98.6 Significant
improvement
98.4 over conventional
generator
98.2 50-Hz machine
(PF: 0.80) These performances correspond to a 38% reduction
98.0
Efficiency of 60-Hz machine in loss (770 kW) and an 18-dBA reduction in noise
conventional (PF: 0.85)
generator compared to the former 100-MW generators. The
97.8
70 120 170 220 specifications of GH1550A are listed in Table 1.
Output (MVA) This report describes the technologies applied to
PF: power factor
the air-cooled turbine generator GH1550A — which
is superior to a conventional hydrogen-cooled type
Fig. 2—Comparison of Efficiencies of GH1550A and
Conventional Generators.
with regard to both efficiency and noise.
GH1550A improves efficiency by 0.5 point in comparison with
that of the conventional generator. The efficiency of air-cooled TECHNICAL CHALLENGES OF GH1550A
generators developed over recent years(5),(6) is converted into The technical challenges concerning the GH1550A
the case of operation under two power factors stated in the are listed in Table 2. The generator, which is shown in
figure. Fig. 4, converts rotational energy of the turbine into
electrical energy. That is to say, a rotating magnetic
field generated by the rotor is transformed into the
Generator noise Noise levelFamiliar noises
(measurement distance: 1 m) form of current and voltage to the exterior through a
• Under a railway
100 dBA bridge stator coil installed in a stator core. The generator
• Conventional • Siren of ambulance
60-Hz air-cooled operates in a high magnetic field at high current, and
generator copper loss generated by electrical current flow in
• Conventional 90 dBA • In a noisy factory
50-Hz air-cooled • Karaoke bar conductors, iron loss generated by passage of the
generator
magnetic field through the core, and other electrical
Significant noise reduction • Pedestrian crossing/
80 dBA alongside national losses are generated in each component of the
GH1550A (60 Hz) highway
77 dBA • Inside a train generator.
GH1550A (50 Hz) In order to remove the heat arising from these
74 dBA
70 dBA
• Ring tone of a phone losses, fans are attached to the ends of the rotor shaft,
• Noisy office
and cooling airflow is circulated around the interior
of the generator. The maximum circumferential
Fig. 3—Comparison of Noise from GH1550A and Conventional
rotation speed of the rotor is about 200 m/s.
Generators.
Consequently, ventilation loss and friction loss (which
GH1550A achieves noise reduction of 18 dBA in comparison
with that of the conventional generators. depend on circumferential velocities of the fan and
Hitachi Review Vol. 57 (2008), No. 6 287
TABLE 2. Technical Challenges Design challenges Usual countermeasures Challenge points
Concerning GH1550A
Creating Reduction of electrical • Optimum conductor • When conductor size is reduced,
Technical challenges concerning high loss size is assumed. copper loss increases.
GH1550A are listed. efficiency • Low-loss magnetic • When conductor size is increased,
steel sheet is used. stray-load loss increases.
• Low-loss magnetic steel sheet is
not as readily available as standard
magnetic steel sheet.
Rotor
Stator coil
Secondary model Entire generator model Terminal air duct
Center section of stator coil Stator core
determined in which components loss (such as stray- Fig. 8—Comprising Items of Stray-load Loss.
load loss) is being generated, and measures for The items that comprise the stray-load loss of the generator are
reducing load can be tailored to each component. shown schematically.
The generation locations and comprising items of
stray-load loss are shown by the proportional chart in
Fig. 8, and a method for reducing stray-load loss in
the generator windings (including these comprising Circulating
Incoming
current
losses) is shown schematically in Fig. 9. It is clear magnetic flux
that stray-load loss generated in the generator windings
Strands
can be divided into circulating-current loss flowing in
a cycle between winding strands and eddy-current loss
Circulating current loss
generated locally in strands. The circulating-current
loss can be reduced by counterbalancing magnetic Eddy Incoming
current magnetic flux
fields linking winding strands by means of “wiring
transposition” (that is, a method of transposing pairs
of strands together), and eddy-current loss can be Strands
99.1 99.1
PF1.0
99.0 99.0
PF1.0
98.9 98.9
Efficiency (%)
Efficiency (%)
PF0.90 PF0.85
98.8 98.8 PF0.80
98.7 PF0.85 98.7
98.6 98.6
98.5 98.5
Fig. 11—Efficiency
98.4
Measurement
98.4
Results for Air-
98.3 98.3
cooled Generator
98.2 98.2
GH1550A.
98.1 98.1
60 80 100 120 140 50 70 90 110 130 As an air-cooled
Output (MW) Output (MW) generator, the
(a) 60 Hz (b) 50 Hz GH1550A achieves
very high efficiency.
A B
1.5 m
REFERENCES
(1) T. Kakimoto et al., “Development of a Low-noise Air-cooled
Turbine Generator,” The Institute of Electrical Engineers of
C D Japan, Rotator Research Workshop materials, RM-07-41 (May
2007) in Japanese.
(2) K. Hattori et al., “Introducing a High-efficiency Air-cooled
Generator GHI550A,” Journal of the Gas Turbine Society of
Fig. 12—Noise-measurement Results for GH1550A. Japan 34, No. 4 (July 2006) in Japanese.
As an air-cooled generator, the GH1550A noise is reduced (3) K. Hattori et al., “Optimization of the Structure of a Level
remarkably. Transition Stator Coil of a Turbine Generator,” The Institute
of Electrical Engineers of Japan, Rotator Research Workshop
materials, RM-04-141 (Oct. 2004) in Japanese.
(4) A. Nakahara et al., “Analysis of Excitation Loss during Loaded/
during 60-Hz operation, noise reduction compared to unloaded Periods of a Turbine Generator by Using Three-
dimensional Magnetic-field Analysis,” Transaction of the
a conventional generator is 18 dBA, thereby lowering
Institute of Electrical Engineers of Japan D124, No. 8, pp. 830-
the noise to the level of a conventional hydrogen-
836 (Aug. 2004) in Japanese.
cooled generator. (5) S. Muramatsu et al., “Development of 250-MVA Air-cooled
Turbine Generator,” Hitachi Review 54, pp. 121–125 (Oct.
CONCLUSIONS 2005).
This report described technologies applied to our (6) K. Hattori et al., “Sophisticated Design of Turbine Generator
air-cooled generator “GH1550A.” We confirmed that with Inner Cooler Ventilation System,” Hitachi Review 51, pp.
the efficiency of GH1550A reaches the world’s highest 148–152 (Dec. 2002).
High Efficiency and Low Noise Air-cooled Turbine Generator “GH1550A” 292