IEEE Std 1250™-2018
(Revision of IEEE Std 1250-2011)

IEEE Guide for Identifying and


Improving Voltage Quality in Power
Systems

Sponsor

Transmission and Distribution Committee


of the
IEEE Power and Energy Society

Approved 27 September 2018

IEEE-SA Standards Board

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
Abstract: The use of some electrical equipment attached to typical power systems creates power
quality concerns. There is an increasing awareness that some equipment is not designed to
withstand the surges, faults, distortion, and reclosing duty present on typical utility distribution
systems. Traditional concerns about steady-state voltage levels and light flicker due to voltage
fluctuation also remain. These concerns are addressed by this guide by documenting typical
levels of these aspects of power quality and indicating how to improve them. Other documents
that treat these subjects in more detail are referenced.

Keywords: benchmarking, dips, disturbance analyzers, faults, harmonic distortion, IEEE 1250,
light flicker, momentary voltage disturbances, noise, performance, power conditioners, power
quality, sags, susceptible equipment, surge protection, surges, swells, transients, voltage
fluctuation, voltage quality

Some of the material used in this standard was reprinted with permission from documents
produced by EPRI:

EPRI makes no warranty or representations, expressed or implied, with respect to


the accuracy, completeness, or usefulness of the information contained in the
Material. Additionally, EPRI assumes no liability with respect to the use of, or for
damages resulting from, the use of the Material.

The Institute of Electrical and Electronics Engineers, Inc.


3 Park Avenue, New York, NY 10016-5997, USA

Copyright © 2018 by the Institute of Electrical and Electronics Engineers, Inc.


All rights reserved. Published 16 November 2018. Printed in the United States of America.

IEEE is a registered trademark in the U.S. Patent & Trademark Office, owned by the Institute of Electrical and Electronics Engineers,
Incorporated.

PDF: ISBN 978-1-5044-5203-8 STD23330


Print: ISBN 978-1-5044-5204-5 STDPD23330

IEEE prohibits discrimination, harassment and bullying. For more information, visit http://www.ieee.org/web/aboutus/whatis/policies/p9-
26.html.

No part of this publication may be reproduced in any form, in an electronic retrieval system or otherwise, without the prior written permission
of the publisher.

2
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
Important Notices and Disclaimers Concerning IEEE Standards Documents
IEEE documents are made available for use subject to important notices and legal disclaimers. These
notices and disclaimers, or a reference to this page, appear in all standards and may be found under the
heading “Important Notices and Disclaimers Concerning IEEE Standards Documents.” They can also be
obtained on request from IEEE or viewed at http://standards.ieee.org/IPR/disclaimers.html.

Notice and Disclaimer of Liability Concerning the Use of IEEE Standards


Documents
IEEE Standards documents (standards, recommended practices, and guides), both full-use and trial-use, are
developed within IEEE Societies and the Standards Coordinating Committees of the IEEE Standards
Association (“IEEE-SA”) Standards Board. IEEE (“the Institute”) develops its standards through a
consensus development process, approved by the American National Standards Institute (“ANSI”), which
brings together volunteers representing varied viewpoints and interests to achieve the final product.
Volunteers are not necessarily members of the Institute and participate without compensation from IEEE.
While IEEE administers the process and establishes rules to promote fairness in the consensus development
process, IEEE does not independently evaluate, test, or verify the accuracy of any of the information or the
soundness of any judgments contained in its standards.
IEEE does not warrant or represent the accuracy or content of the material contained in its standards, and
expressly disclaims all warranties (express, implied and statutory) not included in this or any other
document relating to the standard, including, but not limited to, the warranties of: merchantability; fitness
for a particular purpose; non-infringement; and quality, accuracy, effectiveness, currency, or completeness
of material. In addition, IEEE disclaims any and all conditions relating to: results; and workmanlike effort.
IEEE standards documents are supplied “AS IS” and “WITH ALL FAULTS.”
Use of an IEEE standard is wholly voluntary. The existence of an IEEE standard does not imply that there
are no other ways to produce, test, measure, purchase, market, or provide other goods and services related
to the scope of the IEEE standard. Furthermore, the viewpoint expressed at the time a standard is approved
and issued is subject to change brought about through developments in the state of the art and comments
received from users of the standard.
In publishing and making its standards available, IEEE is not suggesting or rendering professional or other
services for, or on behalf of, any person or entity nor is IEEE undertaking to perform any duty owed by any
other person or entity to another. Any person utilizing any IEEE Standards document, should rely upon his
or her own independent judgment in the exercise of reasonable care in any given circumstances or, as
appropriate, seek the advice of a competent professional in determining the appropriateness of a given
IEEE standard.
IN NO EVENT SHALL IEEE BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL,
EXEMPLARY, OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO:
PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS;
OR BUSINESS INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY,
WHETHER IN CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR
OTHERWISE) ARISING IN ANY WAY OUT OF THE PUBLICATION, USE OF, OR RELIANCE
UPON ANY STANDARD, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE AND
REGARDLESS OF WHETHER SUCH DAMAGE WAS FORESEEABLE.

Translations
The IEEE consensus development process involves the review of documents in English only. In the event
that an IEEE standard is translated, only the English version published by IEEE should be considered the
approved IEEE standard.

3
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
Official statements
A statement, written or oral, that is not processed in accordance with the IEEE-SA Standards Board
Operations Manual shall not be considered or inferred to be the official position of IEEE or any of its
committees and shall not be considered to be, or be relied upon as, a formal position of IEEE. At lectures,
symposia, seminars, or educational courses, an individual presenting information on IEEE standards shall
make it clear that his or her views should be considered the personal views of that individual rather than the
formal position of IEEE.

Comments on standards
Comments for revision of IEEE Standards documents are welcome from any interested party, regardless of
membership affiliation with IEEE. However, IEEE does not provide consulting information or advice
pertaining to IEEE Standards documents. Suggestions for changes in documents should be in the form of a
proposed change of text, together with appropriate supporting comments. Since IEEE standards represent a
consensus of concerned interests, it is important that any responses to comments and questions also receive
the concurrence of a balance of interests. For this reason, IEEE and the members of its societies and
Standards Coordinating Committees are not able to provide an instant response to comments or questions
except in those cases where the matter has previously been addressed. For the same reason, IEEE does not
respond to interpretation requests. Any person who would like to participate in revisions to an IEEE
standard is welcome to join the relevant IEEE working group.
Comments on standards should be submitted to the following address:
Secretary, IEEE-SA Standards Board
445 Hoes Lane
Piscataway, NJ 08854 USA

Laws and regulations


Users of IEEE Standards documents should consult all applicable laws and regulations. Compliance with
the provisions of any IEEE Standards document does not imply compliance to any applicable regulatory
requirements. Implementers of the standard are responsible for observing or referring to the applicable
regulatory requirements. IEEE does not, by the publication of its standards, intend to urge action that is not
in compliance with applicable laws, and these documents may not be construed as doing so
Copyrights

IEEE draft and approved standards are copyrighted by IEEE under U.S. and international copyright laws.
They are made available by IEEE and are adopted for a wide variety of both public and private uses. These
include both use, by reference, in laws and regulations, and use in private self-regulation, standardization,
and the promotion of engineering practices and methods. By making these documents available for use and
adoption by public authorities and private users, IEEE does not waive any rights in copyright to the
documents.

Photocopies

Subject to payment of the appropriate fee, IEEE will grant users a limited, non-exclusive license to
photocopy portions of any individual standard for company or organizational internal use or individual,
non-commercial use only. To arrange for payment of licensing fees, please contact Copyright Clearance
Center, Customer Service, 222 Rosewood Drive, Danvers, MA 01923 USA; +1 978 750 8400. Permission
to photocopy portions of any individual standard for educational classroom use can also be obtained
through the Copyright Clearance Center.

4
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
Updating of IEEE Standards documents

Users of IEEE Standards documents should be aware that these documents may be superseded at any time
by the issuance of new editions or may be amended from time to time through the issuance of amendments,
corrigenda, or errata. An official IEEE document at any point in time consists of the current edition of the
document together with any amendments, corrigenda, or errata then in effect.

Every IEEE standard is subjected to review at least every ten years. When a document is more than ten
years old and has not undergone a revision process, it is reasonable to conclude that its contents, although
still of some value, do not wholly reflect the present state of the art. Users are cautioned to check to
determine that they have the latest edition of any IEEE standard.

In order to determine whether a given document is the current edition and whether it has been amended
through the issuance of amendments, corrigenda, or errata, visit the IEEE-SA Website at
http://ieeexplore.ieee.org/xpl/standards.jsp or contact IEEE at the address listed previously. For more
information about the IEEE SA or IEEE’s standards development process, visit the IEEE-SA Website at
http://standards.ieee.org.

Errata

Errata, if any, for all IEEE standards can be accessed on the IEEE-SA Website at the following URL:
http://standards.ieee.org/findstds/errata/index.html. Users are encouraged to check this URL for errata
periodically.

Patents

Attention is called to the possibility that implementation of this standard may require use of subject matter
covered by patent rights. By publication of this standard, no position is taken by the IEEE with respect to
the existence or validity of any patent rights in connection therewith. If a patent holder or patent applicant
has filed a statement of assurance via an Accepted Letter of Assurance, then the statement is listed on the
IEEE-SA Website at http://standards.ieee.org/about/sasb/patcom/patents.html. Letters of Assurance may
indicate whether the Submitter is willing or unwilling to grant licenses under patent rights without
compensation or under reasonable rates, with reasonable terms and conditions that are demonstrably free of
any unfair discrimination to applicants desiring to obtain such licenses.

Essential Patent Claims may exist for which a Letter of Assurance has not been received. The IEEE is not
responsible for identifying Essential Patent Claims for which a license may be required, for conducting
inquiries into the legal validity or scope of Patents Claims, or determining whether any licensing terms or
conditions provided in connection with submission of a Letter of Assurance, if any, or in any licensing
agreements are reasonable or non-discriminatory. Users of this standard are expressly advised that
determination of the validity of any patent rights, and the risk of infringement of such rights, is entirely
their own responsibility. Further information may be obtained from the IEEE Standards Association.

5
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
Participants
At the time this guide was submitted to the IEEE-SA Standards Board for approval, the Voltage Quality
Working Group had the following membership:

Theo Laughner, Chair


Steve Tatum, Vice Chair
David Zech, Secretary

Mohamad Abdelrahman Geza Joss Scott Peele


Rich Bingham Marc Lacroix Paulo Ribeiro
Gary Chang Chester Li Sarah Ronnberg
Tom Cooke Alex McEachern Daniel Sabin
Jiri Drapola Carl Miller Ken Sedziol
Joseph Grappe Dave Mueller Harish Sharma
Mark Halpin Matthew Norwalk Brian Wong
Steven Johnston Francisc Zavoda

The following members of the balloting committee voted on this guide. Balloters may have voted for
approval, disapproval, or abstention.

Ali Al Awazi John Houdek Christopher Petrola


Saleman Alibhay William Howe Iulian Profir
Jason Andrews Steven Johnston Reynaldo Ramos
Curtis Ashton Laszlo Kadar John Roach
Thomas Barnes Innocent Kamwa Charles Rogers
Steven Bezner Peter Kelly Thomas Rozek
Rich Bingham Yuri Khersonsky Ryandi Ryandi
Jeffrey Brogdon James Kinney Daniel Sabin
Gustavo Brunello Gary Kobet Steven Sano
Demetrio Jr Bucaneg Boris Kogan Sergio Santos
William Bush Jim Kulchisky Bartien Sayogo
William Byrd Benjamin Lanz Ken Sedziol
Thomas Callsen Theo Laughner Suresh Shrimavle
Sean Carr Lawrenc Long Jerry Smith
Wen-Kung Chang Bruce Mackie Gary Smullin
Michael Chirico Reginaldo Maniego Wayne Stec
Glenn Davis John McDaniel Gary Stoedter
Mamadou Diong Thomas McDermott K. Stump
Gary Donner Sean McGuinness Sercan Teleke
Neal Dowling Arun Narang David Tepen
Donald Dunn Alexandre Nassif James Van De Ligt
Jorge Fernandez Daher Arthur Neubauer John Vergis
Gearold O. H. Eidhin Joe Nims William Walter
Dale Fredrickson Matthew Norwalk Daniel Ward
Mietek Glinkowski Gregory Olson Steven Whisenant
Joseph Grappe Marty Page Kenneth White
Randall Groves Jan Paramalingam James Wikston
Thomas Gruzs Bansi Patel Wilsun Xu
Lee Herron Dhiru Patel Nicholas Zagrodnik
Werner Hoelzl Marc Patterson Francisc Zavoda
Ronald Hotchkiss David Zech

6
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
When the IEEE-SA Standards Board approved this guide on 27 September 2018, it had the following
membership:

Jean-Philippe Faure, Chair


Gary Hoffman, Vice Chair
John D. Kulick, Past Chair
Konstantinos Karachalios, Secretary

Ted Burse Xiaohui Liu Robby Robson


Guido R. Hiertz Kevin Lu Dorothy Stanley
Christel Hunter Daleep Mohla Mehmet Ulema
Joseph L. Koepfinger* Andrew Myles Phil Wennblom
Thomas Koshy Paul Nikolich Philip Winston
Hung Ling Ronald C. Petersen Howard Wolfman
Dong Liu Annette D. Reilly Jingyi Zhou

*Member Emeritus

7
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
Contents
1. Overview .................................................................................................................................................... 9

1.1 Scope ................................................................................................................................................... 9


1.2 Purpose ................................................................................................................................................ 9

2. The power system ....................................................................................................................................... 9

2.1 Introduction ......................................................................................................................................... 9


2.2 Overview of power systems............................................................................................................... 10

3. Identifying power quality in electrical systems ........................................................................................ 12

3.1 Introduction ....................................................................................................................................... 12


3.2 Basic types of power quality variations ............................................................................................. 13
3.3 Steady-state (continuous) voltage characteristics .............................................................................. 13
3.4 Disturbances ...................................................................................................................................... 28
3.5 Conclusions ....................................................................................................................................... 36

4. Susceptibility of power system loads ....................................................................................................... 36

4.1 Types of susceptible loads ................................................................................................................. 36


4.2 Ride-through capability ..................................................................................................................... 39

5. Power quality improvements for end users .............................................................................................. 39

5.1 End user wiring and grounding.......................................................................................................... 40


5.2 Premium power solutions .................................................................................................................. 40
5.3 End-user power conditioning (within the facility) ............................................................................. 43
5.4 Controlling harmonics ....................................................................................................................... 49
5.5 Surge protective devices (SPDs)........................................................................................................ 51
5.6 Special considerations for variable frequency drives (VFDs) ........................................................... 51
5.7 Special considerations for residential loads ....................................................................................... 52
5.8 Economic analysis of power conditioning alternatives...................................................................... 52

Annex A (informative) Glossary .................................................................................................................. 54

Annex B (informative) Lookup table of standards ....................................................................................... 57

Annex C (informative) Bibliography............................................................................................................ 58

8
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Guide for Identifying and
Improving Voltage Quality in Power
Systems

1. Overview

1.1 Scope

The reader of this guide will find discussions of ways to identify and improve power quality in power
systems, as well as references to publications in this area. More specifically, this guide includes the
following:

a) Power quality levels from benchmarking studies


b) Factors that affect power system performance
c) Mitigation measures that improve power system performance
d) References to current relevant in-depth IEEE standards and other documents

This guide only addresses subjects in depth where no other power quality reference does so. It is a
“gateway” document for power quality that points the way to other documents in this field.

1.2 Purpose

The primary purpose of this guide is to assist power delivery system designers and operators in delivering
power with power quality that is compatible with electrical end-use equipment. Another purpose is to point
utility system customers toward power quality solutions that may exist in the power utilization system and
equipment.

2. The power system

2.1 Introduction

This subclause describes typical utility power systems. Understanding the basics of power system design
and operation is helpful in understanding the power quality characteristics described in Clause 3. Power
quality characteristics can be affected at various levels of a power system. Electricity is typically generated
and delivered at either 50 Hz or 60 Hz.

9
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

2.2 Overview of power systems

Power systems are usually thought of as having three main divisions—generation, transmission, and
distribution. With the proliferation of distributed energy resources (DER) such as wind turbines, solar
panels, and fuel cells, generation is no longer centralized into a small number of power plants. DER is
connected to transmission, distribution, and consumer low voltage electrical systems. Figure 1 shows a
diagram of a changing electrical power system.

Figure 1—The electric power system

Interconnection of the generation, transmission, and distribution systems takes place in an electrical
substation. Substations may include transformers that raise or lower the voltage depending on the need. A
substation that has a step-up transformer increases the voltage while decreasing the current, whereas a step-
down transformer decreases the voltage while increasing the current for distribution. Electric power may
flow through several substations between generating plants and consumers, and it may be changed in
voltage several times.

The generation and transmission components are typically connected in an interconnected grid fashion.
Within the “grid,” the transmission lines transport bulk power for long distances that typically cross
multiple service territories and multiple utilities. Figure 2 shows a simple transmission system, referred to
as a transmission network, illustrating how most of the substation buses have more than one source. In most
circumstances, the loss of a single line or generator should not cause overloads within the remaining
network. This offers a high degree of reliability because power can be maintained to most buses even with
the loss of a line or source.

Distribution lines (commonly called primaries) are usually not interconnected but are designed in a radial
fashion except in some cities that use a mesh or network distribution scheme. Traditional radial distribution
systems consist of a source originating at a substation in which the system voltage is stepped down (see
Figure 3). The distribution bus has breakers that feed lines (feeders) that carry the power to many
customers in an area. There are usually line protective components (reclosers and fuses) downstream of the
substation breaker on distribution lines. These components create situations in which only a portion of the
distribution line may need to be de-energized to clear a fault (short circuit), thereby saving many customers
on the line from experiencing interruptions unnecessarily. This protection scheme is commonly called line
sectionalization. With smart grid becoming more common, another distribution protection scheme called
segmentation is being utilized. Segmentation involves electronic line reclosers communicating with one
another and isolating the smallest amount of customers closest to the fault location. It also involves
switching portions of one circuit over to other circuits in some cases. DER sources can connect to
distribution feeders near the substation or out on the feeder. Typically, there is a line protective component
placed at the DER metering point.

10
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

Figure 2—Transmission network showing generators, substations, and line sections

Figure 3—Distribution substation and example of recloser and fuses along line

Power system voltages are typically expressed in line-to-line kV. The line-to-line voltage is √3 or 1.732
times the line-to-neutral voltage on wye systems. Practically all generation and transmission is three phase.
Distribution lines typically leave the substation as three phase and may proceed that way for several miles.
However, they may also have lateral tap lines that are only providing one or two phases, depending on the

11
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

loads being served. Electrical services to customers may be from the transmission or the distribution
system. Table 1 describes the various components and typical voltage ranges of the utility system.

Table 1 —Common parts of the power system


Converts sources of energy such as fuel, falling water, or nuclear
Conventional Generation
material to electricity.
Source of electric power that is not directly connected to a bulk power
Distributed Energy Resource transmission system. DERs include both generators and energy
storage technologies.
Bulk power transport connecting generating stations to substations
Transmission
serving load areas.
Generally 230 kV to 765 kV.
Long lines with few, if any, taps or customer connections.
May be overhead or underground; underground circuits are short
because of charging current limitations.
Loading limits for lines and loading areas including normal, long-term
emergency, and short-term emergency limits.
Loading may be limited by system stability, voltage control, or
thermal considerations.
Loading follows a cycle with time of day, season, and weather.
Not distinguished in many systems. Lower level bulk power
Subtransmission
connecting transmission and distribution substations.
Generally 46 kV to 161 kV.
May serve large loads directly.
Distribution Local connections to supply customers or groups of customers.
4 kV to 35 kV.
Short lines with many taps, laterals, or branches; direct customer
connections; may be reconfigured from time to time.
Loading is especially variable as customers turn devices ON and OFF.
May be overhead or underground, with underground especially in
urban or new residential areas.

A significant goal related to the operation of the utility power system is to provide reliable power with a
minimum number of interruptions. The utility systems are designed to isolate problem areas quickly and to
interrupt as few customers as possible. The system protection schemes must quickly identify a faulted
component and then trip or open the proper isolating component to cause the fewest number of customers
to experience the loss of power.

3. Identifying power quality in electrical systems

3.1 Introduction

This subclause describes expected power quality characteristics at various levels of a power system.
Electric utilities strive to maintain good power quality. Limiting disturbances and distortion that affect
power quality minimizes damage and the costs to maintain the network. There are some statutory
guidelines, generally put forward by regulatory agencies that provide limits for frequency, voltage, and
sometimes reliability (interruptions).

Methods of describing the power quality characteristics are presented along with example benchmarking
results. Important characteristics that may impact the power quality characteristics are also described.
Finally, most utilities strive to meet their customers’ needs for reliability and power quality.

12
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

3.2 Basic types of power quality variations

It is useful to divide power quality characteristics into the following two basic categories:

a) Steady-state (continuous) power quality characteristics. This refers to the quality of the normal
voltage supplied to a facility. How much can the voltage magnitude vary from the nominal value?
How distorted is the voltage or current? What is the imbalance among the three-phase voltages or
current? What is the magnitude, frequency, and angle of each phase? All of these characteristics
can be quantified, and limits for the variations can be developed.

b) Disturbances. This refers to power quality variations that occur at random intervals and are not
associated with the continuous characteristics of the voltage. The variations include sustained
interruptions, momentary interruptions, voltage sags (and swells), and transients. All of these
disturbances can impact a facility, depending on the equipment susceptibility and investments that
have been made in power conditioning.

Each of these two basic categories has indices associated with it. Indices provide the foundation for
characterizing the supply system power quality levels in a consistent manner. Indices can be used to
establish baselines of performance as a function of system characteristics. The following subclauses
describe indices that can be used to describe power quality levels in both of these major categories along
with example benchmarking results that can provide the basis for establishing targets and limits.

3.3 Steady-state (continuous) voltage characteristics

Steady-state power quality characteristics must meet minimum requirements to assure the proper operation
of equipment. The basic concepts of voltage levels are established in ANSI C84.1 [B3] 1 where service
voltage ranges and utilization voltages ranges are stated. There are two ranges, range A and range B. The
service voltage is at the point where the electrical system of the supplier and the electrical system of the
user are connected. The utilization voltage is at the line terminals of utilization equipment.

The concepts of compatibility levels are established in IEC 61000-2-2:2002 [B20]. This concept applies to
all steady-state types of power quality. It is not as applicable to disturbances, such as voltage sags (dips),
interruptions, and transients. The normal variations of steady-state power quality characteristics allow them
to be characterized with trends over time and with statistical distributions. The statistical nature of these
characteristics lends them to being represented by specific statistical levels. For instance, the limits in EN
50160-2010/A1:2015 [B14] for steady-state power quality are evaluated at the 95% probability level.
Recent discussions have indicated that other probability levels may also be appropriate for fully
characterizing performance.

Figure 4 illustrates the relationship between the severity of network events (left-most curve) and the
sensitivity of end-use equipment to those events (right-most curve). The goal is for the severity of all
network events to be below a pre-defined level of compatibility (center) and for all equipment to also be
immune to misoperation for all events below that same compatibility level. Various planning, alarm, and
immunity levels are established and maintained in order to help achieve this outcome.

1
The numbers in brackets correspond to those of the bibliography in Annex C.

13
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

Figure 4—Concept of compatibility levels for the electric supply system and the immunity
characteristics of equipment

Figure 5 illustrates the concept of the “compatibility level” compared to a time trend of a steady-state
power quality characteristic (for example, harmonic distortion). Other important power quality levels are
also shown in both Figure 4 and Figure 5.

Figure 5—Important concepts for compatibility levels of the steady-state power quality
characteristics of the supply system

The following is a list of the characteristics illustrated in Figure 5:

Equipment damage level—This is the level of quality that may pose a threat to equipment health if it is
exceeded. Such conditions are important to identify when they occur and to prevent if possible. Examples
may include harmonic resonance, ferroresonance, high neutral currents, conditions that may cause
overheating, and so on. There should be some margin between the compatibility level for the supply and
the equipment damage level.

14
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

Equipment immunity level—This is the level of quality that may affect equipment performance if it is
exceeded. It is also defined statistically. There should be some margin between the compatibility level for
the supply and the equipment immunity level.

Alarm level—This is the level of quality at which notification will occur (i.e., the level at which an
investigation or other response may be warranted). The alarm level should be above the planning level but
below equipment immunity, equipment damage, and safety levels.

Compatibility level—This is the level of quality that, if exceeded, could affect equipment performance, or
objectionable flicker observed.

Utility planning level—This is the level of quality that the electric utility establishes as its design
objective. Usually, the planning level is defined at some level below the compatibility level to help assure
that the actual compatibility level will not be exceeded. For instance, the compatibility level for harmonic
voltage distortion might be 8%, but the planning level might be 5% to help make sure that the 8% level is
not exceeded.

Assessed level—This is the actual level existing on the system, usually based on measurements. For
instance, the evaluation of performance for the European standards requires measurements over a 1 week
period and then the assessed level for comparison with the minimum performance requirements (based on
the compatibility levels) is the level that is exceeded for 5% of the measurements (one measured value
every 10 min).

Additionally, this level should define the steady-state power quality levels that allow proper operation of
virtually all customer equipment. Thus, if these power quality levels are met at the supply point, the steady-
state quality should be considered acceptable and should not result in customer problems. There is little
value to providing even better power quality if these levels are not likely to cause problems. Extremely
susceptible equipment that requires even better quality justifies special power conditioning and should not
be the basis of the overall system requirements.

The steady-state power quality levels should be evaluated using the measurement procedures outlined in
IEC 61000-4-30: 2015 [B24]. This standard provides a convenient reference to make sure that all systems
are being evaluated in the same manner. The IEEE 1159 working group has developed a similar set of
recommended characterization procedures (IEEE Std 1159™-2009 [B31]) that are consistent with the
methods in the IEC standard.

Studies of the typical levels of these steady-state characteristics are provided from the following two
important sources:

 The EPRI Distribution Power Quality (DPQ) project ([B15]) describes steady-state power
quality characteristics for distribution systems in the United States. Note that these statistics are
based on the evaluation of single-cycle samples of the three-phase voltages. These samples are
then analyzed to determine the root mean square (rms) voltage magnitudes, the imbalance, and
the harmonic distortion levels. Flicker levels were not characterized in the EPRI DPQ project.
This method of evaluating steady-state power quality characteristics is different from the
method recommended in IEC 61000-4-30: 2015 [B24] and related standards. These methods use
10 min rms values as the basis for characterizing the steady-state power quality. The 10 min
calculations can involve smoothing compared with the single-cycle samples.
 In the CIGRE C4.07 Working Group Report [B10], this working group gathered survey
information describing both steady-state power quality and disturbances from systems around
the world. In general, the surveys referenced in this report used IEC methods for characterizing
performance.

15
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

3.3.1 Voltage regulation

The ability of equipment to handle steady-state voltage variations varies. The steady-state voltage variation
limits for equipment are usually part of equipment specifications. The Information Technology Industry
Council (ITIC) specifies equipment withstand recommendations for IT equipment according to the ITIC
Curve [formerly the Computer Business Equipment Manufacturer’s Association (CBEMA) curve]. The
1996 ITIC Curve specifies that equipment should be able to withstand voltage variations that last longer
than 10 s within ± 10% of equipment nominal.

Steady-state voltage will vary at different points along the electric supply network. As load current flows
through the lines and transformers, voltage drops are caused by the impedances. Utilities use various design
strategies and equipment to control or regulate the voltage levels on the network to provide the end users
with suitable voltage levels.

Voltage regulation of a system is affected by the electrical equipment from the generators to the end user.
However, voltage regulation is tied most closely with the distribution system. The distribution system will
typically have voltage-regulating transformers that can either increase or decrease the voltage that is
supplied to the voltage input of service transformers. These voltage-regulating transformers are commonly
capable of increasing or decreasing the distribution voltage up to 10%, usually in multiple steps of either
0.625% or 1.25% per step. The wide operating range allows the distribution voltage to correct
automatically for the varying load conditions and voltage variations on the system. The voltage-regulating
feature can either be built into the substation distribution transformer itself or be separate regulating
transformers located downstream of the substation transformer. Substation transformers with regulating
capabilities are called either tap changing under load (TCUL) or on load tap changing (OLTC)
transformers. They have multitapped transformer windings usually designed into the low-voltage winding
of the transformer. All three phases will change steps simultaneously either to raise or lower the voltage by
changing the transformation ratio. Single-phase voltage regulators are also used extensively on distribution
systems downstream of the substation transformer. They are often installed at strategic points along
distribution lines to maintain proper voltage levels and can be cascaded along the circuit.

The current that flows to provide the reactive power requirements of inductive loads, such as motors, on the
network is a significant cause of line voltage drop. A phase angle relationship exists between the reactive
and real currents drawn by loads on a power system. A properly sized capacitor located near an inductive
load will serve to counteract the reactive power conducted through the power system by the inductive load.
By using capacitor banks to provide reactive power for inductive loads, such as motors, the total current
flowing from the substation is reduced, and so the voltage drop along the distribution line is reduced also.
Utilities use capacitor banks located on distribution lines or in substations to help control voltage by
controlling reactive power flow. Utility capacitor banks either will be switched by automatic controls or
will be manually switched seasonally. Automatic capacitor switching controls use such things as voltage
level, temperature, time of day, or reactive power flow to determine whether to close or open a particular
capacitor bank.

3.3.1.1 Recommended limit and assessment method

Because the objective is to define minimum acceptable requirements based on an evaluation at the Point of
Common Coupling (realizing that the voltage variations inside a facility may be greater than the voltage
variations on the system or at the supply point), the recommended level is ±5% with an evaluation at the
95% probability level.

3.3.1.2 Example survey

Figure 6 illustrates the statistics of voltage regulation levels obtained in the EPRI DPQ project [B15].
Voltage regulation is described in this case as the range of voltage over the period of the day expressed as a
percent of nominal. Although the percent regulation is given as an absolute value, the results illustrate that
almost all sites achieve a total variation level within 10%. The 95% for the entire sample of sites is a
voltage regulation range of 8.5%.

16
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

Figure 6—Voltage regulation statistics (total daily voltage variation range) from EPRI DPQ
project (1 June 1993 to 1 June 1995) [B15]

3.3.2 Voltage imbalance

Voltage balance is referred to as unbalance or imbalance and both are used interchangeably with one
another throughout the industry, even IEEE Standards Dictionary Online list both together. In this
subclause, the term voltage imbalance is used. 2
There are many reasons for voltage imbalance on utility distribution systems. It is well known that the most
common cause of voltage imbalance on a utility distribution system is current imbalance on the system
itself. Depending on the length of the circuit and the circuit make up, the system may seem to be balanced
at the substation but out on the circuit it could have a current imbalance causing a voltage imbalance
situation. Current imbalance can become a challenge on utility circuits because the utility system has
single-phase customers on the system, along with underground networks and long overhead networks in
rural areas. This can create a voltage imbalance at different points on the distribution system and at
different times of day. Another cause of voltage imbalance in a utility distribution system is non-
transposition of transmission lines. In a transmission system with long circuits with no phase transposition,
the coupling with high load balanced current will cause voltage imbalance and current imbalance. The
transposing of lines to cancel the effect of the circuit will help keep this type of voltage imbalance at a
minimum. VAR balances with capacitor banks and loads on the system can also create balance issues for
utility distribution systems. There are two effects from a three-phase capacitor banks when opening a single
fuse. One effect is that the VAR imbalance may cause a voltage imbalance on the system. The other effect
is the loss of one fuse will cause a voltage drop on that phase, and the remaining phase will have the
associated voltage rise. VARs are also developed from underground cable capacitance. Single-phase
underground networks can cause imbalances due to VAR loading from the cabling on the system. A larger
underground circuit on one phase vs. another phase can cause the same effect as a blown fuse on a three-
phase capacitor bank.
Banking of transformers can cause voltage imbalance if the transformer impedances are not matched within
a certain percentage of their %Z rating. When installing a three-phase bank, the bank impedances should be
within 7.5% of each other for %Z rated values more than 2.5% and 10% for values %Z rated values 2.5%

2
IEEE Standards Dictionary Online is available at: http://dictionary.ieee.org.

17
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

and less (IEEE Std C57.12.00-2015 [B37]). This will help ensure that the loading on the bank will not
cause excessive voltage drop difference on each bank thus causing a voltage imbalance.
With a renewed emphasis on voltage reduction to decrease loading on the utility system, other challenges
are presented. Specifically, single-phase regulators on a utility system installed to level the voltage profile
along the circuit, may create voltage imbalance. Most regulator controls are phase to ground (neutral)
sensing for voltage regulation. In most cases, the single-phase regulator will improve voltage balance.
However, if a system has imbalanced current, single-phase regulators may raise or lower each phase-to-
neutral voltage in significantly different amounts, and could make the system have a greater voltage
imbalance, when measuring phase-to-phase voltage, due to a phase angle shift. Even a 1 to 2 degree phase
angle shift can have a great effect on the voltage imbalance at the measured point in the system.
Understanding the effects of voltage imbalance is important to recognize an issue on the electrical system.
Voltage imbalance has an influence on heating of three-phase devices such as motors, transformers, drives,
and rectifier circuits. This excess heating can cause damage to the device. For example, according to Figure
7, a three-phase motor running at full load should be de-rated if the voltage imbalance exceeds 1%.

Figure 7—Figure 14-1 in NEMA MG 1 [B50]

The efficiency of the device can be reduced as well. Experimentation has shown that when voltage
imbalance is between 3% and 5% the efficiency of a motor can decline by 1% to 3% (see Agamloh, Peele,
and Grappe article [B1]). ANSI C-84.1 [B3] standard Annex C field survey results states that
“approximately 98% of the electric supply systems surveyed were within the 0% to 3% voltage imbalance
range.” A 1% voltage imbalance can cause approximately 7% to 8% current imbalance in traditional poly-
phase motors. Effects on VSD and rectifying load can cause even higher current imbalances. Motors
typically have circuit protection installed in the circuit to trip them off, when they experience imbalance
conditions above a threshold value. This includes the extreme case of voltage imbalance known as single
phasing. This is where one of the incoming phases serving the loads has been lost. Single phasing can
originate on the primary source voltage or the secondary source voltage. Protection relays use three basic
sensing techniques, thermal, current, or voltage, depending on their function. Many of the devices installed
to protect the motor and the circuit, are protection relays and fall into different categories such as Thermal
Overload Relay, Over Current relay, Over and Under Voltage Relay, Single Phasing Relay, and Imbalance
relay.

Voltage imbalance relays typically operate by sensing an imbalance in the phase-to-phase voltage, such that
once the sensed imbalance exceeds a specified threshold, a control signal is generated that may be used to
interrupt power flow to the protected device (by tripping a circuit breaker or contactor). These devices can
be put on each individual motor for protection, or with the advent of shunt trip breakers, on entire circuits
or facilities. Some facilities have also started implementing Voltage Imbalance relays on their main
switchgear.

There are different ways to calculate voltage imbalance and they have been well defined in many papers
and documents. NEMA’s definition of voltage imbalance in Equation (1) is the most useful definition

18
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

applied in the field. This definition specifies voltage imbalance as the maximum deviation from average
voltage divided by average voltage expressed as a percentage. The voltages used in this calculation must be
phase-to-phase voltage:

Vun
(
max Vab − Vavg , Vbc − Vavg , Vca − Vavg ) ×100 (1)
Vavg

Maximum Deviation from Average Voltage


Vunbalance % × 100
Average Voltage

where

Vun is the percentage voltage imbalance


Vab , Vbc , Vca are phase-to-phase voltages
Vavg is the average of the three-phase voltages

ANSI C84.1-2016 [B3] also uses this same calculation for voltage balance. ANSI also states, “Electric
supply systems should be designed and operated to limit the maximum voltage imbalance to 3% when
measured at the electric-utility revenue meter under no-load conditions.” This is a recommendation only
within the standard and not a requirement.

IEC 61000-2-2:2002 [B20] specifies a compatibility level of 2% for voltage imbalance, recognizing that
systems with large single-phase loads may have voltage imbalance levels as high as 3%.

EN 50160:2010/A1:2015 [B14] requires that utilities maintain voltage imbalance less than 2% for 95% of
the 10 min samples in 1 week. For systems with significant single-phase loads, the imbalance can be as
high as 3%.

Clearly, if the three-phase voltages are equal, the imbalance would be zero. The voltage imbalance is
created when at least one of the phase-to-phase voltages is different from the other phase-to-phase voltages.
It is also well known that the unbalanced voltages can be resolved into symmetrical components called
sequence voltages. The formal or true definition of voltage unbalance percentage is defined as the ratio of
negative sequence voltage to positive sequence voltage [Equation (2)].

V2
Vunf= × 100 (2)
V1

Negative Sequence Voltage


=Vunbalance % × 100
Positive Sequence Voltage

where
Vunf is the voltage imbalance factor
V1 is positive sequence voltage
V2 is the negative sequence voltage

In Equation (2) if the voltages V1 and V2 are expressed with their phase angles, the ratio becomes the
complex unbalance factor. IEEE Std 1159-2009 [B31] covers more details on the use of these and other
equations.

19
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

3.3.2.1 Recommended limit and assessment method

The CIGRE working group recommends that the 95% value for weekly measurements of the 10 min
imbalance values be used for comparison with recommended imbalance limits (voltage characteristics).
The most commonly used value for this characteristic is 2%. It seems to be a value that is very achievable
and also has minimal consequences for customer equipment applied at low voltage. Equipment applied at
medium voltage might have more stringent requirements for voltage balance.

3.3.2.2 Example surveys

Negative sequence voltage imbalance statistics from the EPRI DPQ project [B15] are given in Figure 8 and
shows that the 95% level for negative sequence imbalance over all the sites in the project was about 1.3%.

Figure 8—Voltage imbalance statistics (entire data set for all sites) from EPRI DPQ project
(1 June 1993 to 1 June 1995) [B15]

Figure 9—Measurement data for voltage unbalance at MV, high voltage (HV), and extremely
high voltage (EHV)—all sites (CIGRE C4.07/CIRED Report [B10])

20
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

The CIGRE C4.07/CIRED Working Group [B10] gathered survey data from around the world. Only a few
surveys actually compiled information about imbalance, but the results are still informative for developing
a recommended minimum performance level. Figure 9 illustrates the results (95% probability level over
one week of measurements at each site) for the different system voltage levels. The medium voltage (MV)
results are most interesting. In this case, none of the sites had an imbalance level exceeding 2% at the 95%
probability level.

3.3.3 Voltage distortion

Traditional utility generators produce voltage with almost no harmonic distortion. The voltage harmonic
distortion on the system is mostly because of the nonlinear customer loads that are served. These loads
draw harmonic currents that interact with the system impedance to create voltage distortion. Because of
this, voltage harmonic distortion is usually a local phenomenon related to serving loads with high harmonic
current content. More recently some nonlinear generation, such as photovoltaics with inverters, have been
found to produce distortion as well.

Harmonic distortion in the supply voltage results in increased heating in transformers, motors, capacitors,
and conductors. This increased heating is usually the most important effect. Sensitivity of customer
equipment to voltage distortion may be dependent on both the magnitude of the distortion levels and the
specific harmonic components. For instance, transformer eddy current losses increase with approximately
the square of the frequency.

An unintended consequence of the use of capacitors, by either the utility or its customers, is their effect on
harmonics. Capacitors cause a change in system impedance, and voltage distortion is directly related to the
system impedance. Their capacitive reactance will create a resonant impedance at one frequency or at
multiple frequencies. If a harmonic current exists having the same frequency as a resonant impedance, there
will be increased voltage distortion. In some cases, this distortion will be in excess of the recommended
limits of IEEE Std 519-2014 [B28]. In those cases, the utility may have to change the size of the capacitor
bank, relocate it, or install a tuned filter.

IEEE Std 519-2014 [B28] establishes current harmonic limits for customers and voltage harmonic limits
for electrical utilities. Examples of the limits set by the document are shown in Table 2 and Table 3. The
harmonic current limits are designed to prevent voltage distortion from reaching excessive levels. The
relative size of a customer load compared with the supply network serving the load determines the amount
of harmonic current the user is allowed to inject into the utility system. There is no guarantee that harmonic
voltage distortion limits will not be exceeded even though each customer on a given line conforms to the
current injection limits. Because voltage distortion is created by the voltage drops that occur due to current
distortion and system impedance, one method to reduce voltage distortion is to reduce system impedance.

Very short-term effects of harmonics can include the misoperation of electronic controls or the operation of
uninterruptible power supplies. There may be a need for limits on the short-term harmonics as well as on
the long-term levels that cause heating.

3.3.3.1 Recommend limits and survey methods

The IEEE Std 519-2014 [B28] recommended limit for harmonic voltage distortion levels at medium
voltage is 5% at the point of common coupling (PCC) for the total harmonic distortion. At voltage < 1 kV,
IEEE Std 519-2014 [B28] recommends a limit of 8% at the PCC for total harmonic distortion.

Individual harmonic limits are also important, especially at higher frequencies. Higher frequency voltage
harmonic components need to be limited to lower levels because of the potential duty on capacitor banks
(both on the utility distribution system and in customer systems). Also, higher voltage harmonic
components can cause the misoperation of customer equipment because of the tendency to introduce
multiple zero crossings into the voltage waveform. Specific limits for higher voltage components are not

21
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

proposed here—these will be addressed in future revisions of IEEE Std 519-2014 [B28]. The individual
harmonic limits in IEEE Std 519-2014 [B28] and in IEC standards provide some guidance.

The recommended limit is compared with the 95% probability level of the 10 min voltage distortion values
measured over a one-week period. Examples of the types of limits set by the document are found in Table 2
and Table 3, although these particular tables come from European standards instead of IEEE Std 519 [B28].

Table 2 —Harmonic compatibility levels


Odd harmonics Odd harmonics
Even harmonics
Non-multiple of 3 Multiple of 3
Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic
Order Voltage Order Voltage Order Voltage
h % h % h %
5 6 3 5 2 2
7 5 9 1,5 4 1
11 3,5 15 0,4 6 0,5
13 3 21 0,3 8 0,5
17 ≤ h ≤ 49 2,27 × (17/h) − 0,27 21 < h ≤ 45 0,2 10 ≤ h ≤ 50 0,25 × (10/h) + 0,25
NOTE—The levels given for odd harmonics that are multiples of three apply to zero sequence harmonics. Also, on
a three-phase network without a neutral conductor or without a load connected between line and ground, the values
of the 3rd and 9th harmonics may be much lower than the compatibility levels, depending on the unbalance of the
system.

NOTE—Table 2 is reproduced with permission from the EN 50160:2010/A1:2015 [B14].

Table 3 —Individual harmonic voltage limits from EN 50160:2010/A1:2015 [B14]


ODD HARMONICS EVEN HARMONICS
not multiple of 3 multiples of 3
Relative Relative Relative
Order h Voltage Order h Voltage Order h Voltage
5 6.0% 3 5.0% 2 2.0%
7 5.0% 9 1.5% 4 1.0%
11 3.5% 15 0.5% 6–24 0.5%
13 3.0% 21 0.5%
17 2.0%
19 1.5%
23 1.5%
25 1.5%

NOTE—Table 3 is reproduced with permission from the EN 50160:2010/A1:2015 [B14].

A comparison of IEEE Std 519-2014 [B28] limits with the limits from EN 50160:2010/A1:2015 [B14]
show that the harmonic distortion limits in Europe are considerably relaxed compared with the IEEE limits.
New revisions to IEEE Std 519-2014 [B28] address this compatibility issue, at least at low-voltage
interface points. Even with the less severe limits in Europe, few problems related to harmonics are reported.

3.3.3.2 Example survey

Harmonic levels were monitored in the EPRI DPQ project based on single-cycle samples rather than on
10 min values. However, the statistics for large numbers of samples are likely to be similar to the statistics
obtained with 10 min values at the system level because the changes in harmonic levels are gradual. Larger
differences could occur at individual locations with dynamic loads, such as arc furnaces.

Most of the DPQ results are reported as average harmonic levels. For instance, Figure 10 gives the
distribution of average voltage distortion levels for all the sites in the EPRI DPQ project [B15]. The

22
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

average distortion level across all the sites is 1.57%. No sites had an average voltage distortion level
exceeding 5%. However, this can be misleading because the voltage distortion limits are meant to be
compared with the 95% probability level for the harmonic distortion, not the average value. Figure 11 gives
the distribution of 95% probability level voltage distortion (CP95) values for all the sites in the EPRI DPQ
project [B15]. In this case, about 3% of the sites have distortion levels exceeding 5%. These cases usually
involve resonance conditions associated with power factor correction on the distribution system.

Figure 10—Distribution of average voltage distortion levels for all sites


in the EPRI DPQ project [B15]

Figure 11—Distribution of CP95 voltage distortion values (level not exceeded 95% of the time)
for all sites in the EPRI DPQ project [B15]

23
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

Limited survey results were collected from MV systems in the CIGRE C4.07/CIRED effort [B10]. The
results from two surveys (178 sites) are summarized in Table 4. These give the most important individual
harmonic distortion levels and are very consistent with the DPQ survey results. (Note that the use of
commas in Table 4 is the European convention instead of the U.S. decimal point convention.)

Table 4 —CIGRE/C4.07 survey results

Measurement results Measurement results


Harmonic order 95%-site for Uh,sh95 max-site for Uh,sh95 Planning levels

Min Max Mean Min Max Mean


3 1,5 2,8 2,15 2 3,7 2,85 4

5 2,56 4,5 3,53 4,2 5 4,6 5

7 1,3 1,5 1,4 1,5 3,4 2,4 4

11 0,5 0,95 0,75 1 3,8 2,4 3

A survey of harmonic levels was conducted at residential locations in eight different countries in Europe
(EPRI PEAC [B63]). Figure 12 gives the consolidated results from all 74 sites combined from this survey.
Note that the results are actually very consistent with the results from the EPRI DPQ project [B15]. The
95% probability level for voltage THD across all the sites in the European survey project was 3.8%. This
compares with a voltage THD level of 4.0% at the aggregate 95% level in the EPRI DPQ project [B15].
The overall harmonic distortion levels are very similar in the United States and Europe.

Figure 12—Results of harmonic survey at European residential locations

3.3.3.3 Higher frequency harmonics

Higher order individual harmonic limits are also important, especially at higher frequencies. Higher
frequency voltage harmonic components need to be limited to lower levels because of the potential duty on
capacitor banks (both on the utility distribution system and in customer systems). Also, higher voltage
harmonic components can cause the misoperation of customer equipment because of the tendency to
introduce multiple zero crossings into the voltage waveform. Specific limits for higher voltage components
are not proposed here—these will be considered in future revisions of IEEE Std 519 [B28]. The individual
harmonic limits in IEEE Std 519-2014 [B28] and in IEC standards provide some guidance.

24
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

The recommended limit is compared with the 95% probability level of the 10 min voltage distortion values
measured over at least a one-week period.

3.3.4 Voltage fluctuations

Voltage fluctuations are generally considered to be cyclic variations of voltage where the changes in
amplitude do not exceed 10%. The magnitude variation is typically less than the sensitivity threshold of all
but the most sensitive end-use equipment. The main disturbing effect of these voltage fluctuations is
changes in the illumination intensity of light sources. When the illumination intensity fluctuates
periodically, it can produce an unpleasant visual sensation to people that is called flicker. Even though
flicker implies that there is a physiological relationship involved because of its relation to human visual
perception and a periodic time element, many utilities will use the term “flicker” when referring to
repetitive fluctuations as well as a single-step voltage change.

Humans can be very susceptible to light flicker caused by voltage fluctuations. Human perception of light
flicker is almost always the limiting criteria for controlling small voltage fluctuations. Figure 13 illustrates
the level of perception of light flicker from an incandescent bulb for rectangular variations. The sensitivity
is a function of the frequency of the fluctuations, and it is also dependent on the voltage level of the
lighting.

Sensitivity or objection to flicker is a subjective phenomenon, and depends on the physiology of the eye
and brain of the person who is exposed to the variation in luminance output caused on an incandescent light
bulb due to a variation in the RMS voltage level.

Flicker was originally related to the behavior of a 230 V, 60 W incandescent light bulb when subjected to
voltage fluctuations. Other types of lighting may provide different fluctuation of the luminance and flicker
perception problems when subjected to the same voltage fluctuations. EPRI testing illustrated the different
characteristics of other types of lighting and developed the concept of a gain factor for the lighting for
comparison of susceptibility with that of a 60 W incandescent bulb. In this context, a lower gain factor
means that the fluctuation of light output from a light source is less susceptible to a given voltage
fluctuation. Figure 14 provides an example.

Figure 13—Curves illustrating the level of rectangular voltage fluctuations that will result in a
Pst value of 1.0 when measured with the IEC flickermeter

25
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

Figure 14—Lamp gain versus flicker frequency for fluorescent electronic


and incandescent lamps

Typically, voltage fluctuations on utility systems are caused by sudden large changes in the amount of load
current. As load or generation current flows through the wires and transformers of the electrical system, it
produces voltage change proportional to the impedance of the wires and transformers. Common causes of
sudden load or generation current changes include the following:
 Large motors starting
 Large loads being switched ON or OFF
 Switching to isolate sections of the network for maintenance
 Variable loads such as metal shredders and wood chippers
 Arc furnace operation
 Large or multiple welders
 Switching of capacitor banks
 Wind/photovoltaic (PV) or other intermittent generation sources

Utilities usually place limits on the amount of starting current allowed for large motors. The limits are
typically established based on the allowable percentage voltage drop at the PCC. If the customer PCC is
located far from the substation, the system impedance will be larger than the impedance of a PCC located
close to the substation. Therefore, the allowable inrush current is lowest for motors located far from a
substation.

When responding to voltage fluctuation concerns, utilities often focus on the impedance of the local
electrical system. Lowering the system impedance by changing wire size or transformer size is a common
solution. Other less commonly used options used by utilities include compensating reactive power flow by
installing shunt connected VAR compensation on the electrical grid. Typical switched capacitors will not
provide a solution to the voltage fluctuations discussed here. Instead, an advanced VAR support system
capable of quickly responding to the dynamic VAR requirements of the system is needed.

These systems are commonly referred to as static VAR compensators (SVC) or static synchronous
compensators (STATCOM). SVC systems combine electronic switching with capacitors and reactors to
provide leading and lagging VAR compensation. STATCOM systems combine electronic switching with
electronic voltage source converters to provide dynamic leading or lagging VAR compensation. Both types
of systems are costly and often include negotiations with the customer that is deemed to be creating the
voltage fluctuations. However, when compared against the much larger cost of building a new transmission
line to solve a light flicker problem, the cost is occasionally justified.

Additional information is available in IEEE Std 1453-2015 [B34].

26
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

3.3.4.1 Basic EMC concepts related to voltage fluctuations

The flicker levels in IEC standards and in IEEE Std 1453-2015 [B34] are characterized by the following
two parameters:

 10 min “short-term flicker severity”—Pst: This value is obtained from a statistical analysis of
the “instantaneous flicker value” in a way that models incandescent lamps and the observation
of light intensity variations.
 2 h “long-term flicker severity”—Plt: This is calculated by combining 12 successive Pst
measurements using a cubic relationship.
Both of these parameters are defined along with the equipment to measure them in IEC 61000-4-15:2015
[B23].

A human observer can tolerate a certain amount of light flicker before becoming annoyed. IEC 61000-2-
2:2002 [B20] defines this level of flicker as the compatibility level. It is important to note that compatibility
levels are defined for LV systems only (IEC 61000-3-7:2008 [B21]) where the following is true:

 Short-term flicker compatibility level (Pst) is 1.0


 Long-term flicker level (Plt) is 0.8
A flicker planning level at individual customers is utilized so that the overall flicker level at MV, HV, and
EHV buses does not result in an LV flicker level that is above the compatibility level, thereby greatly
reducing the probability of having customer complaints. Suggested planning levels for flicker are provided
in IEC 61000-3-7:2008 [B21] and IEEE Std 1453-2015 [B34]. To maintain proper coordination, it is
suggested that flicker planning levels be based on 99th percentile values.

The flicker planning limits can be found in Table 2 of IEEE Std 1453-2015 [B34] and are shown below in
Figure 15:

Figure 15—Recommended flicker planning levels in IEEE Std 1453-2015 [B34]

Note that individual step changes in the voltage, such as would be caused by a motor starting or switching a
capacitor bank, are often limited separately from the continuous flicker limits. IEC 61000-2-2:2002 [B20]
specifies a compatibility level of 3% for the individual voltage variations. EN 50160:2010/A1:2015 [B14]
specifies a limit of 5% for these variations but mentions that more significant variations (up to 10%) can
occur for some switching events. These step changes in voltage are referred to as rapid voltage change
(RVC). IEC 61000-3-7 [B21] specifies planning limits for RVC. These limits are adopted in IEEE Std
1453-2015 [B34].

3.3.4.2 Recommended limits and assessment method

The recommended compatibility limit for flicker is Pst = 1.0 at the 95% probability level. This is consistent
with the compatibility levels in IEEE Std 1453-2015 [B34] and or IEC 61000-2-2:2002 [B20] and is based
on the actual design of the flicker meter. In other words, this flicker limit should prevent customer
complaints associated with light flicker.

27
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

The limit is lower than the limit specified in EN 50160:2010/A1:2015 [B14]. However, it is an appropriate
limit when considering the philosophy of establishing a limit to prevent customer complaints rather than
setting a limit that is a legal requirement for the utility to meet.

The Pst level is measured with a flicker meter that complies with IEEE Std 1453-2015 [B34] and IEC
61000-4-15:2010 [B23] requirements. The Pst values are calculated for 10 min intervals; 95% of these
values should be below the limit in a 1 week measured period.

3.3.5 Summary of steady-state power quality performance levels

Table 5 summarizes the recommended steady-state power quality characteristics (planning levels). All of
these are based on 10 min samples calculated according to IEC 61000-4-30:2015 [B24]. They are evaluated
based on the 95% probability level. In other words, the system should be designed so that these levels are
expected to be exceeded less than 5% of the time. Ideally, all locations on the power system should meet
these power quality levels. However, there will always be some locations that have power quality
characteristics that may exceed these levels in one or more categories. When a situation such as this is
identified that causes customer issues, the utility should work to solve the problem (that may be caused by
one or more customers or may be related to a system condition).

It is important to remember that the power quality levels indicated in Table 5 can be considered normal
when measured at the point of common coupling with customer facilities, and minimum requirements may
not be defined for all categories. A customer should not assume that the power quality levels will be
significantly better than the levels indicated. For instance, when applying power factor correction, it is
reasonable to assume that the background harmonic distortion levels on the supply system could be as high
as 3% for individual harmonics and 5% for the total distortion. This could influence the design
requirements for power factor correction equipment within a facility.

Table 5 —Summary of typical power quality performance expectations (table applies to


distribution voltage)
Power quality category Example limits
±5% of nominal for normal conditions
Voltage regulation
±10% of nominal for unusuala conditions
Voltage unbalance 2% negative sequence
5% total harmonic distortion
Voltage distortion
3% individual harmonic components
Pstb less than 1.0
Voltage fluctuation/flicker
Individual step changes less than 4%
Voltage frequency ±0.015 Hzc
a
Unusual conditions are conditions of abnormal stress for the electric supplier such as when an essential transmission
line is out of service during a period of exceptionally heavy system loading. Such conditions are typically unplanned,
rare, and brief.
b
Pst is a measure of flicker where a value of 1.0 indicates that 50% of the people are likely to notice a flicker in a 60 W
incandescent lamp. Measurement procedures are defined in IEC 61000-4-15:2010 [B23] and have been adopted by
IEEE Std 1453-2015 [B34].
c
Typical steady-state maximum frequency deviation in an interconnected power system in North America.

3.4 Disturbances

Disturbances are power quality issues that cannot be characterized with the same time trends and statistical
distributions that are used for the steady-state power quality characteristics. These variations occur
randomly, and each event could have an effect on customer facilities.

Disturbances from the electric utility system are typically caused either by a fault or by a switching
transient. A fault usually involves a short circuit between an energized phase conductor and ground or

28
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

between two or more energized phase conductors. The time duration of a fault is usually between one cycle
and 1 s. An interruption is what occurs after a protective device senses and isolates a fault.

With the advent of large solar system (1 MW and above) some rural locations may have issues with
magnetizing inrush on solar farms. If the solar system is large compared to the distribution substation, this
can become an issue.

A switching transient may occur when large inductive loads, capacitor banks, or line sections are switched.
The electrical system reaction to adding or removing components and loads often creates a short duration
change in the voltage waveform. The time duration of a switching event is usually between one-half cycle
and three cycles.

It is highly recommended that one reviews and becomes very familiar with IEEE Std 1159 [B31] for
describing techniques for defining, measuring, quantifying, and interpreting electromagnetic disturbances
on the power system.

3.4.1 Reliability

The most commonly discussed type of disturbance is an interruption. However, it is important to recognize
and distinguish that reliability is fundamentally a different subject matter compared to power quality. The
term interruption is common to both subjects, but is defined and considered differently within their context.
Most utilities around the world report on the reliability performance of the power system. A common index
used to track reliability for power systems is the System Average Interruption Frequency Index (SAIFI).
For power systems in most developed countries, average SAIFI levels are generally accepted to be in the
range of 0.5 to 5.0 interruptions per year (depending on factors such as weather, underground vs. overhead
systems, networked systems vs. radial systems, etc.). This is the number of times that customers experience
an actual power interruption each year (usually defined as an interruption lasting more than 5 min). The
average SAIFI across the United States is about 1.3 interruptions per year. Typically, this index is also
adjusted so that it does not include “major events” that affect a significant portion of the system (the index
is used to evaluate the performance of the system for events that could possibly be avoided through system
investments, maintenance, etc.).

Although reliability indices are useful for regulators and for establishing company goals, they have limited
use to a specific customer because these are based on the entire system. It would be much more important
to get information about the expected number of interruptions where that specific customer is actually
connected to the system. The utility may be able to provide location-specific historical data about reliability
that would be more useful for evaluating the need for uninterruptible power supply (UPS) or backup
generation to protect critical operations.

Detailed information about calculating reliability indices and characterizing reliability performance are
provided in IEEE Std 1366-2012 [B33].

3.4.2 Voltage sags and momentary interruptions

Facility operations can be affected by more than just long duration interruptions. Momentary voltage sags
lasting less than 100 milliseconds are often sufficient to cause disruptions to susceptible equipment and
operations (see example in Figure 16). Even though the effect of these disturbances can be the same as long
duration interruptions, they can be more important because they occur much more frequently. These
disturbances are caused by faults on distribution circuits and transmission circuits. The interconnected
nature of the system means that faults remote from a facility can still cause a momentary voltage sag that
could be sufficient to affect operations.

Power system faults cause interruptions and voltage sags on the electric system. During a fault, very high
current levels flow until protective devices isolate the fault. The many causes of faults include lightning,
animal contacts, tree contact, underground cable dig-ins, and equipment failures. While fault current is

29
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

flowing, a voltage sag impacts the involved electrical system. Just what constitutes the “involved electrical
system” varies depending on where the fault occurs. A fault on a high-voltage transmission line may impact
several substations and affect power quality 100 or more miles from the fault. A fault on a medium voltage
distribution line will typically only impact power quality of the feeders on a common substation bus.
Figure 16 is an example of percent remaining voltage possible because of a fault on the transmission
system.

Figure 16—Percent remaining voltage

Industrial facilities are often impacted by the incompatibility of their equipment to voltage sags. The
impacts are most significant where the automated industrial process is difficult and time consuming to
restart. The system strength at the PCC of an industrial plant is a key factor in minimizing the number of
voltage sag disturbances that will be experienced because of faults on the utility grid. Usually, because of
the system impedance characteristics, the transmission system will not be significantly impacted by faults
on distribution lines. However, distribution lines will be impacted by faults on the transmission system.
Because of the lower incidence of faults on the transmission system, customers sometimes request service
from dedicated substations.

Figure 17 is an example of the types of faults experienced by a typical distribution-fed customer.

Electric utilities typically direct maintenance activities toward minimizing fault rates. Reducing the number
of faults on the system improves the system reliability, reduces voltage sags, and minimizes equipment
failure. Typical fault reduction activities include tree trimming, lightning arrester installation, grounding
improvements, and animal guard installation.

30
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

Figure 17—Faults experienced by typical distribution customer

EPRI conducted a benchmarking project that provided an estimate for the average number of voltage sags
that customers experience on distribution systems across the United States. To present the results of this
extensive benchmarking project, a new index to describe voltage sag performance was developed. This
index represents the average number of voltage sags experienced by a customer each year with a specified
characteristic. For SARFIx, the index would include all of the voltage dips where the minimum voltage was
less than x. For example, SARFI70 represents the expected number of voltage sags where the minimum
voltage is less than 70% of nominal.

Figure 18—Example of a short duration voltage sag caused by a remote fault; this voltage sag
caused tripping of a plastics production line

31
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

SARFI indices become a very important consideration for many process industry customers because the
indices represent events that impact the reliability of the process. There are typically very few actual
interruptions. Therefore, voltage sags represent the most important power quality variation affecting
industrial and commercial customers. As shown in Figure 18, a voltage sag caused tripping of industrial
process equipment.

The SARFI index that is appropriate for a facility will depend on the sensitivity of the equipment in the
facility to these voltage variations. This information may not be available without extensive monitoring and
evaluation of equipment response to actual disturbances. Figure 19, from the EPRI benchmarking project,
illustrates how the voltage sag performance is dependent on the minimum voltage level being considered.
For instance, the average for the number of voltage sags per year with a minimum voltage less than 70% is
about 18 events per year in the United States. However, if equipment could be affected by voltage sag with
a minimum voltage of 90% (very minor voltage sag), then the number of events per year is about 50.
Obviously, the equipment sensitivity is a critical factor in the importance of these disturbances. More
information can be found about different types of voltage sags in IEEE Std 1668-2017 [B36].

Figure 19—Average SARFI statistics from nationwide EPRI benchmarking project;


these show the average number of voltage sags that can be expected for
a distribution system customer in the United States as a function of the
voltage sag severity (minimum voltage magnitude)

Another way to use the SARFI index is to count all the voltage sag events that are below a specified
compatibility curve. This is referred to as the SARFI-curve approach. For example, SARFI-CBEMA
considers voltage sags and interruptions that are below the lower CBEMA curve. SARF-ITIC considers
voltage sags and interruptions that are below the lower ITIC curve. SARFI-SEMI considers voltage sags
and interruptions that are below the lower SEMI F47 curve. An example is shown in Figure 20 where each
recorded sag is indicated as one point in the magnitude-duration plot (note that “magnitude” is used here as
a synonym to retained voltage). The SARFI-90 value is 87 in this case; SARFI-CBEMA is 43, SARFI-ITIC
is 26, and SARFI-SEMI is 12.

Time aggregation is important with voltage sag events (and momentary interruption events). Time
aggregation avoids counting multiple events that are associated with the same physical event (fault). The
procedures for time aggregation and for other approaches for characterizing system voltage sag
performance are described in IEEE Std 1564-2014 [B35].

32
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

Figure 20—Scatter plot of voltage sag events superimposed with compatibility curves for
calculation of SARFI indices

The average statistics—especially nationwide statistics—are not very useful for an individual facility trying
to determine whether investment in power conditioning is needed or economically justified. It is of value to
utility for benchmarking of their particular system. Expected voltage sag performance at the individual
plant location is needed. Some utilities calculate the expected voltage sag performance throughout its
system. Figure 21 is an example of the voltage sag performance (SARFI-70) across all of its substations
(Infrastructure Reliability [B39]). The chart shows the three-year average voltage sag performance
compared with the voltage sag performance in the last year. This helps identify systems with significant
changes that could warrant investigation. The voltage sag performance is also broken down into events
caused by distribution faults and events caused by transmission faults because the transmission faults
cannot be prevented by maintenance and improvements on the distribution system and must be addressed
separately. This information can be provided to any customer to help them understand the power quality
that can be expected where they are connected to the system.

33
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

Figure 21—Example voltage sag statistics (SARFI-70) at utility substations

3.4.3 Transients

Voltage transients can also be an important consideration for the quality of supply. Transients can be
caused by lightning during storms or by almost any switching event on the power system. Transients can be
classified into two basic categories, impulsive and oscillatory. These terms reflect the waveshape of the
current or voltage transient. An impulsive transient is a sudden, non-power frequency change in the steady
state condition of the voltage or current that may be unidirectional in polarity (positive or negative with
respect to point of initiation on the supply frequency wave). Impulsive transients are normally characterized
by their rise and decay times. It is good practice to include surge protection for a facility or at least critical
equipment to avoid failures caused by excessive transient voltages.

Conversely, oscillatory transients may affect equipment even with transient protection for high-magnitude
(impulsive) transients. For instance, adjustable speed drives can sometimes be affected by capacitor
switching transients (Figure 22) because these transients can have enough energy to charge up the direct
current (dc) capacitor in the drives to levels that will cause tripping on the dc overvoltage setting. Capacitor
switching transients can also cause problems with low-voltage power factor correction equipment,
electronic ballasts for fluorescent lighting, and other electronic equipment. Transients like the one in Figure
22 are a normal part of the electric supply. Understanding this can help in developing appropriate
specifications for adjustable speed drives and other critical equipment. Usually, the logical mitigation in
such cases will be the addition of line reactors or isolation transformers installed for the affected
equipment.

34
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

Figure 22—Example of a typical transient voltage characteristic that could occur when a
substation capacitor bank is energized

Utilities do employ various measures to limit the capacitor switching transient because of capacitor bank
switching at the transmission voltage level. These measures may include the use of pre-insertion resistors
or inductors in the switching device or even synchronous closing control schemes. However, most utilities
do not employ any transient limiting measures for distribution line capacitor banks.

Surge arresters installed by utilities are designed to protect high-voltage equipment by limiting the transient
voltage levels on the system. However, the arresters installed at MV and HV are not adequate to protect
customers’ facilities from transient activity. IEEE 62 series covers surge protection devices.

3.4.4 Frequency deviations

Frequency is directly related to the rotational speed of the generators in the network. The frequency of the
electrical supply is the one variable that is the same value in steady state at every point within an
interconnected network. In other words, during steady-state conditions, the all generators are rotating in
synchronism. A variation in frequency is determined by the variation of the active power requirements of
the customers on the network. As the active power requirements of the network increase or decrease, the
frequency of the generators would tend to decrease or increase, respectively. However, generators have
automated speed regulators (ASRs), also known as governors, that react to changing load requirements and
maintain the system frequency by continuously adjusting the speed of the rotor. This acts to create a
continuous balance between the generated power output and the active power requirements on the system.
Utilities must maintain a substantial level of spinning reserve to maintain that balance always when power
requirements increase.

Frequency is normally very tightly controlled in interconnected utilities. Because of historic dependency of
power system synchronized clocks (such as common alarm clocks) on frequency, small deviations in this
frequency are accumulated, and this accumulation is periodically balanced back to zero. For example, at all
times except during disturbances, the frequency deviation of the voltage in the Western United States has
been found not to exceed 0.015 Hz (PacifiCorp, Engineering Handbook [B51]). However, when major
disturbances occur on the transmission system, the frequency can temporarily deviate from normal steady-
state performance. These deviations are of two types: large generation/load imbalances and major
blackouts.

35
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

3.4.4.1 Large generation/load imbalances

When large generators or large loads, sized at several hundred megawatts, suddenly trip offline, the
interconnected power system is left with an imbalance of active power. It compensates for this by adjusting
its frequency. For example, in the interconnected Western United States power system, this frequency
deviation has been measured during such disturbances and found not to exceed 0.10 Hz and to last for no
more than a few seconds. Corrective action is taken by generator governors and usually last no more than a
few minutes. Such an event occurs somewhere in a large interconnected power system several times per
month.

3.4.4.2 Major blackouts

When a large portion of an interconnected power system trips offline, the balance of the system may be left
with an enormous active power imbalance. Protection schemes are put in place usually to prevent such a
disturbance from blacking out the entire interconnected system. When this happens, the portion of the
power system that remains with power can deviate in frequency by as much as 0.75 Hz. This kind of
disturbance is rare in developed countries.

3.5 Conclusions
There is a wide range of power quality variations that can be important to a facility engineer.
Understanding the power quality that can be expected from the supply system is a critical part of
developing the best design for equipment specifications and for the facility protection.

Electrical power is a product that is generated, delivered, and used practically instantaneously. As a result,
there are some unique challenges when it comes to quality control. The use of the product, the sine wave of
voltage, is ultimately affected by both how it is delivered and how it is used. Understanding the normal
variability of the steady-state parameters and the characteristics of disturbances is important when trying to
identify power quality issues for particular customers.

In general, equipment should be designed to withstand the normal steady-state power quality variations that
can be expected as part of the normal operation of the power system. However, it is unrealistic to expect the
equipment to handle all disturbances that occur. Understanding the expected disturbances and how often
they can occur is necessary to optimize investments in equipment protection.

Electric utilities must design for electric systems that provide a balance among cost, quality, and reliability
of the electricity delivered to the majority of users. Designing for near-perfect power quality is seldom
justifiable and rarely necessary. The clauses and subclauses that follow, concerning susceptible loads and
end user power conditioning, explain why some customer loads are more susceptible to voltage
disturbances than others and the range of measures available to help address the needs of the sensitive
equipment.

4. Susceptibility of power system loads


Digital electronic devices, particularly those with a memory, are extremely susceptible to very short-
duration power disturbances. These disturbances may result in customer complaints unless adequate ride-
through capability is provided. This clause discusses some common devices that can be included in the
category of susceptible loads.

4.1 Types of susceptible loads

Minicomputers, electronic cash registers, and data terminals are a few examples of susceptible loads that
often fall victim to momentary voltage disturbances. These disturbances can interrupt the operation of
susceptible circuitry and cause memory loss, system malfunction, or component failure.

36
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

4.1.1 Computers

It is reasonable to expect that quality computer equipment will generally meet the requirements of the
conceptual voltage tolerance curve shown in Figure 23. The ITI curve is actually an envelope that defines
the transient and steady-state limits within which the input voltage can vary without either affecting the
proper performance of computer equipment or damaging it. Computer power supplies generate harmonic
distortion and typically are not very susceptible to it unless the voltage waveform is very distorted.
Distortion of the voltage near the zero crossings can cause timing errors.

Figure 23—ITI (formerly CBEMA) Curve—2000

4.1.2 Process control

The microprocessor and microcomputer have fostered the emergence of a new family of commercial and
industrial process automation techniques, which are referred to as facility management systems (for
commercial buildings) and flexible manufacturing systems (for industrial applications). Commercial facility
management systems typically include sensors for input data, remote terminal units, the central processor,

37
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

and man–machine interface devices. The functions managed can include heating, ventilating, and air-
conditioning; security; access control; and energy management. Industrial flexible manufacturing systems
are assemblies of machine tools, cutting tools, and work piece-handling devices employed to process a
variety of finished parts.

The previous discussion on computer sensitivity likewise applies to process control. In addition, motor
starters, contactors, relays, and other devices held closed by a coil and magnetic structure are especially
susceptible to short-time interruptions and voltage sags. As a guide, a voltage sag to 60% or 70% of rated
voltage for 0.5 s will de-energize many of these devices. Many control relays, sealed-in by their own
contacts, will drop out if voltage is lost for 0.5 cycles or more (IEEE Std 446-1995 [B26]).

4.1.3 Telecommunications

When considering the susceptibility of telecommunications equipment, a distinction should be made


between common equipment in the public telecommunications network and individual terminal equipment
that connects to the network. Most of the critical common equipment uses batteries to buffer disturbances
and interruptions of the electric utility service, so short-term transients normally have little or no effect on
the power supply, but a transient can couple in through the phone or network connections and cause
significant damage if unprotected. Also, the individual terminals that connect to the public
telecommunication networks often connect directly to the electric utility service and are subjected to
disturbances.

ATIS-0600315.2018 [B4], among other things, specifies the susceptibility to interruption, sag, and
disturbance for dc-powered network telecommunications equipment power supplies, similar to the ITI
curve for ac-powered computer and industrial process equipment. In short, dc power supplies for network
telecommunications equipment should have enough capacitance built in to ride through complete loss of dc
power input for up to 10 ms.

4.1.4 Electric arc lighting

High-intensity discharge (HID) lighting includes mercury, metal halide, and high-pressure sodium lamps
used for security and street lighting applications. In the event of a power interruption or voltage sag lasting
more than one cycle, HID lamps extinguish and do not restart for several minutes. The exact magnitude of
the voltage drop causing this condition depends on the lamp ballast.

4.1.5 Consumer electronics

An ever-increasing variety and number of digital electronics are found in digital video recorders,
microwave ovens, stereos, televisions, and clocks. Some of these have back-up systems (e.g., batteries) that
prevent disruption to timer/clock functions when power is lost for short periods of time. Others do not.

4.1.6 Adjustable speed drives

Adjustable speed drives (ASDs) are used to control the speed, torque, acceleration, and direction of the
rotation of a motor. Unlike constant speed systems, the ASD permits the selection of an infinite number of
speeds within its operating range. The two basic types of ASDs commonly used today are dc drives and
adjustable alternating current (ac) frequency drives.

DC drives utilize a power converter to convert the fixed ac voltage to an adjustable dc output for
controlling a dc motor. Adjustable-frequency ac drives convert three-phase 60 Hz input power to an
adjustable frequency source for controlling the speed of squirrel-cage induction motors or other ac motors.

Problems have been documented involving nuisance tripping of some manufacturers’ ac drives because of
switching transients associated with capacitors on the customer’s or utility’s system.

38
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

4.2 Ride-through capability

The practice of removing temporary faults on utility systems calls for tripping the circuit breaker (or
recloser), reclosing, and repeating these steps a number of times if the initial trip and reclose operation is
not successful in clearing the fault.

If reclosing is successful on the initial attempt, then customer loads on the faulted circuit would have
experienced a complete loss of voltage for a duration ranging from approximately 3 cycles to several
seconds, depending on the characteristics of the protective device as well as on the reclosing cycle used by
the particular utility. For adjacent circuits connected to the same substation bus, a voltage sag is
experienced for the duration of the fault; although this sag may last for only a few cycles, the voltage can
be low enough to cause susceptible equipment to reset or ASDs to trip.

Subsequent reclosing attempts commonly involve durations of 15 s or more during which the circuit
voltage supply is interrupted. Figure 23 shows that most computer equipment can tolerate a complete loss
of voltage for 0.5 cycles (60 Hz basis) or less. Thus, a single reclosing operation would cause this
equipment to malfunction.

Momentary power interruptions can result in a wide variety of user equipment problems, ranging in
severity from blinking clocks to the shutdown of a factory process. Most of the momentary interruptions
result from circuit breakers (or reclosers) tripping and reclosing to clear temporary faults and thus to avoid
long-term interruptions.

Power supplies found in susceptible equipment have some inherent ride-through capability. Typical ride-
through capabilities of power supplies range from 10 ms to 25 ms. This time is too short to be of much help
in averting problems associated with utility momentary interruptions; it may, however, be sufficient to
allow the operation of static switches or other high-speed source transfer devices used to assure the supply
of power to susceptible equipment.

A study of electronically controlled consumer electronic equipment (Anderson and Bowes [B2]) indicates
that without battery backup, loss of memory occurs for relatively short interruptions of supply power.
Digital clocks, microwave ovens, and videocassette recorders (VCRs) were tested for susceptibility to
voltage abnormalities. Although there were significant differences between the models studied, the average
data indicates that 40% of all clocks malfunctioned for a 120-cycle (2 s) interruption, and all malfunctioned
at 1000 cycles. All microwave ovens malfunctioned at 120 cycles; 62% of the VCRs malfunctioned at
120 cycles, and all malfunctioned at 1000 cycles, except two VCRs that had battery backup (these
withstood all momentary interruptions). An extension of this study to personal computers and printers
(Bowes [B6]) showed that all these devices malfunctioned with a six-cycle interruption, with four
computers malfunctioning for interruption durations of one cycle or less.

Based on a survey of 95 companies, 90% of all first recloser operations used by electric utilities occur
within 10 s (IEEE Power and Energy Society [B25]).

5. Power quality improvements for end users

Given the rapid growth in the utilization of computers, adjustable speed drives, programmable logic
controllers, and other susceptible loads that are vulnerable to misoperation from voltage disturbances, it is
useful to consider the range of measures that is available to help address the special electrical needs of this
type of equipment. Optimizing power quality is a process of weighing the costs of mitigating actions
against the benefits of improved productivity.

As an alternative to modifying their electrical systems, customers may attempt to specify and purchase less
susceptible or more tolerant load equipment. IEEE Std 1346-1998 [B32] is an important reference on
equipment sensitivity issues. It is also important to assure that equipment ratings match the voltage that is
being supplied to the equipment. For example, 220 V equipment is not well served by 208 V.

39
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

5.1 End user wiring and grounding

On the end user side, building wiring problems, such as poor connections, open neutrals, overloads, faults,
or locally generated switching transients, need to be considered before the addition of power conditioning.
Also, grounding techniques may affect the performance of equipment and, most importantly, may amplify
load equipment sensitivity and the adverse effects of voltage disturbances.

5.1.1 Grounding, noise elimination, and circuit design

Before considering power conditioning equipment, it is important that the installation be thoroughly
checked to determine whether there are other problems that might adversely affect susceptible equipment.
Often it is found that very simple actions, such as the tightening of a loose connection, can correct a
problem that is perceived as bad power quality. Obviously, such problems should be addressed before more
costly measures are considered. Overloads or bad electrical connections often appear as localized hot spots
in energized electrical equipment. Infrared heat scans for location of such hot spots are widely accepted in
today’s industry for monitoring the health of electrical equipment. These scans save millions of dollars
each year in reduced unscheduled downtime and lower capital costs relating to repair of failed equipment
(Holliday and Kay [B17]).

Where appropriate, the susceptible equipment should be fed with a separate “dedicated” circuit, which
connects as close as possible to the utility source to minimize effects of other customer loads that could
otherwise cause voltage disturbances. This may require the use of extra transformers, circuits, conduit, and
equipment. Exposure to overvoltage transients may be limited by appropriate application of low-voltage
surge-protection equipment.

Noise problems in susceptible-equipment installations most often result from improper grounding practices.
Proper grounding techniques are outside the scope of this guide. Refer to IEEE Std 1100-2005 [B30] for
extensive information on this subject.

5.2 Premium power solutions

Premium power solutions are sometimes offered by an electrical utility at an extra cost. These solutions can
be managed by the end user seeking to reduce production disruptions from power quality problems such as
voltage sags. Often, premium power solutions utilize a third-party solution provider for maintenance,
operation, and even capital investment. They typically employ technology (power electronics equipment,
devices, circuit configurations, etc.) at 1 kV through 38 kV to mitigate power quality problems upstream of
a facility. Generally, these solutions are more attractive if the economics are considered on a long-term
model. Some examples of premium power solutions are covered in more detail in the subclauses that
follow. IEEE Std 1564-2014 [B35] identifies appropriate voltage sag indices and characteristics on
electrical power and supply systems as well as the methods for calculating them. It is called the System
Average RMS (Variation) Frequency Index (SARFI). Methods are provided for quantifying the severity of
individual voltage sag events (single-event characteristics), for quantifying the performance of multiple
events at a specific location (single-site indices), and for quantifying the performance of multiple events for
the whole system (system indices). The methods are appropriate for use in 50/60 Hz transmission,
distribution, and utilization electric power systems, though there may be applications to systems with other
fundamental frequencies.

5.2.1 Static transfer switch (with dual feed)

If a facility has access to two independent utility power feeds, a static line transfer switch can be
considered. The capability to switch power rapidly to an alternate supply can address a high percentage of
power problems, depending on how separate the two sources are. Static switches, of course, are not
effective in the event of a common disturbance, as might be the case for a fault on the utility transmission
system.

40
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

Figure 24—Static transfer switch

A typical static switch power circuit consists of two pairs of thyristors per phase connected as shown in the
upper portion of Figure 24. When the preferred source is of proper voltage, control logic turns on its
thyristors. Power can then flow from the preferred source to the load. The control logic is typically
equipped with three “preferred source voltage sensors,” which monitor overvoltage, undervoltage, and loss
of voltage, as shown in the lower portion of Figure 24.

The static switch can automatically transfer susceptible loads when power is suddenly lost on either one of
the two synchronized incoming utility lines without disturbance. Total sensing and transfer time is within a
quarter of a cycle (<5 ms) and should not affect most susceptible-equipment operations.

Figure 25 illustrates the trip and reclose sequence of a typical substation circuit breaker that would
coordinate with the automatic transfer of a typical switch. Deviations outside the preset limits (set points)
shown in Figure 24 cause the static switch to transfer to the alternate source. Transfer is prevented,
however, if the alternate source voltage is not present.

Upon restoration of preferred voltage above the “return to preferred” level and below the overvoltage level
for a timed period, the control logic checks for synchronism of the phase and voltage balance between the
preferred and alternate sources and then initiates retransfer to preferred.

41
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

If, during normal operation, a malfunction of the static switch occurs that would otherwise cause a
disturbance to the load, automatic transfer and latch to the alternate source takes place to maintain load
power continuity.

Properly made static switches are dependable and inherently maintenance free with no periodic exercising
requirements to maintain high-speed operation and no contacts to clean.

Figure 25—Typical substation breaker trip and reclose sequence

5.2.2 Dynamic voltage restorer

Another option for protecting plant intake from voltage sags is the dynamic voltage restorer (DVR) that can
be applied at the medium voltage level. The DVR is a custom power technology for power quality
improvement on distribution circuits.

The DVR works on the principle of supplying the missing voltage as shown in Figure 25. The unit does this
utilizing a series connected transformer to the load, through which the power electronics can boost the
voltage. The voltage boost obtained is the ratio of the device size to the load. Generally, DVRs have been
applied most commonly at 30% to 40% boost.

The basic DVR configuration is illustrated in Figure 26. The system injects a compensation voltage in
series with the line by connection of fast switching inverter on the secondary of a transformer in the line.
The inverter can create compensation voltages to correct for some transients, as well as voltage sags.

Figure 26—One line diagram illustrating DVR operation

42
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

5.3 End-user power conditioning (within the facility)

On the customer side, equipment operation, circuit design, and power-conditioning measures can be used to
mitigate or protect against voltage disturbances. The source of these voltage disturbances may be from the
customer as well as from the utility side of the meter.

5.3.1 Overview of power conditioners

Many types of conditioners are available, ranging from the very inexpensive, which protect against only the
least significant types of voltage disturbances, to the expensive, which protect against almost all
eventualities. Table 6 is a summary and comparison of power conditioners.

Table 6 —Power conditioner comparison


Relative Sag Harmonic Conducted Outage ride-
Power Surge Undervoltage Overvoltage
cost or swell distortion noise through
conditioner type protection (sustained) (sustained)
(%)a protection protection protection capability
Surge
<1 X nil
suppressors
Filters <1 SP X nil

Low-voltage
<1 X nil
line reactors
Constant
voltage 35 X X X A X 1 cycle
transformers
Motor
45 X X X P X A 0.3 s a
generators
High-speed
75 X X X X X A 60 s
flywheel
Dual feeders 50−100 b

Static transfer 25 A X X continuous


Standby UPS 60 A X A X A A 15 min
On-line UPS 60 X X X X X X 15 min
UPS and
engine 100 X X X X X X continuous
generator
NOTE—X = protection provided; SP = special distortion-correction filters are available; A = available or provided; P = very short periods
only.
a
1 s with flywheel.
b
Requires two or more independent sources.

5.3.2 High-reliability power backup systems

In most susceptible-equipment sites, operation of the susceptible equipment without cooling can extend to
about 15 min. Beyond that time, even with susceptible-equipment power available, the system should be
shut down if both the susceptible equipment and its cooling system are not on backup power. To provide
for indefinite interruptions of both, a combination of UPS and engine generator is added.

Figure 27 illustrates such a system. The UPS operates normally, conditioning the power to the susceptible
equipment with the engine generator at rest. Upon loss of power, the battery continues to supply the
susceptible equipment, while the cooling and lighting loads go out.

43
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

Figure 27—Combination UPS and engine generator

After a preset period intended to prevent nuisance starts (typically 15 s to 30 s), the engine generator
automatically starts and restores power to the cooling and lighting systems and to the UPS. Normal UPS
operation resumes when the UPS battery is no longer in service. The presence of the generator permits the
use of smaller batteries that may have about 5 min of storage. While operating in this mode, the engine
generator may be subjected to sudden load changes, such as the starting of a compressor motor in the air
conditioning system. This situation can cause a momentary frequency excursion, because of engine-speed
change, until corrected by the governor. The frequency (and/or its rate of change) can exceed the tolerance
of the susceptible equipment causing malfunctions. However, with the interposing UPS, the frequency can
be maintained within tolerance, eliminating possible problems.

Engine generators increase the cost and maintenance of an installation and should be added only if long
interruptions are anticipated and if these losses create a significant problem.

5.3.3 Uninterruptible power supply

UPS systems are an important solution to provide the continuous operation of computer or other susceptible
systems when line voltage interruptions last approximately 0.5 s or longer (a common event for utility fault
clearing). A UPS can provide continuous regulated power under all normal and abnormal utility power
conditions, including interruptions.

UPS systems are typically solid state, although some are currently made using rotating machinery in
combination with solid-state conversion. UPS systems have three general configurations, as illustrated in
simplified form in Figure 28. Most systems contain a storage battery, though some systems use high-speed
flywheels or other technologies for energy storage.

44
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

Figure 28—UPS configurations

5.3.3.1 Standby UPS systems

A standby UPS system includes a rectifier/battery charger, a static inverter, and a static automatic-transfer
switch. The normal flow of power is directly from the line to the load through the transfer switch. In some
versions, however, a regulator is included on the line side or on the load side of the transfer switch to
provide output regulation to susceptible loads. In the event of incoming power loss, the transfer switch is
actuated to pick up the inverter output, which delivers phase-synchronized power to susceptible loads,
usually resulting in less than a 0.25-cycle interruption.

During ac line failure, a standby UPS supplies susceptible-equipment power from the battery through the
inverter.

45
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

5.3.3.2 Online UPS systems

An online UPS system, which includes a larger rectifier/battery charger than the other systems, provides
power to the load through the rectifier and inverter. During a line failure, the inverter operates from the
battery to provide phase-synchronized power to the susceptible load. In the event of inverter output failure
or overload, phase synchronized transfer to the bypass line results in an interruption of less than
0.25 cycles.

5.3.3.3 Rotary UPS systems

Rotary UPSs are gaining in popularity for very large size applications. These units are available, up to
10 000 kVA. Figure 29 is a block diagram of a rotary UPS. It is similar in concept to a conventional M-G
set, where the main difference is that a rotary UPS system utilizes a battery bank for energy storage. This
enables a rotary UPS to provide a ride though time of several minutes, depending on the battery bank
sizing. During normal operation, the motor turns the generator, while the battery bank is charged by a
separate dc generator. During a power failure, the dc motor turns the ac generator, using battery power. The
transition to and from battery power is accomplished by motor controls without the use of contactors or
switches so that the ac generator output is totally uninterrupted. This type of design completely eliminates
the rectifier/charger, inverter, and static bypass switch of conventional UPS systems.

Figure 29—Rotary UPS

5.3.4 Power distribution units (PDUs)

Many grounding problems for large data processing rooms can be avoided, and safer installations can be
provided by the use of properly designed PDUs, usually arranged for installation on a computer room floor
close to the loads that they serve (Figure 30).

These units generally contain input isolating (and usually step-down) transformers with electrostatic
shielding to minimize the effects of potential line-to-ground noise. They include a main circuit breaker that
provides isolation and emergency power-off by push button. The transformers feed panel boards that are
equipped with multiple circuit breakers (and sometimes fuses). Each circuit breaker is connected to a
properly wired and properly grounded flexible under-floor cable with plug-compatible receptacle for the
susceptible equipment it serves (Figure 30 illustrates a typical PDU circuit, several of which might be used
in a large installation). PDUs can also be equipped with power monitoring and alarm functions, as well as
some simple forms of power conditioning. Note that typical utility distribution transformers are not
shielded and, hence, cannot be relied on to provide such shielding in situations where no power distribution
unit exists.

46
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

Figure 30—Power distribution unit

5.3.5 Voltage sag correctors

As voltage sags are much more common than complete interruptions, voltage sag correctors provide for an
important need, particularly in industrial applications. Generally, these devices do not provide backup
power to the load; rather, they simply seek to restore the missing voltage. In this way, voltage sag
correctors can be smaller and much less expensive than UPS systems.

5.3.5.1 Constant voltage transformers (CVT)

CVTs, aka ferroresonant regulators, consist of a linear and a nonlinear inductor as well as a capacitor in a
parallel resonant circuit with the nonlinear inductor (Figure 31).

These elements are generally incorporated into an isolation transformer configuration together with
additional filtering to eliminate self-induced harmonics. This filtering can handle a reasonable level of
harmonic distortion at the output induced by nonlinear computer load, but excess harmonics can produce
overheating of the regulator. The circuit is tuned to the rated output voltage and frequency.

47
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

Figure 31—Ferroresonant regulator

Ferroresonant regulators maintain a constant output voltage for a wide range of input voltage, particularly
at a light load. Their inherent current-limiting characteristic, which limits maximum current at full voltage,
can be a limitation when starting motors or computer central processing units. Because of this
characteristic, they are generally operated at a considerably underrated condition. Some short-term
overvoltages occur at the output ferroresonant regulator upon recovery from an interruption.

The tuned circuit has a small amount of stored energy and will ride through interruptions of about one
cycle, provided the interruption is not a fault close to the input, which would drain the stored energy. It will
not ride through a 0.5 s interruption typical of the automatic reclosure on a utility circuit; however, many
will ride through up to 50% voltage sag for 0.5 s, which would probably be sufficient to handle fault
clearing on a nearby circuit. Ferroresonant regulators are large and heavy because of the magnetics
involved, but they are simple and reliable.

5.3.5.2 Motor-generator sets

Motor-generator sets consist of electric motors driving ac generators. The load is supplied by the generator
and is electrically isolated from the utility supply. Motor-generators can isolate the load from impulses and
from voltage sags and swells. For power-line voltage changes of ±20% or more, voltage to the load is
maintained at nominal.

A useful feature of the motor-generator is its ability to bridge severe short-term sags or interruptions. The
inertia of the rotating elements permits the motor-generator to span interruptions of up to about 0.3 s. This
is mainly limited by the drop in frequency (speed) as energy is removed. This period can be extended by
adding inertia via a flywheel as shown in Figure 32. This amount of time provides protection for the
common case of fault clearing and reclosing on a utility distribution system. Some systems use variable-
speed constant frequency or quick-starting engine generator techniques to get more advantage from the
flywheel inertia. The cost is considerably higher than conventional motor-generators. The motor-generator
set with flywheel is sometimes classified as UPS equipment.

48
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

Figure 32—Motor-generator set with flywheel

The problems with motor-generators are mostly on the output or load side. High generator output
impedance can cause substantial voltage sags in response to sudden load changes, such as resulting from
large motor-starting current, and response to load changes can be sluggish. Also, unless it is oversized, the
drive motor may overheat under long-term, low-line voltage conditions.

Motor-generator efficiency is typically relatively low, so that electrical energy costs over its lifetime may
be substantial. Heat dissipation, equipment weight and bulk, and the potential for audible noise are factors
that should be considered in motor-generator installations. Essentially silent machines are available at extra
cost. Bearings should be inspected and periodically replaced and/or lubricated in many cases, particularly
when flywheels are used. Reliability potential, however, is very high.

5.3.5.3 Active voltage conditioner

Active voltage conditioners are low-voltage, inverter-based power conditioners. These devices are designed
to provide voltage sag ride through capability to industrial, three-phase equipment. They are often applied
to machining centers and extrusion process, to prevent costly shut downs and equipment failures. Smaller
units (10 kVA to 200 kVA units) generally depend on electronics, whereas larger units (200 kVA to
10 000 kVA) may employ an injection transformer in a similar manner to the dynamic voltage restorer.

The key specifications for an active voltage conditioner are the efficiency, power rating, allowable voltage
sag depth (provided voltage correction), and the duration of the correction. Often these units are sized to
provide correction for the most common voltage sags (30% of depth). This sizing realizes that it would take
a much more expensive unit to correct for deeper voltage sag events that are not as common. An economic
model is usually developed, in conjunction with the annual voltage sag profile of the facility, to determine
the optimal sizing and expenditure required.

5.4 Controlling harmonics

In general, electrical and electronic equipment, such as rectifier power supplies, are not greatly affected by
small amounts of harmonic distortion. Problems may occur where there is enough harmonic current
distortion to affect the supply voltage adversely. High levels of reactive harmonic current injection may
overload building wiring and service transformers and may cause abnormal rms voltage or very distorted
waveshape.

5.4.1 Harmonics at point of use

IEEE Std 519-2014 [B28] recommends total demand distortion limits at the point of common coupling to
other users, including the effect of customer load-induced harmonics. In actual practice, the utility system
distortion is usually less than the proposed limits, but the customer load-induced harmonics often cause
voltage THD to exceed 5% at the point of use. Also, current distortion in three-phase, four-wire systems

49
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

feeding multiple nonlinear single-phase loads, such as computer power supplies, often creates excessive
neutral current. The result may be wiring overloads and fire hazards or damage to the delta-wye supply
transformer typically provided.

It is recommended that the harmonic current limits be followed to protect the facility power system, which
is probably more vulnerable to adverse harmonic effects than the facility loads.

The following actions help reduce the effects of load-induced waveform distortion (Griffith [B16] provides
more detail):

 Reduce the impedance of the power source. A larger source transformer (or generator) of the
same type will have a lower impedance and will reduce voltage distortion proportionally. This
may also be necessary to accommodate the extra heating because of third harmonics (and odd
multiples of third) circulating in the delta winding (CBEMA [B8]). This is typically an
expensive solution.
 Move the symptomatic load to a lower impedance circuit. The best results occur when a
dedicated circuit is run from the main service transformer to the load or to a step down
transformer adjacent to the load.
 Move the harmonic-producing loads to other circuits. The best results occur when the harmonic-
producing loads are moved to a circuit that is on a separate power source, thereby providing
some degree of electrical isolation.
 For the special case of third harmonics and their odd multiples, a properly sized delta-connected
transformer will provide a circulating path for these harmonics, reducing their effect upstream
from the transformer (toward the power source and other loads common to it). Single-phase
rectified input switching power supplies are rich in third harmonic current but contain
significant higher-order harmonics.
 Provide harmonic filters in lieu of capacitors to control harmonic current flow.
 In three-phase systems, harmonics can also be mitigated by special transformer circuitry. One
example is the use of a zigzag transformer or a Scott-T or T-connected transformer.
 In three-phase systems supplying separate single-phase loads with nonsinusoidal current input,
the shared neutral circuit should be increased in current rating to about twice the phase rating
(CBEMA [B8]). The capability of the supply transformer should be checked for the
nonsinusoidal load by consulting IEEE Std C57.110-2008 [B38].

5.4.2 Harmonic filters

Harmonic filters are designed to control the level of voltage and current distortion generated by all the
elements of the equipment to which they are connected, including susceptible equipment, which often
generates distortion by itself. Filters consist of active or passive circuit elements. Most such filters in use
today are passive and provide a short-circuit path for the harmonics generated by the load using one or
more series-tuned traps.

Problems in application include excessive voltage or current resulting from resonance with other elements
in the power system and excessive power frequency current drawn by the filter. In addition, because of
their low impedance to specific harmonics, they attract currents of the same harmonic if they exist
elsewhere on the power system, potentially overloading the filter. For these reasons, such filters are
generally applied on an engineered or special basis. However, some filters come with isolating and/or
power-factor-correcting circuitry as a standard feature that can mitigate these problems.

50
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

5.5 Surge protective devices (SPDs)

SPDs protect susceptible electronic equipment from surges. These devices usually contain component(s)
that provide a voltage-dependent diversion of surge current. Some units also contain passive filter
components, such as series inductors and parallel capacitors.

Two of the most common voltage-dependent components that are used in these devices are metal oxide
varistors and large junction avalanche diodes that are specifically designed for surge diversion.

Components exhibiting surge-protection characteristics are often integrated into the PDUs, UPSs, power
supplies, and power-conditioning equipment. However, these provide a level of surge protection that may
not be adequate for all conditions. Additional surge protection may be needed, depending on the severity of
the environment.

The proper application of an SPD requires a coordinated approach based on the expected energy deposition
into the candidate device at the applied location. Typically, a building service entrance or main panel
device would be expected to divert a greater part of the surge current than a device installed at a secondary
panel, a receptacle, or within equipment. If two SPDs are installed in cascade, coordination of the
operation—that is, energy deposition commensurate with the respective ratings of the two devices—
depends on the relative clamping voltages of the devices, on the distance separating them, and on the
waveform (postulated in the absence of known specifics about the installation) of the impinging surge (Lai
and Martzloff [B42]).

The selection of the appropriate voltage rating is based on the nominal service voltage, including normal
and abnormal upward deviations (ANSI C84.1-2016 [B3]) and the maximum continuous operating voltage
(MCOV) of the SPD. The MCOV rating of the SPD should be selected to be at least 120% of the nominal
rms service voltage (Standler [B60] and CIGRE C4.7 [B10]). Specifying the MCOV to be between 150%
and 200% of the nominal rms service voltage provides additional protection against degradation of the SPD
by swells or relatively low-level transient overvoltages (Martzloff and Leedy [B46]). More information on
surge protective devices can be found in UL 1449 [B64] and IEEE C62 series of documents.

5.6 Special considerations for variable frequency drives (VFDs)

5.6.1 Input line reactors

Low-voltage line reactors (inductors) provide an alternative to isolation transformers for attenuating
voltage disturbances on susceptible circuits. They have been successfully applied to three-phase ac ASDs to
prevent nuisance overvoltage tripping during capacitor switching. The additional series inductance of the
reactor reduces the current surge into the ASD, thereby limiting the dc overvoltage.

5.6.2 Effect of VFD inverter switching pulses on motors

VFDs most commonly utilize insulated gate bipolar transistors to invert the dc bus voltage to the variable
voltage and frequency required to control the speed of the ac motor. However, the pulse width modulated
output of the drive unit also generates a voltage rise (dv/dt) on the output waveform. It is not uncommon for
the voltage rise to approach 10 kV/μs.

When the motor is separated from the VFD by more than a critical length of cable, these pulses reflect back
upon themselves at the motor, and can be damaging to the motor insulation. The critical length is
determined by the pulse rise time (to 50% value) and the travel time of the cable. The velocity of a
traveling wave in a cable can be estimated at 1 × 108 m/s. With most VFDs, the critical length will be
longer than 7.62 m (25 ft).

Inverter duty motors can be employed to address this concern, which is highlighted in IEEE Std 841™-2009
[B29] and NEMA MG 1 [B50]. Also, line terminators can be installed at the motors, or line reactors can be
installed on the output of the VFD to address this concern.

51
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

5.7 Special considerations for residential loads

The home office needs for quality power may require better service reliability than that normally supplied
by the area electric power supplier (area EPS), because the area EPS service is subjected to the extensive
environmental exposures (lightning, wind, tree contact, etc.) as well as harmonics generated by other
customers. Depending upon the criticality of the home office business, consideration should be given to the
addition of power conditioning equipment, a UPS for short-term momentary disturbances and/or on-site
emergency generation to address long time loss of electric service.

5.8 Economic analysis of power conditioning alternatives

Figure 33 illustrates a general approach to power conditioning. The usual approach is to place the power
conditioner in front of the susceptible load. Figure 34 shows that this location can be interpreted in several
different physical locations: anywhere from inside the plant to out on the utility system. It also shows that
the cost of this protection increases as the location moves toward the utility system.

Figure 33—Approach to the application of power conditioning equipment

The cost of protecting equipment from disturbances increases dramatically as one progresses out from the
critical load locations. For example, a power conditioner that can be used to protect process controls, as
opposed to the entire process, is smaller and much more economical. Therefore, it is very important first to
understand the process completely before any power conditioning equipment is applied. Protection of an
entire plant, for instance, is often very costly and generally not required. A site survey should always be
done that characterizes susceptible and critical loads. Many plant loads may not be critical and, therefore,
may not need power conditioning equipment.

52
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

Figure 34—Four locations for power conditioning equipment, showing the relative economic
cost and complexity

5.8.1 Cost/benefit considerations

Another key factor in the application of power conditioning equipment is cost/benefit. This refers to the
economic justification and payback of applying power conditioning equipment. Some customers may have
processes very critical in nature, losing a tremendous amount of money every time a power quality event
occurs. This can be attributed to production downtime and/or lost product. Some industries are much more
vulnerable to power quality variations and, therefore, tend to have a quicker payback when applying power
conditioning equipment. This type of cost/benefit analysis should be done as part of any power
conditioning application project. Table 7 provides an example of cost/benefit analysis of power quality
solutions.

Table 7 —Example results from cost/benefit analysis


Operating Benefit/cost
Power conditioning technology Cost benefit Capital cost Annual cost
cost ratio
Utility side options
Feeder reactors $ 375,000 $1,000,000 2% $ 275,375 1.36
Static switch $ 375,000 $ 600,000 5% $ 183,823 2.04
DVR $ 822,500 $3,000,000 10% $1,082,226 0.76
SSVR $ 720,000 $3,000,000 10% $1,074,627 0.67
Customer side options
CVTs $ 389,000 $ 200,000 15% $ 80,705 4.82
UPS protection $ 903,750 $6,000,000 15% $2,442,568 0.37

53
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

Annex A

(informative)

Glossary

NOTE—Numbers in parentheses align with definition numbers in The IEEE Standards Dictionary Online. 3

current transformer (CT): (2) (metering) An instrument transformer designed for use in the measurement
or control of current.
electromagnetic compatibility (EMC): (1) (supervisory control, data acquisition, and automatic control)
(station control and data acquisition) A measure of equipment tolerance to external electromagnetic fields.
(2) (control of system electromagnetic compatibility) The ability of a device, equipment, or system to
function satisfactorily in its electromagnetic environment without introducing intolerable electromagnetic
disturbances to anything in that environment.
electromagnetic disturbance: (1) An electromagnetic phenomenon that may be superimposed on a wanted
signal. (2) (overhead power lines) Any electromagnetic phenomenon that may degrade the performance of
a device, a piece of equipment, or a system.
equipment grounding conductor: (2) The conductor used to connect the noncurrent-carrying parts of
conduits, raceways, and equipment enclosures to the grounding electrode at the service equipment (main
panel) or secondary of a separately derived system.
frequency deviation: (5) An increase or decrease in the power frequency from nominal. The duration of a
frequency deviation can be from several cycles to several hours.
ground: (3) (A) A conducting connection, whether intentional or accidental, by which an electric circuit or
equipment is connected to the earth, or to some conducting body of relatively large extent that serves in
place of the earth. (B) High frequency reference.

NOTE—Grounds are used for establishing and maintaining the potential of the earth (or of the conducting body) or
approximately that potential, on conductors connected to it, and for conducting ground currents to and from earth (or
the conducting body).

ground loop: (2) A potentially detrimental loop formed when two or more points in an electrical system
that are nominally at ground potential are connected by a conducting path such that either or both points are
not at the same ground potential.
harmonic: A sinusoidal component of a periodic wave or quantity having a frequency that is an integral
multiple of the fundamental frequency.

NOTE—For example, a component, the frequency of which is twice the fundamental frequency, is called a second
harmonic.

harmonic components: The components of the harmonic content expressed in terms of the order and rms
(root-mean-square) values of the Fourier series terms describing the periodic function.
harmonic content: (1) The function obtained by subtracting the dc (direct current) and fundamental
components from a nonsinusoidal periodic function. (2) The deviation from the sinusoidal form, expressed
in terms of the order and magnitude of the Fourier series terms describing the wave. (3) Distortion of a
sinusoidal waveform characterized by indication of the magnitude and order of the Fourier series terms
describing the wave.

3
Notes in text, tables, and figures of a standard are given for information only and do not contain requirements needed to implement
this standard.

54
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

immunity (to a disturbance): The ability of a device, equipment, or system to perform without
degradation in the presence of an electromagnetic disturbance.
isolated equipment ground: An isolated equipment grounding conductor run in the same conduit or
raceway as the supply conductors. This conductor may be insulated from the metallic raceway and all
ground points throughout its length. It originates at an isolated ground-type receptacle or equipment input
terminal block and terminates at the point where neutral and ground are bonded at the power source.
isolation: (3) Separation of one section of a system from undesired influences of other sections.
maximum demand: (1) (power operations) The largest of a particular type of demand occurring within a
specified period.
momentary: When used as a modifier to quantify the duration of a short duration variation, refers to a time
range at the power frequency from 30 cycles to 3 s.
momentary interruption: A type of short duration variation. The complete loss of voltage (<0.1 pu) on
one or more phase conductors for a time period between 0.5 cycles and 3 s.
noise: (11) Electrical noise is unwanted electrical signals that produce undesirable effects in the circuits of
the control systems in which they occur.
nominal voltage: (3) A nominal value assigned to a circuit or system for the purpose of conveniently
designating its voltage class (as 208/120, 480/277, 600).
nonlinear load: A load that draws a nonsinusoidal current wave when supplied by a sinusoidal voltage
source.
notch: (2) A switching (or other) disturbance of the normal power voltage waveform, lasting less than a
half cycle, which is initially of opposite polarity than the waveform and is thus subtracted from the normal
waveform in terms of the peak value of the disturbance voltage. This includes complete loss of voltage for
up to a half cycle.
oscillatory transient: A sudden, non-power frequency change in the steady-state condition of voltage or
current that may occur on either the positive or negative polarity value.
overvoltage: (9) When used to describe a specific type of long duration variation, refers to a measured
voltage having a value greater than the nominal voltage for a period of time greater than 1 min. Typical
values are 1.1 pu to 1.2 pu.
potential transformer (PT); also, voltage transformer: (1) (voltage transformer). An instrument
transformer that is intended to have its primary winding connected in shunt with a power-supply circuit, the
voltage of which is to be measured or controlled.
power disturbance: Any deviation from the nominal value (or from some selected thresholds based on
load tolerance) of the input ac power characteristics.
power quality: The concept of powering and grounding electronic equipment in a manner that is suitable
to the operation of that equipment and compatible with the premise wiring system and other connected
equipment.
pulse: (4) A wave that departs from an initial level for a limited duration of time and ultimately returns to
the original level.
sag: (2) A decrease in rms voltage or current at the power frequency for durations of 0.5 cycles to 1 min.
Typical values are 0.1 pu to 0.9 pu.
shield: (7) (instrumentation cables) (cable systems) A metallic sheath, usually copper or aluminum, applied
over the insulation of a conductor or conductors for the purpose of providing means for reducing
electrostatic coupling between the conductors so shielded and others which may be susceptible to or which
may be generating unwanted (noise) electrostatic fields.

55
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

shielding: (3) The process of applying a conducting barrier between a potentially disturbing noise source
and electronic circuitry. Shields are used to protect cables (data and power) and electronic circuits.
Shielding may be accomplished by the use of metal barriers, enclosures, or wrappings around source
circuits and receiving circuits.
Static series voltage regulator (SSVR): A device that boosts voltage under certain conditions to protect a
load on a feeder branch from voltage dips.
sustained: When used to quantify the duration of a voltage interruption, refers to the time frame associated
with a long duration variation (i.e., greater than 1 min).
sustained interruption: A type of long duration variation. The complete loss of voltage (<0.1 pu) on one
of more phase conductors for a time greater than 1 min.
swell: (3) An increase in rms voltage or current at the power frequency for durations from 0.5 cycles to
1 min. Typical values are 1.1 pu to 1.8 pu.
System Average Interruption Frequency Index (SAIFI): A commonly used reliability indicator by
electric power utilities. It is the average number of interruptions that a customer would experience.
temporary interruption: A type of short duration variation. The complete loss of voltage (<0.1 pu) on one
or more phase conductors for a time period between 3 s and 1 min.
total demand distortion (TDD): (1) The total root-sum-square harmonic current distortion, in percent of
the maximum demand load current (15 min or 30 min demand).
point of common coupling (PCC): (3) The point at which the electric utility and the customer interface
occurs. Typically, this point is the customer side of the utility revenue meter.
total harmonic distortion (THD), also distortion factor (harmonic factor): The ratio of the root-mean-
square of the harmonic content to the root-mean-square value of the fundamental quantity, expressed as a
percent of the fundamental.
transient: (7) Pertaining to or designating a phenomenon or a quantity that varies between two consecutive
steady states during a time interval that is short compared to the time scale of interest. A transient can be a
unidirectional impulse of either polarity or a damped oscillatory wave with the first peak occurring in either
polarity.
undervoltage: (1) When used to describe a specific type of long duration variation, refers to a measured
voltage having a value less than the nominal voltage for a period of time greater than 1 min. Typical values
are 0.8 pu to 0.9 pu.
uninterruptible power supply (UPS): An electrical apparatus that provides emergency power to a load
when the input power source or mains power fails.
voltage distortion: Any deviation from the nominal sine waveform of the ac line voltage.
voltage imbalance, polyphase systems: The ratio of the negative or zero sequence component to the
positive sequence component, usually expressed as a percentage. In the United States, it is also commonly
measured as the ratio of the maximum deviation to the average of the three phases (ANSI C84.1-2016
[B3]).
voltage regulation: (6) The degree of control or stability of the rms voltage at the load. Often specified in
relation to other parameters, such as input-voltage changes, load changes, or temperature changes.

56
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

Annex B

(informative)

Lookup table of standards

Clause Description Relevant standard(s)

3.3 Steady State IEC 61000-2-2:2002 [B20], EN 50160:2010/A1:2015 [B14]

3.3 Measurement IEC 61000-4-30: 2015 [B24], IEEE Std 1159-2009 [B31]
3.3.1 Voltage Regulation ITIC, CBEMA
3.3.1.1 Voltage Regulation Limits ANSI C84.1-2016 [B3], IEC 61000-2-2:2002 [B20], EN
50160:2010/A1:2015 [B14]
3.3.2.1 Voltage Imbalance ANSI C84.1-2016 [B3], IEC 61000-2-2:2002 [B20], EN
50160:2010/A1:2015 [B14]
3.3.3.1 Voltage Distortion Limits IEEE Std 1453-2015 [B34], IEC 61000-2-2:2002 [B20], EN
50160:2010/A1:2015 [B14]
3.3.4.1 Flicker IEEE Std 1453-2015 [B34], IEC 61000-4-15:2010 [B23], IEC 61000-2-
2:2002 [B20], IEC 61000-3-7:2008 [B21], EN-50160:2010/A1:2015
[B14]
3.3.4.2 Flicker Planning Limits IEC 61000-3-7:2008 [B21]
3.3.4.3 Flicker Limits/Assessment IEC 61000-2-2:2002 [B20], EN 50160:2010/A1:2015 [B14], IEC 61000-
4-15:2010 [B23]
3.3.6 Steady State Power quality IEC 61000-4-30:2015 [B24]
3.4.1 Reliability Indices IEEE Std 1366-2012 [B33]
3.4.2 Voltage Sag Indices IEEE Std 493-2007 [B27], IEEE Std 1564-2014 [B35], IEEE Std 1668
[B36]
4.2.4 Voltage Distortion IEEE Std 519-2014 [B28]
4.2.5 Voltage Fluctuations IEEE Std 1453-2015 [B34]
5.1.1 Susceptible Loads— IEEE Std 446-1995 [B26]
Computers
5.1.2 Susceptible Loads—Process IEEE Std 446-1995 [B26]
Control
6 Equipment Sensitivity IEEE Std 1346-1998 [B32]
6.1.1 Grounding IEEE Std 1100-2005 [B30]
6.4.1 Total Demand Distortion IEEE Std 519-2014 [B28]
6.4.1 Nonsinusoidal Load IEEE Std C57.110-2008 [B38]
6.5 Surge Protection Devices ANSI C84.1-2016 [B3], CIGRE C4.7 [B10], UL 1449 [B64], IEEE Std
C62 Series
6.6.2 VFD IEEE Std 841-2009 [B29], NEMA MG 1 [B50]

57
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

Annex C

(informative)

Bibliography

[B1] Agamloh, E.B; Peele, Scott; and Grappe, Joe, “A comparative analysis of voltage magnitude
deviation and unbalance on standard and premium efficient induction motors,” Conference Record of 2012
Annual IEEE Pulp and Paper Industry Technical Conference (PPIC), 17−21 June 2012. 4

[B2] Anderson, L. M. and Bowes, K. B., “The effects of power-line disturbances on consumer electronic
equipment,” IEEE Transactions on Power Delivery, vol. 5, no. 2, pp. 1062–1065, April 1990.

[B3] ANSI C84.1-2016, American National Standard for Electric Power Systems and Equipment—
Voltage Ratings (60 Hertz). 5

[B4] ATIS 0600315.2018, Voltage Levels for DC-Powered Equipment Used in the Telecommunications
Environment. 6

[B5] Bollen, M. H. J., Understanding Power Quality Problems. New York: IEEE Press, 2000.

[B6] Bowes, K. B., “The effects of power line disturbances on electronic products,” Official Proceedings
of the First International Power Quality Conference, Long Beach, CA, p. 216, Oct. 15–20, 1989.

[B7] Burke, J. J., Griffith, D. C., and Ward, D. J., “Power quality—two different perspectives,” IEEE
Transactions on Power Delivery, vol. 5, no. 3, pp. 1501–1513, July 1990.

[B8] CBEMA Information Letter. “Three Phase Power Source Overloading Caused by Small Computers
and Electronic Office Equipment,” 1988. Change to ITIC.

[B9] Chamberlin, D. M. and Pidcock, D. J., “The northeast utilities distribution disturbance and
interruption monitoring system,” IEEE Transactions on Power Delivery, vol. 6, no. 1, pp. 267–274, Jan.
1991.

[B10] CIGRE C4.7/CIRED Joint Working Group report. Power Quality Indices and Objectives, 2004.

[B11] Davidson, R., “Suppression voltage ratings on UL listed transient voltage surge suppressors
(TVSS),” Proceedings, Open Forum on Surge Protection Application, National Institute of Standards and
Technology Special Publication, pp. 89–92, 1991.

[B12] Dranetz Field Handbook for Power Quality Analysis. Edison, NJ: Dranetz Technologies, Inc., 1991.

[B13] Dugan, R. C., Electrical Power Systems Quality. New York: McGraw-Hill Professional, 2002.

[B14] EN 50160:2010/A1:2015, Voltage characteristic of electricity supplied by public electricity


networks. 7

4
Available at https://ieeexplore.ieee.org/document/6293004/authors#authors.
5
ANSI publications are available from the Sales Department, American National Standards Institute, 25 West 43rd Street, 4th Floor,
New York, NY 10036, USA (http://www.ansi.org/).
6
ATIS publications are available from Alliance for Telecommunication Industry Solutions at ANSI (http://www.ansi.org/).

58
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

[B15] EPRI TR-106294-V2:1996, An Assessment of Distribution System Power Quality. 8

[B16] Griffith, D. C., Uninterruptible Power Supplies and Other Power Conditioners for Critical
Equipment. Marcel Dekker, Inc., 1989.

[B17] Holliday, A. J. and Kay, J. A., “The use of infrared viewing systems in electrical control equipment,”
Pulp and Paper Industry Technical Conference, 2005. June 2005, pp. 291–295.

[B18] Horton, R. and Haskew, T., “Determination of flicker transfer coefficients near large synchronous
generators,” IEEE Transactions on Power Delivery, vol. 25, no. 1, Dec. 2009.

[B19] Horton, R. and Haskew, T. “Effect of transfer coefficients on MV and LV flicker levels,” 2010 IEEE
Power and Energy Society General Meeting, July 2010.

[B20] IEC 61000-2-2:2002, Electromagnetic Compatibility (EMC)—Part 2-2: Environment—


Compatibility Levels for Low-Frequency Conducted Disturbances and Signalling in Public Low-Voltage
Power Supply Systems. 9

[B21] IEC 61000-3-7:2008, Electromagnetic Compatibility (EMC)—Part 3-7: Limits—Assessment of


Emission Limits for the Connection of Fluctuating Installations to MV, HV and EHV Power Systems.

[B22] IEC 61000-4-7:2002/A1:2009, Electromagnetic Compatibility (EMC)—Part 4-7: Testing and


Measurement Techniques—General Guide on Harmonics and Interharmonics Measurements and
Instrumentation, for Power Supply Systems and Equipment Connected Thereto.

[B23] IEC 61000-4-15:2010, Electromagnetic Compatibility—Part 4-15: Testing and Measurement


Techniques—Flickermeter—Functional and Design Specifications.

[B24] IEC 61000-4-30:2015, Electromagnetic Compatibility (EMC)—Part 4-30: Testing and Measurement
Techniques—Power Quality Measurement Methods.

[B25] IEEE Power and Engineering Society, “Distribution line protection practices—industry survey
results,” IEEE Transactions on Power Delivery, vol. 3, no. 2, pp. 514–524, Apr. 1988

[B26] IEEE Std 446™-1995 (IEEE Orange Book), IEEE Recommended Practice for Emergency and
Standby Power Systems for Industrial and Commercial Applications. 10, 11

[B27] IEEE Std 493™-2007 (IEEE Gold Book), IEEE Recommended Practice for the Design of Reliable
Industrial and Commercial Power Systems.

[B28] IEEE Std 519™-2014, IEEE Recommended Practices and Requirements for Harmonic Control in
Electrical Power Systems.

[B29] IEEE Std 841™-2009, IEEE Standard for Petroleum and Chemical Industry-Premium-Efficiency,
Severe-Duty, Totally Enclosed Fan-Cooled (TEFC) Squirrel Cage Induction Motors—Up to and Including
370 kW (500 hp).

7
EN publications are available from the European Committee for Standardization (CEN), 36, rue de Stassart, B-1050 Brussels,
Belgium (http://www.cenorm.be).
8
EPRI publications are available from the Electric Power Research Institute, 3420 Hillview Avenue, Palo Alto, CA 94304
(http://www.epri.com).
9
IEC publications are available from the Sales Department of the International Electrotechnical Commission, Case Postale 131, 3 rue
de Varembé, CH-1211, Genève 20, Switzerland/Suisse (http://www.iec.ch/). IEC publications are also available in the United States
from the Sales Department, American National Standards Institute, 11 West 42nd Street, 13th Floor, New York, NY 10036, USA.
10
The IEEE standards or products referred to in this clause are trademarks owned by the Institute of Electrical and Electronics
Engineers, Incorporated.
11
IEEE publications are available from the Institute of Electrical and Electronics Engineers, 445 Hoes Lane, Piscataway, NJ 08854,
USA (http://standards.ieee.org/).

59
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

[B30] IEEE Std 1100™-2005 (IEEE Emerald Book), IEEE Recommended Practice for Powering and
Grounding Sensitive Electronic Equipment.

[B31] IEEE Std 1159™-2009, IEEE Recommended Practice for Monitoring Electric Power Quality.

[B32] IEEE Std 1346™-1998, IEEE Recommended Practice for Evaluating Electric Power System
Compatibility With Electronic Process Equipment (withdrawn). 12

[B33] IEEE Std 1366™-2012, IEEE Guide for Electric Power Distribution Reliability Indices.

[B34] IEEE Std 1453™-2015, IEEE Recommended Practice for the Analysis of Fluctuating Installations
on Power Systems.

[B35] IEEE Std 1564™-2014, IEEE Guide for Voltage Sag Indices.

[B36] IEEE Std 1668™-2017, IEEE Recommended Practice for Voltage Sag and Short Interruption Ride-
Through Testing for End-Use Electrical Equipment Rated Less than 1000 V.

[B37] IEEE Std C57.12.00™-2015, IEEE Standard for General Requirements for Liquid-Immersed
Distribution, Power, and Regulating Transformers.

[B38] IEEE Std C57.110™-2008, IEEE Recommended Practice for Establishing Transformer Capability
When Supplying Nonsinusoidal Load Currents.

[B39] “Infrastructure Quality and Reliability,” EPRI Report issued to members Sept. 22, 2003.

[B40] Key, T. S., “Diagnosing power quality-related computer problems,” IEEE Transactions on Industry
Applications, vol. IA-15, no. 4, July/Aug. 1979.

[B41] Key, T. S., “Evaluation of grid-connected power systems: The utility interface,” Transactions on
Industry Applications, vol. IA-20, no. 4, pp. 735–741, July/Aug. 1984.

[B42] Lai, J. S. and Martzloff, F. D., “Coordinating cascaded surge-protective devices: High-low versus
low-high,” Conference Proceeding, Vol. 2, IEEE/IAS Annual Meeting, Oct. 1991.

[B43] Martzloff, F. D. and Gauper, H. G., “Surge and high-frequency propagation in industrial power
lines,” IEEE Transactions on Industry Applications, vol. IA-22, no. 4, July/Aug. 1986.

[B44] Martzloff, F. D. and Gruzs, T. M., “Power quality site surveys: Facts, fiction, and fallacies,” IEEE
Transactions on Industry Applications, vol. 24, no. 6, Nov./Dec. 1988.

[B45] Martzloff, F. D. and Hahn, G. J., “Surge voltages in residential and industrial power circuits,” IEEE
Transactions on Power Apparatus and Systems, vol. PAS-89, no. 6, July/Aug. 1970.

[B46] Martzloff, F. D. and Leedy, T. F., “Selecting varistor clamping voltage: Lower is not better!”
Proceedings, Zürich EMC Symposium, pp. 137–142, 1989.

[B47] McEachern, A., Handbook of Power Signatures. Foster City, CA: Basic Measuring Instruments,
1988.

[B48] Mohan, N., Power Electronics: Converters, Applications, and Design. New York: John Wiley &
Sons, 2003.

12
IEEE Std 1346-1998 has been withdrawn; however, copies can be obtained from Global Engineering, 15 Inverness Way East,
Englewood, CO 80112-5704, USA, tel. (303) 792-2181 (http://global.ihs.com/).

60
Copyright © 2018 IEEE. All rights reserved.

Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded on March 13,2019 at 13:49:51 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1250-2018
IEEE Guide for Identifying and Improving Voltage Quality in Power Systems

[B49] Morrison, R. and Lewis, W. H., Grounding and Shielding in Facilities. New York: Wiley
Interscience, 1990.

[B50] NEMA MG 1-2016, Motors and Generators. 13

[B51] PacifiCorp, Engineering Handbook, Section 1C.8.1—Voltage Frequency. Portland, OR: PacifiCorp,
Dec. 6, 1996, p. 1.

[B52] “Power System Reliability Analysis: Application Guide Report,” prepared by CIGRE Working
Group 03 of Study Committee 38, 1987.

[B53] Renner, H. and Sakulin, M., “Flicker propagation in meshed high voltage networks,” Ninth
International Conference on Harmonics and Quality of Power, 2000, vol. 3, pp. 1023–1028, Oct. 2000.

[B54] Sabin, D. D., Brooks, D. L., and Sundaram, A., “Indices for assessing harmonic distortion from
power quality measurements: definitions and benchmark data,” IEEE Transactions on Power Delivery, vol.
14, no. 2, pp. 489–496, Apr. 1999.

[B55] Sabin, D. D., Grebe, T. E., and Sundaram, A., “RMS voltage variation statistical analysis for a
survey of distribution system power quality performance,” IEEE Power Engineering Society 1999 Winter
Meeting, vol. 2, pp. 1235–1240, Jan–Feb. 1999.

[B56] Sabin, D. D., Grebe, T. E., Brooks, D. L., and Sundaram, A., “Rules-based algorithm for detecting
transient overvoltages due to capacitor switching and statistical analysis of capacitor switching in
distribution systems,” 1999 IEEE Transmission and Distribution Conference, vol. 2, pp. 630–635, Apr.
1999.

[B57] SEMI F47-0706:2006, Specification for Semiconductor Processing Equipment Voltage Sag
Immunity. 14

[B58] Smith, S. B. and Standler, R. B., “The effects of surges on electronic appliances,” IEEE
Transactions on Power Delivery, vol. 7, no. 3, pp. 1275–1281, July 1992.

[B59] Soares Book on Grounding and Bonding, 10th ed. International Association of Electrical Inspectors,
2008.

[B60] Standler, R. B., “Coordination of surge arresters and suppressors for use on low-voltage mains,”
Proceedings, Zürich EMC Symposium, pp. 517–524, 1991.

[B61] Standler, R. B., “Development of a performance standard for surge arresters and suppressors,” IEEE
1991 Symposium on Electromagnetic Compatibility, Cherry Hill, NJ, pp. 458–463, Aug. 1991.

[B62] Standler, R. B., Protection of Electronic Circuits from Overvoltages. New York: Wiley Interscience,
1989.

[B63] Technical Coordination and Data Analysis for Measuring Voltage Distortion Level on the European
Low-Voltage Residential Network: Final Report Revision 1, The Low Frequency Emission Industry
Coalition (LFEIC) and EMC Consultant: November 2003, prepared by EPRI PEAC.

[B64] UL 1449, Standard for Surge Protective Devices. 15

13
NEMA publications are available from the National Electrical Manufacturers Association (http://www.nema.org/).
14
SEMI publications are available from SEMI Global Headquarters, 3081 Zanker Road, San Jose, CA 95134 (http://www.semi.org/).
15
UL publications are available from Underwriters Laboratories (http://www.ul.com/).

61
Copyright © 2018 IEEE. All rights reserved.