Sie sind auf Seite 1von 8

Data sheet

Pressure reduction controller for oil V21D28 (PN 16, 25)

Description The controller has a control valve, an actuator


with one control diaphragm and a spring for
pressure setting.

Features:
- safe and reliable operation
- pressure relieved valves
- maintenance free
- self acting
- high control accuracy
- without external impulse tubes

Main data:
· DN 15-65
· kVS 3.6-55 m3/h
· PN 16, 25
· Setting range:
1-5 bar/3-11 bar/10-16 bar/12-20 bar
V21D28 is a self-acting pressure reduction · Temperature:
controller primarily for use in oil applications
- Light/heavy/fuel oil/high viscosity media:
such as light and heavy oil, fuel oil and especially
2 ... 140 °C
high viscosity media. In case of heavy oil there is
no need to heat it with steam. It can be used for · Connections:
pressure reduction in heating and cooling plants. - Flange

The controller is normally open and closes on


rising pressure.

Ordering V21D28 PN 16 Controller


∆p ∆p
Example: DN kVS
Picture Connection setting range Code No. setting range Code No.
Pressure reduction controller for oil, (mm) (m3/h) (bar) (bar)
DN15, kVS 3.6, PN 16, setting range 15 3.6 065-4297 065-4290
1-5 bar, tmax 140 °C, flange.
20 6.6 065-4298 065-4291
- 1 × V21D28 DN 15 controller 25 9.3 065-4299 065-4292
Code no: 065-4297 Flanges acc. to
32 13.5 1-5 065-4300 3-11 065-4293
EN 1092-2
The controller will be delivered 40 23.5 065-4301 065-4294
completely assembled. 50 35 065-4302 065-4295
65 55 065-4303 065-4296

V21D28 PN 16 Controller
∆p
DN kVS
Picture Connection setting range Code No.
(mm) (m3/h) (bar)
15 3.6 065-4490
20 6.6 065-4484
25 9.3 065-4485
Flanges acc. to
32 13.5 10-16
EN 1092-2
40 23.5
-
50 35
65 55

DH-SMT/SI VD.CC.L3.02 © Danfoss 05/2010 1


Data sheet Pressure reduction controller for oil V21D28 (PN 16, 25)

Ordering (continuous) V21D28 PN 25 Controller


∆p
DN kVS
Picture Connection setting range Code No.
(mm) (m3/h) (bar)
15 3.6 065-4560
20 6.6 065-4561
25 9.3 Flanges acc. to EN 065-4562
12-20
32 13.5 1092-2 065-4563
40 23.5 065-4564
50 35 065-4565

Service kits
DN kVS
Picture Type designation Connection Code No.
(mm) (m3/h)
15 3.6 065-4540
20 6.6 065-4541
25 9.3 Flanges acc. to EN 065-4542
Valve V21
32 13.5 1092-2 065-4543
40 23.5 065-4544
50 35 065-4545

∆p
Size
Type designation PN setting range Code No.
(cm2) (bar)
80 1-5 003G1049
16 32 3-11 003G1048
Actuator D28 oil
32 10-16 003G1601
25 35 12-20 003G1602

Technical data Valve


Nominal diameter DN 15 20 25 32 40 50 65
k vs value 3.6 6.6 9.3 13.5 23.5 35 55
m /h
3
Nominal flow 1.5 3.0 4.5 7.0 11 18 27
Nominal pressure PN 25
Max. differential pressure bar 16
Medium Light/heavy/fuel oil/high viscosius media
Medium pH Min 7/max 10
Medium temperature °C 2 … 140
Connections Flange
Materials
Valve body EN-GJS-400-18-LT (GGG 40.3)
Valve seat Stainless steel (1.4104)
Valve cone Stainless steel (1.4104)
Sealing Metal

Actuator
Actuator size cm2 32 35 80
Diff. pressure setting silver 3-11 - 1-5
ranges and spring black bar 10-16 - -
colours black/blue - 12-20 -
Nominal pressure PN 16 25 16
Materials
Steel, mat. No. EN-GJS-400-18-LT Steel, mat. No.
Housing 1.0338, chromated (GGG 40.3) + 1.4404 1.0338, chromated
Diaphragm (rolling) / Bellows FKM 1.4571 FKM

2 VD.CC.L3.02 © Danfoss 05/2010 DH-SMT/SI


Data sheet Pressure reduction controller for oil V21D28 (PN 16, 25)

Application principle

Installation positions Controller can be installed in horizontal pipes


only with a pressure actuator oriented upwards.
This installation position enables the transfer of
media temperature to the actuator.

Pressure temperature
diagram

PN 16

EN-GJS-400-18-LT (GGG 40.3)


working area

PN 25

EN-GJS-400-18-LT (GGG 40.3)


working area

DH-SMT/SI VD.CC.L3.02 © Danfoss 05/2010 3


Data sheet Pressure reduction controller for oil V21D28 (PN 16, 25)

Design

PN 16 12
1. Valve body
2. Valve seat
3. Valve cone
7
4. Valve stem
5. Union nut
6. Actuator stem
7. Diaphragm plate
8. Rolling diaphragm
9. Larger diaphragm plate
10. Diaphragm housing
11. Setting spring
12. Nut for setpoint adjustment 11

12
PN 25
1. Valve body
2. Valve seat
3. Valve cone 9
4. Valve stem
5. Union nut 11
6. Actuator stem
7. Spring support plate
10
8. Bellow 8
10
9
9. Cover plate 8 7
10. Bellows housing
11. Setting spring 6 6
5 5
12. Spindle for setpoint
adjustment 4 4

3 3
2 2

1 1

V21D28-PN 16 V21D28-PN 25

Function The pressure behind the control valve is being


internally transferred to the actuator chamber
and act on control diaphragm. On the other side
of the diaphragm atmospheric pressure is acting.
Control valve is normally open. It closes on
rising pressure and opens on falling pressure to
maintain constant pressure.

Settings Pressure setting


Pressure setting is being done by the adjustment
of the setting spring for pressure control. The
adjustment can be performed on the basis of
pressure indicator.

4 VD.CC.L3.02 © Danfoss 05/2010 DH-SMT/SI


Data sheet Pressure reduction controller for oil V21D28 (PN 16, 25)

Dimensions
Ø 195

Ø 172 Ø 172

H2
H1
H

L L L

∆p = 3.0-11 (DN 15-65) ∆p = 0.5-2.5 (DN 20) ∆p = 12-20 (DN 15-50)


∆p = 10-16 (DN 15-40) ∆p = 1.0-5.0 (DN 15-65)

DN 15 20 25 32 40 50 65
L 130 150 160 180 200 230 290
H 580 585 595 605 615 620 630
mm
H1 585 590 600 610 620 625 635
H2 765 770 780 790 800 805 815

DH-SMT/SI VD.CC.L3.02 © Danfoss 05/2010 5


Data sheet Pressure reduction controller for oil V21D28 (PN 16, 25)

6 VD.CC.L3.02 © Danfoss 05/2010 DH-SMT/SI


Data sheet Pressure reduction controller for oil V21D28 (PN 16, 25)

DH-SMT/SI VD.CC.L3.02 © Danfoss 05/2010 7


Data sheet Pressure reduction controller for oil V21D28 (PN 16, 25)

8 VD.CC.L3.02 Produced by Danfoss A/S © 05/2010