Sie sind auf Seite 1von 2

24ABS3

Baset Series Air Conditioner with Puronr


1---1/2 To 5 Nominal Tons

Wiring Diagrams
BLU CAP BLU
CONNECTION SCHEMATIC DIAGRAM (LADDER FORM)
BRN YEL *ST +t
DIAGRAM 2 1 *SC
H YEL L1 L2
COMP
*SR CONT R
(NOTE #8) 5 C
C
BLU 11 21
BLK F COMP
*CHS S
*CH C S
BLK BLK 5 2 *ST
or BLK BLK R *SC
RED EQUIP +t
(NOTE #9) YEL GND 1
RED or BLK YEL H
CONT CONT
*SR
L1 *CHS OFM
11 21 BRN C 23 23
208/230 1Ø L2 OFM
POWER 23 23 *CH F
BLK CAP
SUPPLY (NOTE #14)
EQUIP GND CONT
YEL
*HPS *DTS *LPS
(NOTE #14) BRN/YEL T2
YEL/ BLU BLK LOGIC
VIO
*CTD T1 T3
*LPS *DTS *HPS T2 *LLS * CTD
YEL YEL BLK BLK BLU BLU LOGIC
T1 T3 Y IFR
*LLS BRN/YEL G
EXTERNAL
BLK BLK POWER R C
C R
YEL/ BLU SUPPLY
R 24 V INDOOR
THERMOSTAT EXTERNAL POWER SUPPLY 24 V
(NOTE #3)
LEGEND
Y G R
INDOOR THERMOSTAT (NOTE #6) INDOOR BLOWER MOTOR
FACTORY POWER WIRING
FACTORY CONTROL WIRING
CONDENSING UNIT CHARGING INSTRUCTIONS FIELD CONTROL WIRING
For use with units using R-22 refrigerant FIELD POWER WIRING
REQUIRED LIQUID LINE TEMPERATURE COOLING ONLY COMPONENT CONNECTION
Liquid (PSIG) Required Subcooling CHARGING PROCEDURE FIELD SPLICE
Pressure 1. Only use sub cooling charging method when OD JUNCTION
at Service Temperature (ºF) ambient is greater than 70ºF and less than 100ºF, PLUG RECEPTACLE
Valve 5 10 15 20 indoor temp is greater than 70ºF and less than CONT CONTACTOR
163 83 78 73 68 80ºF, and line set is less than 80 ft.
2. Operate unit a minimum of 15 minutes before CAP CAPACITOR (DUAL RUN)
171 86 81 76 71
checking the charge. *CH CRANKCASE HEATER
179 89 84 79 74
3. Measure liquid service valve pressure by attaching *CHS CRANKCASE HEATER SWITCH
187 92 87 82 77 an accurate gauge to the service port.
196 95 90 85 80 4. Measure the liquid line temperature by COMP COMPRESSOR
205 98 93 88 83 attaching an accurate thermistor type or *CTD COMPRESSOR TIME DELAY
101 96 91 86 electronic thermometer to the liquid line *DTS DISCHARGE TEMP SWITCH
214
near the outdoor coil.
223 104 99 94 89 *HPS HIGH PRESSURE SWITCH
5. Refer to unit rating plate for required
233 107 102 97 92 subcooling temperature. IFR INDOOR FAN RELAY
243 110 105 100 95 6. Find the point where the required subcooling *LLS LIQ LINE SOLENOID VALVE
temperature intersects the measured liquid LOW PRESSURE SWITCH
253 113 108 103 98 *LPS
service valve pressure.
264 116 111 106 101 7. To obtain the required subcooling temperature OFM OUTDOOR FAN MOTOR
274 119 114 109 104 at specific liquid line pressure, add refrigerant *SC START CAPICATOR
if liquid line temperature is higher than indicated. *SR START RELAY
285 122 117 112 107 When adding refrigerant, charge in liquid form
using a flow restricting device into suction *ST START THERMISTOR
297 125 120 115 110
service port. Recover refrigerant if temperature
309 128 123 118 113 is lower. Allow a tolerance of +/- 3ºF.
* MAY BE FACTORY INSTALLED

NOTES:
1. Symbols are electrical representation only.
CAUTION
2. Compressor and fan motor furnished with inherent thermal protection. 1. Compressor damage may occur if system is over charged.
3. To be wired in accordance with National Electric N.E.C. and local codes. 2. This unit is factory charged with R-22 in accordance with
4. N.E.C. class 2, 24 V circuit, min. 40 VA required, 60 VA on units installed with LLS. the amount shown on the rating plate. The charge is
5. Use copper conductors only. Use conductors suitable for at least 75ºC (167ºF).
6. Connection for typical cooling only thermostat. For other arrangements see installation adequate for most systems using matched coils and tubing
instructions. not over 15 feet long. Check refrigerant charge for maximum
7. If indoor section has a transformer with a grounded secondary, connect the grounded efficiency. See Product Data Literature for required Indoor
side to the BRN/YEL lead.
8. When start relay and start capacitor are installed, start thermistor is not used. air Flow Rates and for use of line lengths over 15 feet.
9. CH not used on all units. 3. Relieve pressure and recover all refrigerant before system
10. If any of the original wire, as supplied must be replaced, use the same or equivalent wire. repair or final disposal. Use all service ports and open all
11. Check all electrical connections inside control box for tightness.
12. Do not attempt to operate unit until service valves have been opened. flow-control devices, including solenoid valves.
13. Do not rapid cycle compressor. Compressor must be off 3 minutes to allow pressures to 4. Never vent refrigerant to atmosphere. Use approved
equalize between high and low side before starting. recovery equipment.
14. Wire not present if HPS, LPS or CTD are used. 330361-101 REV. F

Fig. 1 – Wiring Diagram — Model sizes 1--1/2 -- 5 tons, 208/230--1


CONNECTION DIAGRAM SCHEMATIC DIAGRAM (LADDER FORM)
*CHS * CH L1 L2 L3
RED or BLK BLK
PRM L2
L2 RED or BLK L3 L1
208/23 0 3Ø BLU
CONT COMP
OR L1 T1 T2
11 21 BLK
460 3Ø
L3 T3
POWER 13 23 CONT T2
CAP EQUIP T1
SUPPLY YEL 11 21 COMP
YEL GND
T3
EQUIP GND OFM CAP CONT
BRN
BLK 23 13
YEL BLK
*CHS
BLU OFM
PRM *CH
YEL
BLU PRM
L1 L3 L2
CONT 24V COM
CONT 24 COM
BLK
BRN/YEL BRN/YEL
*LPS *HPS
VIO T2 CONT
YEL/BLU
LOGIC
T1 T3
*LPS *HPS * CTD *LLS * CTD
T2
YEL YEL BLU BLU LOGIC Y
T1 T3
IFR
G
BRN/YEL
R C
*LLS R
EXTERNAL INDOOR
BLK BLK THERMOSTAT EXTERNAL POWER SUPPLY 24 V
POWER
C
R SUPPLY
IFR LEGEND NOTES:
24 V
(NOTE #3)
NOTE 1. Symbols are electrical
PRM LED INDICATOR FACTORY POWER WIRING
representation only.
Y G R OFF: NO 24VAC FACTORY CONTROL WIRING
2. Compressor and fan motor
ON: OK furnished with inherent
INDOOR THERMOSTAT (NOTE #6) INDOOR BLOWER MOTOR FLASH: PHASE PROBLEM FIELD CONTROL WIRING
thermal protection.
FIELD POWER WIRING
3. To be wired in accordance
CONDENSING UNIT CHARGING INSTRUCTIONS with National Electric
COMPONENT CONNECTION
N.E.C. and local codes.
For use with units using R-22 refrigerant FIELD SPLICE
4. N.E.C. class 2, 24 V circuit,
min. 40 VA required,
JUNCTION
REQUIRED LIQUID LINE TEMPERATURE COOLING ONLY CHARGING 60 VA on units installed
CONT CONTACTOR with LLS.
Liquid (PSIG) Required Subcooling PROCEDURE 5. Use copper conductors
Pressure CAP CAPACITOR (DUAL RUN) only. Use conductors
Temperature (ºF) 1. Only use sub cooling charging method suitable for at least
at Service when OD ambient is greater than 70ºF *CH CRANKCASE HEATER 75ºC (167ºF).
Valve 5 10 15 20
and less than 100ºF, indoor temp is *CHS CRANKCASE HEATER SWITCH 6. Connection for typical
cooling only thermostat.
greater than 70ºF and less than 80ºF, COMP COMPRESSOR For other arrangements
163 83 78 73 68 see installation instructions.
and line set is less than 80 ft. *CTD COMPRESSOR TIME DELAY 7. If indoor section has a
171 86 81 76 71 2. Operate unit a minimum of 15 minutes
*HPS HIGH PRESSURE SWITCH transformer with a
179 89 84 79 74 before checking the charge. grounded secondary,
IFR INDOOR FAN RELAY connect the grounded
187 92 87 82 77 3. Measure liquid service valve pressure by side to the BRN/YEL lead.
*LLS LIQ LINE SOLENOID VALVE
196 95 90 85 80 attaching an accurate gauge to the 8. If any of the original wire,
service port. *LPS LOW PRESSURE SWITCH as supplied must be
205 98 93 88 83 replaced, use the same or
4. Measure the liquid line temperature by OFM OUTDOOR FAN MOTOR equivalent wire.
214 101 96 91 86 attaching an accurate thermistor type or PRM PHASE ROTATION MONITOR 9. Check all electrical
connections inside control
223 104 99 94 89 electronic thermometer to the liquid line * MAY BE FACTORY INSTALLED box for tightness.
92 near the outdoor coil. 10. Do not attempt to operate
233 107 102 97
95 5. Refer to unit rating plate for required
CAUTION
unit service valves have
been opened.
243 110 105 100 1. Compressor damage may occur if system is 11. Do not rapid cycle
subcooling temperature.
253 113 108 103 98 6. Find the point where the required over charged. compressor.
2. This unit is factory charged with R-22 in Compressor must be off
264 116 111 106 101 subcooling temperature intersects the 3 minutes to allow
accordance with the amount shown on the
274 119 114 109 104 measured liquid service valve pressure. pressures to equalize
rating plate. The charge is adequate for most between high and low
285 122 117 112 107 7. To obtain the required subcooling systems using matched coils and tubing not side before starting.
temperature at specific liquid line over 15 feet long. Check refrigerant charge 12. It is imperative to connect
297 125 120 115 110 for maximum efficiency. See Product Data 3Ø field power to unit with
pressure, add refrigerant if liquid line correct phasing. The
309 128 123 118 113 temperature is higher than indicated.
Literature for required Indoor air Flow Rates
Phase Rotation Monitor
and for use of line lengths over 15 feet. will not allow the contactor
When adding refrigerant, charge in liquid 3. Relieve pressure and recover all refrigerant
to be energized if the
form using a flow restricting device into before system repair or final disposal. Use all phasing is not correct. If
suction service port. Recover refrigerant service ports and open all flow-control phasing is reversed,
devices, including solenoid valves. simply inter change any
if temperature is lower. Allow a two of the three power
4. Never vent refrigerant to atmosphere. Use
330757-101 REV.C tolerance of +/- 3ºF. connections on field side.
approved recovery equipment.

Fig. 2 – Wiring Diagram — Model sizes 2--1/2 -- 5 tons, 208/230--3 and Model sizes 3 -- 5 tons, 460--3

Copyright 2009 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 09/09 Catalog No: 24ABS3---1W
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: New

Das könnte Ihnen auch gefallen