Project : SOBHA HARTLAND - VILLA SITE DEVELOPMENT

MEP Consultant: SOBHA MEP DESIGN STUDIO

Booster Pump Design Calculations ( P-1 ) As per tender drawings.


SANITARY LOADING UNITS TABLE REF. PLUMB. DESIGN HAND BOOK

Sl No Fixture Qty Loading Unit (L U) Total L U

1 WC 0 2 0

2 WHB 20 1.5 30

3 Bath tub 0 10 0

4 Shower tray 0 3 0

5 Bidet 0 3 0

6 KS 0 5 0

7 Hand Spray 0 2.5 0

8 Washing Machine 0 10 0

9 Dish Washer 0 5 0

10 Urinal 0 4.5 0 0 0

11 Drinking fountain 0 0.5 0

Total Loading Unit 30

Say 30 L U

From the attached chart the equivalent system flow rate is 0.6 L/s Say = 1 L/s

Boster Pump Head Calculation

Water flow rate = 1.5 L/s

Suitable Velocity for Pumped water supply


(1 to 2 meter/sec. ) as per Plumb. Inst. Design = 1.2 meter/sec. (assumed)
Handbook page 15

Pipe size considered as per the std. chart (mm) = 40mm upvc class E or 50mm PPR

Friction head for all pipes/ fittings & Valves + Head required at the last point of
Total Delivery head =
discharge

Delivery static head = 1 Mtr


Vertical Running Pipes = 10 Mtr

Horizontal Running Pipes = 187 Mtr

Friction loss through pipes

As per the manufacturer flow chart, loss of head = 0.04 Mtr / Mtr

Friction head at vertical pipe = 10 X 0.04

= 0.40 Mtrs

Friction head at horozontal pipe = 187 X 0.04

= 7.48 Mtrs

Total friction head in Pipes = 7.88 Mtrs

Friction loss for Fittings & Valves


Friction Head Friction Head,
Sl No Fittings Qty K value Velocity
Formula in Mtr
1 Elbow 90o Deg 16 1 1.2 Kv2/2g 1.17

2 Elbow 45o Deg 0 0.4 1.2 Kv2/2g 0.00

3 Tee 8 1.2 1.2 Kv2/2g 0.70

Total Equivalent length for fittings (Friction head in fittings) 1.88


Friction Head Friction Head,
Valves Qty K value Velocity
Formula in Mtr
1 Gate Valve 3 0.12 1.2 Kv2/2g 0.03

2 Check Valve (NRV) 1 10 1.2 Kv2/2g 0.73

3 Strainer 1 10 1.2 Kv2/2g 0.73

3 Flexible connection 1 0.1 1.2 Kv2/2g 0.01

Total Equivalent length for Valves (Friction head in Valves) 1.50


Total friction head in Pipes + Friction head in fittings
Total Frictional head , HF =
+ Friction head in Valves
= 11.26 Mtr

Head required at the last point of discharge(max.) = 15.00 Mtr

Total head = 27.26 Mtr

Allow 10 % Safety factor = 2.73 Mtr

Total Head Required = 29.99 Mtr, say 30 Mtr or 98.4 ft

REMARKS:as per calculations:

Use booster Pump set (1D) Horizontal Multi-stage pump @ (30 m) head @ 1.5 L/s (24 GPM)

Using universal standard formula, Motor KW = Water flow in L/s X head in Mtrs./101.2 X EFF.

WHERE: 101.2 = 33000 ft.lb-min/hp x 3.75 ltrs. /60 sec. x 3.28 ft. x 8.33 lb /.746 kw

Allow pump effeciency selection curve @ approximately 70 %

Then; substituting above data, Motor KW = 1.5 L/s X 30 M /101.2 X .70

Therefore; the required, Motor KW = 0.635 kw @ 2900 RPM, FOR 2 POLES

OR, Motor HP = 0.85 HP @ 2900 RPM, FOR 2 POLES

SUMMARY AS CALCULATED

TYPE OF PUMPS= BOOSTER PUMP SET

NO. OF PUMPS = 1 NOS. ( 1 D )

DESIGN FLOW RATE= 1.5 L/s

TDH (TOTAL DYNAMIC HEAD) = 30 mtrs.

PUMP PIPE DISCH. DIA.= 40 mm nominal

SPEED = 2900 RPM

NO. OF POLES = 2 POLES

APPROX. POWER = 0.85 HP

APPROX. POWER = 0.635 kW

Prepared by Nick Abate/Arshad

SOBHA ELECTRO MECHANICAL WORKS LLC

DUBAI - UAE

Date: 09.10.2016
Project : SOBHA HARTLAND - GREENS PHASE-2 SITE ESTABLISHMENT (B+G+8)

MEP Consultant: SOBHA HARTLAND ELECTRO MECHANICAL WORKS LLC

Booster Pump Design Calculations as per seting out plan.


SECL-PNCD-SH-PH.02_03 GEN-03 logistics - Rev-00

SANITARY LOADING UNITS TABLE REF. PLUMB. DESIGN HAND BOOK

Sl No Fixture Qty Loading Unit (L U) Total L U

1 WC 0 2 0

2 WHB 0 1.5 0

3 Drinking water cooler 0 1.5 0

4 Bip tap 0 1.5 0

5 Bidet 0 3 0

6 Discharge points in each floor 39 5 195

7 Hand Spray 0 2.5 0

8 Washing Machine 0 10 0

9 Dish Washer 0 5 0

10 Urinal 0 4.5 0 0

11 Drinking fountain 0 0.5 0

Total Loading Unit 195

Say 200 L U

From the attached chart the equivalent system flow rate is 2.30 L/s Say = 2.5 L/s

Boster Pump Head Calculation

Water flow rate = 2.5 L/s

Suitable Velocity for Pumped water supply


(1 to 2 meter/sec. ) as per Plumb. Inst. Design = 1.2 meter/sec. (assumed)
Handbook page 15

Nominal pipe size (internal dia) considered as per the std. chart (mm) = 50mm nominal dia (Internal dia)

Friction head for all pipes/ fittings & Valves +


Total Delivery head =
discharge

Delivery static head = 36 Mtr


Vertical Running Pipes = 36 Mtr

Horizontal Running Pipes = 180 Mtr

Friction loss through pipes


As per the manufacturer flow chart, loss of head = 0.04 Mtr / Mtr

Friction head at vertical pipe = 36 X 0.04

= 1.44 Mtrs

Friction head at horozontal pipe = 180 X 0.04

= 7.20 Mtrs

Total friction head in Pipes = 8.64 Mtrs

Friction loss for Fittings & Valves


Friction Head
Sl No Fittings Qty K value Velocity
Formula
1 Elbow 90o Deg 10 1 1.2 Kv2/2g

2 Elbow 45o Deg 0 0.4 1.2 Kv2/2g

3 Tee 15 1.2 1.2 Kv2/2g

Total Equivalent length for fittings (Friction head in fittings)


Friction Head
Valves Qty K value Velocity
Formula
1 Gate Valve 3 0.12 1.2 Kv2/2g

2 Check Valve (NRV) 1 10 1.2 Kv2/2g

3 Strainer 1 10 1.2 Kv2/2g

3 Flexible connection 1 0.1 1.2 Kv2/2g

Total Equivalent length for Valves (Friction head in Valves)

Total friction head in Pipes + Friction head in


Total Frictional head , HF =
+ Friction head in Valves
= 12.20 Mtr

Head required at the last point of discharge(max.) = 15.00 Mtr

Total head = 63.20 Mtr

Allow 15 % Safety factor = 9.48 Mtr

Total Head Required = 72.68 Mtr, say 75 Mtr or 246

REMARKS:as per calculations:

Use booster Pump set (1D + 1S) Horizontal Multi-stage pump @ (75 m) head @ 2.5 L/s (32 GPM)

Using universal standard formula, Motor KW = Water flow in L/s X head in Mtrs./101.2 X EFF.

WHERE: 101.2 = 33000 ft.lb-min/hp x 3.75 ltrs. /60 sec. x 3.28 ft. x 8.33 lb /.746 kw

Allow pump effeciency selection curve @ approximately 70 %

Then; substituting above data, Motor KW = 2.5 L/s X 75 M /101.2 X .70

Therefore; the required, Motor KW = 2.65 kw @ 2900 RPM, FOR 2 POLES


OR, Motor HP = 3.55 HP @ 2900 RPM, FOR 2 POLES

SUMMARY AS CALCULATED

TYPE OF PUMPS= BOOSTER PUMP SET

NO. OF PUMPS = 1 set. ( 1 D + 1 S)

DESIGN FLOW RATE= 2.5 L/s

TDH (TOTAL DYNAMIC HEAD) = 75 mtrs.

PUMP PIPE DISCH. DIA.= 65 mm nominal

SPEED = 2900 RPM

NO. OF POLES = 2 POLES

APPROX. POWER = 3.55 HP

APPROX. POWER = 2.65 kW

Prepared by Nick Abate/Arshad

SOBHA ELECTRO MECHANICAL WORKS LLC

DUBAI - UAE

Date: 08.03.2018
0

Friction head for all pipes/ fittings & Valves + Head required at the last point of
discharge
Friction Head,
in Mtr
0.73

0.00

1.32

2.06
Friction Head,
in Mtr
0.03

0.73

0.73

0.01

1.50

Total friction head in Pipes + Friction head in fittings


+ Friction head in Valves

Mtr, say 75 Mtr or 246 ft

@ (75 m) head @ 2.5 L/s (32 GPM)