When altitude increases, air density drops. Thus, after 1000 m for every 100 m dielectric of air drops %1.5. The
distance between two electrodes for the altitudes between 1000-1500 m should be chosen %15 above the table
below, after 1500 m for each 500 m the distance should be increased %7.5
Insulation Maximum Allowable Arc Horns Distance VDE Safety Distances Between
Voltage Class Working Voltage (kV) 0111/261 (mm) Terminals
(kV)
Phase to Phase to
Phase (mm) Ground (mm)
0,5 0,6 - 15 20
1 115 - 25 40
3 3,6 - 50 65
10 12 86 110 115