1. Flexure
Type of Column l
Concrete 𝐵−𝑐
2
𝐵 − 𝑐⁄2
Masonry
2
2𝐵 − (𝑐 + 𝑐𝑝 )
Steel
4
Note: 1. If the column has a circular, octagonal, or other similar shape, use a square
with an equivalent cross-sectional area.
1. B = footing width; c = column width; cp = base plate width.
The factored moment, Mu, at critical section is:
𝑞𝑛𝑢 𝐵 𝑙 2
𝑀𝑢 =
2
𝑃
Where: qnu = factored net soil pressure = 𝐴𝑢
𝑓
Af = actual area of the footing used
𝐴𝑠 𝑓𝑦
Where: 𝑎 =
0.85𝑓′ 𝑐 𝑏
d = effective depth
2. Required Reinforcement
The required area of steel, As, for each direction
1.08𝑀𝑢
𝐴𝑠 =
∅ 𝑓𝑦 𝑑
The minimum area of tensile reinforcement for structural slabs and footings of uniform thickness
stated in sections 401.6.4 and 407.13.2.1 NSCP 2001 are as follows:
1. The maximum spacing shall not exceed the lesser of 3h and 450mm (Sec. 410.6.4, NSCP 2001)
2. The maximum spacing (center to center) is the largest of
a) 2db
b) 25 mm + db
c) (1.33 + max. aggregate size) + db
3. Shear
3.1. One-way Shear (Beam Shear)
where: (𝐵 − 𝑐)
𝑙𝑣 = −𝑑
2
√𝑓𝑐 ′ 𝑏𝑤 𝑑
𝑉𝑛 = 𝑉𝐶 =
6
where: 𝐶1 = c + d
𝛼𝑠 𝑑 √𝑓𝑐′𝑏𝑜 𝑑
b) 𝑉𝑐 = ( + 2)
𝑏𝑜 12
√𝑓𝑐′𝑏𝑜 𝑑
c) 𝑉𝑐 =
3
where:
αs = 40 for interior column
= 30 for edge column
= 20 for corner column
βo = ratio of long side to the short side of column
bo = perimeter of critical section for footing
= 4C = 4 (c + d)