STANDARD OPERATION
PROCEDURE FOR

SIMULATION SYNCHRONIZING PANEL


C/W INSTALLATION

1
www.zamoda.my
LEGEND

1 1

1. Turn ‘ON’ incoming AUX. Voltage 415V 50Hz healthy (SESB). Refer voltmeter incoming
aux power supply No.1 & No.2 .

2. Ensure incomings Simulator Circuit Breaker 20A TPN No.1 & No.2 in
‘OFF’ Position

3 3

3. Incoming Neutral Knife switch Simulator No.1 & No. 2 ‘OFF’ position, knife switch
No.1 and No.2 in position up.

2
www.zamoda.my
4. Simulator No.1 speed reostat (ST1) &
No.2 speed reostat (ST2) set at 80% on
setting mode.

5. (PB10 & PB12) Simulator Emergency


stop push button in lock mode.

6. Incoming supply ON/OFF & common


supply ON/OFF switches in ‘OFF’ mode.

a) SW1 – Simulator No.1 Incoming

b) SW2 – Supply Simulator No.2


Incoming

c) SW3 – Supply Simulator


No.1 Common supply

d) SW4 – Simulator No.2


Common supply

3
www.zamoda.my
START FOR SIMULATION SYNCHRONZING NO.1

1. Release simulator No.1 emergency stop 4


push button (PB10)

2. Start Simulator No.1 by pressing AC


Prime Mover No.1 push button (PB9) 1
3. Prime Mover run 2

4. Voltage & Frequency available:

a. Set voltage 400V by voltage


simulator No.1 rheostat (VT1)

b. Set frequency 50Hz by speed


simulator No.1 rheostat (ST1)

4
www.zamoda.my
6
5

5. Turn Simulator No.1 neutral ON/OFF knife switch to ‘ON’ mode. IMPORTANT : Make
sure knife switch is at ON position before powering the bus.

6. Turn Simulator No.1 incoming circuit breaker (MCCB 20A) to ‘Close’

5
www.zamoda.my
START FOR SIMULATION SYNCHRONZING NO.2 WITH SYNCH

1. Release Simulator No. 2 emergency stop push


button (PB12)

2. Start Simulator No.2 by pressing Start AC


5
Simulator No.2 push button (PB11)

3. Prime Mover Run

4. Turn Simulator No.2 ON/OFF neutral knife


switch to ‘ON’ mode 1

2
5. Voltage & Frequency available:

- Set voltage 400V by Simulator No. 2


6
voltage rheostat (VT2)
- Set frequency 50Hz by speed Simulator
No.2 rheostat (ST2)
- Unit No.2 is ready to synchronize with unit
No.1

6. Turnkey switch Simulator No.2 (SW2)


incoming supply & key switch

Simulator No.2 common supply.

(SW4) to ‘ON’ mode.

Note : 4
To synchronize unit no.1 to unit no.2,

Simulator No.1 incoming circuit breaker

must be at open position and simulator

no.2 incoming circuit breaker at close

position. Turn key switch simulator

No.1 incoming.

6
www.zamoda.my
7. Adjust Simulator No.2 speed Rheostat (ST2)
clockwise until the pointer of synchroscope
following meter reach 12 o’clock ± 10% and the

a) Synch. Matching light shown (DARKER) 7


b) Synch. Enable indicator turn ‘ON’ mode

8. Turn Simulator No.2 Circuit breaker (MCCB


20A) to Close position.

9. To correct both PF set Simulator No.2


voltage (RHEOSTAT)

10. Turn ‘OFF’ neutral ON/OFF knife switch


Simulator No.2.

11. Parallel successfully done. 7

8 10

7
www.zamoda.my
STOP SIMULATOR NO.2

IMPORTANT : Before proceed to step 2(Open


MCCB)

1. Restore neutral knife switch simulator No.2 to


‘ON’ mode

2. Turn Simulator No.2 incoming circuit breaker


(MCCB 20A) to ‘OPEN’ mode 2 1
3. Turn key Simulator No.2 incoming supply
switch (SW2) & key Simulator No.2 common
supply switch (SW4) to ‘OFF’ mode

4. Stop Simulator No.2 by pressing emergency


stop push button (PB1)

5. Simulator No.2 successfully stop.

Note :

4
Always make sure one of neutral

knife switch is in ‘ON’ position when

powering the bus.

3 3
This to prevent the loss of neutral

connection in power supply that can

damage any equipment (load) that use

single phase supply from the bus.

8
www.zamoda.my
STOP SIMULATOR NO.1

1. Turn Simulator No.1 Circuit

Breaker (MCCB 20A) to ‘OFF’ mode

2. Stop Simulator No.1 by pressing Simulator


No.1 Emergency Stop push button (PB10)

3. Simulator No.1 successfully stop

4. Turn Simulator No.1 Neutral


Knife ON/OFF Switch Simulator

No.1 to ‘OFF’ mode.

COMPLETE SEQUENCE