Pro-MEC
Vacuum Circuit Breakers
Vacuum Interrupter
Vacuum Circuit Breaker &
Vacuum Interrupter

LSIS Pro-MEC VCB is user-friendly to give more convenience


and safety by providing high speed interrupting time (3cycles),
adopting the rapid auto-reclosing method, and having
wide range of accessories.

7.2kV Draw-out (F class)

24kV Draw-out (F class)


Pro-MEC VCB/VI
Vacuum Circuit Breaker
Ratings H1-4
Constructional and operating characteristics H1-8
Control circuit diagram H1-9
7.2kV dimension H1-10

Contents 12kV dimension


17.5kV dimension
24kV dimension
H1-19
H1-24
H1-27
Accessories H1-35
Types and ordering information H1-40

H1 Vacuum Interrupter
Features & Ordering information
VI internal structure
Basic functions and interrupting action
VI endurance by interrupting current
Dimensions
Technical data
H1-43
H1-44
H1-45
H1-46
H1-48
H1-50
Vacuum Circuit Breaker
LSIS Pro-MEC VCB is user-friendly to give more convenience
and safety by providing high speed interrupting time (3cycles),
adopting the rapid auto-reclosing method, and having
wide range of accessories.

7.2kV Draw-out (F class)


24kV Draw-out (F class)

Wide range of accessories (optional)


� Key Lock � Latch checking switch
� Padlock of earthing switch � TOC (Truck operated cell switch)
� Button padlock � Charge indicator
� Position switch of the earthing switch � Code plate (Miss insertion prevention)
� Button cover � Position padlock
� Locking coil of earthing switch � Capacitor trip device
� Position switch (Cell switch) � Earthing switch Note 1)
� Shutter padlock � Rectifier
� Preparatory trip coil (Secondary trip coil)
� MOC (Mechanically operated cell switch) Note 1) The earthing switch is not available for 17.5kV VCB.

H1-2
VACUUM CIRCUIT BREAKER

[ Compasion table for VCB (Short circuit test) ]

Compasion table for VCB (Short circuit test)

High reliability of the operating mechanism


- Separate design of the main circuit from the
operating mechanism.
- Adopt the toggle link method.
- Improved the reliability of electric circuit.
- Adopt the rapid auto-reclosing method as a
standard option. (O-0.3sec.-CO-3min.-CO)

High interrupting performance Great operational safety


�Make short of the interrupting time. (3cycles) �Reinforce the insulation in the conduct, by adopting the
�Increase the rated short-circuit withstand molded housing in each phase.
characteristics. (1sec. to 3sec.) �Built in the device making the contacts open first when
draw in and out.
�Adopt the tulip-shape connection between the cradle and
the VCB.

H1-3
Vacuum Circuit Breaker
Ratings

Type LVB-06�
�-32D LVB-06�
�-40D
Rated voltage (kV) 7.2 7.2
Rated normal current (A) 1250 2000 3150 1250 2000 3150
Rated frequency (Hz) 50/60 50/60
Rated short-circuit breaking current (kA) 31.5 40
Rated short-circuit breaking capacity (MVA) 390 500
Rated short-time withstand current (kA/3sec) 31.5 40
Rated short-circuit making current (kAp) 82 104
Rated breaking time (Cycle) 3 3
Rated opening time (sec) ≤ 0.04 ≤ 0.04
No-load closing time (sec) ≤ 0.06 ≤ 0.06
Withstand Power frequency (kV/min) 20 20
voltage Impulse (kV/1.2×50㎲) 60 60
Rated operating sequence O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO
Mechanical M2 (10,000 times) M2 (10,000 times)
Type
Electrical E2 (List1) E2 (List1)
test
Capacitive current switching Note 1) C2 C2
Without maintenance (Time) 20000 20000
Mechanical
Maintenance (Time) 30000 30000
Lifetime
Without maintenance (Time) 20000 20000
Electrical
Maintenance (Time) 30000 30000
Auxiliary switch 4a4b, 10a10b 4a4b, 10a10b
Fixed Visible, Fixed Visible, Fixed Visible, Fixed Visible, Fixed
E-type Visible, Tulip Visible, Clip Visible, Tulip Visible, Tulip
Installing F-type Visible, Tulip Visible, Tulip Visible, Tulip Visible, Tulip
Draw-out
method - Visible, Tulip Visible, Tulip Visible, Tulip Visible, Tulip
type G-type Note 2)
T Enclosed, Tulip - Enclosed, Tulip -
M-type Enclosed, Tulip - Enclosed, Tulip -
E-type (kg) 131.5 134.5 210 135 138 210
VCB F-type (kg) 132.5 135.5 211 136 139 211
Weight G, M-type (kg) 132.5(159) 135.5(160) 220 136(162.5) 139(163.5) 220
Note 3) E-type (kg) 52 60 131 52 60 131
Cradle F-type (kg) 54.5 62.5 135 54.5 62.5 135
G-type (kg) 62.5(110) 135(117) 155 62.5(110) 135(117) 155
Applied standard IEC 62271-100 IEC 62271-100
Test laboratory KERI Note 4) � �
Note 1) Applied cable-charging current switching test
2) In the event of ordering Enclosed Tulip type for G class VCB, please add “T” in the end of type name. (Ex: LVB-06G-20D/06-1A2B-T)
3) ( )* indicates the weight of Enclosed Tulip installing method VCB.
4) KERI: Korea Electrotechnology Research Institute

▲ Enclosed VCB ▲ G-type Cradle ▲ Visible, Clip contact ▲ Visible, Tulip contact ▲ Enclosed, Tulip contact
(Draw-out type, G-type) (Enclosed, Tulip contact)

H1-4
Type LVB-12�
�-32D/12, 20-T, 30 LVB-12�
�-40D/12, 20, 30 LVB-17�
�-40D/12, 20, 30
Rated voltage (kV) 12 12 17.5
Rated normal current (A) 1250 2000 3150 1250 2000 3150 1250 2000 3150
Rated frequency (Hz) 60(E1,E2,C2: PT & T) 50(E1,C2:KEMA), 60(M2,E2,C2: PT & T) 60
Rated short-circuit breaking current (kA) 31.5 40 40
Rated short-circuit breaking capacity (MVA) 650 831 1200
Rated short-time withstand current (kA/3sec) 31.5 40 40
Rated short-circuit making current (kAp) 81.9 104 104
Rated breaking time (Cycle) 3 3 3
Rated opening time (sec) 0.04 0.04 ≤0.04
No-load closing time (sec) 0.06 0.06 ≤0.06

Withstand Power frequency (kV/min) 28 28 38


voltage Impulse (kV/1.2×50㎲) 75 75 95
Rated operating sequence O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO
Mechanical M2 (10,000 times) M2 (10,000 times) M2 (10,000 times)
Type
Electrical E2 (List 1) E2 (List 1) E2 (List 1)
test
Capacitive current switching Note) C2 C2 C2
Without maintenance (Time) 20,000 20,000 20,000
Mechanical
Maintenance (Time) 30,000 30,000 30,000
Lifetime
Without maintenance (Time) 20,000 20,000 20,000
Electrical
Maintenance (Time) 30,000 30,000 30,000
Auxiliary switch 4a4b, 10a10b 4a4b, 10a10b 4a4b, 10a10b
Fixed - - -
E-TYPE - - -
Installing
Draw-out F-TYPE - - -
Method
type G-TYPE Enclosed, Tulip Visible, Tulip Enclosed, Tulip Visible, Tulip Visible, Tulip
M-TYPE Enclosed, Tulip - - -
E-TYPE (kg) - - -
VCB F-TYPE (kg) - - -
G, M-TYPE (kg) 159 160 220 162 163 220 200 205 260
Weight
E-TYPE (kg) - - - - - - - - -
Cradle F-TYPE (kg) - - - - - - - - -
G, M-TYPE (kg) 110 117 155 110 117 155 175 175 200
Applied standard IEC 62271-100
Test laboratory PT & T: E1, E2, C2, M2 KEMA, PT & T
Note) Applied cable-charging current switching test

H1-5
Vacuum Circuit Breaker
Ratings

Type LVB-20�
�-13D LVB-20�
�-13D/T LVB-20�
�-16D LVB-20�
�-16D/T LVB-20�
�-25D LVB-20�
�-25D/T
Rated voltage (kV) 24 24 24
Rated normal current (A) 630 630 630
1250 1250 1250
2000
Rated frequency (Hz) 50/60 50/60 50/60
Rated short-circuit breaking current (kA) 12.5 16 25
Rated short-circuit breaking capacity (MVA) 520 665 1000
Rated short-time withstand current (kA/3sec) 12.5 16 25
Rated short-circuit making current (kAp) 32.5 40 65
Rated breaking time (Cycle) 3 3 3
Rated opening time (sec) ≤ 0.04 ≤ 0.04 ≤ 0.04
No-load closing time (sec) ≤ 0.06 ≤ 0.06 ≤ 0.06
Withstand Power frequency (kV/min) 50 50 50
voltage Impulse (kV/1.2×50㎲) 125 125 125
Rated operating sequence O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO
Mechanical M2(10,000 times) M2(10,000 times) M2(10,000 times)
Type
Electrical E2 (List1) E2 (List1) E2 (List1)
test
Capacitive current switching Note 1) C2 C2 C2
Without maintenance (Time) 20000 20000 20000
Mechanical
Maintenance (Time) 30000 30000 30000
Lifetime
Without maintenance (Time) 20000 20000 20000
Electrical
Maintenance (Time) 30000 30000 30000
Auxiliary switch 4a4b, 10a10b 4a4b, 10a10b 4a4b, 10a10b
Fixed Visible, Fixed - Visible, Fixed - Visible, Fixed -
E-type Visible, Clip Enclosed, Tulip Visible, Clip Enclosed, Tulip Visible, Clip Enclosed, Tulip
Installing
Draw-out F-type Visible, Clip Enclosed, Tulip Visible, Clip Enclosed, Tulip Visible, Clip Enclosed, Tulip
method
type G-type Note 2) Visible, Tulip Enclosed, Tulip Visible, Tulip Enclosed, Tulip Visible, Tulip Enclosed, Tulip
M-type - Enclosed, Tulip - Enclosed, Tulip - Enclosed, Tulip
E-type (kg) 145 145 145 145 145 145
VCB F-type (kg) 145 145 145 145 145 145
G, M-type (kg) 155 187 155 187 155 187/218 (2000A)
Weight
E-type (kg) 80 80 80 80 80 80
Cradle F-type (kg) 82 82 82 82 82 82
G-type (kg) 110 120 110 120 110 120
Applied standard IEC 62271-100 IEC 62271-100 IEC 62271-100
KERI � - �
Test laboratory
KEMA - � �
Note 1) Applied cable-charging breaking current
2) In the event of ordering Enclosed Tulip type for G class VCB, please add “T” in the end of type name. (Ex: LVB-06G-20D/06-1A2B-T)

▲ Fixed type VCB ▲ E-type cradle ▲ F-type cradle ▲ G-type cradle ▲ G-type cradle
(Withdrawable by lever) (Withdrawable by screw)
H1-6
Motor
When the closing spring is charged, the control power of motor is turned off by the built-in limit s/w.

The peak value of the Consumption Charging time


Rated voltage Rated current (A)
inrush current (A) power (W) (Sec.)

DC 48V 21 4 350 13
DC 110V 20 3 330 12
DC 125V 20 3 330 12
DC 220V 17 2.6 374 12
Note 1) Range of the normal operating voltage: 85~110%
2) DC 24V is the underdeveloped rating.

Closing Coil (C) Shunt coil (TC)


The coil operated only when the power is applied continuously When the VCB is 'ON' position, even though the control power
over 45ms. It has built-in electrically anti-pumping circuit. of a shunt coil is 'OFF', the VCB maintains the 'ON' position.

Rated voltage Rated current (A) Rated voltage Rated current (A)

DC 48V 6 DC 48V 6
DC 110V 3 DC 110V 3
DC 125V 3 DC 125V 3
DC 220V 2.5 DC 220V 2.5
Note 1) Range of the normal operating voltage: 85~110% Note 1) Range of the normal operating voltage: 70~110%
2) DC 24V is the underdeveloped rating. 2) DC 24V is the underdeveloped rating.

Auxiliary switch
Standard 4a4b / Optional 10a10b �Position of the Aux.contact switch
General Inductive Contact VCB “a” contact “b”contact
Classification
load (A) load (A) configuration ON ON OFF
250V 10 5 OFF OFF ON
AC
125V 10 5
4a4b
Contact Ratings 250V 10 5
10a10b
DC 125V 10 5
30V 10 5
Note) The contact capacity of the following accessories are the same with that of the Aux. switch. Position switch, Closing sp ring
contact, Charging complete indicating contact, Position switch of the earthing switch, Mechanically operated cell switch,
Truck operated cell switch.

Charge indicator of Position indicator of the


the closing spring main contacts
Indicating the condition of the closing spring. Indicating the 'Close' or the 'Open' of the main contacts.
Close position:�ON� � Open position:�OFF� �

Charged Discharged
Close position Open position

Counter
Mechanically counts the switching of the VCB by 5digits analog type counter (Standard option)

H1-7
Vacuum Circuit Breaker
Constructional and operating characteristics

① Charge Indicator
of the closing spring
② Close button
③ Key lock (Optional)
④ Trip button
① ⑤ ⑤ Manual charge hole
⑥ Position indicator
⑪ of the main contacts

⑦ Counter
③ ⑨ ⑧ Screw hole for draw-in
and draw-out
④ ⑨ Nameplate
⑩ Mounting hole
⑥ ⑪ Safety cover

Manual charge
Insert the charge handle into the manual charge hole in the front of a
VCB, and rotate it to clockwise over 40times and the charge
complete with a metal sound.

Motor charge
If you apply the control power to a VCB, the closing spring will be
charged automatically by a motor and then the control power will be
turned off by the built-in limit s/w. Please use the same control
voltage for motor, Closing coil, Trip coil.

Sequence of the switching mechanism

H1-8
Control circuit diagram

∅: External terminal of VCB 52b: Auxiliary switch (NC) Connecting terminal arrangement
52: Vacuum circuit breaker LS1: Closing interlock limit switch (only withdrawable type)
M: Spring charging motor LS2: Motor stopping, closing spring charged indication A Type B Type
TC: Trip coil LS3: Anti-closing, anti-pumping limit switch
TC1: Secondary Trip coil LCS1: Opening latch checking switch(preventing closing
C: Closing coil unless the trip latch is properly reset)
Y: Anti-pump relay LS4, LS5: Position s/w (close in test position)
52a: Auxiliary switch (NO) LS6, LS7: Position s/w (close in run position)

Note 1) LCS1: Latch checking switch


2) Trip coil supervision (Trip coil monitoring contact)
Optional accessories
3) Position switch: 4a (Terminal No.: 1, 2, 3, 4, 5, 6, 7, 8)
4) TC1: Secondary trip coil (Preparatory trip coil Terminal No.: 82,83)
5) In fixed type VCB, LS1 (Closing-coil limit switch) is not available.

H1-9
※ Above circuit diagram is based on ‘OFF’ status of VCB. and closing spring is charged.
Vacuum Circuit Breaker
7.2kV dimension (VCB)

LVB-06P-32D, 40D (Visible, Fixed) - (1250/2000A)


(Unit: mm)

�Top <Terminal conductor>

*125.5 applied to all 7.2kV VCB.

�Front �Side

LVB-06P-32D, 40D (Visible, Fixed) - (3150A)


�Front �Side �Top

H1-10
LVB-06E, F, G-32D, 40D E, F, G class - (1250/2000A)
(Unit: mm)

�Top <Terminal conductor>

�Front �Side

LVB-06G- 32D/T, 40D/T G class (Enclosed, Tulip contact) - (1250/2000A)


�Front �Side

H1-11
Vacuum Circuit Breaker
7.2kV dimension (VCB)

LVB-06E-32D, 40D E class (Visible, Tulip contact) - (3150A)


(Unit: mm)

�Front �Side �Top

LVB-06F-32D, 40D F class (Visible, Tulip contact) - (3150A)

�Front �Side �Top

H1-12
LVB-06G-32D, 40D G class (Visible, Tulip contact) - (3150A)
(Unit: mm)

�Front �Side

�Top

H1-13
Vacuum Circuit Breaker
7.2kV dimension (Cradle)

LCL-06E-32D, 40D E class (Visible, Tulip contact)


(Unit: mm)

�Front �Side
Rating 1250A 2000A
A 10 20

�Top
<Terminal conductor>

LCL-06E-32D, 40D E class (Visible, Tulip contact) - (3150A)

�Front �Side �Top

H1-14
LCL-06F-32D, 40D F class (Visible, Tulip contact) - (1250/2000A)
(Unit: mm)

�Front �Side
Rating 1250A 2000A
A 10 20

<Terminal conductor>

�Top

LCL-06F-32D, 40D F class (Visible, Tulip contact) - (3150A)


�Front �Side

�Top

H1-15
Vacuum Circuit Breaker
7.2kV dimension (Cradle)

LCL-06G-32D, 40D G class(Visible, Tulip contact) - (31.5/40kA 1250/2000A)

�Front �Side (Unit: mm)

�Top

Rating 1250A 2000A


A 10 20

<Terminal conductor>

H1-16
LCL-06G-20D/T, 25D/T, 32D/T, 40D/T G class (Enclosed, Tulip contact) - (630/1250/2000A)
(Unit: mm)

�Front �Side

�Top
<Terminal conductor>

31.5/40kA
Rating
1250A 2000A
A 12 25
B ∅48

H1-17
Vacuum Circuit Breaker
7.2kV dimension (Cradle)

LCL-06G-32D, 40D G class (Visible, Tulip contact) - (3150A)


(Unit: mm)

�Side

�Top
<Terminal conductor>

<User busbar reguirement>


*To connect with VCB ’s bushing terminals
user busbar should have below dimensions
and two holes.

H1-18
12kV dimension (VCB)

LVB-12G-32D/T G class (Enclosed, Tulip contact) - (1250/2000A)


(Unit: mm)

�Front �Side

LVB-12G-40D G class (Enclosed, Tulip contact) - (1250/2000A)

�Front �Side �Top

470 325 330


150 150
295
726.5

668

69
355

496 288 33.5


10

549 438

40kA 1250/2000A G class

H1-19
Vacuum Circuit Breaker
12kV dimension (VCB)

LVB-12G-40D G class (Enclosed, Tulip contact) - (3150A)


(Unit: mm)

�Front �Side
620 325 336

360
806.6

348.5
714 290

10
747 502

�Top
210 210
676

40kA 3150A G class

H1-20
12kV dimension (Cradle)

LCL-12G-25D/T, 32D/T G class (Enclosed, Tulip contact) - (630/1250/2000A)


(Unit: mm)

�Front �Side

�Top
<Terminal conductor>

25kA
Rating
1250A 2000A
A 12 25
B ∅48

H1-21
Vacuum Circuit Breaker
12kV dimension (Cradle)

LCL-12G-40D G class (Enclosed, Tulip contact) - (1250/2000A)


(Unit: mm)

�Front �Side

1250A:12t
2000A:25t

295

1235
630
731.5

946

40kA 1250/2000A G class

<Terminal conductor>
�Top
150 150
60
26
26
83
RUN

150
600

560

150

4-∅14 Mount hole

100 662

H1-22
LCL-12G-32D/LCL-12G-40D G class (Enclosed, Tulip contact) - (3150A)
(Unit: mm)

�Front �Side
12 12

360

1100
439
764

1014

40kA 3150A G class

<Terminal conductor>
�Top
230 230

120
70
35
145
210
760
800

210

4-∅14 Mount hole

100 724

H1-23
Vacuum Circuit Breaker
17.5kV dimension (Cradle)

LVB-17G-40D G class (Visible, Tulip contact) - (1250/2000A)


(Unit: mm)

�Front �Side �Top

LVB-17G-40D G class (Visible, Tulip contact) - (3150A)

�Front �Side �Top

H1-24 H1-24
LCL-17G-40D G class (Visible, Tulip contact) - (1250/2000A)
(Unit: mm)

�Side

�Top
<Terminal conductor>

H1-25
Vacuum Circuit Breaker
17kV dimension (VCB)

LCL-17G-40D G class (Visible, Tulip contact) - (3150A)


(Unit: mm)

�Side

�Top
<Terminal conductor>

H1-26
24kV dimension (VCB)

LVB-20P-13D, 16D, 25D (Visible, Fixed) - (630/1250/2000A)


(Unit: mm)

�Front �Side

<Terminal conductor>

LVB-20E, F-13D/(T), 16D/(T), 25D/(T) E, F class - (630/1250/2000A)


�Front �Side
<Visible, Clip contact> <Enclosed, Tulip contact>

Note ) In case of 12.5kA & 16kA 630A, the dimension shown in parenthesis should be applied.

H1-27
Vacuum Circuit Breaker
24kV dimension (VCB)

LVB-20G-13D, 16D, 25D G class (Visible, Tulip contact) - (630/1250A)


(Unit: mm)

�Front �Side

LVB-20G-13D/T, 16D/T, 25D/T G class (Enclosed, Tulip contact) - (630/1250/2000A)

�Front �Side

Note 1) ( ): The dimension shown in parenthesis should be applied to LVB-20G-13E/T or LVB-20G-16E/T,


LVB-20G-25E/T for 630A and 1250A in case that distance between phase & phase is 210mm.
2) IP Cover applied both sides in case of 265mm phase distance.

H1-28 H1-28
24kV dimension (Cradle)

LCL-20E-13D, 16D, 25D E class (Visible, Clip contact) - (630/1250/2000A)


(Unit: mm)

�Front �Side
Rating A B T
630, 1250A 768 190.5 10
2000A 778 185.5 20

<Terminal conductor>
�Top

Note) Insulation barrirer is not used for rating 12.5kA 630A and 16kA 630A

H1-29
Vacuum Circuit Breaker
24kV dimension (Cradle)

LCL-20E-13D/T, 16D/T, 25D/T E class (Enclosed, Tulip contact) - (630/1250/2000A)


(Unit: mm)

�Front �Side
Rating A B T
630, 1250A 768 190.5 10
2000A 778 185.5 20

10(630/1250A)
20(2000A)
265 265 15

340
1033
115

404.5
280

∅6.5
730 947.5 97.5
960 1120
972 1167

�Top <Terminal conductor>

630A 1250A 2000A


100 45
90 47
20
40 67

660
42
40.5

ST: 260 25
300
265

2-∅14 4-∅14 4-∅14


145
820

80

80
40

40

40

40 20 40 20 40 20
210.5
265

202
245

300

7-∅14
100
40

90

110 400 400 210

Note) Insulation barrirer is not used for rating 12.5kA 630A and 16kA 630A

H1-30
LCL-20F-13D, 16D, 25D F class (Visible, Clip contact) - (630/1250/2000A)
(Unit: mm)

�Front �Side
Rating A B T
630, 1250A 768 190.5 10
2000A 778 185.5 20

<Terminal conductor>
�Top

Note) Insulation barrirer is not used for rating 12.5kA 630A and 16kA 630A

H1-31
Vacuum Circuit Breaker
24kV dimension (Cradle)

LCL-20F-13D/T, 16D/T, 25D/T F class(Enclosed, Tulip contact) - (630/1250/2000A)


(Unit: mm)

�Front �Side
Rating A B T
630, 1250A 768 190.5 10
2000A 778 185.5 20

<Terminal conductor>
�Top

Note) Insulation barrirer is not used for rating 12.5kA 630A and 16kA 630A

H1-32
LCL-20G-13D, 16D, 25D G class (Visible, Tulip contact) - (630/1250A)
(Unit: mm)

�Front �Side

�Top

<Terminal conductor>

H1-33
Vacuum Circuit Breaker
24kV dimension (Cradle)

LCL-20G-13D/T, 16D/T, 25D/T G class (Enclosed, Tulip contact) - (630/1250/2000A)


(Unit: mm)
�Front �Side

�Top
<Terminal conductor>

210mm

Note) ( ): The dimension shown in parenthesis should be applied to LVB-20G-13E/T or LVB-20G-16E/T,


LVB-20G-25E/T for 630A and 1250A in case that distance between phase & phase is 210mm.

�Earthing Switch

H1-34
Accessories

Accessories for VCB


Key lock
When it is locked by a key, the closing operation is not available
(electrically and mechanically) without a Key.

Button padlock
Button padlock protects 'ON' or 'OFF' button when accident is occurred
by operation at discretion.
It is available to operate after release button padlock.

Button cover
Button cover protects 'ON' of 'OFF' button when accident is
occurred by operation at discretion. It is available to operate by push
bar.

<Push bar>

Position switch (Cell switch)


Indicating the position (Run or Test) of a VCB, by mechanically
pressing the switch when a VCB change the position.
- RUN: 2a
- TEST: 2a

<G class>

Note) In case that position of VCB


changed to “Run” or “Test” position,
“a” contact will be closed.

H1-35
Vacuum Circuit Breaker
Accessories

Accessories for VCB


Secondary coil (Preparatory trip coil)
The main coil and the preparatory coil is connected in parallel. So
even though there happens a fault in the trip coil, the VCB can be
tripped by one of the two trip coils.

Latch checking switch


When the Latch is in abnormal position, the Latch checking switch
prevents the closing operation even though there is the 'Closing'
signal.

Charge indicator
Remotely indicates the charging is completed.
(Standard Feature)
- Terminal No.: 9, 10

Position padlock
The hole to prevent the draw-in and out of a VCB from the present
position.('Run' or 'Test')
Standard option in the interlock lever of the E, F class draw-out type
VCB. (Hole size = ∅ 8)

H1-36
Accessories for Cradle
Earthing switch (for G class draw-out type only)
For the safety during the maintenance of a VCB panel, discharge the
charging current in the load side of a VCB with this earthing switch.

Padlock of earthing switch


(for G class draw-out type only)
The hole to prevent the accident through carelessness earthing
switch operation, the locking of the earthing switch is available when
the switch is in 'OFF' position.
(Hole size = ∅8)

Position switch of the earthing switch


(for G class draw-out type only)
Indicates the 'ON' or 'OFF' status of the earthing switch. (5a5b)

Locking coil of earthing switch


(for G class draw-out type only) <Earthing Switch Position Switch>

To prevent the accident through carelessness earthing switch


operation, the earthing switch can be changed to 'ON' position after
releasing the lock by magnetizing the coils.

<Earthing Switch Locking Coil>

H1-37
Vacuum Circuit Breaker
Accessories

Accessories for Cradle


Shutter padlock
The hole to lock the shutters (load and line side) in close position, to
increase the safety during the maintenance of a VCB draw-out
position.
(Hole size = ∅8)

Mechanically operated cell switch (MOC)


-for G class draw-out type only
The auxiliary switch (3a4b), which Indicate the 'ON' or 'OFF' condition
of a VCB, but operated only when the VCB is in 'Run' state. (Installed
in the bottom of a cradle)

Note) #11, 21 are Early “b” contact

Truck operated cell switch (TOC)


-for G class draw-out type only
The auxiliary switch (3a4b), which indicate the 'Run' state of a VCB
and is operated by the movement of a VCB frame. (Installed in the
bottom of a cradle)

Note) #11, 21 are Early “b” contact

Code plate (Miss insertion prevention)


-for E, F class draw-out type only
To prevent the insert a VCB to a cradle, when the ratings of VCB and
cradle are different.

Padlock
To prevent the insert draw-in/out handle to a screw hole by operating
G class VCB temporarily

H1-38
Optional accessories
Capacitor trip device (CTD) �Dimension
When the control power is off, the
CTD supply the power for tripping
a VCB.

Ratings Specification
Type CB-T1 CB-T2
Rated input voltage AC100/110V AC200/220V
Freguency (Hz) 50/60 50/60 �Connection diagram �CDT
Charging volt(V) 140/155 280/310
Charging time Within 10 Sec. after the AC power off
Tripping time Within 30 Sec. after the AC power off
Allowable Input
85% ~ 100% 85% ~ 110%
voltage range
Capacitor rating(μF) 1000 560

Rectifier �Dimension
When the DC power is not available, rectify the AC power and
get the DC power for closing coil.
Type AC Input voltage Output current Rating time
1∅ 100/110V
150

100
VCB-X 40A DC 10 sec.
1∅ 200/220V

70
29.5
25

80 40

�Connection diagram

Standard tool
+

- ~ ~

E, F class G class

Handle for draw-in and out Manual charging handle


Handle for draw-in and out the VCB Handle for charging the spring manually.
(Standard feature in the draw-out type) (Standard feature)

H1-39
Vacuum Circuit Breaker
Types and ordering information

12kV

LVB 12 G 32 D 12 1A 2B B, C1, D1

LS VCB Installation method Revision No. Control voltage


G G class draw-out type D Pro-MEC 1A DC110V
G class draw-out type 1B DC220V
M
+ Bushing 1C DC48V
Rated voltage 1E DC125V
12 12kV

Breaking current Rated current Auxiliary switch


32 31.5kA 12 1250A 2B 4a4b(A type connector) Accessories
40 40kA 20 2000A 2E 10a10b(A type connector) B Position Switch (RUN/TEST:2a2a)
30 3150A 2G 4a4b(B type connector) C1 Button Padlock (ON)
2H 10a10b(B type connector) C2 Button Padlock (OFF)
C3 Button Padlock (ON/OFF)
D1 Button Cover (ON)
D2 Button Cover (OFF)
D3 Button Cover (ON/OFF)
E Button padlock (ON)+ Button cover (OFF)
F Button padlock (OFF)+ Button cover (ON)
G Key Lock
H Secondary Trip Coil(Preparatory trip coil)
J Fire-endurable wiring cable ass’y
K Opening Latch Checking Switch
S Pad Lock (G class)
T Enclosed type, Tulip contact

Cradle

LCL 12 G 32 D 12 A, B, C

LS Cradle Installation method Breaking current Revision No. Rated current Accessories
G class 32 31.5kA D Pro-MEC 12 1250A T Enclosed type, Tulip contact
G
draw-out type 40 40kA 20 2000A
30 3000A
Rated voltage
12 12kV

H1-40
17.5kV

LVB 17 G 40 D 12 1A 2B B, C1, D1

LS VCB Installation method Revision No. Control voltage


P Fixed type D Pro-MEC 1A DC110V
E E class draw-out type 1B DC220V
F F class draw-out type 1C DC48V
Rated voltage G G class draw-out type 1E DC125V
17 17.5kV

Breaking current Rated current Auxiliary switch


40 40kA 12 1250A 2B 4a4b(A type connector) Accessories
20 2000A 2E 10a10b(A type connector) B Position Switch (RUN/TEST:2a2a)
30 3150A 2G 4a4b(B type connector) C1 Button Padlock (ON)
2H 10a10b(B type connector) C2 Button Padlock (OFF)
C3 Button Padlock (ON/OFF)
D1 Button Cover (ON)
D2 Button Cover (OFF)
D3 Button Cover (ON/OFF)
E Button padlock (ON) + Button cover (OFF)
F Button padlock (OFF) + Button cover (ON)
G Key Lock
H Secondary Trip Coil(Preparatory trip coil)
K Opening Latch Checking Switch
S Pad Lock (G class)
J Fire-endurable wiring cable ass’y

Cradle

LCL 17 G 40 D 12 A, B, C

LS Cradle Installation method Breaking current Revision No. Rated current Accessories
E E class draw-out type D Pro-MEC 12 1250A A MOC (3a4b) + TOC (3a4b)
F F class draw-out type 20 2000A Note) ‘A’ is for ‘G’ class only
G G class draw-out type 30 3150A
Rated voltage
17 17.5kV

H1-41
Vacuum Circuit Breaker
Types and ordering information

24kV

LVB 20 G 13 D 06 1A 2B B, C, D

LS VCB Installation method Revision No. Control voltage Accessories


P Fixed type D Pro-MEC 00 - B Position Switch (RUN/TEST:2a2a)
E E class draw-out type Note1) Pro-MEC 1A DC110V C1 Button Padlock (ON)
E C2 Button Padlock (OFF)
Rated voltage F F class draw-out type (Minimized type) 1B DC220V
G G class draw-out type 1C DC48V C3 Button Padlock (ON/OFF)
20 24kV
D1 Button Cover (ON)
G class draw-out type 1E DC125V
M D2 Button Cover (OFF)
+ Bushing AC220(M),
1F D3 Button Cover (ON/OFF)
DC110(TC)
Button padlock (ON)
AC220(M), E
1H + Button cover (OFF)
DC220(TC) Button padlock (OFF)
AC110(M), F
+ Button cover (ON)
1T
DC110(TC) G Key Lock
Secondary Trip Coil
H
(Preparatory trip coil)
Breaking current Rated current Auxiliary switch
J Fire-endurable wiring cable ass’y
13 12.5kA 06 630A Note2) 00 -
K Opening Latch Checking Switch
16 16kA 12 1250A 2B 4a4b(A type connector) P1 Dummy VCB(AMP Jack)
25 25kA 20 2000A 2E 10a10b(A type connector) P2 Dummy VCB(Phoenix Jack)
2G 4a4b(B type connector) Q Earthing Truck(Lower terminal earthing)
2H 10a10b(B type connector) R Earthing Truck(Upper terminal earthing)
S Pad Lock (G class)
T Enclosed type, Tulip contact
Option
Note) 1. Version E is available only at 24kV G class and its distance between phases is 210mm. N CTD(Capacitor Trip Device)
2. "00" is used for ordering Earthing Truck and Dummy VCB
4. Accessory only for versions D and E O Rectifier

Cradle

LCL 20 G 13 D 06 A, B, C

LS Cradle Installation method Breaking current Revision No. Rated current Accessories
E E class draw-out type 13 12.5kA A Conventional 06 630A Note2) A MOS(3a4b)+ TOC(3a4b)
F F class draw-out type 16 16kA D Pro-MEC 12 1250A Note2) B Earthing Switch
G G class draw-out type 25 25kA Pro-MEC 20 2000A Earthing Switch Position Switch+
Rated voltage Note1) E Note2) C
(Minimized type) Earthing Switch Locking coil
20 24kV
T Enclosed type, Tulip contact
Position S/W Block
PS
(24kV E/F class only)

Note) 1. Version E is available only at 24kV G class and its distance between phases is 210mm.
2. Versions A, B and C are available only at G class VCB.

H1-42
Vacuum Interrupter
Features & Ordering information

Features
Accumulation of more than 20 years of
vacuum-related technologies

Simplified arc extinguishing system


Spiral contact structure with Radial magnetic
field provides effective dispersing of the acr
energy.

Simple structure and high quality


Sealing after complete removal of gas in the
vacuum chamber in order to secure a long
vacuum confidentiality

Small size and light weight


The new contact material used to enhance
the competitiveness of the size

Wide rated coverages


Wide interrupting range from 6kV up to
40.5kV 40kA

High reliability and electrical life


Certification by KERI and KEMA according
to the latest standard IEC62271-100 (2008)
E2, LIST3, M2

Modeling system

LV7 A - P

Basic type Revision No ETC.


L LS A, B… Null Straight type
V Vacuum P Potting type
7 Series No. C Wave type
E Embedded type
G Gas Insulation type

H1-43
Vacuum Interrupter
VI internal structure

Largely movable and fixed electrodes and main shield compose the Susol VI.
The main components are shown in the following.

Fixed electrode

Fixed seal cup

Fixed shield

Contacts
Arc shield

Bellows shield Ceramic

Bellows

Movable seal cup

The vacuum rate within the VI is very high(approximately 5x10-5 Torr) and the spacing between
fixed contact and movable contact is about 6 ~ 20mm, depending on the voltage.
The contacts are in a structure that arc can easily be extinguished and the surfaces of the contacts
are made of special alloy (copper - chromium) and the interior is completely sealed to prevent loss
of vacuum.
Therefore the wearing of the contacts can be minimized in the event of short-circuit and the arc
energy by overvoltage or switching can be reduced effectively.

H1-44
Basic functions and interrupting action

Interrupting action by VI

In case of using the flat


contact any of the designs
do not reflect on when
contacts are opening the arc
with high temperature is
contracted and fixed in the
center of the contacts,
Which is called pinch effect.
To prevent the effect two
kinds of contact shapes are
designed.
One is Axial magnetic field
which spreads the arc
before its contraction, and
the other is Radial magnetic
field which
permits the contraction of
the arc but makes it rotated
to disperse the energy.
Because contracted arc is
shaped like a cylinder it is
called Contracted arc or
columnar arc.
Arc voltage waveforms and arc image captured during arcing time

Spiral contact structure (Radial magnetic field ),


using the force (F = j ×B) generated by the Radial magnetic field type contact
interaction of the radial magnetic field caused by
the current flowing through the arc between two
contacts, disperse the arc energy evenly on the
surface of contact by rotating the arc that is
contracted by the pinch effect so as to minimize
contact damage.
The images show arc behavior during the arcing
time of about 8ms by shooting with high-speed
camera capable of shooting 10,000 frames per Columnar arc Direction of
sec. rotating arc
(0.1ms/frame) by focusing on parts of the arcing Current
time on the above graph and simultaneously
measured arc voltage also represented to show arc Arc driving principle in the contacts of Radial magnetic field
state by section

H1-45
Vacuum Interrupter
VI endurance by interrupting current
Number[ops.]

Number[ops.]

Interrupting current [kA] Interrupting current [kA]

VI model LV2 at 7.2kV VI model LV3 at 7.2kV


�N : Operation numbers �N : Operation numbers
�I : Interrupting current �I : Interrupting current
Number[ops.]

Number[ops.]

Interrupting current [kA] Interrupting current [kA]

VI model LV4 at 24kV VI model LV5 at 17.5kV


�N : Operation numbers �N : Operation numbers
�I : Interrupting current �I : Interrupting current

H1-46
Number[ops.]

Number[ops.]

Interrupting current [kA] Interrupting current [kA]

VI model LV8 at 17.5kV VI model LV7-P1 at 24kV


�N : Operation numbers �N : Operation numbers
�I : Interrupting current �I : Interrupting current
Number[ops.]

Interrupting current [kA]

VI model LV8 at 36kV


�N : Operation numbers Note) 1. Above graphs represent the characteristics of the electrical life of LS Susol VCB.
2. Life characteristics of each model in each rating represents the LOG-LOG graphs.
�I : Interrupting current

H1-47
Vacuum Interrupter
Dimensions

LV2 LV3 LV4

17 -0.3
0
21-0.3
0
17-0.3
0

LV5-P LV5A LV8


5.2+0.1

6 +0.1
0

0
-0.1
30 +0.3
0
30 +0.5
0
20 +0.5
0

+0.1 +0.1
0 0

H1-48
LV7-P1 / LV8-P LV7-C LV10404
6 +0.1
0

0
-0.1

30 +0.5
0
0
-0.1
30 +0.3
0

+0.1
0

90
×
4 O

H1-49
Vacuum Interrupter
Technical data

Type LV2 LV3 LV4-E LV5-P

Outer view

Rated voltage (kV) 7.2 7.2 24/25.8 12/17.5

Rated power frequency withstand voltage (kV, rms) 20 20 50 42

Rated impulse withstand voltage (kV, crest) 60 60 135 95


Electrical ratings

Rated frequency (Hz) 50/60 50/60 50/60 50/60

Rated normal current (Amp) 400/630 630/1250 630 630/1250

Rated short circuit current (Sym.) (kA) 8 12.5 20 25 16 20 25

Rated short circuit making current (kA, peak) 20.8 32.5 52 65 41.6 52 65

Rated duration of short-circuit (sec) 33 3 3

Interrupter weight (kg) 0.8 1.4 1.2 2.4


Mechanical data

Moving part weight (kg) 0.3 0.7 0.5 0.7

Outline dimension (mm) a 132 158 208 220

b 91 105 159 163

c 62 80 62 90

Contact stroke (mm) 6±1 10 ±1 12 ±1 10±1

Opening speed, average 0 to 75% of full stroke (m/s) 0 7~1.0 0 7~1.0 1.3~1.5 0.7~1.0

Overtravel during opening, Max. (mm) 22 2 2


Mechanical requirements

Closing speed, average last 33% of full stroke (m/s) 0 7~1.0 0 7~1.0 0 7~1.0 0.7~1.0

Contact bounce duration, Max. (sec) 22 2 2

Added force from atmospheric pressure (kg∙f) 80 154 227 120 154 227

Contact force from atmospheric pressure (kg∙f) 8.5 12.6 9 12.6

Contact erosion limit (mm) 33 3 3

Mechanical life (×10 4, Operations) M2 M2 M2 M2

H1-50
LV5A LV7-P1 LV7-C LV8 LV8-P LV10404

12/17.5 24/25.8 40.5 17.5 36 7.2/12 25.8

42 65 95 38 70 20/28 70

95 125 185 95 170 60/75 150

50/60 50/60 50/60 50/60 50/60 50/60

2000 2500 ~3150 ~3150 ~3150 ~3150 4000 3150

20 25 25 31.5 40 25 31.5 40 50 25 31.5 40 40 50 40

52 65 65 81.9 104 65 81.9 104 130 65 81.9 104 104 130 104

34 44 4 4 3

3.0 7.3 9.8 6.6 7.3 8.7

1.0 2.2 2.6 2.2 2.2 2.0

220 272 390 272 272 317

160 216 329 210 216 210

80 145 145 135 145 135

10±1 12 ±1 17~19 12 ±1 17~19 10±1 17 ±1

0.7~1.0 1.0~1.3 1.3~1.5 1.0~1.3 1.3~1.5 1.0~1.3

22 22 2 1.5

0.7~1.0 0.7~1.0 0.7~1.0 0.7~1.0 0.7~1.0 0.7~1.0

22 22 2 2

154 227 227 306 367 227 306 367 460 227 306 367 367 406 367

12.6 25.5 25.1 25.8 25 25.8

33 33 3 3

M2 M2 M2 M2 M2 M2

H1-51
Pro-MEC MCSG VCB
Vacuum Circuit Breaker for MCSG
Features and Structure H2-2
Control circuit diagram H2-4
Dimensions H2-5

Contents

H2
Vacuum Circuit Breaker for MCSG
Features and Structure

Features
�Module type VCB
�Convenient especially for fabricating MCSG
- Housing is designed like VCB compartment style
- MCSG panel can be easily constructed if combined with Low voltage compartment, Busbar
compartment and Cable compartment.

�Convenient for maintenance and offering high safely


- Earthing switch can be operated from outside of the panel, and which makes earthing of 3 phases at the
same time.
- Without opening the compartment panel door, breaker can be drawn in or out electrically or manually

�Main functions
- Breaker : draw- in or out electrically or manually
- Compartment : 3-positions

�Standard
- IEC 62271-100

① Name plate
② Manual closing button
③ Keylock
④ Manual trip button
⑤ Manual charging hole
⑥ Contact position
indicator
⑦ Closing spring

charge indicator

⑤ ⑧ Operation counter

⑨ Insertion &

⑥ Draw-out screw
① ⑩ Geared Mechanism

Electrical
drive unit

Compartment Earthing switch Bushings Shutter

H2-2
Ratings
Type LVB‐
‐25□
□-25□
□/06 LVB‐
‐25□
□-25□
□/20
Rated voltage (kV) 25.8
Rated normal current (A) 630 2000
Rated frequency (Hz) 60
Rated short-circuit breaking current (kA) 25
Rated short-circuit breaking capacity (MVA) 1100
Rated short-time withstand current (kA) 25/3s
Rated short-circuit making current (kA) 65
Rated breaking time (Cycles) 3
Withstand Power frequency (kV) 50/1min
voltage Impulse (kV/1.2××50㎲ ) 125
TRV rising rate (kV/㎲ ) 0.47
TRV max. (kV) 41
Rated operating sequence O-0.3s-CO-3min-CO
Mechanical lifetime 10,000operations
Electrical lifetime 10,000operations
Rated control voltage (V) DC 110V
Rated trip voltage( V) DC 110V
Standard auxiliary switch 4a4b, 8a8b
Rated opening time (s) ≤ 0.04
No-load closing time (s) ≤ 0.06
Rated charging motor current (A) ≤7
Rated closing coil current (A) ≤5
Rated trip coil current (A) ≤5
Closing spring charging time (s) ≤ 12
Draw-in/out motor voltage (V) DC 110V
Draw-in/out motor current (A) ≤5
Distance between phases (mm) 265
breaker 205 236.5
Weight (kg)
compartment 281 293
Installing G
Applied standard IEC 62271-100

�Breaker

LVB 25 G 25 I 06 1A 2B B,C,D
LS VCB Installation method Version Control voltage Accessories
G Gclass draw-out 1A DC110V B Position Switch
1B DC220V C1 Button Padlock(ON)
Rated voltage Rated current 1C DC48V C2 Button Padlock(OFF)
25 25.8kV 06 630A 1E DC125V C3 Button Padlock(ON/OFF)
20 2000A 1F AC220(M), DC110(TC) D1 Button Cover(ON)
Breaking current 1H AC220(M), DC220(TC) D2 Button Cover(OFF)
25 25kA 1T AC110(M), DC110(TC) D3 Button Cover(ON/OFF)
E Button Padlock(ON)+Button Cover(OFF)
Auxiliary switch F Button Padlock(OFF)+Button Cover(ON)
2G 4a4b(B type connector) G Key Lock
2H 8a8b(B type connector) H Secondary Trip Coil

�Cradle(Compartment)

LCL 25 C 13 D 06 A,B,C
LS VCB Rated voltage Installation method Breaking current Version Rated current Accessories
25 25.8kV C Bushing 25 25kA 06 630A B Earthing Switch
20 2000A E Door

H2-3
3
H2-4
Auxiliary switch
8a 8b
P P P P
4a 4b Position S/W
CW CCW
CS CS (인입) (인출) Test Run
A1 9 A3 A5 13 14 15 16 17 22 24 26 28 40 42 44 46 36 38 50 52 54 56 58 70 1 3

43 43
89X 89Y 13 13
44 44 89X 89Y
LS2 3 LS3 4
1 1 3 14 14
Ya 1 1
4 2 2 4 LS6 LS5
6
1 2 2 1
Yb 21 21
5 89M
5 6 89Y 89X 22 24 26 28 40 42 44 46 36 38 50 52 54 56 58 70 1 3
30 52a 22 22 2
M 52b PS1 PS2
31 8 8
6 3 7 6' 23 25 27 29 41 43 45 47 37 39 51 53 55 57 59 71 2 4
89X 89Y 33 33
C Y 9 9 89Y 89X

TRIP POWER SOURCE


4 8 1

MOTOR POWER SOURCE


34 34

CLOSING POWER SOURCE


34
1 TC 52b
LS1 2
2 35

A2 10 A4 A6 23 25 27 29 41 43 45 47 37 39 51 53 55 57 59 71 2 4
Control circuit diagram

N N N
Indication for closing spring "charged" is available.

Note. Diagram shows the circuit breaker in position“OFF”with closing spring“Charged”

∅ : External terminal of VCB


52 : Vacuum circuit breaker
M : Spring charging motor
TC : Trip coil
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
TC1 : Secondary trip coil
D 1 2 3 4 9 10 D
Vacuum Circuit Breaker for MCSG

C : Closing coil
C 50 51 52 53 C Y : Anti-pump relay
B 13 14 15 16 17 36 37 38 39 B 52a : Auxiliary switch (NO)
A A1 A2 A3 A4 A5 A6 22 23 24 25 26 27 28 29 A 52b : Auxiliary switch (NC)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 LS1 : Closing interlock limit switch(only withdrawable type)
( 4a 4b ) LS2 : Motor stopping, closing spring charged indication
LS3 : Anti-closing, Anti-pumping limit switch
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 LS5 : "Off" at Test Position
D 1 2 3 4 9 10 D LS6 : "Off" at Run Position
C 50 51 52 53 54 55 56 57 58 59 70 71 C PS1 : Position S/W("On" at Test Position)
PS2 : Position S/W("On" at Run Position)
B 13 14 15 16 17 42 43 44 45 46 47 36 37 38 39 B
89X : Auxiliary Relay for Inserting
A A1 A2 A3 A4 A5 A6 22 23 24 25 26 27 28 29 40 41 A 89Y : Auxiliary Relay for withdrawing
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 89M : Motor for withdrawing and Inserting
( 8a 8b )
SECONDARY DISCONNECT WIRING
( TOP VIEW )
Dimensions

Cradle(Compartment) - w/o Earthing Switch

�Front Lead wire


<A-A Section View>
293.8
�Rear
(2m) 180 263.8
A

45
70 103 75

C 10 60 2-∅13

372.6
st:310

30
425

86
190
26.8 3-∅10

340
340
1365

1365

425

86
1082

30
60
265 265 265 265

652.4
175

425
B B (Earthing)
(212.4)

∅6.5
(183.4)

183.4
15.4

TEST RUN

95

95
1

45
35

A
53 894 53 410 553 1 Earthing 968
1000 963 1000

�Top <B-B Section View>


<Front> <Rear> <Front> <Rear>
410 3-∅11
65 (Mounting Hole)
3-∅11×22 <C-View(Cover 2 Cutting)>
(Mounting Hole)
User Bus
205

128 50
265

20 370 40 513 16.8


175
103
600
950

700

700

20-M8 POP NUT 844


(DP:18)

50 340 40 483 50 15 933 (15)


963

G type breaker + track(electric draw-in/out)

630A
265 265 445

2000A

445
340
1013

340
608

860 350 50
886 481
912 785

H2-5
Vacuum Circuit Breaker for MCSG
Dimensions

Cradle(Compartment) - w/ Earthing Switch

�Front �Side �Rear


16-∅10
10-M8 POP NUT
35 (Mounting Hole Side) 35 238.8 (DP:18)
A

45
25t(2000A)
125

10t(630/1250A)

398.6
st:310

415
Test Run
500

74 Test

190
(Door)

340
**Option 3-∅10

415
1750

500

265 265
User Bus
175

415
767.4
(Earthing)
36 ∅6.5

M12 TAP
500

Test B (DP:24)

415

454
265 265
244

(Earthing S/W)
125

**Option
45

A 35
1000 39 963 320.9 968

�Top <Terminal conductor>


<B-B Section View>
<Front> <Rear> <Front> <Rear>
60
26 2-∅13
25

17

26

9-∅11Mounting Hole
83

20 370 40 513 16.8 65 ∅19 15


340
600

700
950

20-M8 POP NUT


83
17

(DP:18) 140 150


50

26
26
25

60

50 340 40 483 50 100 763 100


70

H2-6
Power Plants VCB
Vacuum Circuit Breaker for Power Plants
Ratings H3-4
Ratings of Accessories H3-5
Accessories H3-6
Control circuit diagram H3-8

Contents Dimensions H3-9


Types and ordering information H3-14

H3
Vacuum Circuit Breaker
Power Plants
A product developed for water and thermal power plants due
to the revision and application of Kepco’s standard (ES150)
followed by the IEC standard revision. It has completed the
high capacity (40~50kA) VCB series for power plants by
securing higher breaking capacity, safety and reliability.

VCB Full Option


To prevent fatal error, property and life loss caused from operator during
operation, it is equipped with safety mechanisms such as shutter padlock.

Bushing applied for Window CT adaptation


The bushing provides sufficient strength to collaborate with the internal insulation and is
adaptable with CT offering safety mechanically and electrically when applying large current.

H3-2
Vacuum Circuit Breakers
for Power Plants

It is recognized for reliability by acquiring new


IEC 62271-100 and ES150 (KEPCO standard
specification on AC breakers)

H3-3
Vacuum Circuit Breaker for Power Plants
Ratings

Type LVB-06G-40H LVB-06G-40J LVB-06G-50J

Rated voltage (kV) 7.2

Rated normal current (A) 1200 2000 3000 1250 2000 2500 3150 1250 2000 3150

Rated frequency (Hz) 60

Rated short-circuit breaking current (kA) 40 50

Rated short-circuit breaking capacity (MVA) 500 624

Rated short-time withstand current (kA/3sec) 40 50

Rated short-circuit making current (kAp) 104 130

Rated breaking time (Cycle) 3

Rated opening time (sec) ≤ 0.04

No-load closing time (sec) ≤ 0.06

Withstand Power frequency (kV/min) 20

voltage Impulse (kV/1.2 ×50㎲ ) 60

Rated operating sequence CO-15s-CO O-0.3s-CO-3min-CO

Rated charging motor current (A) 5 (at DC125V) 5 (at DC110V)

Rated closing coil current (A) 3 (at DC125V) 3 (at DC110V)

Rated shunt coil current (A) 3 (at DC125V) 3 (at DC110V)

Type Mechanical M2

test Electrical E2 (Maintenance free) E2 (List1)

Capacitive current switching C2

Lifetime Mechanical Without maintenance 10000 operations

Maintenance 20000 operations

Electrical Without maintenance 10000 operations

Maintenance 20000 operations

Auxiliary switch 3a3b

Installing Draw-out G-type Visible, Tulip

Weight Breaker G-type (kg) 200 260 200 260 200 260

Cradle G-type (kg) 190 230 190 230 190 230

Applied standard ES150 NOTE) IEC 62271-100

Type test laboratory KERI

Note) ES150: KEPCO's standard in which IEC62271-100 is applied


KERI: Korea Electrotechnology Research Institute

H3-4
Ratings and auxiliary devices

Motor
When the closing spring is charged, the control power of motor is turned off by the built-in limit s/w.

The peak value of the Consumption Charging time


Rated voltage Rated current (A)
inrush current (A) power (W) (Sec.)

DC 110V 20 3 330 12
DC 125V 20 3 330 12
Note) Range of the normal operating voltage: 85~110% of rated voltage

Closing Coil (C) Shunt coil (TC)


When the rated volt is applied to the coil the breaker is closed. When the rated volt is applied to the coil the breaker is opened.
The electrical anti-pumping circuit is built-in it.

Rated voltage Rated current (A) Rated voltage Rated current (A)

DC 110V 3 DC 110V 3
DC 125V 3 DC 125V 3
Note) Range of the normal operating voltage: 75~125% of rated voltage Note) Range of the normal operating voltage: 60~125% of rated voltage

Auxiliary switch
Standard configuration : 3a3b1b of early-b contact function exists inside Position of the Auxiliary switch
Resistive Inductive Contact Switch Mechanism MOC TOC
Classification
load (A) load (A) configuration
Breaker a b a b a b
110V 10 5
Contact Ratings DC 3a3b CLOSE ON OFF ON OFF ON OFF
125V 10 5 RUN
Note) The contact ratings of Mechanical Operated Cell Switch(MOC) OPEN OFF ON OFF ON OFF ON
are the same with that of the Aux. switch.
CLOSE ON OFF ON * OFF * ON OFF
TEST
Truck Operated Cell Switch(TOC) OPEN OFF ON OFF * ON * OFF ON
Note) * applied in the VCB of which MOC is operable at the TEST position.
Resistive Inductive Contact
Classification
load (A) load (A) configuration
110V 10 5
Contact Ratings DC 3a3b
125V 10 5

Charge indicator of Position indicator of the


the closing spring main contacts
Indicating the condition of the closing spring. Indicating the 'Close' or the 'Open' of the main contacts.
Close position:�ON� � Open position:�OFF� �

Charged Discharged
Close position Open position

Counter
Mechanically counts the operation of the VCB by 5digits

H3-5
Vacuum Circuit Breaker for Power Plants
Accessories

Accessories for breakers

�Position padlock
It is located at the screw hole to prevent the draw-in and out of a breaker
from the present position(Disconnected, Test or Connected)

�Mechanical position indicator


It is located in the lower part of a breaker to check the present position -
Disconnected, Test or Connected- easily.

�Position interlock
The breaker is locked in each position-Disconnected, Test or Connected,
thus it is necessory to release the lock before draw-in or out of a breaker
from the present position.

�Auto connection
When the breaker is moved to Test position from Disconnected position
the connector for control powers is automatically connected. In case of
reverse moving of the breaker the connector is automatically
disconnected.

�Code plate
When the breaker is inserted to the cradle, if the ratings does not match
with the cradle, it mechanically prevents the breaker from being inserted
into the cradle.

H3-6
Accessories for breakers

�Mechanically operated cell switch (MOC)


It is auxiliary switch (6a6b), which indicates the 'ON' or 'OFF' condition of a
VCB, and operated when the VCB is in 'Run' state.

�Truck operated cell switch (TOC)


It is auxiliary switch (6a6b), which indicates the 'Run' state of a VCB and is
operated by the movement of a VCB frame.

H3-7
H3-8
<TOC> Cell switch in service position
15 16 17

25 26 27
A
12 13 14

22 23 24
<MOC>
15 16 17 30 34 36 38 50 52
P P P
Auxiliary switch
25 26 27 31 35 37 39 51 53 CS CS 3a 3b
B A1 A3 A5 22 24 26 54 56 58
12 13 14 6 22 24 26 28 40

22 23 24 7 23 25 27 29 41
LS2 LS3
4
3 1 3
Ya
Control circuit diagram

4 2 4 6
1
Yb
5 6 22 24 26 54 56 58
52b 30 52a
31
5 3 7 7 23 25 27 55 57 59
M C Y 1

TRIP POWER SOURCE


6 4 8

MOTOR POWER SOURCE


TC

CLOSING POWER SOURCE


1 1
LS4 LS1 2
2 2
A2 A4 A6 23 25 27 55 57 59
N N N Early b

A1 A3 A5 54
A2 A4 A6 55
Note) Diagram shows the circuit breaker in position“OFF”with closing spring“Charged”
22 24 26 56 58
23 25 27 57 59
∅ : External terminal of VCB
52 : Vacuum circuit breaker A B
M : Spring charging motor (12P TAP PLUG)
Vacuum Circuit Breaker for Power Plants

TC : Trip coil 13 14 15 16 17 18 19 20 21 22 23 24
C : Closing coil
A2 A4 A6 23 25 27 55 57 59
Y : Anti-pump relay
A1 A3 A5 22 24 26 54 56 58
52a : Auxiliary switch (NO)
52b : Auxiliary switch (NC) 1 2 3 4 5 6 7 8 9 10 11 12

LS1 : Closing interlock limit switch SECONDARY DISCONNECT WIRING


LS2 : Motor stopping (FRONT VIEW OF RECEPTACLE PLUG)
LS3 : Anti-closing, Anti-pumping limit switch
LS4 : Motor Charging interlock limit switch
Dimensions - Breakers

LVB-06G-40H, 40J G class (Visible, Tulip contact)-(1200, 1250, 2000A) (unit : mm)

�Front �Side

54(male conductor)
722 336

360
815.2
130
351.3

368.2
60

10
696 686.2

717

�Top

254 254
<Conductor>
685.2
532

584

1200/1250/2000A

745

H3-9
Vacuum Circuit Breaker for Power Plants
Dimensions - Breakers

LVB-06G-40H, 40J G class (Visible, Tulip contact)-(2500, 3000, 3150A) (unit : mm)

�Front �Side

79(male conductor)
722 336

Heat sink
(only for 3150A)

360
815.2
130
349.8

60

368.2
10
696 686.2

717

�Top

<Conductor>
254 254
685.2
532

584

2500/3000/3150A

745

H3-10
LVB-06G-50J G class (Visible, Tulip contact)-(1250, 2000A) (unit : mm)

�Front �Side

54(male conductor)
722

115.5 336
140

Moving contact Fixed contact

360
130

815.7
403.8
341.3

368.2
60

696 677.2 10
717

�Top
254 254
676.2
532

584

745

H3-11
Vacuum Circuit Breaker for Power Plants
Dimensions - Breakers

LVB-06G-50J G class (Visible, Tulip contact)-(3150A) (unit : mm)

�Front �Side

79(male conductor)
722
336
115.5 140

Moving contact Fixed contact

360
107
130

815.7
136.5

358.7
341.8

267.8

150.2
445.8
696 541

10
677.2
717

�Top

254 254
676.2
532

584

H3-12
Cradles (unit : mm)

4-M12
252 374
DP20 1134
50 35 240
150 500 361

∅14
∅218

∅148
∅79
310

(Earthing)
50

254
140 123
175

2500/3000/3150A
816
776
103.5

2-M12 252 374

254
DP20 35 240
235.5
∅218

∅148
310

∅54
36

436.5 Mounting 6-∅12


544 Autocon(3a3b)
140 123
M.O.C(6a6b)
1200/1250/2000A

338
360
1035
61(레일폭)

449.5

644
59
61

151.5

75.8

T.O.C(6a6b) 1038.5

H3-13
Vacuum Circuit Breaker for Power Plants
Types and ordering information

Breaker

LVB 06 G 40 J 12 1A 2L P3,Q,R

LS VCB Installation method Standard Control voltage


G G class draw-out H ESB150 1A DC110V Option
J IEC 1B DC220V C1 Button padlock(ON)
1E DC125V C2 Button padlock(OFF)
C3 Button padlock(ON/OFF)
D1 Button Cover(ON)
D2 Button Cover(OFF)
Breaking current
NOTE2)
Rated voltage Rated current Auxiliary switch
D3 Button Cover(ON/OFF)
06 7.2kV 40 40kA 12 1200/1250A 2L 3a3b(Autocon)
Button padlock(ON)+
50 50kA 20 2000A E
Button cover(OFF)
25 2500A
NOTE1)

Button padlock(OFF)+
30 3000/3150A F
Button cover(ON)
G Key Lock
P3 Dummy VCB
Note) 1.Rated current 2500A is available only at 7.2kV 40kA, IEC version(J)
2.Control voltage and Auxiliary switch are not applied to Dummy VCB and Earthing Truck Q Earthing Truck(lower terminal)
R Earthing Truck(upper terminal)

Cradle

LCL 06 G 40 J 12 A1, A2

LS Cradle Installation method standard Option


G G class draw-out H ESB150 MOC(6a6b)+TOC(6a6b)
J IEC A1 MOC active only at RUN
position
MOC(6a6b)+TOC(6a6b)
A2 MOC active only at TEST

Rated voltage Breaking current Rated current and RUN position

06 7.2kV 40 40kV 12 1200/1250A


50 50kV 20 2000A
25 2500A
30 3000/3150A

H3-14
Nuclear Power Plants VCB
Vacuum Circuit Breaker for Nuclear Power Plants
Ratings H4-4
Ratings of Accessories H4-5
Accessories H4-6
Control circuit diagram H4-8

Contents Dimensions
Types and ordering information
H4-9
H4-11

H4
Vacuum Circuit Breaker
Nuclear Power Plants
It was developed for KEPCO nuclear power stations. This breaker
satisfies quality, safety measures (secure from earthquake and
other environments), and surge protection class complies with
“1E-CLASS” ±provisions. It is featured with high breaking
technologies, safety, and reliability by applying our own vacuum
interrupters (50KA) approved by ANSI standard tests.

H4-2
Vacuum Circuit Breakers
for Nuclear Power Plants

VCB Full Option Bushing applied for Satisfies earthquake and


Window CT adaptation other internal environment
To prevent fatal error, property and
specifications
life loss caused from operator The bushing provides sufficient
during operation, it is equipped strength to collaborate with the During the lifespan of power stations (40yrs),
with safety mechanisms such as internal insulation and is adaptable it is designed to operate its fundamental
shutter padlock. with CT offering safety mechanically breaking functions even under the most
and electrically when applying severe conditions like earthquake, which is
large current. critical from safety perspectives. These
technologies proven through tests that
comply with KEPIC standard and relevant
specifications are to guarantee nuclear
reactor safety.
H4-3
Vacuum Circuit Breaker for Nuclear Power Plants
Ratings

Type LVB-05G-50B LVB-15G-40B

Rated voltage (kV) 4.76 15

1200 1200

Rated normal current (A) 2000 2000

3000 -

Rated frequency (Hz) 60 60

Rated short-circuit breaking current (kA) 50 40

Rated short-circuit breaking capacity (MVA) 410 1040

Rated short-time withstand current (kA/3sec) 50 40

Rated short-circuit making current (kA) 130 104

Rated breaking time (Cycle) 3 3

Rated opening time (sec) ≤ 0.04 ≤ 0.04

No-load closing time (sec) ≤ 0.06 ≤ 0.06

Withstand Power frequency (kV/1min) 19 36

voltage Impulse (kV/1.2×


× 50㎲ ) 60 95

Rated operating sequence 0-0.3s-CO-3min-CO

Rated charging motor current DC 125V (A) 5 5

Rated closing coil current DC 125V (A) 3 3

Rated shunt coil current DC 125V (A) 3 3

Mechanical(w/o maintenance) 10000 operations 10000


Lifetime
Electrical(w/o maintenance) 10000 operations 10000

Auxiliary switch 5a3b 5a3b

Installing G-type G-type

1200,2000A (kg) 300 300


Weight
3000A (kg) 350 -

Applied standard ANSI C37 ANSI C37

Type test laboratory KERI KERI

H4-4
Ratings of Accessories

Motor
When the closing spring is charged, the control power of motor is turned off by the built-in limit s/w.

The peak value of


Ratedcurrent(A)
the inrush current (A)
Range of the normal Consumption Charging time
Rated voltage
4.76kV 15kV 4.76kV 15kV operating voltage power (W) (sec)

50kA 40kA 50kA 40kA

DC 125V 15 15 5 5 90~140 360 8

Closing Coil (C) Shunt Coil (TC)


When the rated volt is applied to the coil the breaker is closed. When the rated volt is applied to the coil the breaker is
The electrical anti-pumping circuit is built-in it. opened.

The peak value of The peak value of


the inrush current (A) the inrush current (A)
Range of the normal Range of the normal
Rated voltage Rated voltage
4.76kV 15kV operating voltage 4.76kV 15kV operating voltage

50kA 40kA 50kA 40kA


DC 125V 3 3 90 ~ 140 DC 125V 3 3 70 ~ 140

Auxiliary switch
Standard configuration : Reversible 8C(5a3b)
and 2c(2b) with early-b contact function Position of the Auxiliary switch

Resistive Inductive Contact Switch Mechanism MOC TOC


Classification
load(A) load(A) configuration Breaker a b ab ab

250V 10 5 CLOSE ON OFF ON OFF ON OFF


AC RUN
125V 10 5 OPEN OFF ON OFF ON OFF ON

Contact Ratings 250V 10 5 8c CLOSE ON OFF ON OFF ON OFF


TEST
DC 125V 10 5 OPEN OFF ON OFF ON OFF ON

30V 10 5

Note) The contact ratings of Mechanical Operated Cell Switch(MOC)


are the same with that of the Aux. switch.

Charge indicator of Position indicator of the


the closing spring main contacts
Indicating the condition of the closing spring. Indicating the 'Close' or the 'Open' of the main contacts.
Close position:�ON� � Open position:�OFF� �

Charged Discharged
Close position Open position

Counter
Mechanically counts the operation of the VCB by 5digits

H4-5
Vacuum Circuit Breaker for Nuclear Power Plants
Accessories

Accessories for breakers


�Position padlock
It is located at the screw hole to prevent the draw-in and out of a breaker
from the present position(Disconnected, Test or Connected)

�Mechanical position indicator


It is located in the lower part of a breaker to check the present position -
Disconnected, Test or Connected- easily.

�Auto connection
When the breaker is moved to Test position from Disconnected position the
connector for control powers is automatically connected.
In case of reverse moving of the breaker the connector is automatically
disconnected.

�Reversible contact
10 auxiliary switches are provided. 8 of them consist of reversible 8c which
can be changed from a(b) to b(a). Factory composition is 5a3b. And the
other 2 switches are supplied as 2b with early-b contact function

�Code plate
When the breaker is inserted to the cradle, if the ratings does not match
with the cradle, it mechanically prevents the breaker from being inserted
into the cradle.

�Auto discharge
In case the breaker is drawn-out when the closing spring is charged in the
position-Disconnected, Test or Connected, or the breaker is moved to
Disconnected position from Test position the closing spring shall be
automatically released.

H4-6
Accessories for cradles
�Mechanically operated cell switch (MOC)
This 6a6b switch indicates the 'ON' or 'OFF' condition of a VCB and is
operated in the positions of 'Run' and 'Test"..

�Truck operated cell switch (TOC)


This 6a6b switch indicates the 'Run' state of a VCB and is operated by the
movement of a VCB frame.

H4-7
H4-8
P P P
Auxiliary switch
CS CS
5a 3b
A1 A3 A5 22 24 26 28 40 54 56 58

LS2 3 LS3 1 3 4
Ya
4 2 4 6
1
Yb
5 22 35 24 37 26 39 28 51 40 53 43 54 45 56 47 58
5 30 6
52b 52a
M
31
Control circuit diagram

6 6’ 23 34 25 36 27 38 29 50 41 52 42 55 44 57 46 59
3 7

TRIP POWER SOURCE

MOTOR POWER SOUREC


C Y 1

CLOSING POWER SOURCE


4 8
TC
1
2
LS1
2
A2 A4 A6 23 25 27 29 41 55 57 59

N N N early b

∅ : External terminal of VCB 13 14 15 16 17 18 19 20 21 22 23 24

52 : Vacuum circuit breaker


A2 A4 A6 23 25 27 29 41 55 57 59
M : Spring charging motor
TC : Trip coil A1 A3 A5 22 24 26 28 40 54 56 58
C : Closing coil
1 2 3 4 5 6 7 8 9 10 11 12
Y : Anti-pump relay
52a : Auxiliary switch (NO)
SECONDARY DISCONNECT WIRING
52b : Auxiliary switch (NC)
LS1 : Closing interlock limit switch (only withdrawable type) (FRONT VIEW OF RECEPTACLE PLUG)
LS2 : Motor stopping, closing spring charged indication
LS3 : Anti-closing, Anti-pumping limit switch
Vacuum Circuit Breaker for Nuclear Power Plants

Note) Diagram shows the circuit breaker in position“OFF”with closing spring“Charged”


Dimensions

Breaker
722
254 254

722
745

<Front view>

109 228 109 228


360

360
817

816
369

3000A

86.5
109.5 442.5
713

1200/2000A
<Side view>

H4-9
Vacuum Circuit Breaker for Nuclear Power Plants
Dimensions

Cradle
936

254 254

644
850

<Front view>

343 137
100

252
213
310

203
36

4-M12 DP18
360

1070

2-M12 DP24
1200/2000A
449

50
157

2-M12 DP24
3000A
195 630

1020

<Side view>

H4-10
Types and ordering information

Breaker

LVB 05 G 40 B 20 1A 2K 1

LS VCB Installation method Version Control voltage Note) Nuclear class


G G class draw-out B Pro-MEC 1A DC110V 1 1E class
1B DC220V 2 Non 1E class
1C DC48V
1E DC125V

Note) 1A,1B,1C are only available


at 15kV class

Rated voltage Breaking current Rated current Auxiliary switch


05 4.76kV 40 40kA 12 1200A 2K 8c 접점
15 15kV 50 50kA 20 2000A
30 3000A

Cradle

LCL 05 G 40 B 20 1

LS Cradle Installation method Version Nuclear class

G G class draw-out B Pro-MEC 1 1E class

2 Non 1E class

Rated voltage Breaking current Rated current


05 4.76kV 40 40kA 12 1200A

15 15kV 50 50kA 20 2000A


30 3000A

H4-11
Memo

H4-12
� For your safety, please read user's manual thoroughly before operating.
� Contact the nearest authorized service facility for examination, repair, or adjustment.
� Please contact a qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Safety Instructions � Any maintenance and inspection shall be performed by the personnel having expertise concerned.

ⓒ 2008.11 LSIS Co.,Ltd. All rights reserved. www.lsis.biz

� HEAD OFFICE � Global Network


�LSIS (Middle East) FZE �
�Dubai, U.A.E.
Korea Gyeonggi-do Anyang-si dongan-gu Address: LOB 19 JAFZA VIEW TOWER Room 205, Jebel Ali Freezone P.O. Box 114216, Dubai, United Arab Emirates
Tel: 971-4-886 5360 Fax: 971-4-886-5361 e-mail: jungyongl@lsis.biz
LS-ro 127 (Hogye-dong) �Dalian LSIS Co., Ltd. �
�Dalian, China
Tel. (82-2)2034-4887, 4873, 4918, 4148 Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, China
Tel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: lixk@lsis.com.cn
Fax. (82-2)2034-4648 �LSIS (Wuxi) Co., Ltd. �
�Wuxi, China
Address: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu, 214028, P.R.China
Tel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: xuhg@lsis.com.cn
�LSIS-VINA Co., Ltd. �
�Hanoi, Vietnam
� CHEONG-JU PLANT Address: Nguyen Khe - Dong Anh - Ha Noi - Viet Nam
Tel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: srjo@lsisvina.com
Cheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku, �LSIS-VINA Co., Ltd. �
�Hochiminh , Vietnam
Cheong Ju, 361-720, Korea Address: 41 Nguyen Thi Minh Khai Str. Yoco Bldg 4th Floor, Hochiminh City, Vietnam
Tel: 84-8-3822-7941 Fax: 84-8-3822-7942 e-mail: sbpark@lsisvina.com
�LSIS Shanghai Office �
�Shanghai, China
Address: Room E-G, 12th Floor Huamin Empire Plaza, No.726, West Yan'an Road Shanghai 200050, P.R. China
Tel: 86-21-5237-9977 (609) Fax: 89-21-5237-7191 e-mail: jinhk@lsis.com.cn
�LSIS Beijing Office � �Beijing, China
Address: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District,
Beijing 100013, P.R. China
Tel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: cuixiaorong@lsis.com.cn
�LSIS Guangzhou Office �
�Guangzhou, China
Address: Room 1403,14F,New Poly Tower,2 Zhongshan Liu Road,Guangzhou, P.R. China
Tel: 86-20-8326-6764 Fax: 86-20-8326-6287 e-mail: linsz@lsis.biz
�LSIS Chengdu Office �
�Chengdu, China
Address: Room 1701 17Floor, huanminhanjun internationnal Building, No1 Fuxing Road Chengdu, 610041, P.R. China
Tel: 86-28-8670-3101 Fax: 86-28-8670-3203 e-mail: yangcf@lsis.com.cn
�LSIS Qingdao Office �
�Qingdao, China
Address: 7B40,Haixin Guangchang Shenye Building B, No.9, Shandong Road Qingdao 26600, P.R. China
Tel: 86-532-8501-6568 Fax: 86-532-583-3793 e-mail: lirj@lsis.com.cn
�LSIS NETHERLANDS Co.Ltd �
�Qingdao, Netherlands
Address: 1st. Floor, Tupolevlaan 48, 1119NZ,Schiphol-Rijk, The Netherlands
Tel: 31-20-654-1420 Fax: 31-20-654-1429 e-mail: junshickp@lsis.biz