Structural Computation
August 2019
Contents
General Notes
1. Structural drawings shall be used in conjunction with the specifications and drawings
by other disciplines. All work shall conform to the requirements of the codes listed
below.
2. Contractors shall verify all dimensions and elevations relating to existing conditions by
making field surveys and measurements prior to commencing fabrication or
construction.
3. The general contractor shall ensure that all construction methods used will not cause
damage to adjacent buildings, utilities, or other property. This requirement is
particularly important during foundation installation.
5. The general contractor shall obtain copies of the latest contract documents including
all addenda, and provide the relevant portions to all sub-contractors and suppliers prior
to submittal of shop drawings and fabrication and erection of structural members.
6. The general contractor shall compare and coordinate the drawings of all disciplines
and report any discrepancies between the drawings to the architect and engineer.
7. Details labeled “typical” shall apply to all situations that are the same or similar to those
specifically detailed. See detail titles for applicability of a particular detail. Typical
details shall apply whether or not they are specifically keyed at each location. The
engineer shall have final authority to determine applicability of typical details.
9. Delegated engineer requirements: the National Structural Code of the Philippines has
issued statements on responsibilities of professional engineers, pursuant to chapters…
Certain components of the structure require the work of delegated engineers for the
design of those components. All relevant procedures presented in the NSCP shall
apply to this project.
10. The general contractor shall review and determine that dimensions are coordinated
between architectural and structural drawings prior to fabrication or start of
construction.
11. No structural member shall be cut or notched or otherwise reduced in strength unless
approved by the structural engineer.
12. The general contractor shall coordinate architectural, mechanical, electrical and
plumbing drawings for anchored, embedded or supported items. Notify the architect /
engineer of any discrepancies.
Construction Responsibility
1. The contract structural drawings and specifications represent the completed structure,
and are not intended to indicate the method or means of construction. The contractor
shall supervise and direct the work and shall be solely responsible for all construction
means, methods, procedures, techniques, sequences, and for job safety.
General Notes and Specifications
Pg. 02
2. The engineer does not have control or charge of, and shall not be responsible for ,
construction means, methods, techniques, sequences, or procedures, for safety
precautions and programs in connection with the work, for the acts or omissions of the
contractor, subcontractor, or any other persons performing any of the work, or for the
failure of any of them to carry out the work in accordance with the contract documents.
3. Periodic site observation visits may be provided by the structural engineer. The sole
purpose of these observations is to review the general conformance of the construction
with the structural contract documents. These limited observations should not be
construed as continuous or exhaustive to verify that all construction is in compliance
with the construction documents. The general contractor shall be responsible for
performing all work in compliance with the construction documents.
Specifications
Design code used for various components are summarized below:
Material Properties
Steel Properties
Steels used must be intended for structural application as defined in general by the
specifications of the American Society for Testing Materials (ASTM) . Structural steel material
conforming to one of the following ASTM specifications is approved for use under this
specification:
2. Structural Tubing:
ASTM A500 , A501, A618, A847
3. Bars:
ASTM A36/A36M, A529/A529M, A572/A572M, A709/A709M
4. Steel Bolts:
ASTM A307, A325/A325M, A449,,A490/A490M, F1852
5. Nuts:
ASTM A194/A194M, A563/A563M
Load Estimation
Dead Loads:
Self-weight
assigned to all members
Load Combinations:
Shelves
Load Combination 1: D
APPENDIX C
Pg. 05
Section Properties
Nominal Section Member Assignment
Main Frame:
L 20203
Single
Depth: 50 mm (2 in.)
Width: 50 mm (2 in,)
Thickness: 5 mm ( 3/16 in.)
Main Frame:
L 20203
Double
Depth: 50 mm (2 in.)
Width: 50 mm (2 in,)
Thickness: 5 mm ( 3/16 in.)
Tubulars:
S/S Round Tubes
Φ 25mm – 3 mm
Outer Diameter: 25 mm (1 in.)
Thickness: 3 mm
0.1
18 PRISMATIC PASS EQ H1-1B 0.047 1 C 0 0.01 0.93
21 LD L20203 PASS SEC. F1 0.015 1 0T 0 0.02 0.1
1.79
22 PRISMATIC PASS EQ H1-2 0.124 1 C 0.01 0.02 0
23 LD L20203 PASS SEC. F1 0.015 1 0T 0 0.02 0.1
0.03
24 PRISMATIC PASS EQ H1-1B 0.055 1 T 0 0.02 0.89
0.02
25 LD L20203 PASS SEC. F1 0.017 1 C 0.02 0.02 0.1
0.19
55 PRISMATIC PASS EQ H1-1B 0.055 1 C 0 0.02 0
0.1 -
59 PRISMATIC PASS EQ H1-1B 0.053 1 T 0 0.02 0.47
-
60 LD L20203 PASS EQ. H2-1 0.007 1 0T 0.01 0.01 0.1
0.06
61 PRISMATIC PASS EQ H1-1B 0.058 1 C 0 0.02 0.93
0.26
62 PRISMATIC PASS EQ H1-1B 0.054 1 C 0 0.02 0
-
63 LD L20203 PASS SEC. F1 0.013 1 0T 0.01 0.02 0.1
1.19 -
67 PRISMATIC PASS EQ H1-1B 0.089 1 C 0 0.02 0.4
0.93
68 PRISMATIC PASS EQ H1-1B 0.063 1 C 0 0.01 0.89
0.37
69 PRISMATIC PASS EQ H1-1B 0.051 1 C 0 0.01 0.89
0.1 -
70 LD L20203 PASS SEC. F1 0.045 1 C 0.02 0.06 0.1
-
74 ST L20203 PASS EQ H1-1B 0.183 1 0C 0.11 0.06 0
-
75 ST L20203 PASS EQ H1-1B 0.124 1 0T 0.07 0.02 0
-
76 ST L20203 PASS EQ H1-1B 0.062 1 0T 0.04 0.01 0
-
77 ST L20203 PASS EQ. H3-8 0.029 1 0T 0.01 0 0
78 LD L20203 PASS SEC. F1 0.366 1 0C 0 0.51 0.1
80 LD L20203 PASS SEC. F1 0.235 1 0C 0.01 0.33 0.1
82 LD L20203 PASS SEC. F1 0.132 1 0C 0.01 0.18 0.1
84 LD L20203 PASS SEC. F1 0.059 1 0T 0.01 0.08 0.1
0.01
86 LD L20203 PASS SEC. F1 0.357 1 C 0 0.5 0.1
0.01 -
88 LD L20203 PASS SEC. F1 0.227 1 C 0.01 0.32 0.1
90 LD L20203 PASS SEC. F1 0.127 1 0C 0 0.18 0.1
92 LD L20203 PASS SEC. F1 0.056 1 0C 0.01 0.08 0.1
1.18 -
94 ST L20203 PASS EQ H1-1B 0.231 1 C 0.13 0.11 0.1
1.18 -
96 ST L20203 PASS EQ H1-1B 0.166 1 C 0.09 0.04 0.1
1.19 -
98 ST L20203 PASS EQ H1-1B 0.089 1 C 0.05 0.01 0.1
1.19 -
100 ST L20203 PASS EQ H1-1B 0.03 1 C 0.01 0.01 0
0.14
102 ST L20203 PASS EQ H1-1B 0.037 1 T 0 0.02 0
0.14 - -
103 ST L20203 PASS EQ H1-1B 0.044 1 T 0.03 0.01 0.1
0.14 - -
104 ST L20203 PASS EQ H1-1B 0.038 1 T 0.02 0.01 0
0.14
105 ST L20203 PASS EQ. H3-8 0.07 1 T 0 0 0.1
0.02
106 LD L20203 PASS SEC. F1 0.058 1 C 0.02 0.08 0.1
0.02
108 LD L20203 PASS SEC. F1 0.128 1 C 0.01 0.18 0.1
0.02
110 LD L20203 PASS SEC. F1 0.225 1 C 0 0.31 0.1
0.03
112 LD L20203 PASS SEC. F1 0.35 1 C 0 0.49 0.1
0.1 -
114 LD L20203 PASS SEC. F1 0.102 1 C 0.02 0.14 0.1
0.1 -
116 LD L20203 PASS SEC. F1 0.186 1 C 0.01 0.26 0.1
APPENDIX C
Pg. 08
0.11
118 LD L20203 PASS SEC. F1 0.299 1 C 0 0.42 0.1
0.11
120 LD L20203 PASS SEC. F1 0.441 1 C 0 0.61 0.1
0.34
122 ST L20203 PASS EQ. H3-8 0.102 1 T 0.04 0.05 0.1
0.35
124 ST L20203 PASS EQ H1-1B 0.038 1 T 0.01 0.02 0.1
0.35 - -
126 ST L20203 PASS EQ H1-1B 0.047 1 T 0.03 0.01 0
0.35 -
128 ST L20203 PASS EQ H1-1B 0.043 1 T 0.02 0 0
0.01
130 ST L20203 PASS EQ H1-1B 0.478 1 C 0.28 0.14 0
131 ST L20203 PASS EQ H1-1B 0.389 1 0C 0.23 0.07 0
132 ST L20203 PASS EQ H1-1B 0.264 1 0C 0.16 0.04 0
133 ST L20203 PASS EQ H1-1B 0.15 1 0C 0.09 0.02 0
134 ST L20203 PASS EQ H1-1B 0.068 1 0C 0.04 0.01 0
135 ST L20203 PASS EQ. H3-8 0.029 1 0T 0.01 0 0
136 LD L20203 PASS SEC. F1 0.788 1 0C 0.01 1.1 0.1
0.01 -
138 LD L20203 PASS SEC. F1 0.578 1 C 0.04 0.81 0.1
-
140 LD L20203 PASS SEC. F1 0.401 1 0C 0.04 0.56 0.1
-
142 LD L20203 PASS SEC. F1 0.256 1 0C 0.03 0.36 0.11
-
144 LD L20203 PASS SEC. F1 0.143 1 0C 0.02 0.2 0.1
-
146 LD L20203 PASS SEC. F1 0.063 1 0T 0.01 0.09 0.1
0.02
148 LD L20203 PASS SEC. F1 0.707 1 C 0 0.99 0.1
0.01
150 LD L20203 PASS SEC. F1 0.51 1 C 0.01 0.71 0.1
0.01 -
152 LD L20203 PASS SEC. F1 0.345 1 C 0.01 0.48 0.1
0.01 -
154 LD L20203 PASS SEC. F1 0.212 1 C 0.02 0.3 0.11
-
156 LD L20203 PASS SEC. F1 0.112 1 0C 0.03 0.16 0.1
-
158 LD L20203 PASS SEC. F1 0.044 1 0C 0.02 0.06 0.1
1.2
160 ST L20203 PASS EQ H1-1B 0.269 1 C 0.15 0.13 0.1
1.21
162 ST L20203 PASS EQ H1-1B 0.192 1 C 0.11 0.05 0.1
1.22
164 ST L20203 PASS EQ H1-1B 0.092 1 C 0.05 0.01 0.1
1.23 - -
166 ST L20203 PASS EQ H1-1B 0.081 1 C 0.04 0.02 0
1.23 - -
168 ST L20203 PASS EQ H1-1B 0.119 1 C 0.07 0.02 0
1.23 - -
170 ST L20203 PASS EQ H1-1B 0.134 1 C 0.08 0.03 0.1
Connection Design
Support reactions are tabulated below.
Use dyna bolt with 12 mm diameter with an embedment length of at least 50mm. Apply
grouting.
Interaction
Node L/C Fx (kN) Fy (kN) Fz (kN) Pexp Vx exp Vy exp
Ratio
28 DL -1.22 0.76 -0.718 -1.22 -0.718 0.76 0.23
29 DL 1.236 0.004 0.118 1.236 0.118 0.004 0.14
30 DL -0.132 0.237 -0.196 -0.196 -0.132 0.237 0.04
31 DL -0.518 0.216 -0.461 -0.461 -0.518 0.216 0.10
32 DL 2.646 1.094 -1.358 2.646 -1.358 1.094 0.44
APPENDIX C
Pg. 09
Source:
https://www.itwredhead.com/portals/0/fmproductcatalog/documents/products/33/dynabolttechni
caldata.pdf
′
𝐹𝑐𝑟 = 𝑓𝐶𝐻𝐵 × 𝐴𝐶𝑂𝑁𝐸
𝐴𝐶𝑂𝑁𝐸 = 𝜋𝑟 √𝑟 2 + ℎ2
Since angle of rupture is 450 then r = h. Moreover, CHB strength is at 800 psi
𝐹𝑐𝑟 = 61.09 𝑘𝑁