 2
109 674896 G.E. 2P CIRCUIT BREAKER G100;20A/C;10KA-G102C20 2
110 674897 G.E. 2P CIRCUIT BREAKER G100;25A/C;10KA-G102C25 2
111 675029 G.E. 1P CIRCUIT BREAKER G100;40A/D;10KA-G101D40 2
112 675059 G.E. 2P CIRCUIT BREAKER G100;25A/D;10KA-G102D25 2
113 675060 G.E. 2P CIRCUIT BREAKER G100;32A/D;10KA-G102D32 2
114 675093 G.E. 4P CIRCUIT BREAKER G100;40A/D;10KA-G104D40 2
115 675094 G.E. 4P CIRCUIT BREAKER G100;50A/D;10KA-G104D50 2
116 730055 G.E. DISCONNECTOR LOADBREAK SWITCH 3P-63A DILOS 1 2
117 730061 G.E. DISCONNECTOR LOADBREAK SWITCH 3P-80A DILOS 1 2
118 730067 G.E. DISCONNECTOR LOADBREAK SWITCH 3P-100A DILOS 1 2
119 730096 G.E. DISCONNECTOR LOADBREAK SWITCH 3P-200A DILOS 2 2
120 730252 G.E. AUXILIARY CONTACTS FOR DILOS 1,2,3 4
121 730255 G.E. HANDLE WITH EXTENSION SHAFT FOR DILOS 4
122 730263 G.E. TERMINAL COVERS FOR DILOS 2 2
123 731024 G.E. SET 2 TERMINAL COVERS FOR DILOS 1 4
124 BCLF01 G.E. INST. AUXILIARY CONTACT BLOCK 6
127
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
5 YEARS MCC SPARE PARTS LIST
No. Catalogue Code Manufacturer Description Quantity
125 BCLF10 G.E. INST. AUXILIARY CONTACT BLOCK 4
126 BELA G.E. MECHANICAL INTERLOCK FOR CL45 2
127 BRLL11 G.E. INST. AUXILIARY CONTACT BLOCK 12
128 BSLDZ G.E. VOLTAGE SUPPRESSOR BLOCK (DIODE) 2
129 BSLR2R G.E. TRANSIENT VOLTAGE SUPPRESSOR BLOCK 130-240VAC 6
130 BSLR3R G.E. TRANSIENT VOLTAGE SUPPRESSOR BLOCK 130-240VAC 2
131 CK08CA311N G.E. 3P CONTACTOR Uc=220/230V;50Hz 2
132 CL00A301TN G.E. 3 POLE CONTACTOR 220/230V50Hz 2
133 CL01AB00TN G.E. 4P CONTACTOR 2NO-2NC;230VAC 2
134 CL02D400TK G.E. 4 POLE CONTACTOR 120-125VDC 2
135 CL06A300MN G.E. 3 POLE CONTACTOR 220/230V50Hz 2
136 CL08A300MN G.E. 3 POLE CONTACTOR 220/230V50Hz 2
137 CL09A300MN G.E. 3P CONTACTOR Uc=220/230;50Hz 2
138 CL25A300TN G.E. 3 POLE CONTACTOR 220-230V50Hz 2
139 CL45A300MN G.E. 3 POLE CONTACTOR 220/230V50Hz 4
140 GPAC10FBA G.E. AUXILIARY CONTACT BLOCK 1NO 6
141 GPAL01FRA G.E. ALARM CONTACT BLOCK 1NC 4
142 GPS1BHAD G.E. 3P CIRCUIT BREAKER 0,4-0,63A 2
143 GPS1BHAE G.E. 3P CIRCUIT BREAKER 0,63-1A 2
144 GPS1BHAF G.E. 3P CIRCUIT BREAKER 1-1,6A 2
145 GPS1BHAH G.E. 3P CIRCUIT BREAKER 2,5-4A 2
146 GPS1BHAJ G.E. 3P CIRCUIT BREAKER 4-6,3A 2
147 GPS1BHAK G.E. 3P CIRCUIT BREAKER 6,3-10A 2
148 GPS1BHAM G.E. 3P CIRCUIT BREAKER 11-16A 2
149 GPS1BHAN G.E. 3P CIRCUIT BREAKER 14-20A 2
150 GPS1BHAR G.E. 3P CIRCUIT BREAKER 24-32A 2
151 GPS1MHAM G.E. 3P MAG-BREAKER 16A 2
152 GPS2BHAS G.E. 3P CIRCUIT BREAKER 28-40A 2
153 GPS2BHAT G.E. 3P CIRCUIT BREAKER 35-50A 2
154 MARN440AT G.E. AUXILIARY CONTACTS BLOCK 4NO 2
155 MCRA022ATN. G.E. MINICONTACTOR 220-240V5〇Hz;22 8
156 MCRC022ATL G.E. MINICONTACTOR 2-2;Uc=125VDC 2
128
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
5 YEARS MCC SPARE PARTS LIST
No. Catalogue Code Manufacturer Description Quantity
157 MCRC031ATL G.E. MINICONTACTOR 3-1 ; Uc=125VDC 2
158 MCRC040ATL G.E. MINICONTACTOR 4-0;Uc=125VDC 2
159 MPOAAE2 G.E. VOLTAGE SUPPRESSOR BLOCK 72-250V;50/60HZ 8
160 MPOCAE3 G.E. VOLTAGE SUPPRESSOR BLOCK 250VDC(DI〇DE) 4
161 NMRDV-6 G.E. DELAYED OFF TIMER24-240VAC/DC 2
162 NMTCV G.E. Delayed ON timer 24-240VAC/DC 2
163 P9ARTWS G.E. INSERT HOLDER 28
164 P9B11VN G.E. CONTACT BLOCKS NC 6
165 P9XPNNG G.E. PUSH-BUTTON (LACK) 2
166 P9XSVD0N G.E. 2 WAYS SELECTOR SWITCH 2
167 P9XSVD5N G.E. 2 WAYS SELECTOR SWITCH WITH SPRING RETURN 2
168 P9XSVE1N G.E. 3 WAYS SELECTOR SWITCH STOP-AUTO-MANU 4
169 P9XUGDDO G.E. PILOT LIGHT YELLOW (DIFFUSED LENS) 8
170 P9XULDDO G.E. PILOT LIGHT BLUE (DIFFUSED LENS) 2
171 P9XURDDO G.E. PILOT LIGHT RED (DIFFUSED LENS) 8
172 P9XUVDDO G.E. PILOT LIGHT GREEN (DIFFUSED LENS) 8
173 RT1L G.E. THERMAL OVERLOAD RELAY 4-6,3A 2
174 RT1V G.E. THERMAL OVERLOAD RELAY 25-32A 2
175 RT1W G.E. THERMAL OVERLOAD RELAY 30-40A 2
176 RT22J G.E. THERMAL OVERLOAD RELAY 64-82A CLASS 20 2
177 RT2E G.E. THERMAL OVERLOAD RELAY 30-43A 2
178 RT2H G.E. THERMAL OVERLOAD RELAY 54-65A 2
179 RT2J G.E. THERMAL OVERLOAD RELAY 64-82A 2
180 RT3F G.E. THERMAL OVERLOAD RELAY 140-190A 2
181 RTXP G.E. BASE FOR SEPARATE MOUNTING 2
182 1591250 ITALWEBER FUS 旧 LE NH1 250A/AM WITH STRIKER 6
183 2550110 ITALWEBER 1P FUSE BASE NHU-1 DIN-MS WITH MICROSWITCH 2
184 2590400 ITALWEBER ADAPTERS FOR NHU-1,2 FUSE BASES CONNECTION - T22 2
185 2590710 ITALWEBER SEPARATING PLATES FOR NHU-1,2 FUSE BASES - 1/2-WS 2
186 CA4-A476-600-EV KRAUS& NAIMER 3 POS. CAM SWITCH 10A, BLACK 2
187 DHR 100 C420 LEM FRANCE AC/DC CURRENT TRANSDUCER 100A,24V DC 2
129
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
5 YEARS MCC SPARE PARTS LIST
No. Catalogue Code Manufacturer Description Quantity
188 4793 2003 SOCOMEC TOROID W1-S35 FOR RESYS P40/M20/M40 2
189 4942 2723 SOCOMEC EARTH LEAKAGE RELAYS RESYS P40,230VCA 2
131
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
SPARE PARTS OF GENERTOR PROTECTION
Line item Device name Description Model Quantity
DIGITAL GENERATOR PROTECTION RELAY: 8CT/8VT,
G60-G01-HKH-F8F-H67-
1 G60A 8"A" DO, 16 DI, 8 "C" DO, 125/250V AC/DC power supply, 1
M8F-P6D-U6D-W6C (GE)
RS485+10Base-F and 10Base-T, 19" rack mounted, EGD.
DIGITAL TRANSFORMER PROTECTION RELAY:
12CT/4VT, 8"A" DO, 16 DI, 8 "C" DO, 125/250V AC/DC T60-G01-HKH-F8H-H67-
2 T60A 1
power supply, RS485+10Base-F and 1〇Base-T, 19" rack M8F-P6D-U6D-W6C (GE)
mounted, EGD.
3 96GW-1 EPM ANALOG OUTPUT MODULE PL90002-〇MA〇N-400 1
POWER ANALOG TRANSDUCER: 3-Phase, 4 Wire, 80 to 230
4 96GW-2, 96GW-3 Vca (45 to 65 Hz) and 110 to 325 Vdc powered. 4 configurable M I CA R 2/4A (ENERDIS) 2
Outputs.
EPM POWER SYSTEM MONITOR: 90-276 Volts AC/DC
P L9650-1-A-0-A-1-0000
5 DMM power supply, Ethernet TCP/IP 10Base-T and RS232 1
(GE)
Communication.
EPM MULTIFUNCTION DISPLAY: Multi-Function LED
6 MEASURES P L9000-P40N (GE) 1
Display. For multiple display options.
7 巳 RACKET FOR SURFACE MOUNTING I/O MODULES PL9000-MBI0 (GE) 2
8 KYZ EPM PULSE OUTPUT MODULE: 4 Solid State Pulse Outputs PL9000-4P01 (GE) 1
132
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
SPARE PARTS OF GENERTOR PROTECTION
Line item Device name Description Model Quantity
SYNC. VOLTAGE TRANSFORMER: 110.110/sqr3 (2
13 TO1, TO2 1TTV020 (FRER) 2
primary):110 V (secondary), 15VA, Class 1.
AX1, K100,
K120, K130, AUXILIARY RELAY: 125VDC, 2 Form C contacts, mounted
14 RD-2DI (ARTECHE) 8
K140, K150, on type ‘,D” socket.
32L-OP1, 74-3
AX1, K100,
K120, K130,
15 Type ‘,D” SOCKET: Front connections, DIN rail. DN-DE (ARTECHE) 8
K140, K150,
32L-OP1, 74-3
74/86G-1,
74/86G-2,
74/86L1-1,
74/86L1-2, BISTABLE AUXILIARY RELAY: 125VDC with diode, 8 Form
16 BJ-8BB (ARTECHE) 8
74/86L2-1, C contacts, mounted on type "J,socket.
74/86L2-2,
74/86UAT-1,
74/86UAT-2
74-1, 74-21, AUXILIARY RELAY: 125VDC with diode, 8 Form C contacts,
17 74-22, K10, K20, RJ-8DI (ARTECHE) 7
mounted on type ‘,J,socket.
K30, 41 E_POS
74/86G-1,
74/86G-2,
74/86L1-1,
74/86L1-2,
74/86L2-1,
18 74/86L2-2, Type J,,SOCKET: Front connections, DIN rail. JN-DE (ARTECHE) 15
74/86UAT-1,
74/86UAT-2 74-1,
74-21, 74-22,
K10, K20, K30,
41E POS
133
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
SPARE PARTS OF GENERTOR PROTECTION
Line item Device name Description Model Quantity
74/86E-1,
74/86E-2,
74/86T-1, BISTABLE AUXILIARY RELAY: 125VDC with diode, 4 Form
19 BF-4BB (ARTECHE) 6
74/86T-2, C contacts, mounted on type ‘,F,,socket.
74/86N-1,
74/86N-2
94EX-1, 94EX-2,
94EX 86N, AUXILIARY RELAY: 125VDC with diode, 4 Form C contacts,
20 RF-4DI (ARTECHE) 5
EXCIT ALAM, mounted on type ‘,F,,socket.
64F
27 CUBICLE LIGHTING: 18W, 230V, 50Hz PS 4139.180 (RITTAL) 2
28 HR CUBICLE HEATER: 450W AS-B-95 (MALABI) 1
29 TH HEATER THERMOSTAT: 5°-55°, one contact. SK 31 1 0 . 0 00 (RITTAL) 1
CUBICLE SOCKET: 2 PLUGS, 10/16A, 250V, 3.500W ,
30 SOC 5002 (L EGRAND) 1
ground connection
EX2100 SIMPLEX
SIMPLEX EXCITATION CONTROL : (3VBCZ004CD001 :
31 EXCITATION CONTROL 1
ED001)
(GE)
CUBICLE: Two panels of 800mm (wide) X 800mm (deep) X
32 2000+100mm (high) with glass front door, 19" swing rack, 8808.600 (RITTAL) 1
colour RAL 7035
134
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
Spare parts list generator accessory compartment
Component
identification Original
Manufacturer Component
Component component Designation Characteristics
item code Type
sequence code manufacturer
number
F 40 ABB ADDA MWK 17 Surge arrester E Ur: 21kV; Uc: 17kV; 10kA; cl.2
Ratio: 250/1A; Burden: 5VA cl.1; Uins:
Current
T 303 FTM AOC 80 E 0,72/3/10kV; Frq: 50Hz; Ith:
transformer
550A/30sec;丨 dyn: 2,5x 丨 th peak
Cn: 0,25^F; Uins: 17,5/38/95kV; Frq:
C 40 DUCATI 415.62.0037 Capacitor E
50Hz;
FANTIN 丨
E 31 C10A Thermostat E Regulation: 0/+60°C
COSMI
E 311 RITTAL SK 3118.000 Hygrostat E Regulation: 50/100%
Ratio: 8000/1/1A; Burden 1: 60VA
Current cl.5P20; Burden 2: 60VA cl.5P20; Uins:
T 31 FTM AOC 390 MT E
transformer 17,5/38/95kV; Frq: 50Hz; Ith:
80kA/1sec;丨 dyn: 200kA peak
Ratio: 8000/1/1A; Burden 1: 10VA cl.0,2
Current Fs<15; Burden 2: 60VA cl.5P20; Uins:
T 41 FTM AOC 390 MT E
transformer 17,5/38/95kV; Frq: 50Hz; Ith:
80kA/1sec;丨 dyn: 200kA peak
Ratio:
15000:sqr(3)//110:sqr(3)/110:sqr(3)V;
Voltage
T 43 FTM CTY 24/U E Burden 1: 20VA cl.0,2; Burden 2: 5VA
transformer
cl.3P (cl.1 from 0,8 to 1,2Un); Uins:
17,5/38/95kV; Frq: 50Hz
XP N.A. ILME N.A. Plug E 24P+T
XP N.A. ILME N.A. Plug E 2P+T
135
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
Spare parts list generator accessory compartment
Component
identification Original
Manufacturer Component
Component component Designation Characteristics
item code Type
sequence code manufacturer
number
Ratio: 15000/300V (15x1,3/sqr(3)kV
Neutral with no saturation) 10A/30sec. 1xh
T 302 OCREV MAT/R grounding E (Design 11A) 1,1A continuous (at
transformer 15/sqr(3)kV) Uins: 17,5/38/95kV; Frq:
50Hz
MICROELETTRI Neutral Rn: 0,346ohm; Userv: 300/sqr(3)kV;
R 302 CA NGR grounding E Uins: 17,5/38/95kV; Frq: 50Hz; Ifault:
SCIENTIFICA resistor 500A/30sec 1xh
Minimun count current: 200A 8/20
microsecond wave - Maximum High
DC - TYCO SC12/AC Surge counter E
Current Withstand: 100kA 4/10
microsecond wave
N.A. N.A. SITRE IS-C15 M.V. insulator E Un: 17,5kV
Anticondensate Pn: 100W; Un: 220/240Vac; Frq:
E 30 TORRESAN KT100 E
heaters 50/60Hz
Un: 220…240Vac; Frq: 50Hz; Pn:
E 31 F.LLI FERRARI ES355 Cooling fan E
0,55kW; ~5040m3/h
Anticondensate Pn: 250W; Un: 220/240Vac; Frq:
E 30 TORRESAN KT250 E
heaters 50/60Hz
VENETA M.V. post
N.A. N.A. IPA 15/750 E Un: 17,5kV
ISOLATORI insulator
M.V. bushing
VENETA
N.A. N.A. 80725 insulator with E Un: 17,5kV
ISOLATORI
bars centralizer
136
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
Appendix – 6- SPARE PARTS OF FIRE FIGHTING
Quant
Component
GE Device Quantity ity *Procur
Part Name Part Location Illustrati Spar Component Supplier
Part Nomenclat used on Rec. ement
/ Description on Item e Supplier (OEM)
Number ure (if Assembl as Cycle
Description on Assembly Number Code -OEM Part
Applicable) y Spare (Days)
Number
s
WISL Weighing on CO2 rack
WISL 101 WISL 101 74 1 M 60 SUNRISE 520070
101 device in container
connection
Flexible between
FH 101 FH 101 NA 74 8 M 60 SUNRISE 504020
hose 10/500 cylinder &
manifold
connection
between
FL 101 Pilot hose FL 101 NA 65 8 M 60 SUNRISE 504030
cylinder &
manifold
Solenoid mounted on
FY 121 FY 101 FY101 4 1 M 60 TYCO SL94004
valve Ass. CO2 cylinder
mounting on
PSV 184 Relief valve PSV 184 PSV 184 4 1 M 60 SUNRISE 503092
CO2 manifold
Pressure mounting on
PSH 183 PSH 183 PSH 183 4 1 M 30 SUNRISE 510040
switch CO2 manifold
Position
mounting at
ZSL 182 Micro ZSL 182 ZSL 182 4 1 M 30 SUNRISE 510013
isolate valve
switch
mounting
LT01 Light inside of LT01 NA 3 1 M 30 SUNRISE SP5017
container roof
137
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
Appendix –7- SPARE PARTS OF START MEANS
Approximate Replacement (emergency
Group Subgroup Marking Consumable
service life stock)
Air intet silencer Air outlet
115 116
110 silencer Slip rug 10Yeas 1Year
117
compartment fetter unit
120 122 Fitefunit(WPII) 2 Years
Slip rug compartment fetter
130 133 1Year
unit (water coder)
100 (Ventilation) Corestate retinal air
142
ventilation motor fan
140
Compete external air
146
ventilation motor fan
Complete slip hug
150 152 assembly ventilation motor
fan
211 Roller 401XX) hours
212 Compressing ring 400D0 hours
210Antifriction 214 Ejector disk
bearing 215 Ordos 40QD0 hours
216 Vungseal
217 Grease nipple
251 Sleeve
200(DE Bearing) 252 Oil ring
FiM external seaing
253a
assembly
250 254 Roasting internal seal
(Sleeve bearing)
255 Type 12sped3l seal
256a FMer piug
256b Sump plug
256c Oil gauge
138
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
Approximate Replacement (emergency
Group Subgroup Marking Consumable
service life stock)
311 Roller 401XX) hours
312 Compressing ring 400D0 hours
310Antifriction 314 Ejector disk
bearing 315 Ordips 40QD0 hours
316a Vnngseal
317 Grease nipple
351 Sleeve
300 (NDE
352 Oil ring
Bearing)
Full external sealing
35Sa
assembling
350 (Sleeve bearing) 354 Roasting internal seal
355 Type 12sped3l seal
356a FMer piug
356b Sump plug
356c Oil gauge
411 Insulators
410 (main booc)
412 Connection bar
400 (Terminal 421 InsUators
boxes) 420 (ISteutral) 422 Connection bar
423 Connection bar
450 (Auxiliary) 457 Auxiliary toenail box
511 Bearing probe on CS
512 Bearing probe on OSC
515 Internal 3r probe
510 (Temperature sensor)
500 516 External air probe
(Instruments) 517 Water inlet r probe
518 V«'3tef outset T°probe
530 (Heating element) 531 Space heater
139
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
Approximate Replacement (emergency
Group Subgroup Marking Consumable
service life stock)
540 (Water leak sensor) 541 complete leakage detector
550 551 Corestate control box
(Pressurization sensor) 552 Valve
560 561 Baishes 1year
Rotor insulation sensor) 562 Bfush holdef
610
611 Compete slip hng assembly
(Slip ring compartment)
621 Contact
620 622 Pw/of socket
(Sip rings short-circuitng
oevoe) 623 Yoke and bearings
600 (Bush 624 Gear reduction unit + nut
compartment) Set of brushes ipenronent
651 1year
contact)
650 Set of brushes (brushes
651
(Brush holderSer system) lifting device)
653 Set of brush holders
654 solenoid
5,6 5 LCD Meter Kit with Cover LCD Meter Kit without Cover 03031-0193-0101 _
03031-0193-0103 A
7 Local Zero and Span Kit 3031-0293-0002 A
88 Standard Terminal Block Transient Protection Block 3031-0332-0003 B
3031-0332-0004 B
Model 2090P
Item Spares
Part Description Part Number
No. Category
1,2 Smart Transmitters (Output Code S) Electronics Cover (with O-ring) 03031-0292-0001 _
10 LCD Meter Cover Assembly 03031-0193-0002 B
2 Cover O-rings 03031-0232-0001 B
Electronics Boards
3 S Output (4-20 mA/Digital HART Protocol) 02088-0306-0002 A
3 S Output (NAMUR Compliant Operation) 02088-0306-0003 A
Optional Mounting Bracket
4 (with 2-inch U-Bolt for Pipe Mounting) 02088-0071-0001 —
9 LCD Meter Kit with Cover 03031-0193-0101 _
9 LCD Meter Kit without Cover 03031-0193-0103 A
8 Calibration Adapter 02088-0197-0001 A
5 Teflon Gaskets (package of 12) 02088-0078-0001 A
6 316 SST Weld Spud with Heat Isolator Groove 02088-0295-0003 _
6 316 SST Weld Spud 02088-0195-0001 _
141
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
Model 2090P
Item Spares
Part Description Part Number
No. Category
7 316 SSTPIugVHeat Sink 02088-0196-0001 A
11 Standard Terminal Block 03031-0332-0003 B
11 Transient Terminal Block 03031-0332-0004 B
Model 2090F
Item No. Part Description Part Number Spares Category
1 Smart Transmitters (Output Code S) Electronics Cover (with 03031-0292-0001 _
O-ring)
5 LCD Meter Cover Assembly 03031-0193-0002 B
2 O-rings 03031-0232-0001 B
Electronics Boards
3 S Output (4-20 mA/Digital HART Protocol) 02088-0306-0002 A
3 S Output (NAMUR Compliant Operation) 02088-0306-0003 A
Optional Mounting Bracket
7 (with 2-inch U-Bolt for Pipe Mounting) 02088-0071-0001 —
4,5 LCD Meter Kit with Cover 03031-0193-0101 _
4 LCD Meter Kit without Cover 03031-0193-0103 A
6 Calibration Adapter, VA inch 02088-0197-0011 A
6 Calibration Adapter, 2 inch 02088-0197-0012 A
8 Standard Terminal Block 03031-0332-0003 B
8 Transient Terminal Block 03031-0332-0004 B
142
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
Appendix –9- SPARE PARTS OF ATPMIZING AIR SYSTEM
BILL OF MATERIALS AND SPARE PARTS
series DII
series E
series B series C types series F
types
type B20S types D30SII types
E30S E40S
part name material B30S B40S C30S C40S D40SII F30S F40S
E50S
B50S B60S C50S C60S D50SII F50S F60S
E60SII
D60SII
Quantity Quantity Quantity Quantity Quantity
1 hosing cast iron 1 1 1 —— _
2 driver stainless steel 1 1 1 —— 1
3 driver arm carbon steel 1 1 1 —— 1
4 actuator rod* carbon steel 1 1 1 —— 1
5 cover carbon steel 1 1 2 2 2
6 pivot pin washer* nylon 4 4 4 4 4
7 connector plate carbon steel 2 2 2 2 2
8 pivot pin * stainless steel 2 2 2 2 2
9 pivot pin retainer* stainless steel 4 4 4 4 4
10 Diaphragm plate* cast iron 1 1 1 _ 1
position indicator
11 stainless steel 1 1 _ _ 1
plate
12 lower casing carbon steel N/A N/A _ _ 1
13 diaphragm buna-N 1 1 _ _ 1
14 upper casing carbon steel 1 1 _ 1 1
15 stop screw carbon steel 2 2 2 2 2
16 spacer nylon N/A N/A N/A _ 2
17 cap screw carbon steel 4 4 8 8 8
18 jam nut carbon steel 2 2 2 2 2
19 indicator pointer aluminum 1 1 _ _ 1
20 cap screw carbon steel 1 1 _ 1 1
21 lock washer carbon steel N/A 4 N/A N/A(6) 20(9)
22 cap screw carbon steel 12 20 18 24 30
23 driver retainer stainless steel 3 3 3 3 3
143
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
BILL OF MATERIALS AND SPARE PARTS
series DII
series E
series B series C types series F
types
type B20S types D30SII types
E30S E40S
part name material B30S B40S C30S C40S D40SII F30S F40S
E50S
B50S B60S C50S C60S D50SII F50S F60S
E60SII
D60SII
Quantity Quantity Quantity Quantity Quantity
24 lock nut carbon steel 9 17 29 34(7) 30
25 spring retainer cast iron 1 1 _ 1 1(4)
26 thrust washer nylon 2(8) 2(8) 2 2 2
27 spring housing cast iron 1(1) 1(1) _ 1(2) 1(1)
28 cap screw carbon steel N/A N/A 4 4 4
29 lock washer carbon steel 4 N/A 4 4 4
30 cap screw carbon steel N/A N/A 10 10 20
31 cap screw carbon steel 4 6 2 2 4
32 lock washer carbon steel N/A N/A 4 4 4
33 compression spring* carbon steel 1 1 _ _ 1
34 caution plate stainless steel 1 1 _ _ 1
metal-backed acetyl
35 top driver bearing 1 1 — _ 1
resin
metal-backed acetyl
36 bottom driver bearing 1 1 — _ 1
resin
metal-backed acetyl
37 pivot pin bearing 2 4 2 2 2
resin
38 name plate aluminum 1 1 — _ 1
39 stud carbon steel N/A N/A 2 2 N/A
40 hex nut carbon steel N/A N/A 2 2 N/A
41 caution plate stainless steel 1 1 — _ 1
144
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
Appendix –10- SPARE PARTS OF WATER WASH SKID
SPARE PARTS FOR 2YEARS OF WATER WASH SKID
Installed Suggested Supplier
Description
Quantity quantity reference
CENTRIFUGAL PUMP (P121 & MO121)
1 1
Complete mechanical seal • 004ECCN-43| STALKERWEGWWS-9E-001-001-E
1 1
Cover Gasket/O-Ring General - 2900121720
BALL VALVES 3"
1 1 JMSWWS-9E-019-V
Repair kit consists of seat, gasket, stem packing of PTFE material
PRESSURE SWITCH (PSL173)
1 1 CCSWWS-9E-005-006-1
Complete unit • 604 GZ11
BALL VALVE 1-1/2"
1 1 JMSWWS-9E-019-V
Repair kit consists of seat, gasket, stem packing of PTFE material
BALL VALVE 2"
1 1 JMSWWS-9E-019-V
Repair kit consists of seat, gasket, stem packing of PTFE material
PRESSURE GAUGE (PI172)
1 1 WIKA WWS-9E-014-1-A
Complete unit • 233.34
PRESSURE SWITCH (PSH171)
1 1 CCSWWS-9E-005-006-1
Complete unit • 604 VZ1
FLOW SWITCH (FS174)
1 1 MOBREY WWS-9E-008-1
Switch-CCB 311
BALL VALVE 1"
4 1 JMSWWS-9E-019-V
Repair kit consists of seat, gasket, stem packing of PTFE material
DETERGENT LEVEL GAUGE(LG151)
1 1
Magnetic roller indicator-MRA-M1105 KUBLER WWS-9E-013-1
1 1
Float ZTSS150 with ring on top
WATER TANK LEVEL GAUGE(LG161)
1 1
Magnetic roller indicator-MRA-M2060 KUBLER WWS-9E-013-1
1 1
Float ZTSS150 with ring on top
WATER TANK LOW LEVEL SWITCH(LSL 162)
1 1 KUBLER WWS-9E-013-1
Magnetic switch AUM80
145
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
SPARE PARTS FOR 2YEARS OF WATER WASH SKID
Installed Suggested Supplier
Description
Quantity quantity reference
WATER AND DETERGENT FLOAT VALVE HV111&HV101
1 1
Valve seat for 1-1/2'' Ssball float ball
1 1 TECHMATIC CONTROL
Float 1-1/2''
1 1 WWS-9E-018--V
Valve seat for 1'' SS ball float ball
1 1
Float 1''
CHECK VALVE
1 1 JMS
2'' complete unit-A122EN050-V
1 1 WWS-9E-017-V
3''complete unit-A122EN080-V
ELECTRICAL BOX (AR001)
2 Disconnector circuit breaker NS100H 2 LONED ELEC WWS-9E-023-E
2 Auxiliary block 2
1 Circuit breaker 1P+N 2A/C 1
1 Circuit breaker 1P+N 3A/C 1
1 Circuit Breaker 1P+N 4A/C 1
1 Thermostat 5-55°C 1
1 Cubicle Heater 20W 1
1 Power Switch 3x100A 1
1 Motor circuit breaker 4-6.3A 1
1 Motor circuit breaker 24-32A 1
1 Auxiliary contact 1NO 1NC 1
2 Auxiliary contact 2NO 2NC 2
1 Auxiliary contact 4NO 1
1 Contactor 32A 230VAC 1
2 Contactor 40A 230VAC 2
20 Relay 20
20 Base for relay 20
3 Timer relay 1NO/NC 3
3 Timer relay 2NO/NC 3
146
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
SPARE PARTS FOR 2YEARS OF WATER WASH SKID
Installed Suggested Supplier
Description
Quantity quantity reference
2 Green light - LED 230VAC 2
2 Orange light - LED 230VAC 2
6 Red light - LED 230VAC 6
5 Black push button 5
1 Auxiliary contact 1 NO 1
3 Auxiliary contact 1NC 3
1 Thermistor protection circuit relay 1
1 Transformer 380-400-415 VAC I 230VAC 630VA 1
1 DC power supply 7.5W 1
147
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
SPARE PARTS FOR 5YEARS OF WATER WASH SKID
Installed Suggested Supplier
Description
Quantity quantity reference
PRESSURE SWITCH (PSH171)
1 1 CCSWWS-9E-005-006-1
Complete unit • 604 VZ1
FLOW SWITCH (FS174)
1 1 MOBREY WWS-9E-008-1
Switch-CCB 311
BALL VALVE 1"
4 4 JMSWWS-9E-019-V
Repair kit consists of seat, gasket, stem packing of PTFE material
DETERGENT LEVEL GAUGE(LG151)
1 1
Magnetic roller indicator-MRA-M1105 KUBLER WWS-9E-013-1
1 1
Float ZTSS150 with ring on top
WATER TANK LEVEL GAUGE(LG161)
1 1
Magnetic roller indicator-MRA-M2060 KUBLER WWS-9E-013-1
1 1
Float ZTSS150 with ring on top
WATER TANK LOW LEVEL SWITCH(LSL 162)
1 1 KUBLER WWS-9E-009-1
Magnetic switch AUM80
WATER AND DETERGENT FLOAT VALVE HV111&HV101
1 1
Valve seat for 1-1/2'' Ssball float ball
1 1 TECHMATIC CONTROL
Float 1-1/2''
1 1 WWS-9E-018--V
Valve seat for 1'' SS ball float ball
1 1
Float 1''
CHECK VALVE
1 1 JMS
2'' complete unit-A122EN050-V
1 1 WWS-9E-017-V
3''complete unit-A122EN080-V
MOTORIZED BALL VALVE
1 1 RCEL WWS-9E-012-V-A
complete unit
FLOW METER
1 1 BURKERT WWS-9E-007-I
complete unit-424012A/423916G(P/N8035)
ELECTRICAL BOX (AR001)
2 Disconnector circuit breaker NS100H 4 LONED ELEC WWS-9E-023-E
2 Auxiliary block 4
1 Circuit breaker 1P+N 2A/C 2
1 Circuit breaker 1P+N 3A/C 2
148
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
SPARE PARTS FOR 5YEARS OF WATER WASH SKID
Installed Suggested Supplier
Description
Quantity quantity reference
1 Circuit Breaker 1P+N 4A/C 2
1 Thermostat 5-55°C 2
1 Cubicle Heater 20W 1
1 Power Switch 3x100A 2
1 Motor circuit breaker 4-6.3A 2
1 Motor circuit breaker 24-32A 2
1 Auxiliary contact 1NO 1NC 2
2 Auxiliary contact 2NO 2NC 4
1 Auxiliary contact 4NO 2
1 Contactor 32A 230VAC 2
2 Contactor 40A 230VAC 4
20 Relay 40
20 Base for relay 40
3 Timer relay 1NO/NC 6
3 Timer relay 2NO/NC 6
2 Green light - LED 230VAC 4
2 Orange light - LED 230VAC 4
6 Red light - LED 230VAC 12
5 Black push button 10
1 Auxiliary contact 1 NO 2
3 Auxiliary contact 1NC 6
1 Thermistor protection circuit relay 1
1 Transformer 380-400-415 VAC I 230VAC 630VA 2
1 DC power supply 7.5W 2
1 Emergency stop push button with key 2
149
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
Appendix –11- SPARE PARTS OF SUMP TANK
LIST OF SPARE PARTS FOR 2 YEARS OF EXPLOITATION SUMP TANK
INSTALL DESCRIPTION SUGGEST SUPPLIER
QUANTITY QUANTITY REFERENCE
1 ECCENTRIC SCREW PUMPS SERIES SETBP (SETBP 50.1) 1 91-466943
MECHANICAL SEAL
1 STATOR 1
1 GASKET FOR DISCHARGE CASING 1
2 COUPLING ROP PIN 2
2 COUPLING ROP BUSH 2
4 BUSH FOR COUPLING ROP PIN 4
2 RETAINING SLEEVE 2
4 CLAMPING BAND 4
1 COUPLING ROD 1
2 COVER SLEEVE 2
1 MAGNETIC FLOAT SWITCH SERIES ALV2 1 119A6188
NPT-VUUUU-L1515-SV-C30EX COMPLET UNIT
1 VALVE 2”(5050) SLEEVE 1 91-465145
1 POPPET 1
1 SPRING SUPPLIED WITH CUP AND ADJUSTING SCREW 1
1 2 PIECE BALL VALVE 2”(705) GASKETS SET 1 91-465146
1 FLANGE IMMERSION HEATER TYPE TPS 5KW REGULATION 1 91-465998
THERMOSTAT
1 SAFETY THERMOSTAT 1
1 PRECISION DIAL THERMOMETERS COMPLET UNIT 1 91-466949
151
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
152
NANDIPUR 425MW CCPP GAS TURBINE MAINTENANCE MANUAL
P3-215 Flow Straightener 1
P3-234 Seal Housing Pipe Nipple (Not© 4) 3
P3-239 Baffle Plat© Lip Seal (Frame Mount) 1
P3-30 Gearbox Vent Nipple 1
153