Sie sind auf Seite 1von 31

1.

Voltage build up with Existing PID Values

Page 1 of 31
2. Voltage build up with changed PID values (170;15;15;30;1;1;pl+5;soft-12)

Page 2 of 31
3. +2.5% Step test with Vp1=10

Page 3 of 31
4. Voltage buildup disrupted due to CMU lower settings (Ug>25%;If>10%)

Page 4 of 31
5. Voltage buildup after CMU settings change (Ug>85%;If>0%)

Page 5 of 31
6. Voltage buildup with PID (120;6;6;30;1.5;0.5;soft:5.0;pl+:5.0)

Page 6 of 31
7. Step test (+/- 7%) with PID values (120;6;6;30;1.5;0.5;pl+:5.0)

Page 7 of 31
8. Step test (+/- 10%) with PID values (120;6;6;30;1.5;0.5;pl+:11.7)

Page 8 of 31
9. Voltage build up in channel 2 (Auto-2)

Page 9 of 31
10. Auto-2 Step test (+/-10%) with PID (120;8;8;40;1.5;0.5;pl+:11.7)

Page 10 of 31
11.Gen. Voltage & Current Auto-1 & 2 for confirmation of Power factor.

Page 11 of 31
12.Over Excitation Limiter (Exciter field current) response (Auto-1)

The value of Ifac is 56.4% & 62.9% at Uref=102.4% and 105.4% resp. 3% step input given to Uref to check the response
after reducing the Limiter reference (F400) to 57%.

Page 12 of 31
13.Over Excitation Limiter (Stator current Inductive) Response (Auto -1)

The value of Igac is 77% & 78% at Uref=102.4% and 105.4% resp. 3% step input given to Uref to check the response
after reducing the Limiter reference (F430) to 70%.

Page 13 of 31
14. Response (Auto -1) of DAVR with PSS off was checked by giving a step input of 4% to Uref.

Page 14 of 31
15. Response (Auto -1) of DAVR with PSS on was checked by giving a step input of 4% to Uref.

Page 15 of 31
16. Response (Auto -2) of DAVR with PSS off was checked by giving a step input of 4% to Uref

Page 16 of 31
17. Response (Auto -2) of DAVR with PSS on was checked by giving a step input of 4% to Uref.

Page 17 of 31
18. Unit#5: Load angle limiter (Auto -1) was tested by reducing the reference (F4A0) from 75 deg. To 57 deg. The actual
value of Delta was 65 deg. The Output of Limiter (F88E) was checked for influencing the AVR output (F8C0).

19. Unit#5: Stator current Limiter (Capacitive) (Auto -1) was tested by reducing the reference (F460) from 105% to 70%.
The actual value of Igac & cosphi was 80% & 0.98(cap) at Uref of 99.4%. The Output of Limiter (F850) was checked for
influencing the AVR output (F8C0).

20. Unit#5: Load angle limiter (Auto - 2) was tested by reducing the reference (F4A0) from 75 deg. To 58 deg. The actual
value of Delta was 68 deg. The Output of Limiter (F88E) was checked for influencing the AVR output (F8C0).

21. Unit#5: Stator current Limiter (Capacitive) (Auto -2) was tested by reducing the reference (F460) from 105% to 70%.
The actual value of Igac & cosphi was 80.7% & 0.98(cap) at Uref of 99.4%. The Output of Limiter (F850) was checked
for influencing the AVR output (F8C0).

22. Unit#5: The stator current limiter (inductive) (Auto-2): The value of Igac is 76.9% at Uref=102.4%. 3% step input
given to Uref to check the response after reducing the Limiter reference (F430) to 70%.

23. Unit#5: The value of Ifac is 62.9% at Uref=105.4%. 3% step input given to Uref to check the response after reducing
the Limiter reference (F400) to 57%.

24. Unit#6: The V/Hz limiter response was checked by reducing the reference (F280) to 100% from 115% in both the
channels with a delay of (F28E) 5 secs. The alarm “V/Hz High” appeared in Output module (A52).

25. Unit#6: Load angle limiter (Auto - 2) was tested by reducing the reference (F4A0) from 75 deg. To 55 deg. The actual
value of Delta was 65.8 deg. The Output of Limiter (F88E) was checked for influencing the AVR output (F8C0).

26. Unit#6: Stator current Limiter (Capacitive) (Auto -2) was tested by reducing the reference (F460) from 105% to 70%.
The actual value of Igac & cosphi was 78.9% & 0.98(cap) at Uref of 99.5%. The Output of Limiter (F850) was checked
for influencing the AVR output (F8C0).

27. Unit#6: Load angle limiter (Auto - 1) was tested by reducing the reference (F4A0) from 75 deg. To 56 deg. The actual
value of Delta was 68.3 deg. The Output of Limiter (F88E) was checked for influencing the AVR output (F8C0).

28. Unit#6: Stator current Limiter (Capacitive) (Auto -1) was tested by reducing the reference (F460) from 105% to 68%.
The actual value of Igac & cosphi was 76.5% & 0.98(cap) at Uref of 100%. The Output of Limiter (F850) was checked
for influencing the AVR output (F8C0).

Page 18 of 31
29. Voltage buildup (Auto-2) with PID values as per unit#5 and Excitation OFF.

Page 19 of 31
30. Auto-2 Step test (+/-10%) with PID(120;8;8;40;1.5;0.5;pl+:11.7)

Page 20 of 31
31. Auto-2 Step test (+/-10%) with PID(120;8;8;40;1.5;0.8;pl+:11.7)

Page 21 of 31
32. Voltage buildup (Auto-1) with PID values (120;8;8;40;1.5;0.8;pl+:11.7).

Page 22 of 31
33. Auto-1 Step test (+/-10%) with PID(120;8;8;40;1.5;0.8;pl+:11.7)

Page 23 of 31
34. Over Excitation Limiter (Exciter field current) response (Auto-2)

The value of Ifac is 56.9% & 65.9% at Uref=103% and 106% resp. 3% step input given to Uref to check the response after
reducing the Limiter reference (F400) to 58%.

Page 24 of 31
35. Over Excitation Limiter (Stator current Inductive) Response (Auto -2)

The value of Igac is 77% at Uref=106% resp. 3% step input given to Uref to check the response after reducing the Limiter
reference (F430) to 70%.

Page 25 of 31
36. Response (Auto -2) of DAVR with PSS off was checked by giving a step input of 4% to Uref

Page 26 of 31
37. Response (Auto -2) of DAVR with PSS on was checked by giving a step input of 4% to Uref

Page 27 of 31
38. Over Excitation Limiter (Exciter field current) response (Auto-1)

The value of Ifac is 52% & 61% at Uref=102% and 106% resp. 4% step input given to Uref to check the response after
reducing the Limiter reference (F400) to 54%.

Page 28 of 31
39. Over Excitation Limiter (Stator current Inductive) Response (Auto -1)

The value of Igac is 74.8 at Uref=105%. 3% step input given to Uref to check the response after reducing the Limiter
reference (F430) to 67%.

Page 29 of 31
40. Response (Auto -1) of DAVR with PSS off was checked by giving a step input of 4% to Uref

Page 30 of 31
41. Response (Auto -2) of DAVR with PSS on was checked by giving a step input of 4% to Uref

Page 31 of 31