Sie sind auf Seite 1von 13

High-voltage power-transformer insulation

E. T. Norris, M.I.Mech.E., Member

Summary
The increase in transmission system voltages in recent years to 500 kV, with even higher prospective values,
makes the internal insulation a large proportion of the transformer cost and therefore economically more
important. The associated increase in MVA rating, and hence in size and weight, has reached beyond
transport limits and demands better insulation of smaller volume.
These factors can both be helped by increasing the working stresses in the insulation. The paper considers
means of achieving this by improvements in impregnation, more uniform dielectric fields and the elimination
of creepage, voids and local stresses due to winding connections and transpositions.
Since oil-impregnated paper is exclusively used in high-voltage power-transformer windings, the elements
paper and oil are first considered and then the combination. This depends entirely upon the purity of the
elements, the completeness of the impregnation and the subsequent prevention of contamination in
service. These are also discussed.
Throughout the paper the possibilities of non-destructive testing are considered.
Distinction is drawn between the orthodox ageing of insulation and the practical life of transformers
in service.
Technical literature on the subject, though extensive, is notable for its discordance. The paper endeavours
to incorporate a distillation of this practical information with the author's judgment and practical experience
in the hope that discussion will lead to explicit confirmation or amendment of the conclusions reached.

1 Introduction have, of course, kept abreast of modern developments in


plastics, and their apparent apathy is due to the unique
For many years, high-voltage power-transformer characteristics of oil-impregnated paper in relation to the
insulation has been universally and almost exclusively oil- peculiar combination of electrical, thermal and mechanical
impregnated paper, the term 'paper' including paper, press- stresses in a transformer winding.
board and presspaper made from cotton, wood pulp, linen,
jute or other cellulose material. The term 'oil' means a mineral This marriage of oil and paper has almost perfect intimacy.
hydrocarbon oil in accordance with B.S. 148: 1951 or similar They are the two cheapest insulating materials available, but
specifications. Other materials such as impregnated wood their combination is the best yet known and gives an electric
(usually laminated) and synthetic-resin-bonded-paper cylin- strength much higher than either separately.
ders and boards are used in small quantities in positions Unlike plastics it has no melting-point or even, which is one
where mechanical strength rather than electrical strength is of the limiting features of plastics, no softening-point. There is
paramount. thus no appreciable loss of mechanical strength at relatively
low temperatures. It will also withstand comparatively high
The paper is divided into four sections on oil, paper, temperatures for very short times—an essential requirement
oil-impregnated paper, and transformer insulation. In many for resisting short-circuit stresses.
important respects these are four separate subjects. Dealing
with the matter in this sequence will simplify the analysis and The one defect in this marriage is that both constituents are
emphasize the comparative simplicity of the basic elements easily contaminated. In each material, impurities of a few
and the complexity of the applied combination. Thus, for parts in 106 are serious. In theory, of course, purity is possible,
example, oil-impregnated paper has characteristics that would and in controlled laboratory conditions very high electric
not obviously be expected from consideration of oil and paper, strengths have been achieved.1 The practical application is
much as, in different ways, the characteristics of salt are not therefore entirely a matter of knowing the highest purity
obvious from the constituents sodium and chlorine. attainable and maintainable and then choosing appropriate
stresses.
Oil-impregnated paper is also the principal insulation in From the knowledge that oil-impregnated paper has been
many high-voltage cables and capacitors as well as trans- studied universally for many years, it might be thought that
formers. Here again, in many important respects, these are its characteristics and behaviour were fully known and
three separate subjects. Technical characteristics and analyses established. This, however, is not so. Some vital factors have
true for one are misleading, or not relevant, for another. been realized only recently, and even today there is room for
Failure to realize these distinctions has been the cause of some much more experimental work and analysis.
confusion and misunderstanding in academic studies, and
between transformer, cable and capacitor engineers. The studies in the next two Sections of oil and paper
separately are not comprehensive or complete but deal only
When one thinks of the recent spectacular developments in with characteristics of importance in the combination oil-
plastics and synthetic insulating materials, it might be expected impregnated paper as applied to high-voltage power trans-
that, although oil-impregnated paper has been known and in formers. Methods and processes of achieving this combination
use for many years, it would have been superseded by one of are not considered.
these more modern insulating materials. This is indeed begin-
ning to be true with cables and capacitors, at least for the 2 Transformer oil
lower voltages, but there is as yet no sign of it happening in
high-voltage power transformers. Designers the world over The oil considered here is a mineral hydrocarbon oil as
normally used in transformers. A typical specification is given
Paper 4088 P, first received 8th May and in revised form 2nd October in B.S. 148: 1951. The principal characteristics can be divided
1962. It is an 'integrating' paper
Mr. Norris is consultant to Ferranti Ltd. into mechanical, physical and electrical.
428 PROCEEDINGS I.E.E., Vol. 110, No. 2, FEBRUARY 1963
2.1 Mechanical
Oil, although a liquid, has two important mechanical
properties, namely changes in volume with temperature and
pressure.
The former provides the essential convective or thermo-
siphon cooling in naturally air-cooled transformers. The latter,
or rather the absence of it, is responsible for the transference of
mechanical vibrations from the core to the tank, i.e. broadly
speaking for transformer noise.
While neither of these characteristics is directly within the
scope of the paper, both temperature and pressure have
important secondary effects, which are considered later
(Sections 2.2.2 and 5.5).

2.2 Physical
The chemical structure of the oil is the province of the
oil chemist, and numerous tests have been devised to prescribe
its performance fully, e.g. acidity or neutralization number,
saponification, interfacial tension, oxidation and steam
emulsion. All have their particular significance to the oil
chemist.

2.2.1 Acidity and oxidation


40 60 80
Present-day practical tests are for acidity and oxidation Temperature, °C
or sludge formation. Years ago these two tests were of
Fig. 1
engineering importance particularly when highly refined oils
of the class A type were a standard. Nitrogen and air content of transformer oil as a function of tem-
perature at 760 mm Hg pressure
Modern oils come easily within the sludge and acidity (a) Air
limits of B.S. 148 and stay within these limits for an unknown (b) Nitrogen
number of years in present transformer operating conditions.
Where high values of sludge and acidity have been measured, 11OO
they are not inherent in the oil but are due to unpolymerized
varnishes, compounds and paints (in particular metallic
dryers) formerly used in the transformer construction.2 Very 1000
small amounts of these impurities produce copious and
apparently unlimited quantities of sludge and sometimes high
acidity. When this occurs, the oil supplier is often unfairly
blamed.
For the oil-impregnated-paper insulation considered, there
will be no such varnish or other compounds in the wind-
ings, but the painting of cores, the insides of tanks and
the varnishing of taped leads must be carefully watched. If
this is done it is doubtful, and certainly not proven, if sludge
or acidity will ever reach a serious value in a modern trans-
former operating in normal service conditions, even with the
oil exposed to air. This question is considered in a later
Section.

2.2.2 Gas solution


Transformer oil will absorb the following quantities of
gas at 25° C and 760mmHg pressure: air, 10%; nitrogen,
8-5%; oxygen, 16%; and carbon dioxide, 100%.
The value for carbon dioxide is included to indicate the
range of gas absorptions and to show how much more
troublesome the gas problem could be.
Increasing the temperature or pressure increases the quantity
of gas the oil can hold in solution. Fig. 1 shows the effect of 300
8 10 12 14 16
temperature3 and Fig. 2 the effect of pressure.4 In many cases Air content , volume °/o
the gas solubility falls with increasing temperature. Trans-
former oil is an exception. Fig. 2
For transformers with the oil surface at atmospheric pres- Air content of transformer oil as a function of pressure
sure, as in the normal conservator tank construction, only
temperature variations need be considered, and these have If a transformer, however, is sealed to some degree, pressure
small effect. Fig. 1 shows, for example, that a 30° C change in and temperature are interrelated by the thermal expansion of
oil temperature changes the amount of dissolved air by only the oil and the sealing characteristics.5 Contemporary methods
0-45%. of sealing are discussed in Section 5.5.
PROCEEDINGS I.E.E., Vol. 110, No. 2, FEBRUARY 1963 429
21 P6
If the oil temperature rises owing to increase in load or
ambient temperature, the oil expands and increases the pres-
sure. For example, an increase from this cause of 7-51b/in2
in the air pressure would increase the air solubility from 10 to 280
15%
The danger arises when the pressure falls. The oil then has
more air than it can hold and becomes supersaturated. The 240
excess air will eventually diffuse out of the oil. It will take some
time, maybe days or weeks, for this to happen, depending on
the ratio of oil surface exposed to the gas and the volume of the

in
o
O
oil. If, however, the oil becomes supersaturated by 15-20% or
the pressure falls suddenly, air bubbles will form in the oil.
These bubbles will also occur in parts of the oil subjected
to high electric stresses.6 It has been reported3 that the electric

o
t,
strength of oil can be reduced to one-third by this means. This
problem is discussed in more detail in Section 5.5.

O
2.3 Electrical
In one respect, the electrical characteristics are simple.
80
The electric strength of oil is virtually infinite, values over
lOOOOkV/in having been measured. Practical values never
approach this limit. For example, the electric-strength accept-
ance test of 40 kV for a new oil in B.S. 148 corresponds to a 40
maximum gradient of 300kV/in, or only 3% of the above
value.
Many studies have been made of the electric strength of oil. 40 50
The results of different research workers are usually discordant Relative humidity of
in spite of earnest discussions, and perplexity ensues. The Fig. 3
explanation is that it is not, in fact, the electric strength of oil
Moisture content of transformer oil as a function of humidity of the
that is being measured but the effect of minute impurities on contact air at 25° C
the electric strength.43 These may vary for a given oil from id) Oil temperature, 25° C
sample to sample and even from hour to hour. Since no ib) Oil temperature, 40° C
(c) Oil temperature, 60° C
attempt is usually made to control the nature or amount (d) Oil temperature, 80° C
of impurity it is not surprising that wide variations occur.
Indeed it would be astonishing otherwise. 100,
The effect of impurities is variable. The most common one,
water, has a definite relation in quantity to the humidity of
the surface air4 (Fig. 3 is typical). Even so, the effect of moisture 52 80[
depends entirely on the nature and the amount of other
impurities present. Large quantities of water do not reduce
appreciably the electric strength of an otherwise clean oil.
Fig. 4 shows the range of values that have been measured.
Another electrical test is the power factor. This is a dimen-
sionless value, conveniently measured and much favoured by
research workers. As a measurement of power loss it is of
course informative and valuable. It is therefore an important
measure for cable and capacitor work. In transformers dielec- 20 30 "40 50
tric losses in the oil are negligible, and the power factor is not Water in oil, parts in
necessarily significant even when high. Fig. 4
There are authentic cases7 of large transformers in satis- Effect of water in transformer oil on the electric strength
factory service over many years with an oil power factor of
0-6-0-8 (power factor and not loss tangent). It is not known strength, because of the differing nature and degree of other
whether these oils, when new, would have passed the tests of minute impurities and, of course, the varying circumstances in
B.S. 148:1951, but sludge and acidity values were still low and which the tests are carried out. Moreover, cases where specific
electric strength was high. These high values have been relations have been found may well have been justified for the
encountered elsewhere and seem to be unexplained. They are, particular circumstances and conditions. The power-factor
of course, quite unusual, but they do indicate that power factor test requires very sensitive and critical measuring techniques
as an absolute value is not necessarily significant. and a skilled laboratory staff, and is not considered suitable
There seems to be no established correlation between power for routine measurements in the field.
factor and either moisture, electric strength or acidity. In some It is concluded by Clark10 that in the academic sense, the
cases,8 but not in others,9 some relation is found between power factor test may be used, as may other tests, if we merely
resistivity and moisture. wish to detect oil change. To be practical, however, the tests
Contradictions of this kind abound in the technical litera- must be selective and reject those oil changes which are not
ture. Here again, it is not a matter of correct measurement or actually harmful. This the power factor test of oil does not do.
of competent laboratory technique in any particular case. The
discrepancies arise partly because oils from differentfieldsand In the absence of a selective test, it is still necessary for us
to determine the specific oil property in which we are interested
refineries vary hydrocarbonically, but ctiiefly, as in the electric by the use of a specific test. If it is the dielectric strength test
430 PROCEEDINGS I.E.E, Vol. 110, No. 2, FEBRUARY 1963
which is in question, it is best to run a dielectric strength test. 3.1.2 Moisture evolution
If it is sludge, it is best to run a test for oil sludging. This is the Water forms a large part of the thermal decomposition
direct, the practical way to evaluate oil condition.
product, and this decomposition will be serious if the drying
In general, the power factor of the oil is no guide to the process is carried too far.
power factor of the oil-impregnated paper.11 An oil of high It is difficult to determine when paper is dry. 17
power factor can give oil-impregnated paper of very low
power factor.12 As the drying process progresses, the rate at which water
The temperature limit seems to be in the paper rather than vapour comes off steadily decreases but water vapour continues
to come off however long the drying is continued. Raising the
in the oil.12 Clean oil, if sealed from the atmosphere, with- temperature increases the rate of drying, but it also increases
stands temperatures up to 140° C for long periods. the rate of decomposition. Water vapour coming from the
thermal decomposition of cellulose is not distinguishable directly
from water vapour coming from the adsorbed state. Thus the
3 Paper fact that water vapour continues to come off after protracted
Cellulose materials employed include kraft, Manila drying at any temperature above about 100° C does not mean
and rag papers, as well as cotton, jute and linen fibres as that the paper can be dried further. It is not feasible to reach a
condition where no more water vapour is evolved by paper.
described in the appropriate standard specifications.13"16 An increase in temperature will result in a higher rate of
The relevant characteristics of paper are physical and moisture evolution which will gradually decrease. If heated,
thermal. The insulation does not deteriorate electrically until further moisture is again thrown out. Pumping off more water
the material has lost all mechanical strength and has become vapour beyond this point while maintaining the paper at a
high temperature is merely continuing the thermal decomposi-
charred and sufficiently weakened and embrittled to crumble.17 tion; it is not decreasing the content of adsorbed water.

3.1 Physical characteristics The gases evolved in the thermal decomposition of paper
are approximately in the proportions17 water: carbon dioxide:
It is only necessary to consider here moisture absorp- carbon monoxide of 70 : 12 : 18. The last two indicate that
tion. It is objectionable partly because it lowers the mechanical the cellulose is being pyrolized rather than dried. Laboratory
strength of the paper, accelerates ageing and, to a lesser methods of distinguishing in this and other ways between
degree, reduces the electric strength both in the dry state and drying and decomposition have been developed.17 They are
when oil-impregnated. not applicable to large masses of inaccessible paper at
different temperatures and moisture conditions. In trans-
3.1.1 Absorbed moisture formers, as will be discussed later, it is fortunately not
Paper will contain about 15% moisture when saturated necessary to carry the drying process so near the danger limit
and between 7 and 9% in normal atmospheric conditions, as as 0 • 1 % apparent moisture.
shown18,11 in Fig. 5. Equilibrium conditions for given tem-
peratures and humidities have been established.19 Paper will
3.2 Thermal decomposition
The mechanical strength of paper is affected as an
ageing process by time and temperature. There has been
extensive study of this phenomenon over many years. Origin-
ally mechanical strengths, tensile or tearing, were used20 as
criteria. These were not found to have any close relation to the
essential characteristics of insulation and have been superseded
by chemical methods.21 The most recent of these by Fabre22
is based on the degree of molecular polymerization termed
DP, the DP number being the relative value compared with
unheated paper. There seems to be little relation between the
ageing measured in any of these terms and the practical life of
the insulation. This aspect is considered further in Section 5.4.
The more recent chemical rate or Arrhenius formula differs
little from the tensile-strength formula for the more usual over-
load temperatures, i.e. up to say 130°C. For the higher
temperatures up to 250° C reached in short-circuit conditions
the new formula gives greatly increased lives. Thus for the
same life at 105° C and a usual half-life of 6° C, the life at 250°C
by the Arrhenius formula is 100 times the old value.
In some ways both formulae are unfortunate. They enable
numerical 'life' values to be calculated to degrees quite outside
the exactness of the supporting data. Thus (again with the same
half-life), the calculated 'life' is decreased 40% by an increase
40 50 in temperature of only 3° C. It is impossible for an operating
Relative humidity, °/o engineer to estimate or determine the mean winding tempera-
Fig. 5 ture over years in service within this order of magnitude, and
Moisture content of kraft paper as a function of the relative humidity so such numerical calculations have little significance or
of the contact air at room temperature realism.
Ageing is greatly affected by moisture and oxygen, but the
pick up its equilibrium moisture quite quickly, and it can, con- relations between the various parameters and the performance
versely, easily be dried down to 0* 1 % moisture by heating in of paper in service are very complex and are still the subject of
air. Vacuum is unnecessary except to save time, but the saving much study. Thermal decomposition occurs at all tempera-
is so great that in practice it is usually employed, forming part tures, though the rate becomes very small for temperatures
of the impregnation process (Section 4.3). below, say, 100° C. This is obvious also from operating
PROCEEDINGS I.E.E., Vol. 110, No. 2, FEBRUARY 1963 431
great for various reasons and moreover can be obtained in
other ways using ordinary paper.23'24 The choice therefore is
economic and must include the increase in the cost of the
100 paper. If, however, the increase in temperature rating is
10°C, the paper need only be used for that part of the insula-
tion which operates within 10° C of the hottest-spot tempera-
10 y ture. Cost differentials are generally small, vary as the loss
levels, and decrease as the kVA size increases.45
Since the modifications vary in nature it is not possible to
generalize, but some criticisms report that the tendency to
1 acidity in the oil is increased and that, although the deteriora-
/ tion in mechanical strength with time may be less, the initial
strength is lower.23 There are also potential difficulties with
0-1 / copper migration from the conductors if working tempera-
> tures are increased. These and other possible 'side effects'
must be sought out and resolved, so that, in due course, the
/ practical applications for these papers will be established.
0-01
Their effect on transformer life involves other factors discussed
in Section 5.4.

50 100 150 200 250 300 350


Temperature , °C 4 Oil-impregnated paper
Fig. 6 Since oil-impregnated paper is physically a mixture and
Relation between rate of gas evolution and the temperature of not chemically a compound, one would expect, prima facie,
kraft paper heated in the absence of air that its characteristics and performance should follow from
the component values. There are, however, important excep-
experience over the last 50 years. Fig. 6 (taken from Reference tions.
16) shows the evolution of gas due to the decomposition, and From the two previous Sections it follows that the thermal
Fig. 7 (taken from Reference 22) shows the formation of limit of this combination is determined by the paper and not
by the oil. It is established12 that oil impregnation does not
affect the ageing or thermal decomposition of the paper.
The effect of the paper is to split the oil into minute gaps—
for an individual sheet the thickness of the interwoven fibres
10 and for a cable or taped conductor in a transformer the
thickness of an individual sheet. One theory of electric strength
is that it represents the strength of these small oil spaces,
partly because the strength of the oil is probably lower than
that of the fibre and partly because its permittivity is lower
so that it takes a greater share of the electric stress.
The electric strength of the combination will depend on how
nearly ideal conditions of impregnation and elimination of
impurities can be achieved in practice. The nearest approach is
for capacitors. There are no mechanical stresses to be con-
sidered, thermal stresses are calculable and the electrostatic
field is comparatively simple. Moreover the units can be
permanently hermetically sealed in manufacture, and process-
ing can be controlled in almost ideal conditions.
Cables are a little more difficult. The electrodes are not
ideal, and thermal conditions are complicated by I2R loss in
the conductor. Mechanical stresses are caused by bending,
200 400 600 800 1000 laying and jointing. Consequently typical breakdown gradients
Degree of polymerization may be 3000kV/in for capacitors and 1500kV/in for cables.
Fig. 7 Conditions in transformers are discussed in the next Section,
Formation of water by the thermal decomposition of kraft paper but the corresponding stress will be well below lOOOkV/in.

water. Ageing is increased markedly by both temperature and 4.1 Contamination by moisture
moisture. There is, however, some neutralization here, as The physical equilibrium between water and oil has
increase in temperature tends to drive off moisture. The been noted. There is a similar equilibrium between paper and
resultant will depend upon the balance of the effects in each water. Typical relations are shown in Fig. 8, taken from
particular case. Reference 22. In practice, paper has a greater affinity for water
In recent years a number of methods of treating the paper than for oil and hence will, in general, absorb water out of the
in the processing stage have been developed to give reduced oil. This explains the effectiveness of the blotter filter press.
nominal ageing for a given temperature.* Alternatively the The amount of water in the paper is thus always very much
temperature for the same nominal ageing can be raised. greater than the amount in the oil, both relatively and abso-
Commercially and superficially this seems an important lutely. Water in the paper affects electric strength, power
advance, but, in fact, the net benefit that can be utilized is not factor, ageing, losses and mechanical strength. It is thus the
* Acetylation, cyanoethylation, amine and other additives are typical. most serious problem.
432 PROCEEDINGS LE.E., Vol. 110, No. 2, FEBRUARY 1963
10 20 " 30 40 50 '" 60 70 80 2 3 4 5 6
Water in oil, parts in 106 Moisture in paper, %

Fig. 8 Fig. 9
Humidity equilibria of the combination of air-oil-paper Effect of moisture absorption on the electric strength of oil-impreg-
nated paper
[a) Oil temperature, 20° C
i
[b) Oil temperature,
<c) Oil temperature,
30° C
50° C
(d) Oil temperature, 90° C element is much greater—a matter of weeks compared with
hours. It is correspondingly much more difficult to extract
moisture out of oil-impregnated paper if it has been once
4.2 Contamination by air allowed to penetrate.
Unless the paper is perfectly oil-impregnated there will
be voids of air or other gas. These lower the breakdown value
of the paper because their intrinsic electric strength is lower 4.4 Quality tests
and (since the permittivity is also less) the stress in the voids The principal electrical characteristics are insulation
will be much greater than in the paper. Breakdowns in the resistance, power factor and dispersion. The last two of these
voids do not immediately mean failure of the dielectric, and have the advantage of being dimensionless and easily
these partial discharges are known as corona. measured.
There has been much recent study of corona in oil- The measurement most in favour is power factor. Technical
impregnated paper,26'25 and various means of detection and literature abounds in studies in which it is tacitly assumed
location have been suggested.27'28 Corona is assumed to that power factor is the main criterion of a good insulation.
cause progressive damage leading to eventual premature This is perhaps plausible for capacitors and cables where the
failure (this is by no means inevitable) at relatively low power loss is important both as a loss and as setting a
stresses. The obvious conclusion is that corona should be thermal limit to the rating. As a means of determining
eliminated. There would then presumably be no progressive moisture—its chief use in transformer insulation—it can be
deterioration and working stresses could be based directly misleading. It represents the ratio, with suitable dimensional
on the puncture breakdown value of the insulation as deter- constants, of power loss to capacitance. Both of these are
mined by standard short-time tests. This thought gave rise affected by moisture, the latter because the permittivity of
to the expression 'corona free' as an aim for a standard water (about 80) increases the capacitance. In one instance
guarantee. moisture increased the power loss by 27 % and the capacitance
A recent international study of this subject by a C.I.G.R.fi. by 31 % making the power factor 3% better, quite obscuring
study group25 has made it clear that the matter is not nearly the increase in loss and implying that the material was
so simple and clear cut. The term 'corona' covers a number actually better when wet. This is an extreme case but
of phenomena, some harmful, some obviously not. Moreover, illustrates the possibility of delusion. It is sometimes possible
the expression 'corona free' is not absolutely attainable—even to correct this error by using the product of power factor and
in capacitors and even at working voltage. The expression can permittivity or loss factor, giving, in effect, for a fixed gradient
therefore only have a relative meaning depending on the E (volts per mil) the power loss per unit volume P (watts per
nature and sensitivity of the measuring equipment.26 The cubic inch) of insulation. Thus for a uniform field at 50 c/s,
matter is discussed in more detail in Section 5.1.2.
P = 0-7E2 cos <f>k x 10~ 4 . . . . (1)
where cos (j> is the power factor and k the permittivity.
4.3 Impregnation Some correlation between loss angle, dispersion and
The impregnation of dry paper with clean dry trans- moisture content has been found for oil-impregnated paper
former oil is basically easy. It occurs naturally in time by insulation29 where conditions of moisture and temperature
simple immersion. The time, however, is too long for practical are uniform throughout the material. It will be shown later
thicknesses and volumes, and so heat, vacuum and pressure that these conditions are never attained in a transformer
are all employed in industrial impregnation processes. These winding.
are frequently combined with the preliminary treatments for
achieving the basic elements of dry paper and clean dry oil.
Many methods are in use but are not considered further here. 5 Transformer insulation
The electric strength of oil-impregnated paper is much This Section covers the application of oil and oil-
greater than that of the oil and paper separately, roughly in impregnated paper to high-voltage power transformers. It has
the ratio 1 : 10 (Section 2.3). been explained that transformer windings are more complex
Moisture absorption from either air or surrounding oil is than cables or capacitors. The electrodes are of more irregular
as much in ultimate amount as for dry paper, but the time shapes and the dielectric fields are far from uniform. There
PROCEEDINGS I.E.E., Vol. 110, No. 2, FEBRUARY 1963 433
are high internal temperatures due to the losses, which are The ideal is obviously a completely solid insulation as in>
not only variable with the load but are many times the cables or capacitors. The breakdown stresses are much higher,
possible dielectric losses in the insulation. There are also and consequently the insulation distances can be greatly
mechanical stresses introduced deliberately as part of the reduced giving a smaller and more efficient transformer.
design and, to a much greater degree, in short-circuit Since the distance between primary and secondary windings
conditions.30 will be much less (in the ratio of, say, 3 : 1) the reactance
will be automatically reduced. This is a help where low
reactance is required by the purchaser, but not, of course,
otherwise. There are two major difficulties here.
5.1 Application The electric strength of layers of oil-impregnated paper is
Transformer insulation can be divided into three at its best for a stress normal to the laminations. This can
categories: conductor insulation, coil insulation and the be practically achieved, for example, in a cable except at the
major insulation, the first two forming the interturn and terminations and in a capacitor except at the edges of the foils.
intercoil insulation. In a transformer, however, as previously explained, the dielec-
Until comparatively recently the conductor had to with- tricfieldis affected by winding complications, connections and
stand merely the voltage between turns and the voltage cooling ducts. If the dielectric field is parallel to the lamina-
between adjacent coils with the assistance of a washer or tions the electric strength is greatly reduced, maybe to one-
an oil duct inserted for cooling purposes. The latter stress tenth of the normal value, and much of the advantage of
was usually the maximum or controlling one. In modern disc solid insulation is lost.
coil windings the coils and turns are frequently interleaved The second difficulty is that paper readily bends only in
or transposed to improve the surge voltage distribution and two dimensions. It is difficult to achieve a completely solid
hence the impulse strength. It may well happen then that insulation wall when the field becomes 3-dimensional, such as
physically adjacent conductors are many turns apart in at the ends of windings, between coils or at any other
voltage, and subjected to stresses correspondingly higher than irregularity in the geometry. There is then a danger of small
the voltage per turn. This increase in voltage now means that voids or oil spaces. These reintroduce the stress limitation of
the power-frequency stress between conductors may become oil and further reduce the advantage of solid insulation.
more important than the surge stress. Nevertheless the attraction of completely solid insulation is
Owing to this interleaving of turns and to transpositions so great that efforts have been made to overcome these two-
for reducing eddy-current losses in the strands, the dielectric major difficulties.33-34
field may be distorted and the maximum stresses increased. The aim is to design the insulation, whether oil-impregnated
In disc windings, spacers of pressboard15 are used to paper, pressboard or presspaper, so that it is at all points
provide radial oil ducts required for cooling. The critical normal to the dielectric field, so that it fits tightly around
stress here is by creepage over the surface, which is fortunately corners, coil edges and particularly all points of high stress,
normal to the grain of the spacer. The puncture value is then and so as to eliminate oil voids. To achieve this it will be
usually greater. necessary to scarf, overlap or interleave all joints in washers,
The major insulation, i.e. between high- and low-voltage channels and angles. Static shields may be necessary in places
windings and between these windings and earth, includes to cover sharp edges and prevent local high gradients. These
wrappings, cylinders, washers, collars, flanges and barriers. principles apply equally to disc-coil, multi-layer and inter-
The dielectric field distortions mentioned above for con- leaved shell windings.
ductor insulation apply in equal degree for major insulation. All these requirements are simple in theory and must be
Where the major insulation is concentrated in a single shown in the working drawings and instructions. They must
volume the orthodox arrangement is a series of oil spaces also be met in every detail in the course of assembly of the
and solid barriers or cylinders. In such an assembly the stress winding and coil insulation—mostly in internal positions
on the oil is much greater than in the solid insulation by inaccessible for either check or subsequent inspection. The
virtue of its lower permittivity. The breakdown stress in oil possibilities of minute but disastrous imperfections creeping
is also lower; hence, as the voltage is raised, one or more of in here are obvious and justify designers in moving cautiously
the oil spaces will in due course break down. This will throw in this direction.
larger stress on the barriers, and they, as a general rule, will Cooling is more restricted with solid insulation, so that local
withstand it. The function of the barriers is chiefly to break heating due to electric losses at higher voltages may need
up the oil path into smaller components, which will have attention.
diversity characteristics, and prevent the lining-up of a chain For a uniform field the temperature rise 6 in degrees
of impurities. This type of insulation is therefore inherently Celsius through a thickness d of insulation cooled in both
statistically reliable. It has been proved by operating experi- directions will be approximately
ence over many years.
6 = 3l-25Pd2 (2>
The local failures in an oil space will start as individual
spasmodic weak static discharges and will probably not Combining this with eqn. 1 gives
register as corona or a partial discharge. They are practically 6 = 2l-9E2kcos<f> x 10- 4 . . . . (3>
harmless but should not, of. course, occur at any voltage
within the working range. As the voltage is increased they Assuming a power factor of 0 • 05 and a permittivity of 3 • 5
will become a continuous discharge and could ultimately the temperature rise will be
damage the barriers sufficiently to start a major breakdown. 6 = 3-8£ 2 x 10- 4 (4>
Since the oil path contributes so little to the electric
strength and is in fact a handicap, the barrier type of insula- As a typical example, the major insulation of a 330 kV
tion is wasteful in space, even though, in many cases, some transformer with a working voltage of 33O/-\/3 = 190kV
of the oil spaces can also be utilized for cooling and thus would then have a temperature rise due to dielectric losses of
serve a double purpose. A practical illustration of the extent about 14° C if in one piece with no internal cooling. This,
and complication of insulation in modern high-voltage power temperature does not depend upon the voltage gradient in
transformers is shown in Fig. 10. the insulation.
434 PROCEEDINGS I.E.E., Vol. 110, No. 2, FEBRUARY 1963
^^j^^^j^^^j^d^^^^^ji^^^^^^^i^^^x^^^^^^^^^L^^^]^^^^^^

.10
ss-section of the winding of one phase of a 400 MVA 400/275 kV 3-phase transformer
Solid insulation
| ..Spacers and oil ducts
/ I Copper conductors .
5.1.1 Design calculations It is evident therefore that corona in oil-impregnated-paper
In practical engineering design the stresses that can be insulation is not necessarily damaging, and, indeed, in certain
worked to are primarily based on electric strengths measured forms can be argued as desirable in relieving stress. Present
in standardized conditions for the materials1'13> 15 and for methods of detection give no indication of the dangerous
various forms of electric field in assemblies and sub- or destroying effect and are in that respect unrealistic.
assemblies, such as conductor sections16 and oil ducts between Fortunately corona measurement is not necessary as a
turns and coils.31 routine test in transformers as being built and tested today.
For every part of the insulation in a particular design the There is no clear evidence of transformers failing in service
stresses must be determined separately in each of the follow- due to corona. This is probably because designing a trans-
ing conditions: former to meet the present standard pressure, over-voltage
and impulse tests ensures such a margin of insulation strength
Power frequency: normal working
that the transformer has no corona which could become
pressure tests dangerous at working voltage or in normal working
over-voltage tests conditions.25
Impulse test: full-wave and chopped-wave The study of corona measurement and assessment will, how-
transferred surges ever, continue. It is a promising form of non-destructive test-
Switching surges ing. When its present limitations have been overcome and it
The most severe of these stresses will determine the amount can be relied upon to detect and even locate dangerous
of insulation to be used in each part. Since the electricfieldis stresses within the windings, it may be possible to reduce the
generally far from uniform and the conditions just outlined present standard insulation tests. This aspect is considered in
vary relatively in degree in different parts of the winding, it is Section 5.3.
obviously not possible to lay down any particular stress
or thickness of insulation as a design standard. There are,
indeed, other qualifications also to be considered in reaching 5.2 Operating conditions
the final decision.32 It has been explained that conditions for the full
utilization of oil-impregnated paper in a transformer are much
5.1.2 Corona farther from the ideal than in a capacitor or cable. The dielec-
Corona has been considered briefly in Section 4.2 for tricfieldcannot be controlled so uniformly, as described in the
oil-impregnated-paper insulation. The subject is much more previous Section. Impregnation of the paper cannot be so
complex when transferred to winding insulation, where, inside perfect in the first place and cannot be maintained so well
a single transformer, there will be the variety of stresses in service—even in sealed units. Consequently working stresses
just described. in the insulation are lower in practice than in cables and much
The term 'corona' is, at present, used to include also ioniza- lower than in capacitors.
tion and all forms of partial discharge. In a transformer these For example, it is not present practice to use and maintain
may occur at sharp points such as terminal nuts in the oil, in degassed oil in a transformer. One must distinguish here
oil spaces in the major insulation, or in air or gas pockets between 'degassed' and 'de-aerated'. De-aerated is taken to
within the insulation. It is thus obvious that corona covers a mean the absence of air or gas in suspension and this can and
wide variety of phenomena not all equally dangerous. should be achieved. Degassed means the absence of air or
It is measured in picocoulombs, microvolts or picowatts, gas in solution and demands, first, the initial degassing of the
the most usual instruments being the N.E.M.A.-RIV meter25 oil before impregnation. This is practicable. It also means
for the second unit and the E.R.A. discharge detector28 for preserving the oil from any contact with air or other gas not
thefirst.The relation between these units is not yet established. only during manufacture but continuously throughout its
The detection of corona within a transformer winding is service life. This would require absolute hermetic sealing of the
more difficult because it cannot be measured at its seat or transformer without an air or gas cushion. The sealing must
place of occurrence. Its effect must be transmitted to a terminal be sustained during service and maintenance operations. This
and will be more or less attenuated in the journey. Even when is not as yet practicable in large high-voltage power trans-
so detected the problem of location remains. For large trans- formers. The future possibilities are discussed in Section 5.5.
formers involving high-voltage connections, it is not easy to A large transformer may contain 30 tons of paper and
eliminate external interference. pressboard and 150 tons of oil. It is quite possible to dry this
Detection depends entirely on the sensitivity of the method paper down to 0 • 1 % moisture. To achieve this as an average
of measurement. There seems to be no absolute zero of for the whole mass of the paper would, however, invite the
corona,26 not even in capacitors at working voltage.25 risk of thermal decomposition in parts of it (Section 3.1.2).
'Corona-free' is unrealistic and can be defined only as zero Fortunately indeed this degree of elimination of moisture is
reading on the particular measuring instrument employed. not essential.
Since absolute zero is not practicable it becomes essential It has been explained that power factor as a measure of
to determine some criterion for dangerous or harmful corona, power loss is not so vital in a transformer as in a cable or
and this criterion is, at present, unknown. capacitor. The capacitance is of minor importance. The total
It is known from long experience in service of synthetic- dielectric losses are quite negligible in comparison with the
resin-bonded-paper capacitor bushings that pronounced I2R and core losses in the transformer. Local high values may
corona can occur at working voltage with no harmful effect. be objectionable in causing hot spots in the insulation. These
Similar experience, though not so widespread, is available for will not, however, be shown in an overall power-factor
oil-impregnated-paper insulation. The author designed pos- measurement. The effect of moisture on these values is not of
sibly the first oil-impregnated-paper high-voltage capacitor importance, and consideration of moisture can be limited to
bushings in 1927. Eight 132kV bushings of this type were electric strength and mechanical ageing.
recently examined after 30 years' service. All had power- Measurements in service show moisture values of the order
factor/voltage curves better than when originally put into of 1^4%.22-23'25 In general service conditions, normal
service. Three of them had corona below working voltage.26 operation will keep the moisture in the oil 36 ' 23 down to 10-20
No bushings of this type had ever failed in service. parts in 106, and in an oil-impregnated-paper winding down
436 PROCEEDINGS I.E.E., Vol. 110, No. 2, FEBRUARY 1963
to about 2%. It is not thought practicable to expect moisture and the formation of air or gas bubbles on the electric strength
contents less than 1% in a transformer in service, even if of oil and the probability of damage can readily be imagined
sealed.23 from the previous Section on corona.
The custom of expressing the amount of water in the oil in Serious failures of large high-voltage transformers have
parts in 106 and in the insulation in per cent, combined with been attributed to this bubble formation. It is a trouble that
the relative quantities of these materials in a power trans- has only arisen in recent years with the development of various
former, obscures the true relations. A practical quantitative systems of sealing the oil in the transformer against the
example is enlightening and sometimes startling. oxygen in the atmosphere and the ingress of moisture.6-3
From the values just quoted, a.typical transformer in good These systems are discussed in Section 5.5
condition in service will have, say, 15 parts in 106 of water in
the oil and 2% in the insulation. Assuming again 150 tons of 5.3 Factor of safety
oil and 30 tons of paper, the total quantity of water in the
The orthodox method of ensuring reliability and long
insulation will be life in service has been to consider normal working stresses
30 x 2240 x 2 and to multiply these by a factor of safety intended to cover all
= 134 gal abnormal or emergency service conditions. Test values are
10 x 100
established based on these factors of safety and become
It is not generally realized that a transformer in good work- acceptance tests. Values of 3-5 originated in mechanical
ing condition will normally have so much water in its engineering, e.g. for bridges and boilers. The standard pressure
insulation. and over-voltage tests for transformers have been derived in
The total quantity of water in the oil will be this way. These relatively severe tests are in some ways
inefficient because, although they may serve their purpose in
150 x 2240 x 15 ensuring the safety margin specified, they are not only
= 0-58 gal
8-6 x 106 expensive in testing plant, but frequently create other stresses
not required by the test but which nevertheless have to be
even though there is five times as much oil as there is paper. included in the design.
It is nevertheless not negligible, because if increased from 15
to, say, 25 parts in 106, i.e. from 0-58 to 0-97 gal, the water The more modern approach is to consider not only normal
in the insulation according to Fig. 8 would be increased from working conditions but also all abnormal and emergency
134 to 200 gal. stresses and to base the tests on the worst values thus obtained.
It seems unlikely, however, that, in a large transformer with In meeting these tests, the designer must then allow some
variable temperature and moisture conditions throughout its margin to cover design and manufacturing variations.
insulation in both space and time, the equilibria postulated in This method becomes practicable only as these extra-
Figs. 3, 5 and 8 are ever reached.11 ordinary conditions become realized and understood both in
The reduction in electric strength in service due to moisture nature and in degree. In the ideal case, no so-called factor of
is small. Fig. 9 derived from a range of published measure- safety would then be necessary for the various acceptance
ments shows that the electric strength is only reduced about tests. In practice, the test values can be reduced.
10% for 3% moisture. In power-transformer engineering the introduction of
The most dangerous effect of moisture arises where a impulse tests, of categories of system earthing conditions and
transformer is idle. Moisture absorption is then entirely lightning protection have tended in this direction, and reduc-
dependent on the oil maintenance. Periodic measurement of tions in the standard scale of pressure and over-voltage tests
the electric strength of a sample of oil is not enough because, are being suggested.
as stated in Section 2.3, this can be high in an otherwise clean This trend would be strengthened if non-destructive tests
oil even with serious amounts of water in the oil. Apart from a such as corona, moisture detection (Section 5.2) and decom-
direct measurement of moisture the most valuablefieldmethod position (Section 3.2) can be developed into practical routine
is a crackle test (B.S. 148,1951). This test is liable to be treated safeguards.
unjustifiably with some contempt because of its cheapness and
simplicity, but should always be carried out unless resistivity 5.4 Probable life
measurements are possible.8*37 The nominal ageing of insulation in accordance with
The difficulty of determining the state of the insulation in a Montsinger or Arrhenius rules has been discussed in Sec-
transformer in service (Section 3.1.1) is due to the variable tion 3.2. By supposing an ultimate life to this ageing process
temperature conditions throughout a large mass of insulation. various National Loading Guides38 or Codes of Practice39
The amount of water in transformer insulation in service have been standardized, and detailed tables and charts have
cannot be measured by insulation resistance, power factor or been developed giving overload values and durations for a
dispersion.11 One method in some use is to install samples of wide range of loading conditions.
the paper or pressboard insulation in an accessible position However, the theoretical and arbitrary life due to this
inside the tank before the impregnation process is begun. 'ageing' of the insulation is not synonymous with the actual
These can be abstracted and the moisture content measured life of the transformer in service. The latter is in fact much
whenever it is desired to check satisfactory treatment on longer—so much so as to be not yet known. There is need
arrival on site or indeed periodically in subsequent service. for a statistical analysis by supply system engineers of the
More recently an accessible probe to serve the same purpose rate of failure with age. An explanation for the absence of
has been suggested.11 If the insulation of the heating coil of the such operation records may be that in a supply system with
winding temperature indicator is utilized, conditions corres- a typical growth in transformer capacity of 10% per annum
ponding to the winding hottest-spot temperature will be only roughly 2 % of the transformers will be over 40 years' old.
attained.
It is explained in Section 3.2 that the orthodox ageing is
determined by the loss of some function of mechanical
5.2.1 Gas absorption strength (the electric strength being little affected even for
The gas absorption qualities of transformer oil have extreme ageing), and it is therefore concluded that the
been described in Section 2.2.2. The effect of supersaturation transformer will then be vulnerable to short-circuit forces.
PROCEEDINGS I.E.E., Vol. 110, No. 2, FEBRUARY 1963 437
This vulnerability, though plausible, has not been established of these pressure variations and so perfect and reliable in
in practice. Experimental tests have shown40 that trans- service that the use of degassed, as distinct from de-aerated
formers 'aged to the point where practically no tensile (Section 5.2) oil is possible, the insulation stress level could
strength remained in the insulation, yet withstood standard approach the standard reached in cables or even capacitors
short-circuit tests followed by standard insulation tests'. (Section 4). The reduction in both size and cost of the complete
Moreover, even if these facts are ignored, and it is assumed transformer would then be remarkable.
that the short-circuit strength is reduced far below its original For this standard to be possible, not only must the initial
value and, indeed, below the stresses occurring in service, so degassing, processing and sealing be practically perfect but,
that the transformer is now vulnerable to a short-circuit, it and this is the more difficult matter, the construction must be
will still remain in operation until such a short-circuit occurs. such that the seal is maintained continuously in service—a
Short-circuits in service are rare. Those of a severity seal proof against moisture and air occlusions and also
recorded as such by the average supply authority occur from against overhauls and maintenance in operation. This must
once a year to once in ten years or more,30 and one national also apply to the oil circulating in radiators and heat
estimate41 suggests one maximum short-circuit (i.e. a dead exchangers.
short-circuit under fully asymmetrical conditions) once in a At present, however, there is some doubt as to whether
transformer's life-time. complete sealing, even if it can be achieved, is desirable. It
Quantitative calculations are not possible, but taking into is shown in Section 3.2 that paper and other cellulose
account the progressive nature of short-circuit stresses and materials generate water in the natural course of ageing
the cumulative effect on the strains,30 together with a suggested (Fig. 7). It is also established42 that, at sufficiently high
short-circuit distribution,41 and assuming the ageing is such voltage gradients, gas is evolved if moisture is present.
that the short-circuit strength is reduced to one-sixth of the A construction that prevents moisture entering the trans-
original value, it may be judged that, even in this extreme former will equally prevent it escaping, so that this generated
condition, the transformer still has a probable life of eight water will be trapped, reducing the electric strength and
years. increasing the ageing of the paper. The actual degree of these
To complete the picture (though outside the scope of the effects is, however, not yet known.
paper) the margin is much greater for distribution trans- Various methods of semi-sealing, often with nitrogen, to
formers because the short-circuit stresses are much lower. eliminate possible oxidation effects as well as moisture (see,
It seems, therefore, that, even if the margin on the orthodox however, Section 2.2.2) have been suggested. These have been
ageing calculations just explained are ignored, the estimated comprehensively reviewed in Reference 35.
life of a transformer could be extended by say an additional It is not, however, possible to prevent temperature varia-
eight years for a power transformer and, say 12 years for a tions in a transformer, but there does not seem to be any
distribution transformer. need actually to introduce moisture traps and pressure
It is general practice, at present, to retain transformers in changes and thus run the serious risk of premature ageing,
service until they fail, so that this additional life is, in fact, supersaturation of gas in the oil and the consequent formation
utilized. Even that is not the end, as repair will usually be of gas bubbles.
possible and give them a further lease of life. The orthodox conservator-breather system has proved
satisfactory in service in all parts of the world and over
5.5 Preservation many years.43 A recent survey36 of large transformers with
The dominant weakness of oil-impregnated-paper long service records and various oil preservation systems,
insulation, stressed in Section 1, of being easily contaminated including the standard conservator-breather, showed that
particularly by moisture, emphasizes the need for preservation electric strength and all other oil properties were unaffected
of the original purity throughout its service life if its initial by age up to at least 17 years. It has been shown already
strength is to be maintained. (Section 5.2) that the insulation itself is automatically main-
This problem simplifies to that of preventing moisture from tained in good condition by normal service operation. This
entering the oil-impregnated paper via the oil. may be partly because the temperature which, according to
The orthodox method of oil preservation is by the con- Montsinger and Fabre, ages the paper acts also to increase
servator vessel with dehydrating breather plus an oil seal its life by reducing the moisture content.
between the breather and the atmosphere to prevent the It has been deduced in Section 2.2.1 that, in modern high-
drying agent from attempting to dry the world. This has been voltage power transformers, neither acidity nor oxidation is
standard practice for large high-voltage transformers. serious and that moisture (and gas absorption if pressure
The ideal method, preventing both water and air from sealing is used) is the only service danger. Moisture measure-
getting into the transformer, would be to seal the transformer ments in both oil and insulation are possible (Section 5.2)
tank hermetically with flexible metallic bellows to take care in laboratory conditions. In the field, electric-strength crackle
of oil expansion, as is done in oil-filled cables. If the bellows and resistivity tests on the oil are practical.
were so efficient that pressure variations were negligible this Nevertheless the uncertainty and doubt at present of these
would also prevent the supersaturation of the oil and con- and the laboratory tests such as power factor are such that,
sequent formation of air bubbles as discussed in Section 2.2.2. in addition and as a last resort after the electric strength has
This construction is not yet attainable in high-voltage been checked, the best guide in service is to look at some
transformers owing to the relatively large quantity of oil, its part of the transformer. If the top of the core and clamps
high expansion coefficient and the practical limitation of that are in the hottest oil and most accessible are clean or
metallic bellows. have only a thin film, and if the oil looks clean and feels
The same principle is approached by using a flexible oily and smells of oil and not of burnt feathers, the trans-
plastic diaphragm as an expansion joint.35 Such membranes former may well be assumed to be in satisfactory working
must be both oil-tight and impermeable to gas and vapour condition so far as its insulation is concerned.
over long periods and must, of course, withstand continuous
contact with hot oil. The practical application of this method 6 Conclusions
depends upon the successful search for a suitable material. The principal conclusions are epitomized below. They
If, however, a form of sealing can be attained that is free should be interpreted in detail by reference to their contexts.
438 PROCEEDINGS I.E.E., Vol. 110, No. 2, FEBRUARY 1963
(a) Oxidation, sludge formation, and acidity in oil are subject. It is certainly contradictory and discordant in vital
negligible for high-voltage power transformers working in respects. Some of the relations, though disputable when
normal operating conditions (Section 2.2.1). applied in general, are justified when suitably bounded by
(b) The electric strength of oil is virtually infinite. Measured space, time and circumstance.
values are due to impurities and are correspondingly variable The author has endeavoured to incorporate a distillation of
(Section 2.3). all this published information with his own judgment and
(c) The power factor of oil is not, in itself, a significant experience in the hope that discussion will lead to explicit
guide to oil quality unless circumscribed by particular con- confirmation or amendment of the conclusions reached.
ditions (Section 2.3). Acknowledgments are due to the authors mentioned in the
(d) The thermal drying of paper merges into its decom- Bibliography and to Ferranti, Ltd., for permission to publish
position due to the generation and removal of moisture. The the paper.
distinction is, of course, vital and delimits impregnation
processes and heavy overloading in service (Section 3.1.2).
(e) Moisture in winding insulation is normally quite appre-
ciable but need not seriously affect the electric strength 8 Bibliography
(Section 5.4). 1 HALL, H. c , and KELK, E. : 'Physical properties and impulse strength
(/) The practical application of high-temperature papers of paper', Proceedings I.E.E., 1956, 103 A, p. 564
to increase rating is a matter of economics with very small 2 NORRIS, E. T.: 'General discussion on transformer oils', / . Inst.
Petrol., 1946, 32, p. 434
cost differentials (Section 3.2). 3 KAUFMAN, R. B., PIERCE, J. L., and UHLIG, E. R.: T h e effect of
(g) 'Corona-free' insulation is not absolutely attainable. transformer oil preservation methods on the dielectric strength of
oil', Trans Amer. Inst. Elect. Engrs, 1957, 76, Part III, p. 1315
The expression merely denotes zero reading on the particular 4 KAUFMAN, R. B., SHIMANSKI, E. J., a n d MACFADYEN, K. W . : ' G a s
measuring apparatus employed (Section 4.2). and moisture equilibria in transformer oil', ibid., 1955, 74, Part I,
(h) It is not yet possible to segregate harmful or destructive p. 312
5 DICKSON, M. R. : T h e effects of dissolved gases in the design and
corona. Limiting values cannot therefore be set. Nevertheless, operation of oil-immersed transformers' (E.R.A. Report Ref.
progressive and intensive studies are being made of corona Q/T139)
6 CHADWICK, A. T., RYDER, D. H., and BRiERLEY, A. E. : 'Oil preserva-
and corona measurement (Section 5.1.2). tion systems; factors affecting ionization in large transformers',
(/) The power factor of oil-impregnated paper is, in itself, Trans Amer. Inst. Elect. Engrs, 1960, 79, Part III, p. 92
7 MAURER, L., and WOYNER, T. : 'Unterschuchen an Betriebsoelen
not a reliable guide to insulation quality. The power factor aus Wandertransformatoren fur 220 kV Elektrotechn', Elektrotech.
of transformer windings is still less significant (Sections 4.4 Z., 1956, 77, p. 885
and 5.2). 8 STANNETT, A. w.: T h e resistivity test for insulating oils', Elect.
Times, 12th January 1956, p. 43
(j) The ideal of solid-oil-impregnated paper, as distinct 9 ROHLFS, A. F., and TURNER, F. j . : 'Correlation between the break-
from the usual oil-barrier insulation, depends upon the com- down strength of large oil gaps and oil quality gauges', Trans
Amer. Inst. Elect. Engrs, 1956, 75, Part III, p. 1439
plete elimination of oil voids. Minute imperfections can be 10 CLARK, F. M.: 'Are- new types of transformer oil needed?', Gen.
disastrous (Section 5.1). Elect. Rev., May 1948, p. 9
(k) The orthodox thermal ageing formulae, on which 11 STANNETT, A. w.: T h e measurement of water in power trans-
formers', Proceedings I.E.E., 1962, 109 A, Suppl. 3, p. 80
standard loading guides are based, are relative and therefore 12 GAZZANA-PRIAROGGIA, P., PALANDRI, G. L., a n d PELAGATTI, U. A . :
only applicable to comparative studies (Section 3.2). 'Influence of ageing characteristics of oil-filled cable dielectric',
ibid., 1961, 108 A, p. 467
(/) The actual life of transformer insulation in service is 13 'Papers for electrical purposes': B.S. 698: 1956
not indicated by the orthodox ageing calculations. It is so 14 'Presspaper for electrical purposes': B.S. 255: 1960
15 'Pressboard for electrical purposes': B.S. 231: 1950
much longer as to be not yet known (Section 5.4). 16 'Paper covered rectangular copper conductors for transformer
(m) The conservator-breather-dryer system in general use windings', B.S. 2776: 1956
for many years all over the world has given excellent service. 17 MURPHY, E. J. : 'Gases evolved by the thermal decomposition of
paper', Trans Electrochem. Soc, 1943, 83, p. 161
It has been found to have the unexpected attribute that, with 18 CLARK, F. M.: 'Chemical changes affecting the stability of cellulose
it, the insulation is automatically maintained in good condition insulation', ibid., 1943, 83, p. 143
19 CLARK, F. M. : 'Moisture in oil-treated transformer insulation',
by normal service operation (Section 5.5). Jndustr. engng Chem., 1952, p. 887
(n) Sealed or semi-sealed constructions permitting pressure 20 MONTSINGER, v.: 'Loading transformers by temperature', Trans
Amer. Inst. Elect. Engrs, 1930, 49, p. 776
variations in the oil are undesirable (Sections 2.2.2, 5.2.1 21 DAKIN, T. w.: 'Electrical insulation deterioration treated as a
and 5.5). chemical rate phenomena', ibid., 1948, 67, Part I, p. 113
(/>) The ideal of degassed oil in service will be possible 22 FABRE, J., and PICHON, A.: 'Deteriorating processes and products
of paper in oil. Application to transformer', C.I.G.R.fi., Paris,
only when permanent hermetic sealing can be attained and 1960, Report No. 137
maintained in normal operation. Remarkable improvement 23 LANGLOIS BERTHELOT, R. : 'Factors affecting the thermal performance
of oil immersed transformer windings', C.I.G.R.£., Paris, 1962,
in transformer insulation will then develop (Section 5.5). Report No. 135, 1962
24 POPOV, i.: Temperature rise and length of life of transformers',
C.I.G.R.E\, Paris, 1962, Report No. 101
25 AIGNER, v.: 'Corona detection in transformers', C.I.G.R.fi., Paris,
7 Acknowledgments 1962, Report No. 145
26 HARTILL, E. R., RYDER, D. H., JAMES, R. E., SMITH, L., a n d TAYLOR,
Attention is particularly directed to the reports of the F. w.: 'Some aspects of internal corona discharges in transformers',
C.I.G.R.fi. study group meetings given in References 23, 25 C.I.G.R.fi., Paris, 1962, Report No. 102
27 MEADOR, J. R., and DILLOW, N. E. : 'Dielectric tests on transformers-
and 35. These papers are necessarily written by an individual as influenced by further BIL research', Trans Amer. Inst. Elect.
author. They are, however, both national and international Engrs, 1960, 79, Part III, p. 99
in character as they summarize the conclusions and views, 28 MOLE, c : 'Design and performance of portable AC discharge
detector' (E.R.A. Report Ref. V/T115)
at the time, of most of the world's transformer experts, 29 SMITH, D. c. G. : T h e relation between dispersion and moisture
representing both the manufacturing and operation sides. content in paper insulation' (E.R.A. Report Ref. V/T128)
30 NORRIS, E. T. : 'Mechanical strength of power transformers in
The Bibliography gives a short pertinent selection of the service', Proceedings I.E.E., 1957, 104 A, p. 289
literature on this subject. Many of the references include, in 31 STANDRING, w. c , and HUGHES, R. c.: 'Impulse breakdown charac-
their turn, their own bibliographies, so that most of the teristics of solid and liquid dielectrics in combination', ibid., 1962,.
109 A, p. 473
relevant literature on this problem is accessible. 32 NORRIS, E. T.: 'Design', Journal I.E.E., 1947, 94, Part 1, p. 91
This literature is probably so extensive because of the 33 ALBRIGHT, w. D., and MOORE, H. R. : 'Inner-cooled shell-form
power transformers', Trans Amer. Inst. Elect. Engrs, 1959, 78,
practical, as distinct from the academic, complexity of the Part III, p. 46
PROCEEDINGS I.E.E., Vol. 110, No. 2, FEBRUARY 1963 439
34 HARTMANN, HANS: 'Progress in the design of transformers', 40 SUMNER, w. A., STEIN, G. M., and LOCKIE, A. M. : 'Life expectancy of
C.I.G.R.k, Paris, 1946, Report No. 108 oil-immersed insulation structure', Trans Amer. Inst. Elect. Engrs,
35 LUTZ, H.: 'Transformer oil preservation systems and associated 1953, 72, Part III. p. 924
problems', C.I.G.R.E., Paris, 1960, Report No. 134 41 A.I.E.E. Committee Report: 'Thermal limits of transformers for
36 DEGNAN, w. j . , and SHIMANSKI, E. J. : 'A field survey of transformer short-circuit conditions', ibid., I960, 79, Part III, p. 1083
oil quality', Trans Amer. Inst. Elect. Engrs, 1956, 75, Part I, p. 575 42 KRASUCKI, z.: 'Processes leading to discharges in oil-impregnated
37 FORREST, J. s.: 'An electrical resistance test for insulating oils', paper' (E.R.A. Report Ref. L/T410)
Journal I.E.E., 1948, 95, Part II, p. 337 43 NORRIS, E. T.: 'Transformer oil', / . Inst. Petrol., 1958, 44, p. 367
38 'Guides for loading oil-immersed distribution and power trans- 44 RUSHALL, R. T. : 'Dielectric properties of oil-soaked pressboard as
formers', American Standards Association, Appendix C.57 92 affected by water', Proceedings I.E.E., 1953, 100, Part IIA, p. 81
39 'Guide to loading of transformers', British Standard Code of 45 RODGERS, w. M. : 'Economic implications of higher temperatures
Practice, C.P.I010, 1959 for power transformers', A.I.E.E. Paper DP62-623

Centre, Sub-Centre and Section Chairmen's Addresses


North-Eastern Centre: Chairman's Address
THE GROWTH OF POWER TRANSFORMERS
R. Bruce, M.Sc, Member

Introduction.—The development of transformers over as a design guide and a confirmation of the degree to which
the years has been a gradual process of evolution, their mispositioning of windings on a limb can be tolerated.
principle having remained unchanged. Great strides have It is significant that any slight movement of a winding
been made, however, by more balanced designs and new under fault conditions results in an increase in force on a
ideas in design, aided by improvements in materials and repeated short-circuit, thus emphasizing the necessity of
manufacturing techniques, in raising the limits of voltage preventing displacement by effective clamping.
and rating to the present levels, with higher efficiencies and It is generally accepted that the hoop stresses caused by
proven reliability. radial forces in outer windings can be withstood by the
An important factor in recent progress, resulting in greatly tensile strength of the copper conductors themselves, but in a
increased rating for a given weight of transformer, has been large transformer with windings of soft copper, a severe
the development of cold-reduced grain-oriented core plate, short-circuit may cause small permanent elongation. This
which is capable of low-loss operation at higher flux density elongation is a safeguard against a repetition of the process
than the now almost obsolete hot-rolled plate. due to its work-hardening effect, but if there is a possibility
The properties of the new material have prompted much of long-term annealing at operating temperatures, subse-
thought in adjustments of the conventional methods of core quent faults may have some cumulative action. The use of
manufacture, in order to utilize its characteristics in the most work-hardened copper for windings is being considered as a
beneficial way, in particular, by the use of mitred corner means of eliminating elongation, the compromise to be
joints and techniques for minimizing or eliminating 'through' sought being windability with a sufficiently high proof stress.
clamping bolts. The use of silver-bearing copper may also have some benefit
Practical problems arising from physical non-uniformities in ensuring the elimination of long-term annealing.
of the plate, such as thickness variation and waviness, are In extremes of transport conditions, where the saving of
being gradually reduced. In particular, we look forward to every ton in weight is imperative, the use of aluminium
improvements in uniformity of magnetostriction and per- transformer tanks can be attractive. Benefits in transport-
meability characteristics, which will be beneficial in the further weight reductions by such means must be marginal, but may
reduction of noise levels. nevertheless be necessary. In the overall design of core and
Mechanical design considerations.—With the growth of windings, and tank, the method of lifting should be so devised
transformer ratings and the increase in weights, it is now that materials are utilized to the best advantage and thus kept
necessary to give greater attention to mechanical design. to minimum weight.
The mechanical problem is divisible into two main parts: Processing.—Oil-impregnated papers and pressboards are
(a) Winding design with respect to short-circuit forces. still regarded as the best materials for the insulation within
(6) Lifting and transport, associated with the design of the high-voltage transformers. The natural moisture-absorption
tank to withstand vacuum and pressure. properties of such materials is an accepted disadvantage, but
The calculation of axial forces has been a subject of earnest once dried and oil-impregnated, and maintained free from
pursuit for many years—the application of digital computers subsequent contamination, wholly satisfactory behaviour is
has made practicable complex calculations previously not assured.
attempted—but such calculated forces can be accepted only The shrinkage of absorbent insulating materials resulting
from the drying process is a matter which demands close
Abstract 4124 of Address delivered at Newcastle upon Tyne 8th October attention, and workshop techniques must be devised which
Mr. Bruce is with C. A. Parsons and Co. Ltd. will ensure that the shrinkage is fully taken up and the
440 PROCEEDINGS I.E.E., Vol. 110, No. 2, FEBRUARY 1963

Das könnte Ihnen auch gefallen