• Check foam concentrate level in tank. This • Ensure that the system flow rate through the
can only be carried out after the water has proportioning controller is within the recom-
been drained from around the bladder. As mended flow requirements and pressure for
water is being drained from the tank shell the size controller installed in the system.
drain valve, it will be necessary to open the
bladder vent valve and the tank shell vent • After approximately one minute of foam
valve to allow air into the tank. solution flow, collect a sample of the
discharging foam in a clean container. Shut
• Check all name plates on tank for legibility down the system.
and corrosion.
• Check the drained foam solution in the
• If a hydraulic concentrate control valve is container with a refractometer or a
th
CHEMGUARD INC. 204 S. 6 Avenue • Mansfield, Texas, USA 76063 • (817) 473-9964 • FAX (817) 473-0606
Rev: 04012001 Page VIII - 8
conductivity meter to ensure correct
proportioning of the foam concentrate into
the water stream.
th
CHEMGUARD INC. 204 S. 6 Avenue • Mansfield, Texas, USA 76063 • (817) 473-9964 • FAX (817) 473-0606
Rev: 04012001 Page VIII - 9
th
CHEMGUARD INC. 204 S. 6 Avenue • Mansfield, Texas, USA 76063 • (817) 473-9964 • FAX (817) 473-0606
Rev: 04012001 Page VIII - 10
th
CHEMGUARD INC. 204 S. 6 Avenue • Mansfield, Texas, USA 76063 • (817) 473-9964 • FAX (817) 473-0606
Rev: 04012001 Page VIII - 11
th
CHEMGUARD INC. 204 S. 6 Avenue • Mansfield, Texas, USA 76063 • (817) 473-9964 • FAX (817) 473-0606
Rev: 04012001 Page VIII - 12
th
CHEMGUARD INC. 204 S. 6 Avenue • Mansfield, Texas, USA 76063 • (817) 473-9964 • FAX (817) 473-0606
Rev: 04012001 Page VIII - 13
th
CHEMGUARD INC. 204 S. 6 Avenue • Mansfield, Texas, USA 76063 • (817) 473-9964 • FAX (817) 473-0606
Rev: 04012001 Page VIII - 14
th
CHEMGUARD INC. 204 S. 6 Avenue • Mansfield, Texas, USA 76063 • (817) 473-9964 • FAX (817) 473-0606
Rev: 04012001 Page VIII - 15